    SPECIFIERS GUIDE TO OUR RANGE OF LINTELS

    LINTEL GUIDE

    BETTER BYDESIGN

  • 8/9/2019 IG intels brochure

    2/88

    BBA Certification

    National Building

    Specification Approved

    National House

    Building Council

    British Standards Institution

    ISO 9001 & ISO 14001

    RIBA CPD

    Approved

    Investors in People

    Accreditation

    CERTIFICATE No 05/4192

    Home Builders

    Federation

    Builders Merchants

    Federation

    Building Research

    Establishment

    IG produce the UKslargest range of steel lintelsbacked by industry leadingtechnical support andex-stock delivery service.

    BETTER BYDESIGN

  • 8/9/2019 IG intels brochure

    3/88

    Steel Lintel Guide

    CONTENTS PAGE

    Innovation, Quality & Service 04

    Lintel Performance 08

    Material Specification 09

    Specification Clauses 10

    Installation Guide 12

    Selecting the Correct Lintel 14

    Lintel Range Index 16

    Hi-Therm Lintel 18

    Standard Cavity Wall Lintels 20

    Wide Inner Leaf Cavity Wall Lintels 32

    Wide Outer Leaf Cavity Wall Lintels 50

    Eaves Lintels 64

    Solid Wall & Box Lintels 66

    Timber Frame & Single Leaf Lintels 72

    Extended Range 80

    Stainless Steel Range 84

    www.iglintels.com

  • 8/9/2019 IG intels brochure

    4/88

    4 LINTEL GUIDE

    Innovation

    Through continual innovation the IG range nowprovides lintel solutions for every structuralrequirement, compliant with the latest regulations.

    Founded in 1958, IG Lintels is a divisionof Europes largest manufacturer ofsteel lintels and masonry supportsystems. IG Lintels design, manufactureand supply high quality steel lintelsthroughout Europe.

    IG invented the original open backlintel in 1967, which quickly becamethe industry standard. Our lintels are

    engineered to be the most structurally

    and thermally efficient lintels available.Continual development ensures theyare widely specified for use throughoutEurope on commercial, industrial,residential and institutional projects.

    In 2011 IG introduced Hi-Therm, aunique product designed to exceedthe thermal requirements of futurebuilding regulations.

  • 8/9/2019 IG intels brochure

    5/88

    www.iglintels.com

    5BETTER BYDESIGN

    THERMAL PERFORMANCE

    Building regulations require that lintelsshould be assessed for their effect onthe thermal performance of a building.A lintels thermal performance is expressedin terms of Psi Values () i.e. linear thermaltransmittance.

    STANDARD IG LINTELAll IG standard lintels satisfy the thermalperformance requirements of England andWales Part L of the building regulations,Northern Irelands Part F and ScotlandsTechnical Handbook, section 6.

    Our standard L1 range has Psi valuesranging from 0.2 to 0.3 W/m.k. The exactfigure of your Psi value depends upon thewall construction the lintel is built into. Formore detailed information on Psi valuesapplicable to your wall construction or formore information on accredited constructiondetails please contact IGs technical team.

    STANDARD IG LINTELwith patented Thermal Break Plate

    HI-THERM IG LINTELpatented Galvanised Steel/GRP Lintel

    HI-THERM IG LINTELIGs Hi-Therm Lintel is a combination of GRPand Galvanised Steel. When combined thesetwo materials form the ultimate in lintel design- Psi 0.05 W/m.K

    Testing of IGs Hi-Therm Lintel was carried out bythe BRE (Building Research Establishment) usingPhysibels thermal analysis software TRISCO whichcomplies with BS EN ISO10211-1. The modellingfollows the requirements of the BRE conventionsdocument BR497.

    OUTSTANDING ADVANTAGES

    Outperformsall other cavity wall lintels forthermal performance. GRP has very lowthermal conductivity which practically eliminatescold bridging.

    Outperformsstainless steel and galvanisedsteel for corrosion resistance. The GRP outerflange, quite simply, will never corrode.

    Outperformsstainless steel in price. GRP ismore competitively priced than stainless steel.

    DPC is not normally required. The GRP outerflange does not require the installation of aseparate Damp Proof Course/Cavity Tray.

    (Areas of severe exposure will require a separateDPC. See BS 8104 zones 3+4).

    Hi-Therm has achieved a 1 hour fire resistance testas carried out by Exova Warringtonfire utilising theheating conditions of BS EN 1363-1 1999.

    THERMALPERFORMANCETESTING

    Galvanised Steel

    GRP

    LINTEL HOTLINE

    01633 486486

    ColdOuter Leaf

    WarmInner Leaf

    ThermalBreak Plate

    Thermal Breaki.e. no contact

    10% Contact Only

    ColdOuter Leaf

    WarmInner Leaf

    ThermalBreak Plate

    Insulation fixed inplace by IG

  • 8/9/2019 IG intels brochure

    6/88

    6 LINTEL GUIDE

    SPECIAL LINTELS

    IG offer a complete customdesign service to ensure yourproject has the best lintel forthe job. Our technical expertiseis renowned for delivering

    solutions with total efficiency.

    STANDARD LINTELS

    IG produce a wide range ofstandard galvanised steeland stainless steel lintels.All IG standard lintels satisfythe Thermal Performance

    requirements of all UKbuilding regulations.

    Support

    RANGE

    With the largest range and more support, IG has over 50 yearsexperience in delivering effective service and solutions.

    HI-THERM

    IG has redefined lintelperformance with Hi-Therm,designed to exceed the thermalrequirements in forthcomingbuilding regulations. Hi-Therm

    is supported by an advancedtechnical service package.

    CAVITY TRAYS

    The IG Cavity Tray presentsa lightweight, simple toinstall and long-lastingsolution to preventingdampness from penetrating

    below the roof line.

    BRICKWORKFEATURE LINTELS

    IG Brickwork FeatureLintels are a one pieceprefabricated unit,manufactured bespoke

    to order, achieving eventhe most challengingarchitectural designs.

    MASONRY SUPPORT& WINDPOST SYSTEMS

    IG continues to set the standardfor masonry support andwindpost systems for a range ofbuilding frame configurations.

    The innovative Qwik Fix angleprovides a versatile solution whenmasonry support is required.

  • 8/9/2019 IG intels brochure

    7/88

    www.iglintels.com

    7BETTER BYDESIGN

    TECHNICAL SUPPORT

    IG provides comprehensive technical support forall products. Our free scheduling and specificationservice offers fast turnaround on standard lintels,masonry support and windpost systems.

    IG leads the market with a bespoke designservice for special lintels and brickwork featurelintels, including onsite measurement andtechnical assistance.

    Our in-house experts use the latest thermalmodelling software to advise clients on theoptimum lintel solution for compliance withand beyond the latest building regulations.

    By contacting our engineers at an early stageof your design process, you will potentially gainsignificantly more design flexibility for theoverall project. Please send your drawings to:[email protected]

    Please refer to our Fax Back Forms for speciallintel requirements. Detailed measuring adviceand Fax Back Enquiry Forms are available fordownload at: www.iglintels.com/technical.

    FASTRACK DATABASE FOR CADThe IG Fastrack Database is accessible from theIG website and provides downloads of CAD filesfor a selection of IG Steel Lintels.

    NBS PLUS

    IG provides specification details via RIBA NBS Plus,accessible accessible via our website or via RIBAfor NBS subscribers.

    DELIVERYIGs fast, efficient delivery service is renownedthroughout the construction industry. Ourlogistics solution is recognised by our customersfor superior supply chain management.

    IG continues to provide the largest range oflintels available, with the shortest lead timesin the industry. We have invested in largestock inventories at our three manufacturingand distribution centres reassuring our customersthat all our standard lintels are instantly availableupon request.

    IG has revolutionised the steel lintel industryby manufacturing and delivering speciallintels with lead-times historically associatedwith ex-stock items.

    IG products are available through anational network of merchant suppliers.For information of merchant suppliers

    in your area please visit our website at:www.iglintels.com/merchants

    IGgives a hassle free service from enquiry

    stage through to delivery on site. You canrelax in the knowledge that your order is inthe hands of experts.

  • 8/9/2019 IG intels brochure

    8/88

    8 LINTEL GUIDE

    Standard Lintel

    PerformanceFIRE PERFORMANCE

    IG lintelshave been subjected to a fire test(ref: WARRES No. 101263) in accordance withBS 476:Part20: 1987, at Exova Warringtonfireand achieved a one hour fire performance.

    If longer fire rating figures are required they canbe achieved by applying a proprietary fire boardto the soffit of the inner flange of the steel lintel.Please contact our technical team if furtherfire rating provisions are required.

    CORROSION RESISTANCE

    IGs standard range of lintels are manufactured fromhigh quality grade pre-galvanised mild steel with azinc coating of 600g/m (including both sides).

    The hot dipped, pre-galvanising process is carriedout at the mill to ensure a more consistent quality ofzinc coating. This guarantees a more effective anti-corrosive system. Furthermore pre-galvanised lintelsare much more environmentally friendly than postgalvanised lintels with a lower carbon footprint.

    STRUCTURAL PERFORMANCE

    The IG Lintelrange has safe working loads asdetailed in each applicable loading table in our LintelGuidebrochure. The structural performance figureswithin each table have been ascertained by testingin accordance with the requirements of standardsBS 5977 Part 2 1983 and BS EN 845-2:2003.

    The figures take into account the different loadingarrangements which are common to traditionalcavity wall construction.

    Differential Total UDL kN 3:1Up to 75% loading on the inner leaf.

    Differential Total UDL kN 19:1Up to 95% loading on the inner leaf.

    LINTEL LOAD TABLES

    For full details of load tables specific to your linteltype please see Lintel Range & Loading Tablespages 19-73.

    Lintel types: L1/S 50, L1/S 75, L1/S 100, L1/HD 50,L1/HD 75, L1/HD 100, L1/S 50 WIL 215, L1/S 75

    WIL 215, L1/S 100 WIL 215, L1/S 110, L1/S 130,L1/S 150, L10, L7, L11, L8/RB, L1/TJ, INT 100, L9,IBEAM, L1/E 50, L1/E 100, L5, L6 have been testedas a composite unit with surrounding masonry, builtin accordance with BS EN 1996-2:2006.

    LINTEL LIFE SPAN

    The IG lintel range complies with the technicalrequirements of the BLP (Building Life Plans)regarding the durability data of mild steel,cold formed lintels.

    The service life of IG lintels, when installed with aflexible DPC, will be the same as that anticipatedfor the building. Lintels supplied by IG, almost 60years ago, continue to perform without maintenance- a tested and proven track record.

  • 8/9/2019 IG intels brochure

    9/88

    www.iglintels.com

    9BETTER BYDESIGN

    Material SpecificationIG Lintels are available in three material types, each with distinctfeatures that can be utilised dependent on your project.

    GALVANISED STEEL

    IGs standard range of lintels are manufactured fromhigh quality grade pre-galvanised mild steel toBS EN 10346:2009 DX51D plus Z600 or grade Z275 toBS EN10025-2:2004 with minimised spangle finish anda minimum yield stress of 250N/mm. In accordancewith BS5977: part 2, 1983 (BS EN 845-2:2003) all cutedges are treated with a corrosion resistant paint.Table C.1 - material coating reference L14(BS EN 845 part 2 2003 page 28).

    STAINLESS STEEL

    IGs stainless steel range of lintels use stainless steelgrade 304 2b to BS EN 10088-Part 2 Astm 240(European Grade 1.4307). IGs full range of standardand special lintels are available in stainless steel.

    For detailed information on our range of stainlesssteel lintels see page 86.

    GALVANISED STEEL/GRP

    IGs Hi-Therm lintel range is manufactured from GRPfor the outer leaf and Galvanised steel for the inner leaf.The GRP used is a pultruded fibre reinforced polymermade from polyester resin, fillers and continuousreinforcement consisting of continuous glass fibrestrand roving and glass fibre mat, protected by asurface veil.

    POLYSTYRENE INSULATION

    IGs lintels are insulated with expanded polystyreneand conforms to BS 13163: 2008. The polystyreneexpansion process involves an air and pentane mixture.The release of pentane into the atmosphere causesno Ozone Depletion or Global Warming therefore ourinsulation has an Ozone Depletion Potential (ODP)and Global Warming Potential (GWP) of ZERO.

    The expanded polystyrene (EPS) incorporated into ourpre-insulated lintels does not use, contain or produceformaldehyde, CFCs or indeed any so called CFCs(i.e. HCFC and HFAS). The insulation used in IG lintelsconforms to the Montreal Protocol.

    The thermal conductivity of expanded polystyreneis 0.03 W/mK.

    Pre-galvanised steel

    Continuous profiledinsulation CFC Free

    Plaster key

    Thermalbreak plate

    Pre-galvanised steel

    GRP

    Continuous profiledinsulation CFC Free

    Plaster key

  • 8/9/2019 IG intels brochure

    10/88

    10 LINTEL GUIDE

    Specification Clauses

    Standard:BS EN 845-2: 2003

    Manufacturer:IG Lintels, Avondale Road,Cwmbran, Gwent, NP44 1XYTel: 01633 486 486Web: www.iglintels.com

    Product Reference:

    Types:

    Material/Finish:As product

    Sizes:As required and to achieve aminimum end bearing of 150mm(200mm for heavy duty lintels).

    Additional requirements:

    Placement: Bed on mortar usedfor adjacent work, bearing length(minimum) 150mm.

    NBS plus specifications areavailable on www.iglintels.comorvia RIBA for NBS plus subscribers

    Single Leaf Lintel

    NBS 755:Prefabricated Steel Lintels

    Clause F30: Masonry: Accessories/Sundry items for brick/block/stone cladding

    Cavity Wall Lintel

    Provide IG insulated steel lintels withintegral plaster key and Thermal BreakPlate, manufactured and designed inaccordance with BS EN 845-2:2003.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486,Web: www.iglintels.com

    Product Reference:

    IG:L1/L5... /L6...

    Length:

    Material:High quality grade galvanised steel toBS EN 10346:2009 DX51D standardplus Z600.

    Installation:Lintels to have a minimum end bearingof 150mm on each side of the opening,bedded on mortar. Level the lintel alongits length and across its width. Raise theinner and outer leaves simultaneously,masonry to be laid on a mortar bed andall perpendicular joints to be filled.Lintels may be propped to facilitatespeed of construction.

    Provide IG steel lintels manufacturedand designed in accordance withBS EN 845-2:2003.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486,

    Web: www.iglintels.comProduct Reference:IG:L9.../ L10.../ L11.../ BOX

    Length:

    Material:High quality grade galvanised steel toBS EN 10346:2009 DX51D standardplus Z600.

    Installation:Lintels to have a minimum end bearingof 150mm on each side of the opening,

    bedded on mortar. Level the lintel alongits length and across its width. Masonryto be laid on a mortar bed and allperpendicular joints to be filled.Lintels may be propped to facilitatespeed of construction.

    Timber Frame Lintel

    Provide IG steel lintels manufacturedand designed in accordance withBS EN 845-2:2003. IG Lintels,Avondale Road, Cwmbran,Gwent, NP44 1XY,Tel: 01633 486 486Web: www.iglintels.com

    Product Reference:

    IG:L7/

    Length:

    Material:High quality grade galvanisedsteel to BS EN 10346:2009DX51D standard plus Z600.

    Installation:Lintels to have a minimum endbearing of 150mm on each sideof the opening, bedded on mortar.Level the lintel along its lengthand across its width. Masonry tobe laid on a mortar bed and allperpendicular joints to be filled.Restraint clips are to be installedas per IG installation instructions.Lintels may be propped tofacilitate speed of construction.

    Extended Product Range

    Provide IG insulated steel lintelsmanufactured and designed inaccordance with BS EN 845-2:2003.IG Lintels, Avondale Road,Cwmbran, Gwent, NP44 1XY,

    Tel: 01633 486 486,Web: www.iglintels.com

    Product Reference:IG: L...

    Material:High quality grade galvanisedsteel to BS EN 10346:2009DX51D standard plus Z600.

    Installation:Lintels to have a minimum endbearing of 150mm on each sideof the opening, bedded on mortar.

    Level the lintel along its lengthand width. Raise the inner andouter leaves simultaneously,masonry to be laid on a mortarbed and all perpendicular joints tobe filled. Lintels may be proppedto facilitate speed of construction.

    Stainless SteelLintel Applications

    Provide IG insulated Stainless SteelLintels with patented Thermal BreakPlate. Manufactured and designed inaccordance with BS EN 845-2:2003.

    IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486,Web: www.iglintels.com

    Product Reference:IG:Stainless Steel Lintel SS

    Length:

    Material:Stainless steel grade 304 2B toBS EN 10088-Part 2 Astm 240(European Grade 1.4307)

    Installation:

    Lintels to have a minimum end bearingof 150mm on each side of the openingbedded on mortar. Level the lintel alongits length and across its width. Raisethe inner and outer leaves of masonrysimultaneously. Lintels may be proppedto facilitate speed of construction.

  • 8/9/2019 IG intels brochure

    11/88

    www.iglintels.com

    11BETTER BYDESIGN

    IG LINTEL ACCESSORIES

    Lintel Cavity Weep Hole

    Provide IG cavity weep holes withcavity wall lintels.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486Web: www.iglintels.com

    Product Reference:IG:WH

    Installation:Insert lintel cavity weep holes at450mm centres. At least two peropening must be installed on theouter flange of the lintel.

    Lintel Stop Ends

    Provide IG lintel stop ends to cavitywall lintels.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486Web: www.iglintels.com

    Product reference:IG:SE

    Installation:Place lintel stop ends on both ends ofthe outer flange of the lintel. Ensurethat the stop end is positioned tightlyagainst the front upstand of the lintel.Adjust the stop end to suit the lintelprofile. Position the stop ends in aperpendicular joint nearest the endof the lintel.

    Lintel Arch Boards

    Provide IG white Arch Board.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486,Web: www.iglintels.com

    Product Reference:IG:AR

    Installation:Place arch board on the outer flangeof the lintel. Brickwork on top of archboard must be built on a 10mm bedof mortar.

    Lintel Soffit Cladding

    Provide PVCu IG Soffit Cladding.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486Web: www.iglintels.com

    Product Reference:IG: SCW

    Installation:Attach the built in plastic clip end tothe front outer flange of the lintel.The length of the Lintel soffit shouldbe the same as the opening, not thelength of the lintel.

    Cavity Trays

    Provide IG Gable Abutement Cavity Trayand or Refurbishment Cavity Tray andor Internal or External Corner Tray.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486Web: www.iglintels.com

    Product Reference:IG:GA1/ GA2/ GA3.../RFT

    Installation:Trays to be folded as instructions ontray, to form left and right stop endsas required.

    Brick Arch Sets

    Provide IG Brick Arch Sets.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486Web: www.iglintels.com

    Product Reference:IG:BA

    Installation:Lintels to have a minimum end bearingof 150mm on each side of the opening,bedded on mortar. Level the lintel alongits length and across its width. Raise theinner and outer leaves simultaneously.

    All joints to be filled after lintel has beenbuilt in. Lintels may be proppedto facilitate speed of construction.

    Windposts

    Provide IG Windposts.IG Lintels, Avondale Road, Cwmbran,Gwent, NP44 1XY, Tel: 01633 486 486Web: www.iglintels.com

    Product Reference:U1...U9/ LP1...LP12/ DU3...DU9

    Material:Austenitic Stainless Steel Grade 304.

    Installation:Windposts to be bolted to ground andintermediate floor structures. Windpost

    spacing determined by IG Engineer. LPWindpost to be built into blockwork. DUand U windposts to be placed in cavity.

  • 8/9/2019 IG intels brochure

    12/88

    12 LINTEL GUIDE

    Lintel Installation Guide

    1 Lintels should be installed with a minimum endbearing of 150mm, bedded on mortar andlevelled along its length and across its width.

    2 The masonry above the lintel should be builtin accordance with BS EN 1996-2:2006.

    3 Raise the inner and outer leaves simultaneously

    to avoid excessive eccentricity of loading,with a maximum height difference of 225mm(masonry should be laid on a mortar bed andall perpendicular joints should be filled).

    4 Allow the mortar to cure before applyingfloor or roof loads (Temporary proppingbeneath a steel lintel is practised to facilitatespeed of construction).

    5 The NHBC recommend a damp proof course(DPC) or cavity tray should be installed over

    all openings in external cavity walls.

    6 When installing concrete floor units or otherheavy components above a lintel, care shouldbe taken to avoid shock loading and floorunits should not be dragged into position.Masonry immediately above the lintel shouldbe allowed to cure.

    7 Point loads should not be applied directly ontolintel flanges. Lintels should have a minimumof 150mm masonry between the flange andthe application level of any form of loading.Consult IGs technical department if applyinga point load above a lintel.

    8 The external lintel flange must project beyondthe window/door frame and it is recommendedthat a flexible sealing compound is usedbetween the underside of the lintel flangeand the frame.

    9 When the underside of a lintel is exposed, its

    appearance can be enhanced by the additionof lintel soffit cladding.

    10 Do not cut lintels to length or modify themin any way without consulting an IG engineer.

    ENSURE LINTEL IS LEVEL ALONG ITS LENGTH

    OUTSIDE INSIDE

    Ensure lintel isfully bedded onbricklaying mortar.

    Ensure lintel isfully bedded onbricklaying mortar.

    Ensure lintel is level across its width.

    Ensure lintel is fully bedded onbricklaying mortar

    Ensure a nominal150mm endbearing ateach end.

    Ensure lintel isnot damaged.

    150mmminimum

    150mmminimum

    Structural openingor clear span

    Ensure lintel is level along its length.

    ENSURE LINTEL IS LEVEL ALONG ITS WIDTH

  • 8/9/2019 IG intels brochure

    13/88

    www.iglintels.com

    13BETTER BYDESIGN

    DAMP PROOF COURSE - DPC

    LINTEL POSITION WITHIN A CAVITY WALL

    PROPPING

    A Lintel should be centred inthe cavity and the distancebetween lintel up-stand andmasonry must not exceed 8.5mm

    B Masonry should not overhangany flange by more than 30mm.

    Propping a lintel is sometimespracticed to facilitate speed ofconstruction. It should only beintroduced after initial masonry loadhas been applied to the lintel.

    When propping a lintel, a horizontal

    timber plank should be placedalong the underside of the lintel andsuitable* props secured into placeat maximum 1200mm centres.

    * Suitability of props is theresponsibility of site management.

    In accordance with BS EN 1996-2:2006and NHBC requirements all externalwall lintels MUST be installed witha flexible damp proof course withthe exception of those adequatelyprotected by an eaves overhang orsimilar form of protection.

    Stop ends should be provided asspecified by BS EN 1996-2:2006and the NHBC, to avoid moistureentering the cavity near the reveals.Proprietary stop ends should be usedor alternatively the DPC should extendto the edge of the external lintel flangeand 50-150mm beyond the end of thelintel (depending on coursing) to allowformation of an integral stop end at asuitable perpendicular joint.

    Provide weep holes at a maximumof 450mm intervals (at least two peropening) with fair-faced masonry.

    Consider the use of soffit claddingfor all coastal sites. Stainless steel to beused within 500mof the coast (NHBC).

    OUTSIDE INSIDE

    AAB

    OUTSIDE INSIDE

    Timber Plank

    SAFETY PRECAUTIONS

    IG steel products are produced

    from steel plate which maypresent sharp edges. Suitablepersonal protective equipmentshould be worn at all times duringhandling and installation. Glovesshould be worn to avoid injuryfrom any sharp edges or corners.

    When lifting or carrying alintel undertake a personal riskassessment paying attentionto the size and weight of theproduct. To avoid lifting strains

    any lintels other than the shortestlengths should be lifted by atleast two people or alternativelyby mechanical means.

    Do not use damaged lintels.

    STORAGE

    Lintels should be stored on woodenskids on flat ground. IG recommendsthat they are stored one bundle highonly, unless adequate measures aretaken to ensure that the stack willremain stable. The banding strapsare taut and care should be takenwhen cutting these to avoid personalinjury and/or the bundle collapsing.

    DISPOSAL

    Ensure that all IG packaging andwaste are disposed of responsibly.Due care must be given to theenvironmental impact of thedisposal method.

    COSHH - Control of SubstancesHazardous to Health

    IG lintels are fabricated fromgalvanised or stainless steel andpose notoxicity hazard, they arealso insulated with preformedpolystyrene. Most lintels containa perforated steel key platefor rendering purposes and/or asteel strengthening plate for heavyduty requirements which alsoposes no hazard.

    All components and materials inour products are considered as

    non-hazardous to healthunder normal conditions ofuse as determined by COSHHRegulations 2002.

  • 8/9/2019 IG intels brochure

    14/88

    14 LINTEL GUIDE

    Selecting the correct lintelYOU WILL NEED TO KNOW 5 THINGS:1: What is the wall construction?

    2: What is the length of the lintel?

    3: What is the load to be supported by the lintel?

    4: What is the load ratio between the inner and outer leaves of the cavity wall?

    5: How to interpret the load tables.

    1: Select Wall Type

    2: What is the length of the lintel?

    CavityWall

    TimberFrame

    SingleLeaf

    SolidWall

    InternalPartition

    ExternalSolid Wall

    You will need to know:

    A Outer Leaf = 102mm Brick

    B Cavity = 100mm

    C Inner Leaf = 100mm Block

    Example 1:Cavity Wall Construction

    Example 2:Lintel Length

    Ensure a150mm endbearing ateach end.

    150mm

    minimum

    150mm

    minimum

    Structural openingor clear spane.g 1800mm

    How wide is thestructural opening?

    1 Measure the size of the structuralopening i.e. the clear span

    between the masonry supports.

    2 Add 150mm minimum bearingto each end.

    Example lintel length =150 + 1800 + 150 = 2100mm

    OUTERLEAF

    INNERLEAF

    102mmOuter Leaf

    A

    100mmCavity

    B

    100mmInner Leaf

    C

    hnominal

  • 8/9/2019 IG intels brochure

    15/88

    www.iglintels.com

    15BETTER BYDESIGN

    Manufactured length150mm increments

    600 -1200

    1350 -1500

    1650 -1800

    1950 -2100

    2250 -2400

    2550 -2700

    2850 -3000

    3150 -3600

    3750 -4050

    4200 -4800

    Height h 88

    1.6

    12

    10

    88

    2.0

    16

    13

    107

    2.0

    19

    16

    125

    2.0

    21

    17

    150

    2.0

    23

    18

    162

    2.6

    27

    22

    171

    2.6

    27

    20

    200

    3.2

    27

    20

    200

    3.2

    26

    19

    200

    3.4

    27

    22

    Thickness

    Total UDL kN 3:1

    Total UDL kN 19:1

    L1/S 100 For cavity widths 90-105mm

    3: What is the load to be supported by the lintel?

    4: What is the load ratio between the inner and outer leaves of cavity wall?

    5: How to interpret the load tables

    Example 3:Load on Lintel

    kN kNkNThe load on a lintel comes from...

    1 Masonry

    2 Roof Loads: Truss/Attic/Cut/

    3 Floor Loads: Joists/Slabs/

    4 Live Loads: Residential use/ Commercial use/Industrial use/

    5 Combination of above

    NOTE:If you are not skilled in assessing loads please contact IGs Technical Team on 01633 486 486

    Total UDL kN 19:1Up to 95% of the loadis on the Inner Leaf

    Total UDL kN 3:1Up to 75% of the loadis on the Inner Leaf

    25% 75% 5% 95%

    InnerLeaf

    OuterLeaf Total

    Load (kN) 15 5 20

    Load ratio 3 1 3:1

    Example 4:

    Load / ratio calculation:

    Differential load ration 3:1 = 75% load on the Inner Leaf 25% load on the Outer Leaf

    Differential load ration 19:1 = 95% load on the Inner Leaf 5% load on the Outer Leaf

    Total UDL

    The UDL (UniformlyDistributed Load) is the totalload in (kN) that is uniformlydistributed along the span

    of the lintel relative to theload ratio.

    See Example 4

    Manufactured length150mm increments

    Denotes the lintel lengths including

    end bearing. The 2100mm long lintelin Example 2 is listed in this column.

    See Example 2

    For cavity widths 90 -105mm

    The lintels listed in this table are designedfor cavities 95mm to 105mm wide.

    See Example 1

    L1/S 100

    This is the specification code that you shouldreference when contacting an IG Engineer.

    L1 Lintel type 1

    S Standard Loading

    100 100mm Cavity Width

    Se

    lectin

    gthecorrect

    Lin

    tel

  • 8/9/2019 IG intels brochure

    16/88

    16 LINTEL GUIDE

    CAVITY

    100mm Inner LeafCavity Width 50-165mm

    125 - 150mm Inner LeafCavity Width 50-165mm

    125 - 150mm Outer LeafCavity Width 50-165mm

    215mm Inner LeafCavity Width 50-165mm

    215mm Outer LeafCavity Width 50-165mm

    Lintel Range Index

    CAVITY WALL - 100mm INNER LEAF

    CAVITY WALL - WIDE INNER LEAF

    CAVITY WALL - WIDE OUTER LEAF

    EAVES LINTEL

    HI-THERM STEEL/GRP LINTEL - CAVITY WALL

    WALL TYPE

    Standard Loading HT/S 19

    Heavy Duty Loading HT/HD 19

    Standard Loading L1/S 20

    Heavy Duty Loading L1/HD 22

    L1/XHD 24

    Extra Heavy Duty Loading L5 26

    L5/XHD 28

    Extreme Duty Loading L6 30

    Standard Loading L1/S WIL 32

    Heavy Duty Loading L1/HD WIL 34

    L1/XHD WIL 36

    Extra Heavy Duty Loading L5 WIL 38

    L5/XHD WIL 40

    Extreme Duty Loading L6 WIL 42

    Standard Loading L1/S WOL 50

    Heavy Duty Loading L1/HD WOL 52

    L1/XHD WOL 54Extra Heavy Duty Loading L5 WOL 56

    L5/XHD WOL 58

    Extreme Duty Loading L6 WOL 60

    Standard Loading L1/E 50 65

    L1/E 100 65

    Standard Loading L1/S WIL 215 44

    Heavy Duty Loading L1/HD WIL 215 46

    Extreme Duty Loading L6 WIL 215 48

    Standard Loading L1/S WOL 215 62

    LOADING TYPE CODE PAGE

    LOADING CODE PAGE

    LOADING TYPE CODE PAGE

    LOADING TYPE CODE PAGE

    LOADING TYPE CODE PAGE

    LOADING TYPE CODE PAGE

    102 100CAVITY

    102 100CAVITY

    102 150CAVITY

    102 215

    215 100

    150 100

    Psi 0.05 W/m.K

    CAVITY

    CAVITY

    GALVANISED STEEL LINTEL RANGE

  • 8/9/2019 IG intels brochure

    17/88

    www.iglintels.com

    17BETTER BYDESIGN

    LOADING TYPE CODE PAGE

    LOADING TYPE CODE PAGE

    LOADING TYPE CODE PAGESOLID WALL - 215mm WALL WIDTH

    SOLID WALL - 150mm WALL WIDTH

    WALL TYPE LOADING CODE PAGE

    PRODUCT TYPE CODE PAGE

    LOADING TYPE CODE PAGE

    LOADING TYPE CODE PAGE

    SOLID WALL - 100mm WALL WIDTH

    Standard Loading INT 100 66

    L9 SW 100 66

    BOX 75 68

    BOX 100 69

    Heavy Duty Loading HD BOX 100 70

    Thin Joint Lintels L1/TJ 50, L9/TJ 80

    Roller Shutter 82

    Cant Brick/Stepped Lintel 83

    Feature Plate 83

    Universal Arch Lintel IGAR 83

    Weep Vents & Stop Ends 84

    Standard Loading BOX 140 69

    Heavy Duty Loading HD BOX 140 70

    Standard Loading L7 73

    Heavy Duty Loading L7/HD 74

    Extra Heavy Duty Loading L7/XHD 75

    Standard Loading L8 76

    L8 RB 77

    L10 78

    L11 79

    TIMBER FRAME WALL

    SINGLE LEAF WALL

    EXTENDED LINTEL RANGE

    PAGESTAINLESS STEEL RANGE LINTEL RANGE

    86IG Standard Lintels are also available in stainless steel.Outstanding durability through austenitic chromiunnickel steel BS EN10088-part 2 Astm 240 (EuropeanGrade 1.4307). Suitable for use in coastal andindustrial environments. All IG galvanised steelloading tables apply.

    LintelRange

    Se

    lect

    ion

    Index

    Standard Loading L9 67

    I BEAM 2C 67

    I BEAM 3C 67

    BOX 200 69

    Heavy Duty Loading HD BOX 200 71

    Extra Heavy Duty Loading I BEAM XHD 67

    Various Cavity Widths

    Various Cavity Widths

    Various Cavity Widths

  • 8/9/2019 IG intels brochure

    18/88

    LINTELGUIDE

    18

    DAMP PROOFINGNot required on Hi-Therm lintels.*Check severe exposure.

    Cavity Wall

    Hi-Therm Lintel

    Cavity widths from90mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 100mm

    IG leads the way with the development of a completely unique lintelrange to address the thermal requirements of new building regulations.

    Psi 0.05 W/m.K

    Testing of IGs Hi-Therm Lintel was carried out bythe BRE (Building Research Establishment) usingPhysibels thermal analysis software TRISCOwhich complies with BS EN ISO 10211-1.The modeling follows the requirements ofthe BRE conventions document BR497.

    To help understand the immense thermal benefitsof the Hi-Therm Lintel it must be compared toother lintel types.

    Galvanised Steel

    Insulation fixed inplace by IG

    GRP

    THERMAL

    PERFORMANCE

    TESTING

    Plated Steel Lintel (default) 0.5 W/m. K

    Non-plated Steel Lintel (default) 0.3 W/m.K

    0.23 W/m.KTypical IG Lintel

    0.05 W/m.KIG Hi-Therm Lintel

    Lintel type comparison Values

    Up to 5 times more thermally efficientthan a steel cavity wall lintel, Hi-Thermoutperforms other lintels.

    The significant reductions in thermalbridging due to the GRP component will

    assist in the building design process toachieve compliance with Part L and TheCode for Sustainable Homes.

    The use of Hi-Therm will make asignificant contribution to a buildingsperformance in respect of the FabricEnergy Efficiency Standards (FEES).

    Outperforms Stainless Steel on priceand corrosion resistance.

    Hi-Therm has achieved the 1 hour fireresistance test as carried out by Exova

    Warringtonfire utilising the heatingconditions of BS EN 1363-1 1999.

    DESIGN FEATURES

    Patented GRP and Galvanised Steelhybrid design.

    Galvanised steel is used to support theheavier load on the inner leaf of thecavity wall.

    Profiled CFC free insulation ensures

    the continuity of insulation.

    KEY BENEFITS

    Psi COMPARISON CHART

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    Building regulations require that lintels should beassessed for their effect on the thermal performanceof a building. The thermal performance of a lintelis expressed in terms of Psi Values() i.e. linearthermal transmittance.

  • 8/9/2019 IG intels brochure

    19/88

    www.iglintels.com

    19

    For cavity widths 90-105mm

    For cavity widths 90-105mm

    For cavity widths 130-145mm

    For cavity widths 130-145mm

    For cavity widths 150-165mm

    For cavity widths 150-165mm

    Blockwork built tight against inner face of the

    lintel. Place mortar bed on top of blockworkbefore floor units are laid to provide evendistribution of load. Lintels may be proppedto facilitate speed of construction. See LintelInstallation on page 12. Insulation fixed ontop of the lintel has been cut back on thisillustration for clarity.

    NOTE The exact lintel profile will vary dependent on lintel length and loading

    NOTE The exact lintel profile will vary dependent on lintel length and loading

    HT/S Standard LoadHT/HD Heavy Duty Load

    HT/S 100

    HT/HD 100

    HT/S 130

    HT/HD 130

    HT/S 150

    HT/HD 150

    hnominal

    102mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    fHI-THERM LINTEL

    hnominal

    95 10088

    95 10088

    Height h 135 150 229 215

    Thickness 2.5 2.9 2.9 3.2

    Total UDL kN 3:1 20 21 27 27

    Total UDL kN 19:1 17 17 20 20

    Height h 150 229 229 215

    Thickness 3.2 2.9 3.2 2.9

    Total UDL kN 3:1 30 40 40 35

    Total UDL kN 19:1 22 35 35 32

    Manufactured length 600- 1650- 2250- 3150-

    150mm increments 1500 2100 3000 3600

    Manufactured length 600- 1650- 2550- 3150-

    150mm increments 1500 2400 3000 3600

    Standard Load

    Heavy Duty Load

  • 8/9/2019 IG intels brochure

    20/88

    LINTELGUIDE

    20

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Cavity Wall

    Standard Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 100mm

    90-105mmcavityL1/S 100

    95 100

    h

    nominal

    88

    For cavity widths 50-65mm

    For cavity widths 70-85mm

    For cavity widths 90-105mm

    70-85mmcavity

    L1/S 50

    L1/S 75

    95 100

    hnominal

    48

    95 100

    hnominal

    68

    50-65mmcavity

    Height h 79 95 110 134 150 172 172 209 209 209

    Thickness 1.6 2.0 2.0 2.0 2.0 2.0 2.6 3.2 3.2 3.4

    Total UDL kN 3:1 12 14 19 21 21 26 27 27 26 27

    Total UDL kN 19:1 10 12 16 17 19 22 20 20 19 22

    Height h 88 88 107 125 150 162 171 200 200 200

    Thickness 1.6 2.0 2.0 2.0 2.0 2.6 2.6 3.2 3.2 3.4

    Total UDL kN 3:1 12 16 19 21 23 27 27 27 26 27

    Total UDL kN 19:1 10 13 16 17 18 22 20 20 19 22

    Height h 98 89 106 130 142 168 204 204 204

    Thickness 1.6 2.0 2.0 2.0 2.0 2.6 3.2 3.2 3.4

    Total UDL kN 3:1 12 14 18 21 21 27 27 26 27

    Total UDL kN 19:1 10 12 14 17 19 22 20 19 22

    Manufactured length 600- 1350- 1650- 1950- 2250- 2550- 2850- 3150- 3750- 4200-

    150mm increments 1200 1500 1800 2100 2400 2700 3000 3600 4050 4800

    Manufactured length 600- 1350- 1650- 1950- 2250- 2550- 2850- 3150- 3750- 4200-

    150mm increments 1200 1500 1800 2100 2400 2700 3000 3600 4050 4800

    Manufactured length 600- 1350- 1650- 1950- 2250- 2550- 3150- 3750- 4200-

    150mm increments 1200 1500 1800 2100 2400 3000 3600 4050 4800

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

  • 8/9/2019 IG intels brochure

    21/88

    www.iglintels.com

    21

    L1/S 130

    110-125mmcavityL1/S 110

    95 100

    hnominal

    128

    95 100

    hnominal

    108

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    Blockwork built tight against inner faceof the lintel. Place mortar bed on topof blockwork before floor units are laidto provide even distribution of load.Lintels may be propped to facilitate

    speed of construction. See LintelInstallation on page 12.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L1/SSTANDARD LOAD

    95 100

    hnominal

    148

    150-165mmcavityL1/S 150 For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    Height h 95 121 145 195 195 195

    Thickness 2.0 2.0 2.6 2.9 3.2 3.4

    Total UDL kN 3:1 16 22 24 27 26 25

    Total UDL kN 19:1 13 18 18 22 19 20

    Height h 103 128 190 190 190 190

    Thickness 2.0 2.0 2.5 2.9 3.2 3.4

    Total UDL kN 3:1 16 22 24 27 26 25

    Total UDL kN 19:1 13 18 18 22 19 20

    Height h 100 125 180 180 180 180

    Thickness 2.0 2.0 2.6 2.9 3.2 3.4

    Total UDL kN 3:1 16 22 24 27 26 25

    Total UDL kN 19:1 13 18 18 22 19 20

    Manufactured length 600- 1650- 1950- 2250- 3150- 4200-

    150mm increments 1500 1800 2100 3000 4050 4800

    Manufactured length 600- 1650- 1950- 2250- 3150- 4200-

    150mm increments 1500 1800 2100 3000 4050 4800

    Manufactured length 600- 1650- 1950- 2250- 3150- 4200-

    150mm increments 1500 1800 2100 3000 4050 4800

  • 8/9/2019 IG intels brochure

    22/88

  • 8/9/2019 IG intels brochure

    23/88

    www.iglintels.com

    23

    L1/HD 130

    110-125mmcavityL1/HD 110

    95 100128

    95 100108

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    HEAVIER LOADINGSTables for heavier loads overleaf.

    95 100148

    150-165mmcavityL1/HD 150 For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    Height h 125 145 195 195 195

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 3:1 30 30 35 32 30

    Total UDL kN 19:1 20 22 30 28 26

    Height h 115 155 190 190 212

    Thickness 2.9 2.9 3.2 3.2 3.2

    Total UDL kN 3:1 30 30 35 30 30

    Total UDL kN 19:1 20 22 30 25 26

    Height h 125 160 180 180 200

    Thickness 2.9 2.9 3.2 3.2 3.2

    Total UDL kN 3:1 30 30 35 30 30

    Total UDL kN 19:1 20 22 30 25 26

    Manufactured length 600- 1650- 2250- 3150- 3750-

    150mm increments 1500 2100 3000 3600 4050

    Manufactured length 600- 1650- 2250- 3150- 3750-

    150mm increments 1500 2100 3000 3600 4050

    Manufactured length 600- 1650- 2250- 3150- 3750-

    150mm increments 1500 2100 3000 3600 4050

    hnominal

    hnominal

    hnominal

    Blockwork built tight against inner faceof the lintel. Place mortar bed on topof blockwork before floor units are laidto provide even distribution of load.Lintels may be propped to facilitate

    speed of construction. See LintelInstallation on page 12.

    L1/HDHEAVY DUTY LOAD

  • 8/9/2019 IG intels brochure

    24/88

    LINTELGUIDE

    24

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    Height h 171 171 209 209

    Thickness 3.2 3.2 3.2 3.2

    Total UDL kN 3:1 50 50 55 50

    Total UDL kN 19:1 45 45 45 40

    Height h 167 167 205 205

    Thickness 3.2 3.2 3.2 3.2

    Total UDL kN 3:1 50 50 55 50

    Total UDL kN 19:1 45 45 45 40

    Height h 163 163 203 203

    Thickness 3.2 3.2 3.2 3.2

    Total UDL kN 3:1 50 50 55 50

    Total UDL kN 19:1 45 45 45 40

    Manufactured length 600- 1650- 1950- 2250-

    150mm increments 1500 1800 2100 2700

    Manufactured length 600- 1650- 1950- 2250-

    150mm increments 1500 1800 2100 2700

    Manufactured length 600- 1650- 1950- 2250-

    150mm increments 1500 1800 2100 2700

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Cavity Wall

    Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 100mm

    90-105mmcavityL1/XHD 100

    95 10088

    For cavity widths 90-105mm

    70-85mmcavity

    95 10048

    95 10068

    50-65mmcavity

    For cavity widths 70-85mmL1/XHD 75

    For cavity widths 50-65mmL1/XHD 50

    hnominal

    hnominal

    hnominal

  • 8/9/2019 IG intels brochure

    25/88

    www.iglintels.com

    25

    L1/XHD 130

    110-125mmcavityL1/XHD 110

    95 100128

    95 100108

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    HEAVIER LOADINGSTables for heavier loads overleaf.

    95 100148

    hnominal

    hnominal

    hnominal

    150-165mmcavityL1/XHD 150 For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    Height h 145 145 195

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Height h 155 155 212

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Height h 160 160 200

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    Blockwork built tight against inner faceof the lintel. Place mortar bed on topof blockwork before floor units are laidto provide even distribution of load.Lintels may be propped to facilitate

    speed of construction. See LintelInstallation on page 12.

    L1/XHDHEAVY DUTY LOAD

  • 8/9/2019 IG intels brochure

    26/88

    LINTELGUIDE

    26

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Cavity Wall

    Extra Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 100mm

    90-105mmcavityL5/ 100

    95 10088

    For cavity widths 90-105mm

    70-85mmcavity

    95 10048

    95 10068

    50-65mmcavity

    For cavity widths 70-85mmL5/ 75

    For cavity widths 50-65mmL5/ 50

    Height h 229 229 229

    Thickness 2.5 3.0 3.0

    Total UDL kN 19:1 48 50 38

    Height h 229 229 229

    Thickness 2.5 3.0 3.0

    Total UDL kN 19:1 48 50 38

    Height h 229 229 229

    Thickness 2.5 3.0 3.0

    Total UDL kN 19:1 48 50 38

    Manufactured length 600- 2550- 3750-

    150mm increments 2400 3600 4800

    Manufactured length 600- 2550- 3750-

    150mm increments 2400 3600 4800

    Manufactured length 600- 2550- 3750-

    150mm increments 2400 3600 4800

    hnominal

    hnominal

    hnominal

  • 8/9/2019 IG intels brochure

    27/88

    www.iglintels.com

    27

    L5/ 130

    110-125mmcavityL5/ 110

    95 100128

    95 100108

    hnominal

    hnominal

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    HEAVIER LOADINGSTables for heavier loads overleaf.

    95 100148

    150-165mmcavityL5/ 150 For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    Height h 229 229 229

    Thickness 2.5 3.0 3.0

    Total UDL kN 19:1 48 50 38

    Height h 229 229 229

    Thickness 2.5 3.0 3.0

    Total UDL kN 19:1 48 50 38

    Height h 229 229 229

    Thickness 2.5 3.0 3.0

    Total UDL kN 19:1 48 50 38

    Manufactured length 600- 2550- 3750-

    150mm increments 2400 3600 4800

    Manufactured length 600- 2550- 3750-

    150mm increments 2400 3600 4800

    Manufactured length 600- 2550- 3750-

    150mm increments 2400 3600 4800

    hnominal

    To achieve loading figures lintelmust be built in with blockwork asshown. Ensure all perpendicularand horizontal joints are filled withmortar. Place mortar bed on top of

    blockwork before floor units are laidto provide even distribution of load.Lintels may be propped to facilitatespeed of construction. See LintelInstallation on page 12.

    L5EXTRA HEAVY DUTY LOAD

  • 8/9/2019 IG intels brochure

    28/88

    LINTELGUIDE

    28

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Cavity Wall

    Extra Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 100mm

    90-105mmcavityL5/XHD 100

    95 10088

    For cavity widths 90-105mm

    70-85mmcavity

    95 10048

    95 10068

    50-65mmcavity

    For cavity widths 70-85mmL5/XHD 75

    For cavity widths 50-65mmL5/XHD 50

    Height h 235 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 100 90 80 65 50

    Height h 235 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 100 90 80 65 50

    Height h 235 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 100 90 80 65 50

    Manufactured length 600- 1950- 2550- 3150- 3750-

    150mm increments 1800 2400 3000 3600 4800-

    Manufactured length 600- 1950- 2550- 3150- 3750-

    150mm increments 1800 2400 3000 3600 4800-

    Manufactured length 600- 1950- 2550- 3150- 3750-

    150mm increments 1800 2400 3000 3600 4800-

    hnominal

    hnominal

    hnominal

  • 8/9/2019 IG intels brochure

    29/88

    www.iglintels.com

    29

    L5/XHD 130

    110-125mmcavityL5/XHD 110

    95 100128

    95 100108

    hnominal

    hnominal

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    HEAVIER LOADINGSTables for heavier loads overleaf.

    95 100148

    150-165mmcavityL5/XHD 150 For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    Height h 235 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 100 90 80 65 50

    Height h 235 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 100 90 80 65 50

    Height h 235 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 100 90 80 65 50

    Manufactured length 600- 1950- 2550- 3150- 3750-

    150mm increments 1800 2400 3000 3600 4800-

    Manufactured length 600- 1950- 2550- 3150- 3750-

    150mm increments 1800 2400 3000 3600 4800-

    Manufactured length 600- 1950- 2550- 3150- 3750-

    150mm increments 1800 2400 3000 3600 4800-

    hnominal

    To achieve loading figures lintelmust be built in with blockwork asshown. Ensure all perpendicularand horizontal joints are filled withmortar. Place mortar bed on top of

    blockwork before floor units are laidto provide even distribution of load.Lintels may be propped to facilitatespeed of construction. See LintelInstallation on page 12.

    L5/XHDEXTRA HEAVY DUTY LOAD

  • 8/9/2019 IG intels brochure

    30/88

    LINTELGUIDE

    30

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    263

    283

    207

    207

    243

    207

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Cavity Wall

    Extreme Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 100mm

    90-105mmcavityL6/ 100 For cavity widths 90-105mm

    70-85mmcavity

    50-65mmcavity

    For cavity widths 70-85mmL6/ 75

    For cavity widths 50-65mmL6/ 50

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

  • 8/9/2019 IG intels brochure

    31/88

    www.iglintels.com

    31

    303

    323

    343

    207

    207

    207

    L6/ 130

    110-125mmcavityL6/ 110

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    150-165mmcavityL6/ 150 For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    To achieve loading figures lintel mustbe laterally restrained. Lintels maybe propped to facilitate speed ofconstruction. See Lintel Installationon page 12. Galvanised steel flange

    to outer leaf.

    L6EXTREME LOAD

  • 8/9/2019 IG intels brochure

    32/88

    LINTELGUIDE

    32

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    95

    95

    95

    125

    125

    125

    hnominal

    h

    nominal

    68

    88

    48

    hnominal

    For cavity widths 90-105mmL1/S 100 WIL

    For 150mm wide inner leaf blockwork.

    Height h 82 107 142 177 191 187 187

    Thickness 1.6 2.0 2.0 2.6 3.2 3.2 3.4

    Total UDL kN 3:1 13 17 23 24 30 27 26

    Total UDL kN 19:1 11 14 18 18 26 25 21

    Manufactured length 600- 1350- 1950- 2550- 3150- 3750- 4200

    150mm increments 1200 1800 2400 3000 3600 4050

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Inner Leaf - Cavity Wall

    Standard Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 125mm - 150mm

    90-105mmcavity

    For cavity widths 50-65mm

    For cavity widths 70-85mm 70-85mmcavity

    L1/S 50 WIL

    L1/S 75 WIL

    50-65mmcavity

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    Height h 91 96 110 136 162 172 196 196 196

    Thickness 1.6 2.0 2.0 2.0 2.0 2.6 3.2 3.2 3.4

    Total UDL kN 3:1 12 12 15 20 24 28 30 27 26

    Total UDL kN 19:1 10 10 13 18 20 21 26 25 22

    Height h 93 90 100 134 158 167 192 192 192

    Thickness 1.6 2.0 2.0 2.0 2.0 2.6 3.2 3.2 3.4

    Total UDL kN 3:1 12 13 20 19 24 27 30 27 26

    Total UDL kN 19:1 10 11 17 17 20 21 26 25 22

    Manufactured length 600- 1500- 1800 1950- 2250- 2550- 3150- 3750- 4200

    150mm increments 1350 1650 2100 2400 3000 3600 4050

    Manufactured length 600- 1500- 1800 1950- 2250- 2550- 3150- 3750- 4200

    150mm increments 1350 1650 2100 2400 3000 3600 4050

  • 8/9/2019 IG intels brochure

    33/88

    www.iglintels.com

    33

    L1/S 130 WIL

    110-125mmcavityL1/S 110 WIL

    95

    95

    95

    125

    125

    125

    108

    128

    148

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    Lintels may be propped to facilitatespeed of construction. See LintelInstallation on page 12. Inner leaf

    block should not overhang the lintelflange by more than 25mm.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L1/S WIL

    STANDARD LOADWIDE INNER LEAF

    150-165mmcavityL1/S 150 WIL For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    150mm

    Inner

    Lea

    f

    Height h 95 107 142 185 185

    Thickness 2.0 2.0 2.6 2.9 3.2

    Total UDL kN 3:1 13 17 23 24 24

    Total UDL kN 19:1 11 14 18 18 17

    Height h 90 118 178 178 178

    Thickness 2.0 2.0 2.6 2.9 3.2

    Total UDL kN 3:1 13 17 23 24 24

    Total UDL kN 19:1 11 14 18 18 17

    Height h 88 115 168 168 168

    Thickness 2.0 2.0 2.6 2.9 3.2

    Total UDL kN 3:1 13 17 23 24 24

    Total UDL kN 19:1 11 14 18 18 17

    Manufactured length 600- 1350- 1950- 2250- 3150-

    150mm increments 1200 1800 2100 3000 4050

    Manufactured length 600- 1350- 1950- 2250- 3150-

    150mm increments 1200 1800 2100 3000 4050

    Manufactured length 600- 1350- 1950- 2250- 3150-

    150mm increments 1200 1800 2100 3000 4050

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    hnominal

    hnominal

    hn

    ominal

  • 8/9/2019 IG intels brochure

    34/88

    LINTELGUIDE

    34

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    95

    95

    95

    125

    125

    125

    68

    88

    48

    For cavity widths 90-105mmL1/HD 100 WIL

    For 150mm wide inner leaf blockwork.

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Inner Leaf - Cavity Wall

    Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 125mm - 150mm

    90-105mmcavity

    For cavity widths 50-65mm

    For cavity widths 70-85mm 70-85mmcavity

    L1/HD 50 WIL

    L1/HD 75 WIL

    50-65mmcavity

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    Height h 95 110 161 161 200

    Thickness 2.9 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 25 35 30 36

    Total UDL kN 19:1 17 22 27 25 32

    Height h 130 155 192 192

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 35 30 36

    Total UDL kN 19:1 17 27 25 32

    Height h 113 144 165 188

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 35 30 36

    Total UDL kN 19:1 17 27 25 32

    Manufactured length 600- 1350- 1650- 1950- 2250-

    150mm increments 1200 1500 1800 2100 2700

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

    hnominal

    hnominal

    hnominal

  • 8/9/2019 IG intels brochure

    35/88

    www.iglintels.com

    35

    L1/HD 130 WIL

    110-125mmcavityL1/HD 110 WIL

    95

    95

    95

    125

    125

    125

    108

    128

    148

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    Lintels may be propped to facilitatespeed of construction. See LintelInstallation on page 12. Inner leaf block

    should not overhang the lintel flangeby more than 25mm. Blockwork builttight against inner face of the lintel.Place mortar bed on top of blockworkbefore floor units are laid to provideeven distribution of load.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L1/HD WIL

    HEAVY DUTY LOADWIDE INNER LEAF

    150-165mmcavityL1/HD 150 WIL For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    150mm

    Inner

    Lea

    f

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    Height h 131 148 195 195

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 30 30 36

    Total UDL kN 19:1 17 25 25 32

    Height h 115 155 190 212

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 30 30 36

    Total UDL kN 19:1 17 25 25 32

    Height h 113 148 168 168

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 30 30 36

    Total UDL kN 19:1 17 25 25 32

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

    hnominal

    hnominal

    hnominal

  • 8/9/2019 IG intels brochure

    36/88

    LINTELGUIDE

    36

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    95

    95

    95

    125

    125

    125

    68

    88

    48

    For cavity widths 90-105mmL1/XHD 100 WIL

    For 150mm wide inner leaf blockwork.

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Inner Leaf - Cavity Wall

    Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 125mm - 150mm

    90-105mmcavity

    For cavity widths 50-65mm

    For cavity widths 70-85mm 70-85mmcavity

    L1/XHD 50 WIL

    L1/XHD 75 WIL

    50-65mmcavity

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    hnominalHeight h 161 196 196

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Height h 155 192 192

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Height h 165 188 188

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    hnominal

    hnominal

  • 8/9/2019 IG intels brochure

    37/88

  • 8/9/2019 IG intels brochure

    38/88

    LINTELGUIDE

    38

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    95

    95

    95

    125

    125

    125

    68

    88

    48

    For cavity widths 90-105mmL5/100 WIL

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Inner Leaf - Cavity Wall

    Extra Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 125mm - 150mm

    90-105mmcavity

    For cavity widths 50-65mm

    For cavity widths 70-85mm 70-85mmcavity

    L5/50 WIL

    L5/75 WIL

    50-65mmcavity

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    hnominal

    hnominal

    hnominal

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

  • 8/9/2019 IG intels brochure

    39/88

    www.iglintels.com

    39

    hnominal

    hnominal

    L5/130 WIL

    110-125mmcavityL5/110 WIL

    95

    95

    95

    125

    125

    125

    108

    128

    148

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    Lintels may be propped to facilitate speedof construction. See Lintel Installationon page 12. Inner leaf block should notoverhang the lintel flange by more than25mm. Blockwork built tight against innerface of the lintel. Place mortar bed on topof blockwork before floor units are laid toprovide even distribution of load.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L5/ WIL

    EXTRA HEAVY DUTY LOADWIDE INNER LEAF

    150-165mmcavityL5/150 WIL For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    150mm

    Inner

    Lea

    f

    For 150mm wide inner leaf blockwork.

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    For 150mm wide inner leaf blockwork.

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    For 150mm wide inner leaf blockwork.

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    hnominal

  • 8/9/2019 IG intels brochure

    40/88

    LINTELGUIDE

    40

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    95

    95

    95

    125

    125

    125

    68

    88

    48

    For cavity widths 90-105mmL5/XHD 100 WIL

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Inner Leaf - Cavity Wall

    Extra Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 125mm - 150mm

    90-105mmcavity

    For cavity widths 50-65mm

    For cavity widths 70-85mm 70-85mmcavity

    L5/XHD 50 WIL

    L5/XHD 75 WIL

    50-65mmcavity

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    hnominal

    hnominal

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Manufactured length 600- 1950- 2550- 3150-

    150mm increments 1800 2400 3000 3600

    Manufactured length 600- 1950- 2550- 3150-

    150mm increments 1800 2400 3000 3600

    Manufactured length 600- 1950- 2550- 3150-

    150mm increments 1800 2400 3000 3600

    hnominal

  • 8/9/2019 IG intels brochure

    41/88

    www.iglintels.com

    41

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    hnominal

    hnominal

    L5/XHD 130 WIL

    110-125mmcavityL5/XHD 110 WIL

    95

    95

    95

    125

    125

    125

    108

    128

    148

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    Lintels may be propped to facilitate speedof construction. See Lintel Installationon page 12. Inner leaf block should notoverhang the lintel flange by more than25mm. Blockwork built tight against innerface of the lintel. Place mortar bed on topof blockwork before floor units are laid toprovide even distribution of load.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L5/XHD WIL

    EXTRA HEAVY DUTY LOADWIDE INNER LEAF

    150-165mmcavityL5/XHD 150 WIL For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    150mm

    Inner

    Lea

    f

    hnominal

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Manufactured length 600- 1950- 2550- 3150-

    150mm increments 1800 2400 3000 3600

    Manufactured length 600- 1950- 2550- 3150-

    150mm increments 1800 2400 3000 3600

    Manufactured length 600- 1950- 2550- 3150-

    150mm increments 1800 2400 3000 3600

  • 8/9/2019 IG intels brochure

    42/88

  • 8/9/2019 IG intels brochure

    43/88

    www.iglintels.com

    43

    368

    207

    348

    207

    328

    207

    L6/130 WIL

    110-125mmcavityL6/110 WIL

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    To achieve loading figures lintelmust be laterally restrained.Lintels may be propped tofacilitate speed of construction.See Lintel Installation on page 12.

    L6/ WIL

    EXTREME LOADWIDE INNER LEAF

    150-165mmcavityL6/150 WIL For cavity widths 150-165mm

    102mm

    Ou

    ter

    Lea

    f

    150mm

    Inner

    Lea

    f

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

    For 150mm wide inner leaf blockwork.

  • 8/9/2019 IG intels brochure

    44/88

    LINTELGUIDE

    44

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    95 21048

    hnominal

    Cavity widths90-105mmL1/S 100 WIL 215

    DAMP PROOFING Provide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Inner Leaf - Cavity Wall

    Standard Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    102mm 215mm

    90-105mmcavity

    Cavity widths50-65mm

    Cavity widths70-85mm 70-85mmcavity

    L1/S 50 WIL 215

    L1/S 75 WIL 215

    50-65mmcavity

    Height h 78 104 121 146 171 209

    Thickness 2.5 2.5 2.5 2.5 2.5 2.9

    Total UDL kN 3:1 25 25 25 30 35 40

    Total UDL kN 19:1 20 20 20 25 30 35

    Fin Height 100 120 140 175 225 225

    Height h 100 117 142 168 204

    Thickness 2.5 2.5 2.5 2.5 2.9

    Total UDL kN 3:1 25 25 30 35 40

    Total UDL kN 19:1 20 20 25 30 35

    Fin Height 120 140 175 225 225

    Height h 90 105 138 163 171 200

    Thickness 2.5 2.5 2.5 2.5 2.5 2.9

    Total UDL kN 3:1 25 25 30 35 35 40

    Total UDL kN 19:1 20 20 25 30 30 35

    Fin Height 100 120 175 225 225 225

    Manufactured length 600- 1350- 1650- 1950- 2250- 3150-

    150mm increments 1200 1500 1800 2100 3000 4050

    Manufactured length 600- 1800 1950- 2250- 3150-

    150mm increments 1650 2100 3000 4050

    Manufactured length 600- 1500- 1800- 2250- 2850- 3150-

    150mm increments 1350 1650 2100 2700 3000 4050

    For 215mm wide inner leaf blockwork.

    For 215mm wide inner leaf blockwork.

    For 215mm wide inner leaf blockwork.

    95

    95

    210

    210

    68

    88

    h

    nominal

    hno

    minal

  • 8/9/2019 IG intels brochure

    45/88

    www.iglintels.com

    45

    L1/S 130 WIL 215

    L1/S 110 WIL 215 Cavity widths110-125mm

    Cavity widths130-145mm

    Lintels may be propped to facilitatespeed of construction. See LintelInstallation on page 12. Inner leaf

    block should not overhang the lintelflange by more than 25mm.

    HEAVIER LOADINGS Tables for heavier loads overleaf.

    L1/S WIL 215

    STANDARD LOADWIDE INNER LEAF

    L1/S 150 WIL 215 Cavity widths150-165mm

    102mm

    Ou

    ter

    Lea

    f

    215mm

    Inner

    Lea

    f

    95

    95

    95

    210

    210

    210

    108

    128

    148

    110-125mmcavity

    130-145mmcavity

    Height h 95 121 145 195 195

    Thickness 2.5 2.5 2.5 2.5 2.9

    Total UDL kN 3:1 25 25 30 35 40

    Total UDL kN 19:1 20 20 25 30 35

    Fin Height 120 140 175 225 225

    Height h 103 128 190 190 190

    Thickness 2.5 2.5 2.5 2.5 2.9

    Total UDL kN 3:1 25 25 30 35 40

    Total UDL kN 19:1 20 20 25 30 35

    Fin Height 120 140 175 225 225

    Height h 103 128 190 190 190

    Thickness 2.5 2.5 2.5 2.5 2.9

    Total UDL kN 3:1 25 25 30 35 40

    Total UDL kN 19:1 20 20 25 30 35

    Fin Height 120 140 175 225 225

    Manufactured length 600- 1650- 1950- 2250- 3150-

    150mm increments 1500 1800 2100 3000 4050

    Manufactured length 600- 1650- 1950- 2250- 3150-

    150mm increments 1500 1800 2100 3000 4050

    Manufactured length 600- 1650- 1950- 2250- 3150-

    150mm increments 1500 1800 2100 3000 4050

    For 215mm wide inner leaf blockwork.

    For 215mm wide inner leaf blockwork.

    For 215mm wide inner leaf blockwork.

    hnominal

    h

    nominal

    hnom

    inal

    150-165mmcavity

  • 8/9/2019 IG intels brochure

    46/88

  • 8/9/2019 IG intels brochure

    47/88

  • 8/9/2019 IG intels brochure

    48/88

  • 8/9/2019 IG intels brochure

    49/88

    www.iglintels.com

    49

    L6/130 WIL 215

    L6/110 WIL 215 Cavity widths110-125mm

    Cavity widths130-145mm

    To achieve loading figures lintelmust be laterally restrained.Lintels may be propped tofacilitate speed of construction.See Lintel Installation on page 12.

    L6/ WIL 215

    EXTREME LOADWIDE INNER LEAF

    L6/150 WIL 215 Cavity widths150-165mm

    102mm

    Ou

    ter

    Lea

    f

    215mm

    Inner

    Lea

    f

    110-125mmcavity

    130-145mmcavity

    150-165mmcavity

    For 215mm wide inner leaf blockwork.

    For 215mm wide inner leaf blockwork.

    For 215mm wide inner leaf blockwork.

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    End Bearing 200 200 200 200 200 200

    Total UDL kN 19:1 80 70 62 55 45 40

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    Manufactured length (mm) 600- 5200 5400 5800 6200 6600

    to customer requirements 4800

    413

    433

    453

    207

    207

    207

  • 8/9/2019 IG intels brochure

    50/88

    LINTELGUIDE

    50

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    120

    120

    120

    100

    100

    100

    h

    nominal

    hnominal

    68

    88

    48

    hnominal

    For cavity widths 90-105mmL1/S 100 WOL

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Outer Leaf - Cavity Wall

    Standard Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    125mm - 150mm 100mm

    90-105mmcavity

    For cavity widths 50-65mm

    For cavity widths 70-85mm 70-85mmcavity

    L1/S 50 WOL

    L1/S 75 WOL

    50-65mmcavity

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    Height h 110 122 172 200 200 200

    Thickness 2.5 2.5 2.5 2.9 2.9 3.2

    Total UDL kN 3:1 14 15 23 30 32 30

    Total UDL kN 19:1 11 13 18 22 30 26

    Height h 106 118 168 192 192 192

    Thickness 2.5 2.5 2.5 2.9 2.9 3.2

    Total UDL kN 3:1 14 15 23 30 32 30

    Total UDL kN 19:1 11 13 18 22 30 26

    Height h 93 110 162 188 188 188

    Thickness 2.5 2.5 2.5 2.9 2.9 3.2

    Total UDL kN 3:1 14 15 23 30 32 30

    Total UDL kN 19:1 11 13 18 22 30 26

    Manufactured length 600- 1500- 1800- 2250- 2850- 3150-

    150mm increments 1350 1650 2100 2700 3000 3600

    Manufactured length 600- 1500- 1800- 2250- 2850- 3150-

    150mm increments 1350 1650 2100 2700 3000 3600

    Manufactured length 600- 1500- 1800- 2250- 2850- 3150-

    150mm increments 1350 1650 2100 2700 3000 3600

  • 8/9/2019 IG intels brochure

    51/88

    www.iglintels.com

    51

    For cavity widths 150-165mm

    L1/S 130 WOL

    110-125mmcavityL1/S 110 WOL

    130-145mmcavity

    For cavity widths 110-125mm

    For cavity widths 130-145mm

    To achieve loading figures lintelmust be built in with blockworkas shown. Maximum overhang

    of 30mm on outer leaf. Lintelsmay be propped to facilitatespeed of construction. See LintelInstallation on page 12.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L1/S WOL

    STANDARD LOADWIDE OUTER LEAF

    150-165mmcavityL1/S 150 WOL

    140mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    120

    120

    120

    100

    100

    100

    hnominal

    108

    128

    148

    h

    nominal

    hnominal

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    Height h 95 107 142 185 185 185

    Thickness 2.5 2.5 2.5 2.9 3.2 3.2

    Total UDL kN 3:1 14 15 23 30 32 30

    Total UDL kN 19:1 11 13 18 22 30 26

    Height h 90 118 178 178 178 178

    Thickness 2.5 2.5 2.5 2.9 3.2 3.2

    Total UDL kN 3:1 14 15 23 30 32 30

    Total UDL kN 19:1 11 13 18 22 30 26

    Height h 95 107 168 168 168 168

    Thickness 2.5 2.5 2.5 2.9 3.2 3.2

    Total UDL kN 3:1 14 15 23 30 32 30

    Total UDL kN 19:1 11 13 18 22 30 26

    Manufactured length 600- 1500- 1800- 2250- 2850- 3150-

    150mm increments 1350 1650 2100 2700 3000 3600

    Manufactured length 600- 1500- 1800- 2250- 2850- 3150-

    150mm increments 1350 1650 2100 2700 3000 3600

    Manufactured length 600- 1500- 1800- 2250- 2850- 3150-

    150mm increments 1350 1650 2100 2700 3000 3600

  • 8/9/2019 IG intels brochure

    52/88

  • 8/9/2019 IG intels brochure

    53/88

    www.iglintels.com

    53

    Cavity widths150-165mm

    L1/HD 130 WOL

    110-125mmcavityL1/HD 110 WOL

    130-145mmcavity

    Cavity widths110-125mm

    Cavity widths130-145mm

    To achieve loading figures lintelmust be built in with blockworkas shown. Maximum overhang

    of 30mm on outer leaf. Lintelsmay be propped to facilitatespeed of construction. See LintelInstallation on page 12.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L1/HD WOL

    HEAVY DUTY LOADWIDE OUTER LEAF

    150-165mmcavityL1/HD 150 WOL

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    140mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    120

    120

    120

    100

    100

    100

    hnominal

    108

    128

    148

    h

    nominal

    hnominal

    Height h 112 132 182 182

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 30 30 36

    Total UDL kN 19:1 17 25 25 32

    Height h 103 143 178 178

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 30 30 36

    Total UDL kN 19:1 17 25 25 32

    Height h 113 148 168 168

    Thickness 2.9 2.9 2.9 3.2

    Total UDL kN 3:1 20 30 30 36

    Total UDL kN 19:1 17 25 25 32

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

    Manufactured length 600- 1500- 1950- 2250-

    150mm increments 1350 1800 2100 2700

  • 8/9/2019 IG intels brochure

    54/88

    LINTELGUIDE

    54

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    Height h 161 196 196

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Height h 155 192 192

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    Height h 165 188 188

    Thickness 3.2 3.2 3.2

    Total UDL kN 3:1 45 45 50

    Total UDL kN 19:1 40 40 40

    120

    120

    120

    100

    100

    100

    68

    88

    48

    Cavity widths90-105mmL1/XHD 100 WOL

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Outer Leaf - Cavity Wall

    Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    125mm - 150mm 100mm

    90-105mmcavity

    Cavity widths50-65mm

    Cavity widths70-85mm 70-85mmcavity

    L1/XHD 50 WOL

    L1/XHD 75 WOL

    50-65mmcavity

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    Manufactured length 600- 1650- 1950-

    150mm increments 1500 1800 2100

    hnominal

    hnominal

    hnominal

  • 8/9/2019 IG intels brochure

    55/88

  • 8/9/2019 IG intels brochure

    56/88

  • 8/9/2019 IG intels brochure

    57/88

    www.iglintels.com

    57

    110-125mmcavity

    130-145mmcavity

    Cavity widths110-125mm

    Cavity widths130-145mm

    To achieve loading figures lintel must bebuilt in with blockwork as shown. Maximumoverhang of 30mm on outer leaf. Ensure

    all perpendicular and horizontal joints arefilled with mortar. Place mortar bed on topof blockwork before floor units are laid toprovide even distribution of load. Lintelsmay be propped to facilitate speed ofconstruction. See Lintel Installation on page 12.

    HEAVIER LOADINGSTables for heavier loads overleaf.

    L5/ WOL

    EXTRA HEAVY DUTY LOADWIDE OUTER LEAF

    150-165mmcavity

    L5/110 WOL

    L5/130 WOL

    L5/150 WOL

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    140mm

    Ou

    ter

    Lea

    f

    100mm

    Inner

    Lea

    f

    120

    120

    120

    100

    100

    100

    108

    128

    148

    hnominal

    hnominal

    hnominal

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Height h 229 229 229 229 229

    Thickness 2.9 2.9 2.9 3.2 3.2

    Total UDL kN 19:1 70 60 50 45 40

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    Manufactured length 600- 1650- 2250- 3150- 4200-

    150mm increments 1500 2100 3000 4050 4800

    Cavity widths150-165mm

  • 8/9/2019 IG intels brochure

    58/88

    LINTELGUIDE

    58

    If lintels are required to carryloads not indicated on theload tables, please contactIGs Technical Department.

    Fax Back Enquiry Forms are

    also available for download.

    LINTEL HOTLINE

    01633 486486

    www.iglintels.com/technical

    IG Fastrack CAD Databaseisaccessible from iglintels.com

    L5/XHD 100 WOL

    120

    120

    120

    100

    100

    100

    68

    88

    48

    Cavity widths90-105mm

    DAMP PROOFINGProvide a damp proof course over all lintels. Please see IG installation details for guidance on page 12.

    Wide Outer Leaf - Cavity Wall

    Extra Heavy Duty Load

    Cavity widths from50mm to 165mm

    OUTER LEAF INNER LEAF

    125mm - 150mm 100mm

    90-105mmcavity

    Cavity widths50-65mm

    Cavity widths70-85mm 70-85mmcavity

    L5/XHD 50 WOL

    L5/XHD 75 WOL

    50-65mmcavity

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    For 150mm wide outer leaf blockwork/stonework.

    hnominal

    hnominal

    hnominal

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Height h 235 235 235 235

    Thickness Inner 5.0 5.0 5.0 5.0

    Thickness Outer 2.9 2.9 2.9 3.2

    Total UDL kN 19:1 100 90 80 65

    Manufactured length 600