Industrial Controls: Surion. Surion, a new manual motor starter line. Designed for switching and protecting three phase induction motors of up to 30kW@400VAC and for loads with rated currents up to 63A Complete range of modular auxiliaries designed to be mounted without any tools - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Industrial Controls: Surion

Page 2: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Page 3: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Designed for switching and protecting three phase induction motors of up to 30kW@400VAC and for loads with rated currents up to 63A

Complete range of modular auxiliaries designed to be mounted without any tools

Fuseless compact starter with necessary accessories in four different frame sizes linking the line with the rest of control devices (contactors M and CL, and overload relays)

Surion, a new manual motor starter line

Page 4: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Manual motor starters

Auxiliary devices

Accessories

Fuseless starter range (links, baseplates, busbars, etc. ...)

Complete Range

Page 5: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Frame 1 : GPS1BH / GPS1MH

Rated up to 32A

High breaking capacity

Frame 2 : GPS2BS / GPS2MS

Rated up to 63A

Standard breaking capacity

Frame 2 : GPS2BH / GPS2MH

Rated up to 63A

High breaking capacity

Frame 1 : GPS1BS / GPS1MS

Rated up to 32A

Standard breaking capacity

Complete Range

Page 6: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Frame 1 : GPS1BS / GPS1MS

Rated up to 32A Standard breaking capacity

Frame 1 : GPS1BH / GPS1MH

Rated up to 32A High breaking capacity

Frame 2 : GPS2BH / GPS2MH

Rated up to 63A High breaking capacity

Frame 2 : GPS2BS / GPS2MS

Rated up to 63A Standard breaking capacity

Complete Product Range

Page 7: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Two different frames rated up to 32A and 63ARocker level and rotary actuator mechanismThermal / magnetic protection and magnetic protection only Standards / approvalsWorld wide availableComplete range of modular accessories suitable to be used with all the lineShort-circuit proof, 100 / 50kA @400V ACShort-circuit trip is set to 13 times the Ie maxThermal (set by the current dial) protection class 10Coordination with the M and CL contactor range for fuseless starter applicationsTerminal screw for pozidriv 2 screwdriverON / OFF / Tripping position available in all range (on tripping conditions re-set before set)

Main Features

Page 8: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Worldwide availability, same line, same catalogue number and brand allowing our international customers to order same product throughout the world

Catalogue Number Structure

Page 9: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Overall 45mm widthMax. rated current 32ASuitable for 3-pole induction motors up to 15kW@400V ACLowest setting range: 0,10 ... 0,16AHighest setting range: 24 ... 32AOperation: rocker levelProtection degree IP20Mechanical / electrical endurance 100.000 operationsTotal number of ranges: 15Modular number of accessoriesFuseless starters: linked up to CL45Thermal and magnetic protection and magnetic onlyBreaking capacity @400V: 100kA up to 10A, 50kA up to 13A and 25kA up to32A

Features of GPS1*S (standard breaking capacity)

Page 10: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Overall 45mm widthMax. rated current 32ASuitable for 3-pole induction motors up to 15kW@400V ACLowest setting range: 0,10 ... 0,16AHighest setting range: 24 ... 32AOperation: rotary mechanismProtection degree IP20Mechanical / electrical endurance 100.000 operationsTotal number of ranges: 15Modular number of accessoriesFuseless starters: linked up to CL45Thermal and magnetic protection and magnetic onlyBreaking capacity: 100kA up to 13A and 50kA up to 32A

Features of GPS1*H (high breaking capacity)

Page 11: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Overall 55mm widthMax. rated current 63ASuitable for 3-pole induction motors up to 30kW@400V ACLowest setting range: 6 ... 10AHighest setting range: 45 ... 63AOperation: rotary mechanismProtection degree IP10 (IP20 with the correspondent acc.)Mechanical / electrical endurance 50.000 / 25.000Total number of ranges: 9Modular number of accessoriesFuseless starters: linked up to CL07Thermal and magnetic protection and magnetic onlyBreaking capacity: 100kA up to 10A , 50kA up to 13A and 25kA up to 63A

Features of GPS2*S (standard breaking capacity)

Page 12: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Overall 55mm widthMax. rated current 63ASuitable for 3p induction motors up to 30kW@400V ACLowest setting range: 6 ... 10AHighest setting range: 45 ... 63AOperation: rotary mechanismProtection degree IP10 (IP20 with the correspondent acc.)Mechanical / electrical endurance 50.000 / 25.000Total number of ranges: 9Modular number of accessoriesFuseless starters: linked up to CL07Thermal and magnetic protection and magnetic onlyBreaking capacity: 100kA up to 13A and 50kA up to 63A

Features of GPS2*H (high breaking capacity)

Page 13: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Adjustment is sealed by a transparent plastic coverSetting scale for motor currentSetting rangeInstantaneous short circuit releaseManufacturing dateName plateTripping test indicationCatalog numberBrandClear switch setting range indicator throughout the rocker or rotary operating mechanism OFF / TRIPPED / ON "

Frontal Cover

Page 14: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Terminals: - screw terminal (GPS1) box terminal (GPS2)Remove the plastic cover to fit the frontal auxiliary contact block or alarm blockScrewhead PZ2 & slotted combinationTerminal numbering

Frontal Cover

Page 15: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

IEC label-left side (UL label-right side)Setting rangeApprovals / standardsUtilization categoryInsulation voltage / rated frequencyElectrical drawing :thermal + magnetic or magnetic onlyTerminal capacityScrew head tightening torqueBack up fuse required only if higher short circuitcurrents occurring at the installation pointIcu ultimate short-circuit currentIcs service short-circuit current

Side Labels

Page 16: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Two different actuators: rocker and rotary handle up to 32A and rotary handle only up to 63A with ON / OFF / Trip switching indicator positionClear identification of the status guaranteeing total protection to the usersUnder tripping condition reset it before setContacts can be open mechanically by operating the trip test mechanism (confirming sequence check of the alarm switch)Trip operating to open the contacts can not be prevented even when the handle is forced in the ON position (Trip Free)

ON / OFF / Tripped Position

Page 17: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Ambient temperature:operating temperature: -25°C to +60°Cstorage temperature: -40°C to +80°Ctemperature compensation: -20°C to +60°C

Humidity: not to exceed 95%Corrosion resistance:

salt fog: 90h in salt fog chamberwithout corrosion guaranteeing nocorrosion of terminals

Operating altitude: general performance up to 2000 m

Environmental Conditions

Page 18: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

TerminalsGPS1 :Screw terminal M4, self lifting type screw with clamping plateScrew head : PZ2 & slotted combinationTerminal protection : IP20Max. wire size : 6 mm² (stranded with end sleeve)GPS2 :Box terminal M6Screw head : PZ2 & slotted combinationTerminal protection : IP10 (IP20 with correspondent accessory)Max. wire size : 16 mm² (stranded with end sleeve)

Terminal open during transportation

MountingGPS1 : 35mm DIN rail mounting + accessories in panelGPS2 : 35mm DIN rail mounting or direct screw mounting (2 x M4)

Terminals and Mounting

Page 19: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Mechanical / electrical endurance (max. operational rate : 25 operation / hour)

GPS1 mechanical endurance 100.000 operationselectrical endurance 100.000 operations

GPS2 mechanical endurance 50.000 operationselectrical endurance 25.000 operations

Vibration and shock

Vibration 6g (5-150 Hz) acc. IEC 60068-2-6Shock 30g (pulse width 20ms) acc. IEC 60068-2-27

Rated insulation voltage and rated impulse withstand voltage

GPS1 Uimp = 6 kV AC

GPS2 Uimp = 8 kV AC

Performances

Page 20: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Breaking capacity

Icu : Ultimate short-circuit breaking capacity,still operational after testing with O-t-CO

Ics : Rated service short-circuit breaking capacity,suitable for normal operating after testingwith O-t-CO-t-CO

(O: off / CO: restart and off / t: time delay)

Ics = 100kA Ics = 100% IcuIcs < 100kA Ics min = 75% Icu

Short-circuit Protection

Page 21: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Short-circuit Protection

Page 22: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Short-circuit Protection

Page 23: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

The manual motor starter can be fed at the top or bottom supply terminals without any reduction of the rated values

Back-up fuses are only necessary if there is possibility of a short-circuit current higher than the values indicated on the previous chart for the ultimate short-circuit breaking capacity of the manual motor starter at the installation point of the device

Feeding

Page 24: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

The current of the motor to be protected is set on the setting scale

The short-circuit release is set at the factory to a value equivalent to 13 times the rated current of the manual motor starter

Manual motor starters with thermal overload release aredesigned in accordance with release class 10

All the Surion line is available with magnetic only protection for starter combinations (contactor + overload relay)

In case of overload the relay releases the contactor and the MMS remains closed

Motor Protection

Page 25: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Thermal release trip currentCurve apply for cold state, at operating temperature thetripping time for overload release are reduced of 25%

For single phase and DC loads the three phases must be connected in series

The magnetic release are based on the rated current Inwhich is the max. value of the setting range of the MMS

If the current is set to a lower value, the tripping current is increased by a corresponding factor

The short-circuit release is set at the factory to a valueequivalent to 13 times the rated current of the manualmotor starter

Tripping Characteristics GPS1

Page 26: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Thermal release trip currentCurve apply for cold state, at operating temperature thetripping time for overload release are reduced +/-25%

For single phase and DC loads the three phases must beconnected in series

The magnetic release are based on the rated current Inwhich is the max. value of the setting range of the MMS

If the current is set to a lower value, the tripping currentis increased by a corresponding factor

The short-circuit release is set at the factory to a valueequivalent to 13 times the rated current of the manualmotor starter

Tripping Characteristics GPS2

Page 27: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Auxiliary devices

Page 28: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

1. Auxiliary contacts1A. Frontal1B. Lateral (left or right)

2. Alarm contact block (frontal on the right)

3. Auxiliary / alarm contact (Left)

4. Short-circuit alarm contact block (Left)

5. Shunt trip (Right)

6. Undervoltage trip (Right)

7. Undervoltage release with 2NO early make aux. Contacts ( Right)

8. External handle operator

Complete Auxiliary Range

Page 29: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Catalogue Number Structure

Worldwide availability, same line, same catalogue number and brand allowing our international customers to order same product throughout the world

Page 30: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Worldwide availability, same line, same catalogue number and brand allowing our international customers to order same product throughout the world

Catalogue Number Structure

Page 31: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Single contact 1NO or 1NC

Maximum two contact blocks per manual motor starter (maintaining 45mm and 55mm overall width of the MMS)

Suitable to be used with GPS1 and GPS2

Minimum operational power : 17VDC, 5mA

Rated duty : AC15, DC13 (B300, Q300)

Frontal Auxiliary Contact Block

Electrical drawing

Page 32: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Two lateral auxiliary blocks, two left mountable and two right mountable

Three versions : 1NO+1NC, 2NO and 2NC

Maximum four (2 left + 2 right) contact blocks per module (GPS1**AR - 32A allow only two lateral blocks)

Suitable to be used with GPS1 and GPS2 (GSP1*SAR - 32A rated current max. two auxiliary contact blocks)

Minimum operational power: 17VDC, 5mA

Rated duty : AC15, DC13 (A600, P300)

Width : 9mm

Lateral Auxiliary Contact Block

Electrical drawing

Page 33: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Single contact 1NO or 1NC

Front mounting on the right side

Maximum one contact block per manual motor starter (maintaining 45mm and 55mm overall width of the MMS)

Suitable to be used with GPS1 and GPS2

Tripping for short-circuit, overload and auxiliary release

Rated duty : AC15, DC13 (B300, Q300)

Frontal Alarm Contact Block

Electrical drawing

Page 34: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Side mounting on the left, maximum one per MMSFour versions : 1NO (alarm) + 1NO (auxiliary)

1NO (alarm) + 1NC (auxiliary)1NC (alarm) + 1NO (auxiliary)1NC (alarm) + 1NC (auxiliary)

Mechanical indicator (alarm)Suitable to be used with GPS1 and GPS2Auxiliary contact : minimum operational power : 17VDC, 5mAwith rated duty : AC15, DC13 (A600, P300)Width : 9mmTripping for short-circuit, overload and auxiliary releaseAlarm contact is auto reset and with mechanical indicator

Auxiliary / Alarm Contact Block

Electrical drawing

Page 35: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Side mounting on the left, can be mounted with auxilary contact blocks or alarm / auxiliary contact blocks on the same side

Two contacts : 1NO+1NC

Mechanical indicator

Suitable to be used with GPS1 and GPS2

Width : 9mm

Tripping for short-circuit

Alarm contact auto reset with mechanical indicator

Rated duty : AC15, DC13 (A600, P300)

Short-circuit Alarm Contact Block

Electrical drawing

Page 36: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

For remote control tripping of the manual motor starter

Side mounting on the right

Suitable to be used with GPS1 and GPS2

Width : 18mm

Coil voltage : 24 to 500 VAC and 24 to 240 VDC can only be energized for short periods

Cannot be used together with the undervoltage trip or any lateral auxiliary contact block right mounted

Shunt Trip

Electrical drawing

Page 37: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

MMS operates once the undervoltage trip is energised

Trips the MMS when the voltage is interrupted and prevents theunintentional restart of the motor when the voltage is recovered

Particularly suitable for emergency stop disconnection

Side mounting on the right

Suitable to be used with GPS1 and GPS2

Width : 18mm

Coil voltage : 24 to 500 VAC

Cannot be used together with a shunt trip device or any lateral block mounted on the right side

Undervoltage Trip

Electrical drawing

Page 38: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

MMS operates once the undervoltage trip is energised

Trips the MMS when the voltage is interrupted and prevents the unintentional restart of the motor when the voltage is recoveredParticularly suitable for emergency stop disconnectionThe 2NO early make auxiliary contacts isolate the undervoltage trip from the supply on both sides when the MMS opens or tripsSide mounting on the right

Two frames (two catalog numbers), one for rocker and another for rotary actuator

Width : 18mm

Coil voltage : 24 to 500 VAC

Cannot be used together with the shunt trip

Electrical drawing

Undervoltage Trip with 2 NO early make aux. contacts

Page 39: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Electrical connections for auxiliary devices

Page 40: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Four different types :Standard (black) IP55 for GPS1*HEmergency (yellow/red) IP55 for GPS*1Standard (black) IP55 for GPS2Emergency (yellow/red) IP55 for GPS2Mounting description :

External handle operator

Page 41: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Features

Two different types : Surface mountingFlush mounting

Available only for installing MMS GPS1S*

IP41 and IP55 degree protection

PE terminal inside

Circuit-breaker is actuated via actuator membrane

Two auxiliary blocks (9 and 18 mm width) can be installed inside the enclosure

Enclosures for Surion MMS

Page 42: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Accessories

A padlock device can be fitted with 3 padlocks (OFF position)

Conversion kit from IP41 to IP55 in both type of enclosures

Mushroom button can be fitted with : Impulse functionMechanical latchKey lock

Three different colors indicator lamps with 5 voltage ranges

Enclosures for Surion MMS

Page 43: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Mounting

Inside the enclosures can be fitted :9mm lateral auxiliary block

+18mm lateral block, suitable to be used withundervoltage release for machine tool protection

A conversion kit is necessary to use a 18mm UV Early Make block (GPEUTA)

Enclosures for Surion MMS

Page 44: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Features

Busbar system provide a simply, time-saving and clearlylaid out to assembly MMS in parallel

The busbar system are suitable from 2 to 5 MMS

Fitted 9mm and 18mm auxiliary blocks is available usingthe appropriated spacing

It can be used with both GPS1* and GPS2* frames, but not together at the same busbar

Accessories

Upper feed-in terminal : upper terminal to supply the system

Busbar cover : to protect empty terminals against accidental contacts.

Busbar System

Page 45: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Fuseless Starters

Page 46: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Features

Fuseless starter is the combination of 1 MMS and one or two(reverser) contactors connected each other with a link moduleand assembly in a base plate or busbar adapter

MMS is used to provide protection against the load, usually amotor, from overloads and short-circuits, then fuses orlimiters should be avoid. The contactor is used for switchingtask mainly done in a remote distance

Power with 45mm width device is up to 11kW@400V andwith 55mm width device is up to 30kW@400V

Lateral and front mounting auxiliary blocks can be used withfuseless starter

Base plates and busbar adapter can also be used with the MMS alone

Direct A1-A2 terminal coil accessibility

Coordination type 1 and 2 @ 400/415, 500 V and 690 V

Fuseless Starters

Page 47: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Main accessories

Link modules : provide mechanical and electrical connection between MMS and contactor

Base plates : base support used to fix the MMS and contactor

Busbar adapter : base support which is capable to be fitted directly onto a busbar, with 40 and 60mm centre line spacing (thickness 5 to 10mm) and just with one operation, mechanical “click on” and electrical connections are done

Fuseless Starters

Page 48: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Combination structure (BS: Base Plate, BA: Busbar Adapter, W/O: Without)

(*) : mandatory to use BP

Fuseless Starters

Page 49: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

As a support is used a Base Plate (BP) or Busbar Adapter (BA)If MC contactors series are used BP is not required

All Manual Motor Starters are designed to be used as fuseless starters

A link between the MMS and the contactor is mandatory to secure mechanical / electrical connection

Contactors from MC series up to CL07 can be used.Also is possible a reverse assembly using a wiring kit between contactors

Contactor cover

Fuseless Starters : components

Page 50: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

MMS should be mounted on a BP with a 35mm DIN rail or on a BA with 35mm DIN rail or screws

A link is screwed at the MMS

Contactors should be rotated before the assembly to the link

Fit the contactor cover

The contactor is mounted to both the link and the BP or BA

The contactor should be screwed to both the link and the BP or BA

Fuseless Starters : mounting instruction

Page 51: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Overview Technical Data

Page 52: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Overview Technical Data

Page 53: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Overview Technical Data

Page 54: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Page 55: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Fuseless Starters

Page 56: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Fuseless Starters

Page 57: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Fuseless Starters

Page 58: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls

Fuseless Starters

Page 59: Industrial Controls: Surion

GE Power Controls Surion

GE Power Controls