Hospitals andMajor Medical CentersHospitals andMajor Medical Centers

◆ INERGEN® Fire SuppressionSystems

◆ AUTOPULSE® Detectionand Control Equipment

◆ SENTRY® Hand PortableFire Extinguishers

SENTRY® Hand Portable Fire Extinguishers

In hospitals and medical centers, people withimpaired health can be exposed to fireextinguishing agents. And, in fact, someextinguishing agents may cause cardiacsensitization. Therefore, extra precautions shouldbe taken when selecting fire suppression systemsfor hospitals or medical centers. Only the safestClean Agent Fire Suppression Systems shouldbe considered.

Medical centers have specialconcerns for fire safety

◆ INERGEN agent is a blend of threenaturally-occurring inert gases. It does notdecompose in a fire. Therefore, there are noconcerns about the production of toxic gases.

◆ An extensive collection of published journalarticles and scientific reports from independentinternationally recognized medical and researchspecialists has confirmed that an INERGENatmosphere is safe. Testing has been performed atand beyond normal system design concentrationsto produce a wide safety margin.

◆ INERGEN Fire Suppression Systems have beeninstalled in hospitals and medical centersworldwide. Fires have been successfullyextinguished by INERGEN systems with onlyminor fire damage to the hardware involved.

◆ Innovative and flexible system designs arepossible with INERGEN systems. The use ofselector valves can provide tremendous savingsby reducing the installed cost of an INERGENsystem. Agent storage cylinders can be located inmechanical or storage areas and not take upvaluable space in data centers or diagnostic rooms.

◆ Ansul offers a unique Evergreen DischargeWarranty. Basically, the warranty states thatAnsul will pay for the cost of INERGEN agentreplacement regardless of the cause of discharge(except commissioning discharge tests) for aperiod of 10 years. Ask for Warranty detailsand limitations.

◆ Ansul recommends the installation of SENTRYportable fire extinguishers in hospitals andmedical centers. These extinguishers meet orexceed the standards set forth by the authorityhaving jurisdiction to ensure the highest levels oflife safety and property protection.

The Ansul solution

Agent selection is vital.Halon 1301 and first generationhalocarbon replacement agents decomposewhen they contact flame producing toxicgases such as Hydrogen Fluoride (HF).Third-party information from small,intermediate, and large-scale independenttesting facilities should be evaluated foran unbiased view of the issue. However,NIOSH has established 30 parts per million(PPM) of HF as the maximum legalexposure level. The American IndustrialHygiene Association "EmergencyResponse Planning Guide" identifies 50PPM of HF as a level that could be fatal tohighly susceptible people and generallythe level requires evacuation of allindividuals in the vicinity.

Detectionand ControlEquipment

AUTOPULSE®

Control Units

NOTE: This drawing is conceptual in nature. The fire suppressionsystem depicted constitutes typical hardware requirements. The finalsystem design must consider other factors that are only determinedthrough a pre-installation in-depth analysis of all likely areas of probable fire incident.

▲1

▲2

▲3

▲4

Selector Valveand Piping Arrangement

Nozzles andManifold Orifice

DevicesINERGEN agent is stored as a gasmixture in DOT approved cylinders.INERGEN cylinders can be installedeither vertically or horizontally – andare available in various sizes – allowingthe system design engineer to store theproper amount of agent in the fewestnumber of cylinders to save space andinstallation costs.

Fire detection/suppression system

operation1 Detectors sense fire in the protected areaand electronically signal the AUTOPULSEcontrol unit.

2 The AUTOPULSE control unit thentriggers a series of actions… activatesalarms – shuts down ventilation – and,after the prescribed time delay period,energizes the electric actuator on theINERGEN cylinder valve.

3 The cylinder valve opens allowingINERGEN agent to escape from the storagecylinder(s) into the distribution pipingnetwork.

4 INERGEN agent discharges through thenozzles where it quickly floods theprotected area to suppress the fire.

Installation and serviceINERGEN fire suppression systems areinstalled, maintained, and serviced by aworldwide network of Ansul authorizedfire equipment distributors who are factorytrained and fully equipped to keep yoursystems fire-ready.

Specifications

1.01 SYSTEM ARRANGEMENTA. INERGEN fire suppression system shall be of the engineered fixed-nozzle type with allpertinent components provided by Ansul Incorporated.B. Agent storage cylinders shall be centrally located, free-standing cylinders with wall-mountedretaining brackets. Where multiple cylinders are required for the same hazard, a commonmanifold shall be employed.C. One cylinder shall be designated as the pilot cylinder and employ the electric actuator,mechanical manual actuator, or both. All remaining cylinders shall be pneumaticallyoperated from the INERGEN agent.D. Manifold cylinders shall employ a flexible discharge hose to facilitate installation andsystem maintenance. Each cylinder on a manifold shall also include an agent check valveinstalled to the manifold inlet.

1.02 FLOW CALCULATIONSA. Computerized verification of flow calculations shall be submitted for each INERGEN firesuppression system and include the following data as a minimum:1) Quantity of agent per nozzle. 2) Manifold orifice device and nozzle orifice diameters.3) Pressure at nozzle. 4) Nozzle body nominal pipe size. 5) Number and size of cylinders.6) Total agent quantity. 7) Pipe size and schedule per pipe section. 8) Number, size and typeof fitting per pipe section. 9) Actual and equivalent lengths per pipe section. 10) Discharge time.

2.01 PIPE MATERIALA. System piping shall be of noncombustible materials having physical and chemicalcharacteristics such that its integrity under stress can be predicted with reliability.B. As a minimum, piping materials shall be black steel pipe conforming to ASTM A-53A ERWor ASTM A-106A seamless.C. Under no conditions shall ordinary cast iron pipe, steel pipe conforming to ASTM A-120 orASTM A-53/A-120 be used.D. Piping joints shall be suitable for the design conditions and shall be selected withconsideration of joint tightness and mechanical strength.E. As a minimum, fittings beyond the manifold orifice device shall be black, 300 lb. classconforming to ANSI B-16.3. Ordinary cast iron fittings shall not be used. Distribution pipingdownstream of the manifold orifice device must be a minimum of Schedule 40.F. The system manifold up to the manifold orifice device must be constructed of Schedule 80piping and 2000 lb. or 3000 lb. forged steel fittings.G. All piping shall comply with NFPA 2001: Standard on Clean Agent Fire Extinguishing Systems.H. Piping shall be installed in accordance with good commercial practice to the appropriatecodes, securely supported with UL Listed hangers and arranged with close attention to thedesign layout since deviations may alter the design flow performance as calculated.I. Piping shall be bracketed within 12" (300 mm) of all discharge nozzles.J. All piping shall be reamed, blown clear and swabbed with appropriate cleaner to removemill varnish and cutting oils before assembly.K. Multi-outlet fittings, other than tees, shall not be permitted.L. Assembly of all joints shall conform to the appropriate standards. On threaded pipe joints,TEFLON® tape shall be applied to the male threads only.

2.02 EXTINGUISHING AGENTA. The agent shall be INERGEN®, a trademark registered to Ansul Incorporated.

Form No. F-200134-1 2002 Ansul Incorporated Litho in U.S.A.

www.ansul.com

Ansul IncorporatedOne Stanton Street

Marinette, WI54143-2542

2.03 STORAGE CYLINDERSA. Cylinder assemblies shall be of steel constructionwith a red epoxy paint finish. Each cylinder shall beequipped with a pressure-seat type valve and gauge.The cylinder shall utilize Ansul CV-98 forged brassvalve assemblies providing a leak-tight seal at thevalve-to-cylinder connection. Each valve shall include asafety pressure relief device per CGA test methods.B. Filling of the cylinder assembly shall be by AnsulIncorporated or an authorized INERGEN systemsdistributor in conjunction with a factory authorizedINERGEN agent filling station. Initial filling andrecharge shall be performed in accordance with themanufacturer's established procedures and shall notrequire replacement components for normal service.

2.04 CYLINDER BRACKETA. Each cylinder assembly shall be furnished with awelded steel bracket. The bracket shall hold thecylinders in a saddle with a front securing device. Thebrackets shall be modular in design to allow addedbracketing or stacking of cylinders depending oninstallation requirements.B. Cylinder brackets shall be UL listed and/or FMapproved for use with the INERGEN system.

2.05 SELECTOR/CYLINDER VALVE ACTUATORSA. Electric valve actuators shall be of brass constructionand stackable design with swivel connections to allowremoval for maintenance or testing.B. Actuation devices shall be UL listed and/or FMapproved for use with the INERGEN system.

2.06 DISCHARGE HOSE/CHECK VALVEA. When manifolding, all cylinder assemblies shallinclude a flexible discharge hose and check valve forconnection to the manifold inlet.B. All hose/check valves shall be UL listed and/or FMapproved for use with the Ansul CV98 valve.

2.07 DISCHARGE NOZZLESA. Discharge nozzles shall be of two-piece constructionand sized to provide flow rates in accordance withsystem design calculations.B. A nozzle inlet orifice plate shall be included. Acomputerized, UL listed, flow calculation program shalldetermine the orifice size.C. Orifice(s) shall be machined in the nozzle body toprovide a horizontal discharge pattern based on theapproved coverage arrangements.D. Nozzles shall be permanently marked with themanufacturer's part number and threaded directly tothe discharge piping without the use of special adapters.E. Nozzles shall be UL listed as manufactured byAnsul Incorporated.

2.08 MANIFOLD ORIFICE DEVICEA. An orifice device shall be included in the manifold toreduce pressure in the downstream pipe network. Aseparate manifold orifice device shall be included forthe extended discharge nozzles.B. Manifold orifice devices shall be rated at 2000 lb.Class minimum.C. Manifold orifice devices shall be permanentlymarked with the manufacturer's orifice code.D. Manifold orifice devices shall be UL listed and/orFM approved for use with the INERGEN system.

2.09 SYSTEM CHECKOUT AND TESTINGA. The completed installation shall be inspected byfactory authorized and trained personnel. The inspectionshall include a full operational test of all componentsper the equipment manufacturer's recommendations(including agent discharge).B. Inspection shall be performed in the presence of theowner's representative, architect or engineer'srepresentative, insuring authority, and/or the localauthority having jurisdiction.C. All mechanical and electrical components shall betested according to the manufacturer's recommendedprocedure to verify system integrity.D. Inspection shall include a complete checkout of thedetection/control system and certification of cylinderpressure. A written report shall be filed with the owner.E. The contractor shall provide as-built drawings(2 copies) indicating the installation details. All routingof piping, electrical conduit, and accessories shallbe noted.F. Equipment installation and maintenance manualsshall be provided in addition to the as-built drawings.G. Prior to final acceptance, the contractor shall provideoperational training to the owner's key personnel.Training shall consist of:1) Control system operation. 2) Trouble procedures.3) Abort procedures. 4) Emergency procedures.5) Safety requirements. 6) Demonstration of the system(excluding INERGEN release).H. The quantity of agent shall reflect the actual designquantity of INERGEN agent.I. A functional test shall be completed prior to theconcentration test consisting of detection, alarm,accessories related to the system, control unit and areview of the cylinders, piping, fittings, hangers andcylinder pressure.

3.01 WARRANTYA. All INERGEN system components furnished underthis contract shall be guaranteed against defects indesign, material and workmanship for the full warrantytime which is standard with the manufacturer and/orsupplier but not less than one (1) year from the date ofsystem acceptance. In addition, the installing contractormust guarantee the system against false actuation orleakage due to faulty equipment, design orworkmanship for a period of one (1) year fromfinal acceptance.