User’s Guide InfraStruXure PDU

Upload: truongnguyet

Post on 14-Mar-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

User’s Guide

InfraStruXure PDU

Page 2: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Contents

Introduction ..................................................................... 1Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Initial setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Network management features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Internal Management Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Access priority for logging on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Types of user accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

How to Recover from a Lost Password . . . . . . . . . . . . . . . . . . . . . . . 3

Watchdog Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Network interface watchdog mechanism . . . . . . . . . . . . . . . . . . . . . 4Resetting the network timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Control Console .............................................................. 5How To Log On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Remote access to the control console . . . . . . . . . . . . . . . . . . . . . . . 5Local access to the control console . . . . . . . . . . . . . . . . . . . . . . . . . 6

Main Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Sample main screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Information and status fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Control Console Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8How to use control console menus . . . . . . . . . . . . . . . . . . . . . . . . . 8Control console structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Device Manager menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Network menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9System menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

InfraStruXure PDU User’s Guide i

Page 3: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Web Interface .................................................................10Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Supported Web browsers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

How to Log On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10URL address formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Home Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

How to Use the Tabs, Menus, and Links . . . . . . . . . . . . . . . . . . . . . .13Tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Quick Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Monitoring and Configuring the PDU ..........................14Viewing PDU Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

Accessing detailed PDU status information . . . . . . . . . . . . . . . . . . 14Viewing breaker status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Viewing hardware information and electrical ratings . . . . . . . . . . . 15

Configuring PDU Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Configuring alarm thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Adding a branch breaker or sub-feed breaker . . . . . . . . . . . . . . . . 17Viewing and editing branch circuit breaker settings . . . . . . . . . . . 17Applying configuration changes to all branch circuit breaker settings 18

Configuring Contacts and Relays . . . . . . . . . . . . . . . . . . . . . . . . . . .18Viewing and configuring input contact settings . . . . . . . . . . . . . . . 18Configuring output relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Monitoring and Mapping Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . .19Viewing active alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Configuring the alarm relay map . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Logs ................................................................................20Use the Event and Data Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

Event log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Data log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Using FTP or SCP to retrieve log files . . . . . . . . . . . . . . . . . . . . . . . 23

InfraStruXure PDU User’s Guide ii

Page 4: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Administration: Security............................................... 25Local Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Setting user access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Remote Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25RADIUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Configuring the RADIUS Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Summary of the configuration procedure . . . . . . . . . . . . . . . . . . . . 27Configuring a RADIUS server on UNIX® with shadow passwords 27Supported RADIUS servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Inactivity Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Administration: Network Features............................... 29TCP/IP and Communication Settings . . . . . . . . . . . . . . . . . . . . . . . . 29

TCP/IP settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29DHCP response options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Port Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

DNS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37SNMPv1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37SNMPv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

FTP Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Administration: Notification and Logging................... 41Event Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Types of notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Configuring event actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

InfraStruXure PDU User’s Guideiii

Page 5: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Active, Automatic, Direct Notification . . . . . . . . . . . . . . . . . . . . . . . .43E-mail notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43SNMP traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44SNMP Trap Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Syslog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Queries (SNMP GETs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Administration: General Options .................................48Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48

Set the Date and Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Daylight saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Use an .ini File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49

Temperature Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49

Reset the Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

Configuring Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

About the PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

APC Device IP Configuration Wizard...........................51Capabilities, Requirements, and Installation . . . . . . . . . . . . . . . . . .51

How to use the Wizard to configure TCP/IP settings . . . . . . . . . . . 51System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Use the Wizard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52Launch the Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Configure the basic TCP/IP settings remotely . . . . . . . . . . . . . . . . 52Configure or reconfigure the TCP/IP settings locally . . . . . . . . . . . 53

How to Export Configuration Settings.........................54Retrieving and Exporting the .ini File . . . . . . . . . . . . . . . . . . . . . . . .54

Summary of the procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Contents of the .ini file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Detailed procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

InfraStruXure PDU User’s Guide iv

Page 6: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

The Upload Event and Error Messages . . . . . . . . . . . . . . . . . . . . . . 56The event and its error messages . . . . . . . . . . . . . . . . . . . . . . . . . . 56Messages in config.ini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Errors generated by overridden values . . . . . . . . . . . . . . . . . . . . . . 56

Related Topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

File Transfers................................................................. 58Upgrading Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Benefits of upgrading firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Firmware files (PDU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Obtain the latest firmware version . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Firmware File Transfer Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Use FTP or SCP to upgrade one PDU . . . . . . . . . . . . . . . . . . . . . . . 59How to upgrade multiple PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Use XMODEM to upgrade one PDU . . . . . . . . . . . . . . . . . . . . . . . . . 61

Verifying Upgrades and Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Verify the success or failure of the transfer . . . . . . . . . . . . . . . . . . 61Last Transfer Result codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Verify the version numbers of installed firmware. . . . . . . . . . . . . . 62

InfraStruXure PDU User’s Guidev

Page 7: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Introduction

Product DescriptionFeatures

The APC by Schneider Electric InfraStruXure PDU provides power distribution and management of electrical power to equipment racks. The PDU provides full management capabilities over a network using Telnet, Secure SHell (SSH), HyperText Transfer Protocol (HTTP), HTTP over Secure Sockets Layer (HTTPS), File Transfer Protocol (FTP), Secure CoPy (SCP), Modbus, and Simple Network Management Protocol (SNMP) versions 1 and 3. The PDU also provides the following features:

• Provides connections for an Emergency Power Off (EPO) switch.

• Supports input contact and relay output monitoring for use with dry contact sensors.

• Provides the ability to export a user configuration (.ini) file from a configured PDU to one or more unconfigured PDUs without converting the file to a binary file.

• Supports using a Dynamic Host Configuration Protocol (DHCP) or server to provide the network (TCP/IP) values for the PDU.

• Provides data and event logs.

• Enables you to configure notification through event logging (by the PDU and Syslog), e-mail, and SNMP traps. You can configure notification for single events or groups of events, based on the severity level or category of events.

• Provides a selection of security protocols for authentication and encryption.

Initial setup

You must define three TCP/IP settings for the PDU before it can operate on the network:

• IP address of the PDU

• Subnet mask

• IP address of the default gatewayCaution: Do not use the loopback address (127.0.0.1) as the default gateway. Doing so disables the PDU. You must then log on using a serial connection and reset TCP/IP settings to their defaults.

To configure the TCP/IP settings, see the PDU Installation and Start-Up Manual, available in printed form and on the APC Web site, www.apc.com.

For detailed information on how to use a DHCP server to configure the TCP/IP settings at the PDU, see “TCP/IP and Communication Settings” on page 29.

1InfraStruXure PDU User’s Guide

Page 8: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Network management features

These applications and utilities work with a PDU that connects to the network through its Network Management Card:

• APC InfraStruXure® Central—Provide enterprise-level power management and management of APC agents, UPSs, information controllers, and environmental monitors

• APC PowerNet® Management Information Base (MIB) with a standard MIB browser—Perform SNMP SETs and GETs and to use SNMP traps

• APC Device IP Configuration Wizard—Configure the basic settings of one or more PDUs over the network

• APC Security Wizard—Create the components needed for high security for the PDU when you are using Secure Sockets Layer (SSL) and related protocols and encryption routines

Internal Management FeaturesOverview

Use the Web interface or the control console interface to manage the PDU.

For more information about the internal user interfaces, see “Web Interface” on page 10 and “Control Console” on page 5.

Access priority for logging on

Only one user at a time can log on to the PDU. The priority for access, beginning with the highest priority, is as follows:

• Local access to the control console from a computer with a direct serial connection to the PDU.

• Telnet or Secure SHell (SSH) access to the control console from a remote computer.

• Web access, either directly or through InfraStruXure Central

See “SNMP” on page 37 for information about how SNMP access to the PDU is controlled.

Types of user accounts

The PDU has three levels of access (Administrator, Device User, and Read-Only User), which are protected by user name and password requirements.

• An Administrator can use all the menus in the Web interface and control console. The default user name and password are both apc.

• A Device User can access only the following:

– In the Web interface, the menus on the Home, Power Distribution, Contacts/Relays, Alarms, and Logs tabs and the event and data logs.

– In the control console, the equivalent features and options.

The default user name is device, and the default password is apc.

InfraStruXure PDU User’s Guide2

Page 9: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

• A Read-Only User has the following restricted access:

– Access through the Web interface only. You must use the Web interface to configure values for the Read-Only User.

– Access to the same tabs and menus as a Device User, but without any capability to change configurations, control devices, delete data, or use file transfer options. Links to configuration options are visible but disabled, and the event and data logs display no button to clear the log.

The default user name is readonly, and the default password is apc.To set User Name and Password values for the three account types, see “Setting user access” on page 25.

How to Recover from a Lost PasswordYou can use a local computer, a computer that connects to the PDU or other device through the serial port, to access the control console.

1. At the local computer, select a serial port, and disable any service that uses it.

2. Connect the provided serial cable from the selected port on the computer to the configuration port at the PDU.

3. Run a terminal program (such as HyperTerminal®) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.

4. Press ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to display the User Name prompt, verify the following:

– The serial port is not in use by another application.

– The terminal settings are correct as specified in step 3.

– The correct cable is being used as specified in step 2.

5. Press the Reset button. The Status LED will flash alternately orange and green. Press the Reset button a second time immediately while the LED is flashing to reset the user name and password to their defaults temporarily.

6. Press ENTER as many times as necessary to redisplay the User Name prompt, then use the default, apc, for the user name and password. (If you take longer than 30 seconds to log on after the User Name prompt is redisplayed, you must repeat step 5 and log on again.)

7. From the Control Console menu, select System, then User Manager.

8. Select Administrator, and change the User Name and Password settings, both of which are now defined as apc.

9. Press CTRL+C, log off, reconnect any serial cable you disconnected, and restart any service you disabled.

Watchdog FeaturesOverview

To detect internal problems and recover from unanticipated inputs, the PDU uses internal, system-wide watchdog mechanisms. When it restarts to recover from an internal problem, a System: Warmstart event is recorded in the event log.

3InfraStruXure PDU User’s Guide

Page 10: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Network interface watchdog mechanism

The PDU implements internal watchdog mechanisms to protect itself from becoming inaccessible over the network. For example, if the PDU does not receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes that there is a problem with its network interface and restarts.

Resetting the network timer

To ensure that the PDU does not restart if the network is quiet for 9.5 minutes, the PDU attempts to contact the default gateway every 4.5 minutes. If the gateway is present, it responds to the PDU, and that response restarts the 9.5-minute timer. If your application does not require or have a gateway, specify the IP address of a computer that is running on the network most of the time and is on the same subnet. The network traffic of that computer will restart the 9.5-minute timer frequently enough to prevent the PDU from restarting.

InfraStruXure PDU User’s Guide4

Page 11: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Control Console

How To Log OnOverview

You can use either a local (serial) connection or a remote (Telnet or SSH) connection with a computer on the same network (LAN) as the PDU to access the control console.

Use case-sensitive user name and password entries to log on (by default, apc and apc for an Administrator, or device and apc for a Device User). A Read-Only User has no access to the control console.

If you cannot remember your user name or password, see “How to Recover from a Lost Password” on page 3.

Remote access to the control console

You can access the control console through Telnet or Secure SHell (SSH). Telnet is enabled by default. Enabling SSH disables Telnet.

To enable or disable these access methods:

• In the Web interface, on the Administration tab, select Network on the top menu bar, and then the access option under Console on the left navigation menu.

• In the control console, use the Telnet/SSH option of the Network menu.

Telnet for basic access. Telnet provides the basic security of authentication by user name and password, but not the high-security benefits of encryption.

To use Telnet to access the control console:

1. From a computer on the same network as the PDU, at a command prompt, type telnet and the System IP address for the PDU (for example, telnet 139.225.6.133, when the PDU uses the default Telnet port of 23), and press ENTER.

If the PDU uses a non-default port number (from 5000 to 32768), you must include a colon or a space, depending on your Telnet client, between the IP address (or DNS name) and the port number.

2. Enter the user name and password (by default, apc and apc for an Administrator, or device and apc for a Device User).

SSH for high-security access. If you use the high security of SSL for the Web interface, use Secure SHell (SSH) for access to the control console. SSH encrypts user names, passwords and transmitted data. The interface, user accounts, and user access rights are the same whether you access the control console through SSH or Telnet, but to use SSH, you must first configure SSH and have an SSH client program installed on your computer.

5InfraStruXure PDU User’s Guide

Page 12: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Local access to the control console

For local access, use a computer that connects to the PDU or other device through the serial port, to access the control console:

1. Select a serial port at the computer and disable any service that uses the port.

2. Connect the provided serial cable from the selected port on the computer to the configuration port at the PDU.

3. Run a terminal program (e.g., HyperTerminal), and configure the selected port for 2400 bps, 8 data bits, no parity, 1 stop bit, and no flow control.

4. Press ENTER, and at the prompts, enter your user name and password.

Main ScreenSample main screen

Following is an example of the screen displayed when you log on to the control console at the PDU.

Information and status fields

Main screen information fields.

• Two fields identify the APC operating system (AOS) and application (APP) firmware versions.

Network Management Card AOS vx.x.xPDU APP vx.x.x

• Three fields identify the system name, contact person, and location of the PDU. (In the control console, use the System menu to set these values.)

Name: Test Lab

Contact: Don Adams

Location: Building 3

• The Up Time field reports how long the PDU has been running since it was last turned on or reset.

Up Time: 0 Days 21 Hours 21 Minutes

American Power Conversion Network Management Card AOS vx.x.x (c)Copyright 2009 All Rights Reserved PDU APP vx.x.x--------------------------------------------------------------------------

Name : Test Lab Date : 11/30/2009 Contact : Don Adams Time : 5:58:30 Location : Building 3 User : Administrator Up Time : 0 Days, 21 Hours, 21 Minutes Stat : P+ N+ A+

------- Control Console --------------------------------------------------

1- Device Manager 2- Network 3- System 4- Logout <ESC>- Main Menu, <ENTER>- Refresh, <CTRL-L>- Event Log

InfraStruXure PDU User’s Guide6

Page 13: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

• Two fields report when you logged in, by date and time.

Date : 11/30/2009

Time : 5:58:30

• The User field reports whether you logged in through the Administrator or Device User account. (The Read Only User account cannot access the control console.)

User : Administrator

Main screen status fields.

• The Stat field reports the PDU status.

Stat : P+ N+ A+

If P+ is not displayed, contact APC support staff. See “APC Worldwide Customer Support” on page 68.

P+ The APC operating system (AOS) is functioning properly.

N+ The network is functioning properly.

N? A BOOTP request cycle is in progress.

N– The PDU failed to connect to the network.

N! Another device is using the IP address of this PDU.

A+ The application is functioning properly.

A– The application has a bad checksum.

A? The application is initializing.

A! The application is not compatible with the AOS.

7InfraStruXure PDU User’s Guide

Page 14: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Control Console MenusOverview

The control console provides options to monitor and configure the PDU.

How to use control console menus

The menus in the control console list options by number and name. To use an option, type the option’s number, press ENTER, and follow any on-screen instructions. If you use an option that changes a setting or value, select Accept Changes to save your change before you exit the menu.

While using a menu, you can also do the following:

• Type ? and press ENTER for menu option descriptions if help exists for the menu.

• Press ENTER to refresh the menu

• Press ESC to go back to the menu from which you accessed the current menu

• Press CTRL+C to return to the main (Control Console) menu

• Press CTRL+D to toggle between menus

• Press CTRL+L to access the event log

Control console structureFor menus not specific to the PDU but shared among APC network-enabled devices, names and locations of options differ from those of the Web interface. The menu structure in the control console is retained from earlier firmware versions for compatibility with scripts and programs that rely on that structure.

Main menu

Use the main Control Console menu to access the control console’s management features:

1- Device Manager

2- Network

3- System

4- Logout

Note: When you log on as Device Manager (equivalent to Device User in the Web interface), you can access only the Device Manager menus and the Logout menu.

Device Manager menu

An Administrator or Device User can use the options of the Device Manager menu to configure PDU parameters and display detailed status.

InfraStruXure PDU User’s Guide8

Page 15: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Network menu

To perform these tasks, use the options of the Network menu:

• Configure the TCP/IP settings of the PDU or, if the PDU obtains its TCP/IP settings from a server, configure the settings for the type of server (DHCP or BOOTP).

• Use the Ping utility.

• Define settings that affect FTP, Telnet and SSH, the Web interface and SSL, SNMP, e-mail, DNS, and Syslog.

System menu

To perform these tasks, use the options of the System menu:

• Control Administrator and Device Manager access. (You can control Read Only User access by using the Web interface only.)

• Define the Name, Contact, and Location values for the system.

• Set the date and time used by the PDU.

• Through the Tools option:

– Restart the PDU interface.

– Reset parameters to their default values.

– Delete SSH host keys and SSL certificates.

– Upload an initialization file (.ini file) that has been downloaded from another PDU. The current PDU then uses the values in that .ini file to configure its own settings.

• Access system information about the PDU.

9InfraStruXure PDU User’s Guide

Page 16: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Web Interface

IntroductionOverview

The Web interface provides options to manage the PDU.

See “Web” on page 34 for information on how to select, enable, and disable the protocols that control access to the Web interface and to define the Web-server ports for the protocols.

Supported Web browsersYou can use Microsoft® Internet Explorer (IE) 7.x and higher (on Windows operating systems only) or Mozilla Firefox 3.0.6 or higher (on all operating systems) to access the PDU through its Web interface. Other commonly available browsers may work but have not been fully tested by APC.

The PDU cannot work with a proxy server. Therefore, before you can use a Web browser to access its Web interface, you must do one of the following:

• Configure the Web browser to disable the use of a proxy server for the PDU.

• Configure the proxy server so that it does not proxy the specific IP address of the PDU.

How to Log OnOverview

You can use the DNS name or System IP address of the PDU for the URL address of the Web interface. Use your case-sensitive user name and password to log on. The default user name differs by account type:

• apc for an Administrator

• device for a Device User

• readonly for a Read-Only UserThe default password is apc for all three account types.

Note: If you are using HTTPS (SSL/TSL) as your access protocol, your logon credentials are compared with information in a server certificate. If the certificate was created with the APC Security Wizard, and an IP address was specified as the common name in the certificate, you must use an IP address to log on to the PDU. If a DNS name was specified as the common name on the certificate, you must use a DNS name to log on.

For information about the Web page that displays when you log on, see “Home Page” on page 12.

InfraStruXure PDU User’s Guide10

Page 17: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

URL address formats

Type the DNS name or IP address of the PDU in the URL address field of the Web browser and press ENTER. When you specify a non-default Web server port in Internet Explorer, you must include http:// or https:// in the URL.

Common browser error messages at log-on.

URL format examples.

• For a DNS name of Web1:

– http://Web1 if HTTP is your access mode

– https://Web1 if HTTPS (HTTP with SSL) is your access mode

• For a System IP address of 139.225.6.133 and the default Web server port (80):

– http://139.225.6.133 if HTTP is your access mode

– https://139.225.6.133 if HTTPS (HTTP with SSL) is your access mode

• For a System IP address of 139.225.6.133 and a non-default Web server port (5000):

– http://139.225.6.133:5000 if HTTP is your access mode

– https://139.225.6.133:5000 if HTTPS (HTTP with SSL) is your access mode.

Error Message Browser Cause of the Error

“You are not authorized to view this page” or “Someone is currently logged in...”

Internet Explorer, Firefox

Someone else is logged on.

“This page cannot be displayed.” Internet Explorer Web access is disabled, or the URL was not correct

“Unable to connect.” Firefox

11InfraStruXure PDU User’s Guide

Page 18: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Home PageOverview

On the Home tab, displayed when you log on to the Web interface, you can view active alarm conditions and the most recent events recorded in the event log.

Quick status icons. At the upper right corner of every page, one or more icons and accompanying text indicate the current operating status of the PDU and the number of active alarms of that severity:

Active alarms. The Power Distribution section of the Home page summarizes the status of the PDU:

• The Online icon displays if no alarms exist.

• One or both of the other icons (Critical and Warning) display if any alarms exist, and after each icon, the number of active alarms of that severity.

• The input and output voltages, the supported load, and the active power provided for each phase.

• The bypass voltages, if your PDU model includes a Bypass Input SwitchTo return to the Home page to view its summary of PDU status, including the active alarms, click a quick status icon on any page of the interface.

Recent Device Events. The Recent Device Events section displays, in reverse chronological order, the events that occurred most recently and the dates and times they occurred. Click More Events to view the entire event log.

Icon Description

Critical: A critical alarm exists, which requires immediate action.

Warning: An alarm condition requires attention and could jeopardize your data or equipment if its cause is not addressed.

Online: No alarms are present, and the PDU is operating normally.

InfraStruXure PDU User’s Guide12

Page 19: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

How to Use the Tabs, Menus, and LinksTabs

In addition to the tab for the Home page, the following tabs are displayed. Click a tab to display a set of menu options:

• Power Distribution: View the power output of the PDU and its breakers, and configure alarm thresholds.

• Contacts/Relays: Configure the name and normal state of the PDU’s input contacts and output relays.

• Alarms: View active alarms and recent events, and configure how the relays will respond to PDU alarms.

• Logs: View and configure event and data logs.

• Administration: Configure security, network connection, notification, and general settings.

Menus

Left navigation menu. Each tab (except the tab for the home page) has a left navigation menu, consisting of headings and options:

• If a heading has indented option names below it, the heading itself is not a navigational link. Click an option to display or configure parameters.

• If a heading has no indented option names, the heading itself is the navigational link. Click the heading to display or configure parameters.

Top menu bar. The Administration and Power Distribution tabs have a selection of menu options on the top menu bar. Select one of the menu options to display its left navigation menu.

Quick Links

At the lower left on each page of the interface, there are three configurable links. By default, the links access the URLs for these Web pages:

• Link 1: The home page of the APC Web site

• Link 2: Demonstrations of APC Web-enabled products.

• Link 3: Information on APC Remote Monitoring Services.

To reconfigure the links, see “Configuring Links” on page 50.

13InfraStruXure PDU User’s Guide

Page 20: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Monitoring and Configuring the PDUThe Power Distribution tab has two top menu bar options, Main PDU and Branch Circuits, which provide system performance information and configuration options.

Viewing PDU InformationAccessing detailed PDU status information

Viewing output measurements.

Path: Power Distribution > Main PDU > PDU Monitoring > panel output

The first time you select the Power Distribution tab, then Main PDU from the top menu bar, the PDU Monitoring > panel output page displays. If an alarm caused by an output power condition exists, a status icon and accompanying text display at the top of the page.

The Output Measurements section lists detailed information about power leaving the PDU:

• Voltage: The phase-to-phase output voltage (e.g., L1-2 for phase L1 to phase L2) for a 3-wire connection, or the phase-to-neutral output voltage (e.g., L1 for phase 1 to neutral) for a 4-wire connection.

• Current: The load supported by each phase, in RMS current (Irms).

• Power: The active power, in kW, provided for each phase and for the total of the three phases.

• Apparent Power: The apparent power, in kVA, provided for each phase and for the total of the three phases.

• Power Factor: The ratio between active power and apparent power (kW/kVA). This ratio affects the power available to the load.

• Frequency: The frequency, in Hz, of the output.

Viewing input measurements.

Path: Power Distribution > Main PDU > PDU Monitoring > main input

If an alarm caused by an input power condition exists, a status icon and accompanying text display at the top of the PDU Monitoring > main input page.

The Input Measurements section lists detailed information about the power entering the PDU:

• Main Input Breaker: The status of the main input breaker at the PDU, open or closed. When the PDU is operating normally, this breaker is closed.

• Main Voltage: The phase-to-phase input voltage (e.g., L1-2 for phase L1 to phase L2) for a 3-wire connection, or the phase-to-neutral input voltage (e.g., L1 for phase 1 to neutral) for a 4-wire connection.

• Bypass Voltage (PDU models with a Bypass Input Switch only): The phase-to-phase and phase-to-neutral voltages

InfraStruXure PDU User’s Guide14

Page 21: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Viewing breaker status

Breaker status icons. Color-coded breaker icons show the status of the system breakers:

• Red: The breaker position is causing one or more critical alarms.

• Yellow: The breaker position is causing one or more warning alarms.

• Gray: The breaker position is not influencing the status of the PDU.

• Green: The PDU is operating normally.

Viewing the status of the input breakers.

Path: Power Distribution > Main PDU > PDU Breakers > input breakers

If an alarm caused by the breaker position exists, a status icon and accompanying text display at the top of the PDU Breakers > input breakers page.

• Main Input Breaker: When the PDU is operating normally, this breaker is closed. Bypass Breaker: When the PDU is operating normally, this breaker is closed. The Bypass Input Switch is available on select PDU models only, and it provides a connection for a second power source.

• Cross Tie Breaker: When the PDU is operating normally, this breaker is closed. The output of this breaker feeds the Bypass Input Switch of another PDU. This feature is available on select PDU models only.

Viewing the status of the bypass breakers.

Path: Power Distribution > Main PDU > PDU Breakers > bypass status

At the top of the PDU Breakers > bypasss status page, a status icon and accompanying text summarize the status of the PDU.

• UPS Input Breaker (Q1): When the PDU is operating normally, this breaker is closed.

• UPS Output Breaker (Q2): When the PDU is operating normally, this breaker is closed.

• Maintenance Bypass (Q3): When the PDU is operating normally, this breaker is open. During Maintenance Bypass Operation, this breaker is closed.

Viewing hardware information and electrical ratings

Path: Power Distribution > Main PDU > PDU Info

The Electrical Configuration section of the page lists the electrical hardware in your PDU.

• Input Voltage: The nominal input voltage that the PDU Main Input Switch receives, and the type of electrical connection used by the PDU Main Input Switch. (3-wire connections are measured phase-to-phase; 4-wire connections are measured phase-to-neutral.)

• Input Transformer: Indicates whether the PDU has an input transformer.

• Main Breaker Rating: The rating, in amps, of the breaker supplying power to the PDU.

• Output Voltage: The configured nominal output voltage that is supporting the load.

• Panel Breaker Rating: The rating, in amps, of the breaker supplying power to the distribution circuit breaker panels.

• Maximum System Power: The maximum amount of power, in kW, that the PDU can supply to the load.

15InfraStruXure PDU User’s Guide

Page 22: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

The Installed Options section defines whether the following components are installed in the PDU. The availability of these components varies by PDU model.

• Cooling Fans: Fans that cool the transformer.

• Load Test Port: A port that enables you to test whether the PDU can support the load.

• UPS Input Fuses: Fuses that protect the UPS. These fuses are only present on dual-fed PDUs or on single-fed PDUs without a transformer.

• Bypass Breaker: A Bypass Input Switch that provides a connection for a secondary power source.

• Cross Tie Output Breaker: A breaker that supplies power to the Bypass Input Switch of another PDU.

The Power Metering section specifies the version number of the metering firmware module.

Configuring PDU SettingsConfiguring alarm thresholds

Path: Power Distribution > Main PDU > PDU Monitoring > alarm setup

The PDU Monitoring > alarm setup page displays the configurable low and high alarm thresholds for these measurements:

• Input Voltage L-L: The acceptable range for the voltage entering the PDU.

• Bypass Voltage L-N: The acceptable range for bypass voltage.

• Output Voltage L-N: The acceptable range for the voltage that the PDU provides to the load.

• Output Current: The acceptable range for the output current. The PDU monitors the output current on each phase, and a threshold violation on any phase generates an alarm.

• High Neutral Current: The acceptable range for the current on the output neutral line.

• Frequency: The acceptable frequency variation for the output current, in Hertz.For each measurement, a value below the Low threshold or above the High threshold generates an alarm.

Click Input Thresholds to define the acceptable range for input voltage: The default values are:

• Low threshold: –30% of the expected input voltage

• High threshold: +30% of the expected input voltage

• Low Bypass Voltage Threshold: –12% (select PDU models only)

• High Bypass Voltage Threshold: +12% (select PDU models only)Click Output Thresholds to define the acceptable output ranges. The default values are:

• Output voltage threshold: +/–12%

• High output current threshold: 80%

• Low output current threshold: Disabled

• High neutral current: 80%

• Acceptable frequency range: +/–5 Hertz

InfraStruXure PDU User’s Guide16

Page 23: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Adding a branch breaker or sub-feed breaker

Path: Power Distribution > Branch Circuits > Configuration > add breakers or add sub-feed

In the Breaker Details section of the Configuration > add breakers page, or the Sub-Feed Breaker Details section of the Configuration > sub-feed page, define these settings:

• Panel Position:

– To add a branch breaker, enter its position number. This value is listed on the circuit breaker panel.

– To add a sub-feed breaker, select the three numbers that match its sub-feed position. These values are listed on the breaker panel.

• Number of Poles: Select the number of poles in the breaker.

– For a branch breaker, valid values are 1-pole, 2-pole, or 3-pole. Select the value that matches the type of load (1-phase, 2-phase, or 3-phase) that is receiving power.

– For sub-feed breakers, 3-pole is the only valid value.

• Breaker Rating: Set the rating of this breaker, in Amps.In the Breaker Identification section, type a descriptive name and location (up to 19 characters each) for the breaker.

In the Branch Current Thresholds section, mark the Enable check box to generate an alarm when the electric current violates a threshold, or clear the check box to disable alarms. Define each threshold as a percentage of the rated current.

When the configuration is complete, click Add Branch Breaker (or Add Sub-Feed, if you are configuring a sub-feed breaker) to apply your changes.

Viewing and editing branch circuit breaker settings

Path: Power Distribution > Branch Circuits > Panel Status

Select a group of circuit breakers (01..41 [odd], 02..42 [even], 43..83 [odd], or 44..84 [even]) to view the following data:

• Pos: The position of the breaker on the circuit breaker panel.

• Rating: The rating of the breaker occupying this panel position, in amps.

• Status: The state of the breaker.

– Normal: The breaker is operating normally.

– Warning: The low or high rating threshold has been violated.

– Critical: The minimum or maximum rating threshold has been violated.

• Name: A descriptive name for the breaker.

• Current: The measured root mean square (RMS) current of the panel position.

• Location: A user-configured description of the location of the branch breaker (for example, the phsyical location of the PDU in which it is installed)

To add a breaker, see “Adding a branch breaker or sub-feed breaker” on page 17.

To edit the name, location, or rating of a branch circuit breaker, select the text to modify. A configuration page opens; type your changes in the text field and click Apply.

17InfraStruXure PDU User’s Guide

Page 24: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

To edit threshold settings for a branch circuit breaker, select its name, then select Percent Rating. Mark or clear the check box for each threshold to define whether that threshold will generate breaker alarms. Define each threshold as a percentage of the rated current, then click Apply.

To delete a breaker or group, click Delete Group.

Applying configuration changes to all branch circuit breaker settings

Applying threshold setting changes to all branch breakers. Path: Power Distribution > Branch Circuits > Configuration > global thresholds

1. Mark the Apply check box that is associated with a threshold to apply this configuration to all of the branch breakers, or clear the Apply check box to prevent this setting from overwriting an existing threshold configuration.

2. Define the maximum, high, low, and minimum thresholds as a percentage of the rated current.

3. Click Apply to All Checked to save your changes.

Deleting all branch breaker settings. Path: Power Distribution > Branch Circuits > Configuration > global delete

1. To delete the branch breaker panel settings for a range of breakers, mark its Delete check box. To retain the settings for a range of breakers, clear its check box.

2. Click Delete All Checked to apply your changes.

Configuring Contacts and RelaysViewing and configuring input contact settings

Path: Contacts/Relays > Input Contacts

The first time you select the Contacts/Relays tab, the Input Contacts page displays. View the name of each input contact, its alarm status, and its current state. Up to four inputs can be connected to the PDU.

Click the name of the input to configure a descriptive name (up to 14 characters) and to define its normal state. An alarm will be generated when the input switches to the abnormal state. Click Apply to save your changes.

Configuring output relays

Path: Contacts/Relays > Output Relays

The Output Relays page displays the name and state of each relay. The PDU has four relays.

Click the name of the relay to configure a descriptive name (up to 14 characters) and to define its normal state.

See “Configuring the alarm relay map” on page 19 to define the alarms that will cause the relay to change from its normal state.

InfraStruXure PDU User’s Guide18

Page 25: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Monitoring and Mapping Alarms Viewing active alarms

By default, the first time you click the Alarms tab, the Active Alarms page displays a list of active critical and warning alarms that affect the performance of the PDU.

To view a complete event log, see “Logs” on page 20.

Configuring the alarm relay map

Select the Alarms tab and then Alarm Relay Map to view a list of actions that can cause the relay to change its state.

To configure a relay to react to an alarm condition, mark the check box that corresponds to the alarm condition and the relay:

• Any Load: Change the state of the relay when an over-current or under-current alarm is detected for a circuit breaker panel or branch circuit.

• Overload: An over-current alarm is detected for a circuit breaker panel, branch circuit, or system ground.

• Input Voltage: An input voltage alarm is active.

• Output Voltage: An output voltage alarm is active.

• PDU in Bypass: The Q3 breaker on the PDU is closed

• Any Breaker: The input, bypass input, or cross-tie output breaker is not in its normal state, or a system state alarm (such as System Off, On Battery Only, Bypass Alarm, No Panel Feed, Bypass Alarm, or Forced Bypass) is active.

• Contact 1–4 Alarms: The input is not in its normal state.

To configure the normal state of a relay, see “Configuring output relays” on page 18.

19InfraStruXure PDU User’s Guide

Page 26: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Logs

Use the Event and Data LogsEvent log

Path: Logs > Events > options

You can view, filter, or delete the event log. By default, the log displays all events recorded during the last two days, in reverse chronological order.

For lists of all configurable events and their current configuration, select the Administration tab, Notification on the top menu bar, and by event under Event Actions on the left navigation menu.

For information about configuring event actions, see “Configuring by event” on page 42.

To display the event log (Logs > Events > log):

• By default, view the event log as a page of the Web interface.

• To see the listed events on one page, click Launch Log in New Window from the event log page to display a full-screen view of the log.

Note: In your browser's options, JavaScript® must be enabled for you to use the Launch Log in New Window button.

You can also use FTP or SCP to view the event log. See “Using FTP or SCP to retrieve log files” on page 23.

To filter the log (Logs > Events > log):

• Filtering the log by date or time: To display the entire event log, or to change the number of days or weeks for which the log displays the most recent events, select Last. Select a time range from the drop-down menu, then click Apply. The filter configuration is saved until the PDU restarts. To display events logged during a specific time range, select From. Specify the beginning and ending times (using the 24-hour clock format) and dates for which to display events, then click Apply. The filter configuration is saved until the PDU restarts.

• Filtering the log by event: To specify the events that display in the log, click Filter Log. Clear the check box of an event category or alarm severity level to remove it from view. Text at the upper right corner of the event log page indicates that a filter is active. As Administrator, click Save As Default to save this filter as the default log view for all users. If you do not click Save As Default, the filter is active until you clear it or until the PDU restarts.

• To remove an active filter, click Filter Log, then Clear Filter (Show All). Note: Events are processed through the filter using OR logic.

• Events that you do not select from the Filter By Severity list never display in the filtered event log, even if the event occurs in a category you selected from the Filter by Category list.

• Events that you do not select from the Filter by Category list never display in the filtered event log, even if devices in the category enter an alarm state you selected from the Filter by Severity list.

InfraStruXure PDU User’s Guide20

Page 27: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

To disable the logging of events based on their assigned severity level or their event category, see “Configuring by group” on page 42.

To delete the log (Logs > Events > log):

• When the log is full, the older entries are deleted.

• To delete all events recorded in the log, click Clear Log on the Web page that displays the log. Deleted events cannot be retrieved.

To configure reverse lookup (Logs > Events > reverse lookup):

Reverse lookup is disabled by default. Enable this feature unless you have no DNS server configured or have poor network performance because of heavy network traffic.

With reverse lookup enabled, when a network-related event occurs, both the IP address and the domain name for the networked device associated with the event are logged in the event log. If no domain name entry exists for the device, only its IP address is logged with the event. Since domain names generally change less frequently than IP addresses, enabling reverse lookup can improve the ability to identify addresses of networked devices that are causing events.

Data log

Path: Logs > Data > options

View a log of measurements about the PDU. Each entry is listed by the date and time the data was recorded. The Input Voltage filter is enabled by default.To view the electrical current data for a panel, click its name and click Apply.

To display the data log (Logs > Data > log):

• By default, view the data log as a page of the Web interface.

• To see the listed data on one page, click Launch Log in New Window from the data log page to display a full-screen view of the log.

Note: In your browser's options, JavaScript® must be enabled for you to use the Launch Log in New Window button. You can also use FTP or SCP to view the event log. See “Using FTP or SCP to retrieve log files” on page 23.

To filter the log by date or time (Logs > Data > log):

To display the entire Input Voltage or Panel Current data log, or to change the number of days or weeks for which the log displays the most recent events, select Last. Select a time range from the drop-down menu, then click Apply. The filter configuration is saved until the device restarts.

To display data logged during a specific time range, select From. Specify the beginning and ending times (using the 24-hour clock format) and dates for which to display data, then click Apply. The filter configuration is saved until the device restarts.

To view the entire data log, export the log and then view it using a spreadsheet application. To export the log, see “Using FTP or SCP to retrieve log files” on page 23.

To delete the data log:

To delete all data recorded in the log, click Clear Data Log on the Web page that displays the log. Deleted data cannot be retrieved.

21InfraStruXure PDU User’s Guide

Page 28: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

To set the data collection interval (Logs > Data > interval):

Define, in the Log Interval setting, how frequently data is sampled and stored in the data log, and view the calculation of how many days of data the log can store, based on the interval you selected.

When the log is full, the older entries are deleted. To avoid automatic deletion of older data, enable and configure data log rotation, described in the next section.

To configure data log rotation (Logs > Data > rotation):

Set up a password-protected data log repository on a specified FTP server. Enabling rotation causes the contents of the data log to be appended to the file you specify by name and location. Updates to this file occur at the upload interval you specify.

To upload the file one time and then disable future uploads:

1. In the Data Log Rotation field, mark the Enable check box.

2. Click the Upload Now! button.

3. Clear the Enable check box.

Parameter Description

Data Log Rotation Enable or disable (the default) data log rotation.

FTP Server Address The location of the FTP server where the data repository file is stored.

User Name The user name required to send data to the repository file. This user must also be configured to have read and write access to the data repository file and the directory (folder) in which it is stored.

Password The password required to send data to the repository file.

File Path The path to the repository file.

Filename The name of the repository file (an ASCII text file).

Unique File Name Add a date stamp prefix to the filename, using the format MMDDYYY_filename.txt. If updates occur more than once on the same day, the data is appended to the file created that day.

Delay X hours between uploads. The number of hours between uploads of data to the file.

Upload every X minutes The number of minutes between attempts to upload data to the file after an upload failure.

Up to X times The maximum number of times the upload will be attempted after an initial failure.

Until Upload Succeeds Attempt to upload the file until the transfer is completed.

InfraStruXure PDU User’s Guide22

Page 29: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Using FTP or SCP to retrieve log files

An Administrator or Device User can use FTP or SCP to retrieve a tab-delineated event log file (event.txt) or data log file (data.txt) and import it into a spreadsheet.

• The file reports all events or data recorded since the log was last deleted or (for the data log) truncated because it reached maximum size.

• The file includes information that the event log or data log does not display.

– The version of the file format (first field)

– The date and time the file was retrieved

– The Name, Contact, and Location values and IP address of the PDU

– The unique Event Code for each recorded event (event.txt file only)

Note: The PDU uses a four-digit year for log entries. You may need to select a four-digit date format in your spreadsheet application to display all four digits.

If you are using the encryption-based security protocols for your system, use Secure CoPy (SCP) to retrieve the log file.

If you are using unencrypted authentication methods for the security of your system, use FTP to retrieve the log file.

See the Security Handbook, available on the Utility CD provided with your InRow RD or on the APC Web site (www.apc.com), for information on available protocols and methods for setting up the type of security you need.

To use SCP to retrieve the files. To use SCP to retrieve the event.txt file, use the following command:

scp username@hostname_or_ip_address:event.txt ./event.txt

To use SCP to retrieve the data.txt file, use the following command:

scp username@hostname_or_ip_address:data.txt ./data.txt

To use FTP to retrieve the files. To use FTP to retrieve the event.txt or data.txt file:

1. At a command prompt, type ftp and the IP address of the PDU, and press ENTER.

If the Port setting for the FTP Server option (set through the Network menu of the Administration tab) has been changed from its default (21), you must use the non-default value in the FTP command. For Windows FTP clients, use the following command, including spaces. (For some FTP clients, you must use a colon instead of a space between the IP address and the port number.)

ftp>open ip_address port_number

To set a non-default port value to enhance security for the FTP Server, see “FTP Server” on page 40. You can specify any port from 5001 to 32768.

2. Use the case-sensitive User Name and Password for Administrator or Device User to log on. For Administrator, apc is the default for User Name and Password. For the Device User, the defaults are device for User Name and apc for Password.

3. Use the get command to transmit the text of a log to your local drive.

23InfraStruXure PDU User’s Guide

Page 30: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

ftp>get event.txt

or

ftp>get data.txt

4. You can use the del command to clear the contents of either log.

ftp>del event.txt

or

ftp>del data.txt

You will not be asked to confirm the deletion.

• If you clear the data log, the event log records a deleted-log event.

• If you clear the event log, a new event.txt file records the event.

5. Type quit at the ftp> prompt to exit from FTP.

InfraStruXure PDU User’s Guide24

Page 31: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Administration: Security

Local UsersSetting user access

Path: Administration > Security > Local Users > options

You set the case-sensitive user name and password for each account type in the same manner. Maximum length is 10 characters for a user name and 32 characters for a password. Blank passwords (passwords with no characters) are not allowed.

Note: For information on the permissions granted to each account type (Administrator, Device User, and Read-Only User, see “Types of user accounts” on page 2.

Remote UsersAuthentication

Path: Administration > Security > Remote Users > Authentication Method

Use this option to select how to administer remote access to the PDU.

For information about local authentication (not using the centralized authentication of a RADIUS server), see the Security Handbook, available on the APC Web site, www.apc.com.

APC supports the authentication and authorization functions of RADIUS (Remote Authentication Dial-In User Service).

• When a user accesses the PDU that has RADIUS enabled, an authentication request is sent to the RADIUS server to determine the user’s permission level.

• RADIUS user names used with the PDU are limited to 32 characters.

Account Type Default User Name Default Password Permitted Access

Administrator apc apc Web interface and control console

Device User device apc

Read-Only User readonly apc Web Interface only

25InfraStruXure PDU User’s Guide

Page 32: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Select one of the following:

• Local Authentication Only: RADIUS is disabled. Local authentication is enabled.

• RADIUS, then Local Authentication: RADIUS and local authentication are enabled. Authentication is requested from the RADIUS server first. If the RADIUS server fails to respond, local authentication is used.

• RADIUS Only: RADIUS is enabled. Local authentication is disabled.

Note: If RADIUS Only is selected, and the RADIUS server is unavailable, improperly identified, or improperly configured, you must use a serial connection to the control console and change the Access setting to Local Authentication Only or RADIUS, then Local Authentication to regain access.

RADIUS

Path: Administration > Security > Remote Users > RADIUS

Use this option to do the following:

• List the RADIUS servers (a maximum of two) available to the PDU and the time-out period for each.

• Click Add Server, and configure the parameters for authentication by a new RADIUS server:

• Click a listed RADIUS server to display and modify its parameters.

RADIUS Setting Definition

RADIUS Server The server name or IP address of the RADIUS server.

Note: RADIUS servers use port 1812 by default to authenticate users. To use a different port, add a colon followed by the new port number to the end of the RADIUS server name or IP address.

Secret The shared secret between the RADIUS server and the PDU.

Reply Timeout The time in seconds that the PDU waits for a response from the RADIUS server.

Test Settings Enter the Administrator user name and password to test the RADIUS server path that you have configured.

Skip Test and Apply Do not test the RADIUS server path.

Switch Server Priority Change which RADIUS server will authenticate users if two configured servers are listed and RADIUS, then Local Authentication or RADIUS Only is the enabled authentication method.

InfraStruXure PDU User’s Guide26

Page 33: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Configuring the RADIUS ServerSummary of the configuration procedure

You must configure your RADIUS server to work with the PDU.

For examples of the RADIUS users file with Vendor Specific Attributes (VSAs) and an example of an entry in the dictionary file on the RADIUS server, see the APC Security Handbook.

1. Add the IP address of the PDU to the RADIUS server client list (file).

2. Users must be configured with Service-Type attributes unless Vendor Specific Attributes (VSAs) are defined. If no Service-Type attributes are configured, users will have read-only access (on the Web interface only).

See your RADIUS server documentation for information about the RADIUS users file, and see the APC Security Handbook for an example.

3. Vendor Specific Attributes (VSAs) can be used instead of the Service-Type attributes provided by the RADIUS server. VSAs requires a dictionary entry and a RADIUS users file. In the dictionary file, define the names for the ATTRIBUTE and VALUE keywords, but not for the numeric values. If you change numeric values, RADIUS authentication and authorization will fail. VSAs take precedence over standard RADIUS attributes.

Configuring a RADIUS server on UNIX® with shadow passwords

If UNIX shadow password files are used (/etc/passwd) with the RADIUS dictionary files, the following two methods can be used to authenticate users:

• If all UNIX users have administrative privileges, add the following to the RADIUS “user” file. To allow only Device Users, change the APC-Service-Type to Device.

DEFAULT Auth-Type = System APC-Service-Type = Admin

• Add user names and attributes to the RADIUS “user” file, and verify password against /etc/passwd. The following example is for users bconners and thawk:

bconners Auth-Type = System APC-Service-Type = Admin

thawk Auth-Type = System APC-Service-Type = Device

Supported RADIUS servers

APC supports FreeRADIUS and Microsoft IAS 2003. Other commonly available RADIUS applications may work but have not been fully tested by APC.

27InfraStruXure PDU User’s Guide

Page 34: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Inactivity Timeout Path: Administration > Security > Auto Log Off

Use this option to configure the time (3 minutes by default) that the system waits before logging off an inactive user. If you change this value, you must log off for the change to take effect.

Note: This timer continues to run if a user closes the browser window without first logging off by clicking Log Off at the upper right. Because that user is still considered to be logged on, no user of that account type can log on until the time specified as Minutes of Inactivity expires. For example, with the default value for Minutes of Inactivity, if a Device User closes the browser window without logging off, no Device User can log on for 3 minutes.

InfraStruXure PDU User’s Guide28

Page 35: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Administration: Network Features

TCP/IP and Communication SettingsTCP/IP settings

Path: Administration > Network > TCP/IP

The TCP/IP option on the side menu bar, selected by default when you choose Network on the top menu bar, displays the current IP address, subnet mask, default gateway, and MAC address of the PDU.

On the same page, TCP/IP Configuration provides the following options for how the TCP/IP settings will be configured when the PDU turns on, resets, or restarts: Manual, BOOTP, DHCP, and DHCP & BOOTP.

For information on DHCP and DHCP options, see RFC2131 and RFC2132.

29InfraStruXure PDU User’s Guide

Page 36: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

DHCP response options

Each valid DHCP response contains options that provide the TCP/IP settings that the PDU needs to operate on a network, and other information that affects the operation of the PDU.

Setting Description

Manual The IP address, subnet mask, and default gateway must be configured manually. Click Next>>, and enter the new values.

BOOTP A BOOTP server provides the TCP/IP settings. At 32-second intervals, the PDU requests network assignment from any BOOTP server:• If it receives a valid response, it starts the network services.• If it finds a BOOTP server, but a request to that server fails or times out, the PDU stops

requesting network settings until it is restarted.• By default, if previously configured network settings exist, and it receives no valid response to

five requests (the original and four retries), it uses the previously configured settings so that it remains accessible.

Click Next>> to access the BOOTP Configuration page to change the number of retries or the action to take if all retries fail 1:• Maximum retries: Enter the number of retries that will occur when no valid response is

received, or zero (0) for an unlimited number of retries.• If retries fail: Select Use prior settings (the default) or Stop BOOTP request.

DHCP At 32-second intervals, the PDU requests network assignment from any DHCP server. By default, the number of retries is unlimited.• If it receives a valid response, by default it requires the APC cookie from the DHCP server in

order to accept the lease and start the network services.• If it finds a DHCP server, but the request to that server fails or times out, it stops requesting

network settings until it is restarted.

To change these values, click Next>> for the DHCP Configuration page1:• Require vendor specific cookie to accept DHCP Address: Disable or enable the requirement

that the DHCP server provide the APC cookie.• Maximum retries: Enter the number of retries that will occur when no valid response is

received, or zero (0) for an unlimited number of retries.

DHCP & BOOTP

The default setting. The PDU tries to obtain its TCP/IP settings from a BOOTP server first, and then, if it cannot discover a BOOTP server, from a DHCP server. If it obtains its TCP/IP settings from either server, it switches this setting to BOOTP or DHCP, depending on the type of server that supplied the TCP/IP settings to the PDU.

Click Next>> to configure the same settings that are on the BOOTP Configuration and DHCP Configuration pages1 and to specify that the DHCP and BOOTP setting be retained after either type of server provides the TCP/IP values.

1. The default values for these three settings on the configuration pages generally do not need to be changed: •Vendor Class: APC•Client ID: The MAC address of the PDU, which uniquely identifies it on the local area network (LAN)•User Class: The name of the application firmware module

InfraStruXure PDU User’s Guide30

Page 37: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Vendor Specific Information (option 43). The PDU uses this option in a DHCP response to determine whether the DHCP response is valid. This option contains up to two APC-specific options in a TAG/LEN/DATA format: the APC Cookie and the Boot Mode Transition.

• APC Cookie. Tag 1, Len 4, Data “1APC”

Option 43 communicates to the PDU that a DHCP server is configured to service APC devices. By default, this DHCP response option must contain the APC cookie for the PDU to accept the lease.

To disable the requirement of an APC cookie, see “DHCP” on page 30.

Following, in hexadecimal format, is an example of a Vendor Specific Information option that contains the APC cookie:

Option 43 = 0x01 0x04 0x31 0x41 0x50 0x43

• Boot Mode Transition. Tag 2, Len 1, Data 1/2

This option 43 setting enables or disables Remain in DHCP & BOOTP mode after accepting TCP/IP settings, which, by default, is disabled.

• A data value of 1 enables Remain in DHCP & BOOTP mode after accepting TCP/IP settings. Whenever the PDU reboots, it will request its network assignment first from a BOOTP server, and then, if necessary, from a DHCP server.

• A data value of 2 disables the option Remain in DHCP & BOOTP mode after accepting TCP/IP settings option. The TCP/IP Configuration setting option switches to DHCP when the PDU accepts the DHCP response. Whenever the PDU reboots, it will request its network assignment from a DHCP server only.

Following, in hexadecimal format, is an example of a Vendor Specific Information option that contains the APC cookie and the disable setting for Boot Mode Transition:

Option 43 = 0x01 0x04 0x31 0x41 0x50 0x43 0x02 0x01 0x01

TCP/IP options. The PDU uses the following options within a valid DHCP response to define its TCP/IP settings. All of these options except the first are described in RFC2132.

• IP Address (from the yiaddr field of the DHCP response, described in RFC2131): The IP address that the DHCP server is leasing to the PDU.

• Subnet Mask (option 1): The Subnet Mask value that the PDU needs to operate on the network.

• Router, i.e., Default Gateway (option 3): The default gateway address that the PDU needs to operate on the network.

• IP Address Lease Time (option 51): The time duration for the lease of the IP Address to the PDU.

• Renewal Time, T1 (option 58): The time that the PDU must wait after an IP address lease is assigned before it can request a renewal of that lease.

• Rebinding Time, T2 (option 59): The time that the PDU must wait after an IP address lease is assigned before it can seek to rebind that lease.

31InfraStruXure PDU User’s Guide

Page 38: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Other options. The PDU also uses these options within a valid DHCP response. All of these options except the last are described in RFC2132.

• Network Time Protocol Servers (option 42): Up to two NTP servers (primary and secondary) that the PDU can use.

• Time Offset (option 2): The offset of the PDU's subnet, in seconds, from Coordinated Universal Time (UTC).

• Domain Name Server (option 6): Up to two Domain Name System (DNS) servers (primary and secondary) that the PDU can use.

• Host Name (option 12): The host name that the PDU will use (32-character maximum length).

• Domain Name (option 15): The domain name that the PDU will use (64-character maximum length).

• Boot File Name (from the file field of the DHCP response, described in RFC2131): The fully qualified directory-path to an user configuration file (.ini file) to download. The siaddr field of the DHCP response specifies the IP address of the server from which the PDU will download the .ini file. After the download, the PDU uses the .ini file as a boot file to reconfigure its settings.

Port Speed

Path: Administration > Network > Port Speed

The Port Speed setting defines the communication speed of the TCP/IP port.

• For Auto-negotiation (the default), Ethernet devices negotiate to transmit at the highest possible speed, but if the supported speeds of two devices are unmatched, the slower speed is used.

• Alternatively, you can choose 10 Mbps or 100 Mbps, each with the option of half-duplex (communication in only one direction at a time) or full-duplex (communication in both directions on the same channel simultaneously).

DNSPath: Administration > Network > DNS > options

Use the options under DNS on the left navigation menu to configure and test the Domain Name System (DNS):

• Select servers to specify the IP addresses of the primary and optional secondary DNS server. For the PDU to send e-mail, at least the IP address of the primary DNS server must be defined.

– The PDU waits up to 15 seconds for a response from the primary DNS server or the secondary DNS server (if a secondary DNS server is specified). If the PDU does not receive a response within that time, e-mail cannot be sent. Therefore, use DNS servers on the same segment as the PDU or on a nearby segment (but not across a wide-area network [WAN]).

– After you define the IP addresses of the DNS servers, verify that DNS is working correctly by entering the DNS name of a computer on your network to look up the IP address for that computer.

InfraStruXure PDU User’s Guide32

Page 39: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

• Select naming to define the host name and domain name of the PDU:

– Host Name: After you configure a host name here and a domain name in the Domain Name field, users can enter a host name in any field in the PDU interface (except e-mail addresses) that accepts a domain name.

– Domain Name: You need to configure the domain name here only. In all other fields in the PDU interface (except e-mail addresses) that accept domain names, the PDU adds this domain name when only a host name is entered.

• To override all instances of the expansion of a specified host name by the addition of the domain name, set the domain name field to its default, somedomain.com, or to 0.0.0.0.

• To override the expansion of a specific host name entry (or example, when defining a trap receiver) include a trailing period. The PDU recognizes a host name with a trailing period (such as mySnmpServer.) as if it were a fully qualified domain name and does not append the domain name.

• Select test to send a DNS query that tests the setup of your DNS servers:

– As Query Type, select the method to use for the DNS query:

• by Host: the URL name of the server• by FQDN: the fully qualified domain name• by IP: the IP address of the server• by MX: the Mail Exchange used by the server

– As Query Question, identify the value to be used for the selected query type:

– View the result of the test DNS request in the Last Query Response field.

Query Type Selected Query Question to Use

by Host The URL

by FQDN The fully qualified domain name, my_server.my_domain.

by IP The IP address

by MX The Mail Exchange address

33InfraStruXure PDU User’s Guide

Page 40: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

WebPath: Administration > Network > Web > options

Option Description

access To activate changes to any of these selections, log off from the PDU:• Disable: Disables access to the Web interface. (You must use the control console to re-enable

access. Select Network and Web/SSL/TLS. Then for HTTP, select Access and Enabled. For HTTPS access, also select Web/SSL and Enabled.)

• Enable HTTP (the default): Enables Hypertext Transfer Protocol (HTTP), which provides Web access by user name and password, but does not encrypt user names, passwords, and data during transmission.

• Enable HTTPS: Enables Hypertext Transfer Protocol (HTTPS) over Secure Sockets Layer (SSL). SSL encrypts user names, passwords, and data during transmission, and authenticates the PDU by digital certificate. When HTTPS is enabled, your browser displays a small lock icon.

See “Creating and Installing Digital Certificates” in the Security Handbook on the APC Web site, www.apc.com, to choose among the several methods for using digital certificates.

HTTP Port: The TCP/IP port (80 by default) used to communicate by HTTP with the PDU.

HTTPS Port: The TCP/IP port (443 by default) used to communicate by HTTPS with the PDU.

For either of these ports, you can change the port setting to any unused port from 5000 to 32768 for additional security. Users must then use a colon (:) in the address field of the browser to specify the port number. For example, for a port number of 5000 and an IP address of 152.214.12.114:

http://152.214.12.114:5000https://152.214.12.114:5000

ssl cipher suites

Enable or disable any of the SSL encryption ciphers and hash algorithms:• DES: A block cipher that provides authentication by Secure Hash Algorithm.• RC4_MD5 (enabled by default): A stream cipher that provides authentication by MD5 hash

algorithm.• RC4_SHA (enabled by default): A stream cipher that provides authentication by Secure Hash

Algorithm.• 3DES: A block cipher that provides authentication by Secure Hash Algorithm.

InfraStruXure PDU User’s Guide34

Page 41: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

ssl certificate

Add, replace, or remove a security certificate.

Status:• Not installed: A certificate is not installed, or was installed by FTP or SCP to an incorrect

location. Using Add or Replace Certificate File installs the certificate to the correct location, /sec on the PDU.

• Generating: The PDU is generating a certificate because no valid certificate was found.• Loading: A certificate is being activated on the PDU.• Valid certificate: A valid certificate was installed or was generated by the PDU. Click on this

link to view the certificate’s contents.

If you install an invalid certificate, or if no certificate is loaded when you enable SSL, the PDU generates a default certificate, a process which delays access to the interface for up to five minutes. You can use the default certificate for basic encryption-based security, but a security alert message displays whenever you log on.

Add or Replace Certificate File: Enter or browse to the certificate file created with the Security Wizard.

See “Creating and Installing Digital Certificates” in the Security Handbook on the APC Web site, www.apc.com, to choose a method for using digital certificates created by the Security Wizard or generated by the PDU.

Remove: Delete the current certificate.

Option Description

35InfraStruXure PDU User’s Guide

Page 42: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Console Path: Administration > Network > Console > options

Option Description

access Choose one of the following for access by Telnet or Secure SHell (SSH):• Disable: Disables all access to the control console.• Enable Telnet (the default): Telnet transmits user names, passwords, and data without

encryption.• Enable SSH v1 and v2: Do not enable both versions 1 and 2 of SSH unless you require both.

They use extensive processing power.)• Enable SSH v1 only: SSH version 1 encrypts user names, passwords, and data for

transmission. There is little or no delay as you log on.• Enable SSH v2 only: SSH version 2 transmits user names, passwords, and data in encrypted

form with more protection than version 1 from attempts to intercept, forge, or alter data during transmission. There is a noticeable delay as you log on.

Configure the ports to be used by these protocols: • Telnet Port: The Telnet port used to communicate with the PDU (23 by default). You can

change the port setting to any unused port from 5000 to 32768 for additional security. Users must then use a colon (:) or a space, as required by your Telnet client program, to specify the non-default port. For example, for port 5000 and an IP address of 152.214.12.114, your Telnet client requires one of the these commands:

telnet 152.214.12.114:5000telnet 152.214.12.114 5000

• SSH Port: The SSH port used to communicate with the PDU (22 by default). You can change the port setting to any unused port from 5000 to 32768 for additional security. See the documentation for your SSH client for the command line format required to specify a non-default port.

ssh encryption

Enable or disable encryption algorithms (block ciphers) compatible with SSH version 1 or version 2 clients:

If your SSH v1 client cannot use Blowfish, you must also enable DES.

Your SSH v2 client selects the enabled algorithm that provides the highest security. If the client cannot use the default algorithms (3DES or Blowfish), enable an AES algorithm that it can use (AES 128 or AES 256)

InfraStruXure PDU User’s Guide36

Page 43: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Note: To use SSH, you must have an SSH client installed. Most Linux and other UNIX®

platforms include an SSH client, but Microsoft Windows operating systems do not. Clients are available from various vendors.

SNMPSNMPv1

Path: Administration > Network > SNMPv1 > options

All user names, passwords, and community names for SNMP are transferred over the network as plain text. If your network requires the high security of encryption, disable SNMP access or set the access for each community to Read. (A community with Read access can receive status information and use SNMP traps.)

When using InfraStruXure Central to manage the PDU on the public network of an InfraStruXure system, you must have SNMP enabled in the PDU interface. Read access will allow InfraStruXure Central to receive traps from the PDU, but Write access is required while you use the interface of the PDU to set InfraStruXure Central as a trap receiver.

For detailed information on enhancing and managing the security of your system, see the Security Handbook, available from the APC Web site, www.apc.com.

ssh host key Status indicates the status of the host key (private key):• SSH Disabled: No host key in use: When disabled, SSH cannot use a host key.• Generating: The PDU is creating a host key because no valid host key was found.• Loading: A host key is being activated on the PDU.• Valid: One of the following valid host keys is in the /sec directory (the required location on

the PDU): •A 1024-bit host key created by the APC Security Wizard•A 768-bit RSA host key generated by the PDU

Add or Replace: Browse to and upload a host key file created by the Security Wizard:

If you use FTP or Secure CoPy (SCP) instead to transfer the host key file, you must specify the /sec directory as the target location in the command.

To use the APC Security Wizard, see the Security Handbook on the APC Web site, www.apc.com,.

NOTE: To reduce the time required to enable SSH, create and upload a host key in advance. If you enable SSH with no host key loaded, the PDU takes up to 5 minutes to create a host key, and the SSH server is not accessible during that time.

Remove: Remove the current host key.

Option Description

37InfraStruXure PDU User’s Guide

Page 44: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

SNMPv3

Path: Administration > Network > SNMPv3 > options

For SNMP GETs, SETs, and trap receivers, SNMPv3 uses a system of user profiles to identify users. An SNMPv3 user must have a user profile assigned in the MIB software program to perform GETs and SETs, browse the MIB, and receive traps.

Note: To use SNMPv3, you must have a MIB program that supports SNMPv3.

The PDU supports only MD5 authentication and DES encryption.

Option Description

access Enable SNMPv1 Access: Enables SNMP version 1 as a method of communication with this device.

access control

You can configure up to four access control entries to specify which NMSs have access to this device. The opening page for access control, by default, assigns one entry to each of the four available SNMPv1 communities, but you can edit these settings to apply more than one entry to any community to grant access by several specific IP addresses, host names, or IP address masks. To edit the access control settings for a community, click its community name.• If you leave the default access control entry unchanged for a community, that community has

access to this device from any location on the network. • If you configure multiple access control entries for one community name, the limit of four entries

requires that one or more of the other communities must have no access control entry. If no access control entry is listed for a community, that community has no access to this device.

Community Name: The name that a Network Management System (NMS) must use to access the community. The maximum length is 15 ASCII characters, and the default community names for the four communities are public, private, public2, and private2.

NMS IP/Host Name: The IP address, IP address mask, or host name that controls access by NMSs. A host name or a specific IP address (such as 149.225.12.1) allows access only by the NMS at that location. IP addresses that contain 255 restrict access as follows:• 149.225.12.255: Access only by an NMS on the 149.225.12 segment.• 149.225.255.255: Access only by an NMS on the 149.225 segment. • 149.255.255.255: Access only by an NMS on the 149 segment.• 0.0.0.0 (the default setting) which can also be expressed as 255.255.255.255: Access by any

NMS on any segment.

Access Type: The actions an NMS can perform through the community.• Read: GETS only, at any time • Write: GETS at any time, and SETS when no user is logged onto the Web interface or control

console.• Write+: GETS and SETS at any time. • Disabled: No GETS or SETS at any time.

Option Description

access SNMPv3 Access: Enables SNMPv3 as a method of communication with this device.

InfraStruXure PDU User’s Guide38

Page 45: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

user profiles

By default, lists the settings of four user profiles, configured with the user names apc snmp profile1 through apc snmp profile4, and no authentication and no privacy (no encryption). To edit the following settings for a user profile, click a user name in the list.

User Name: The identifier of the user profile. SNMP version 3 maps GETs, SETs, and traps to a user profile by matching the user name of the profile to the user name in the data packet being transmitted. A user name can have up to 32 ASCII characters.

Authentication Passphrase: A phrase of 15 to 32 ASCII characters (apc auth passphrase, by default) that verifies that the NMS communicating with this device through SNMPv3 is the NMS it claims to be, that the message has not been changed during transmission, and that the message was communicated in a timely manner, indicating that it was not delayed and that it was not copied and sent again later at an inappropriate time.

Privacy Passphrase: A phrase of 15 to 32 ASCII characters (apc crypt passphrase, by default) that ensures the privacy of the data (by means of encryption) that an NMS is sending to this device or receiving from this device through SNMPv3.

Authentication Protocol: The APC implementation of SNMPv3 supports MD5 authentication. Authentication will not occur unless MD5 is selected as the authentication protocol.

Privacy Protocol: The APC implementation of SNMPv3 supports DES as the protocol for encrypting and decrypting data. Privacy of transmitted data requires that DES is selected as the privacy protocol.

NOTE: You cannot select the privacy protocol if no authentication protocol is selected.

access control

You can configure up to four access control entries to specify which NMSs have access to this device. The opening page for access control, by default, assigns one entry to each of the four user profiles, but you can edit these settings to apply more than one entry to any user profile to grant access by several specific IP addresses, host names, or IP address masks.• If you leave the default access control entry unchanged for a user profile, all NMSs that use that

profile have access to this device. • If you configure multiple access entries for one user profile, the limit of four entries requires that

one or more of the other user profiles must have no access control entry. If no access control entry is listed for a user profile, no NMS that uses that profile has any access to this device.

To edit the access control settings for a user profile, click its user name.

Access: Mark the Enable checkbox to activate the access control specified by the parameters in this access control entry.

User Name: Select from the drop-down list the user profile to which this access control entry will apply. The choices available are the four user names that you configure through the user profiles option on the left navigation menu.

NMS IP/Host Name: The IP address, IP address mask, or host name that controls access by the NMS. A host name or a specific IP address (such as 149.225.12.1) allows access only by the NMS at that location. An IP address mask that contain 255 restricts access as follows: • 149.225.12.255: Access only by an NMS on the 149.225.12 segment.• 149.225.255.255: Access only by an NMS on the 149.225 segment.• 149.255.255.255: Access only by an NMS on the 149 segment.• 0.0.0.0 (the default setting) which can also be expressed as 255.255.255.255: Access by any

NMS on any segment.

Option Description

39InfraStruXure PDU User’s Guide

Page 46: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

FTP Server Path: Administration > Network > FTP Server

The FTP server settings enable (by default) or disable access to the FTP server and specify the TCP/IP port (21 by default) that the FTP server uses to communicate with the PDU. The FTP server uses both the specified port and the port one number lower than the specified port.

You can change the Port setting to the number of any unused port from 5001 to 32768 for added security. Users must then use a colon (:) to specify the non-default port number. For example, for port 5001 and IP address 152.214.12.114, the command would be ftp 152.214.12.114:5001.

Note: FTP transfers files without encryption. For higher security, disable the FTP server, and transfer files with Secure CoPy (SCP). Selecting and configuring Secure SHell (SSH) enables SCP automatically.

At any time that you want a UPS to be accessible for management by InfraStruXure Central, FTP Server must be enabled in the PDU interface.

For detailed information on enhancing and managing the security of your system, see the Security Handbook, available on APC Web site, www.apc.com,.

InfraStruXure PDU User’s Guide40

Page 47: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Administration: Notification and Logging

Event Actions Path: Administration > Notification > Event Actions > options

Types of notification

You can configure event actions to occur in response to an event or group of events. These actions notify users of the event in any of several ways:

• Active, automatic notification. The specified users or monitoring devices are contacted directly.

– E-mail notification

– SNMP traps

– Syslog notification

• Indirect notification in the event log. If no direct notification is configured, users must check the log to determine which events have occurred.

For another method of indirect notification, see “SNMP” on page 37. SNMP enables an NMS to perform informational queries. For SNMPv1, configuring the most restrictive SNMP access type, READ, enables informational queries without the risk of allowing remote configuration changes.

You can also log system performance data to use for device monitoring. See “Data log” on page 21 for information on how to configure and use this data logging option.

Configuring event actions

Notification Parameters. For events that have an associated clearing event, you can also set the following parameters as you configure events individually or by group, as described in the next two sections. To access the parameters, click the receiver or recipient name.

Parameter Description

Delay x time before sending If the event persists for the specified time, notification is sent. If the condition clears before the time expires, no notification is sent.

Repeat at an interval of x time The notification is sent at the specified interval (e.g., every 2 minutes).

Up to x times During an active event, the notification repeats for this number of times.

Until condition clears The notification is sent repeatedly until the condition clears or is resolved.

41InfraStruXure PDU User’s Guide

Page 48: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Configuring by event. To define event actions for an individual event:

1. Select the Administration tab, Notification on the top menu bar, and by event under Event Actions on the left navigation menu.

2. In the list of events, review the marked columns to see whether the action you want is already configured. (By default, logging is configured for all events.)

3. To view or change the current configuration, such as recipients to be notified by e-mail, or Network Management Systems (NMSs) to be notified by SNMP traps, click on the event name.

Note: If no Syslog server is configured, items related to Syslog configuration are not displayed.

When viewing details of an event’s configuration, you can change the configuration, enable or disable event logging or Syslog, or disable notification for specific e-mail recipients or trap receivers, but you cannot add or remove recipients or receivers. To add or remove recipients or receivers, see the following:

• “Identifying Syslog Servers” on page 46

• “E-mail recipients” on page 44

• “Trap Receivers” on page 44Configuring by group. To configure a group of events simultaneously:

1. Select the Administration tab, Notification on the top menu bar, and by group under Event Actions on the left navigation menu.

2. Choose how to group events for configuration:

– Choose Grouped by severity, and then select all events of one or more severity levels. You cannot change the severity of an event.

– Choose Grouped by category, and then select all events in one or more pre-defined categories.

3. Click Next>> to move from page to page to do the following:

a. Select event actions for the group of events.

• To choose any action except Logging (the default), you must first have at least one relevant recipient or receiver configured.

• If you choose Logging and have configured a Syslog server, select Event Log or Syslog (or both) on the next page.

b. Select whether to leave the newly configured event action enabled for this group of events or to disable the action.

InfraStruXure PDU User’s Guide42

Page 49: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Active, Automatic, Direct NotificationE-mail notification

Overview of setup. Use the Simple Mail Transfer Protocol (SMTP) to send e-mail to up to four recipients when an event occurs.

To use the e-mail feature, you must define the following settings:

• The IP addresses of the primary and, optionally, the secondary Domain Name System (DNS) servers. (See “DNS” on page 32.)

• The IP address or DNS name for SMTP Server and From Address. (See “SMTP” on page 43.)

• The e-mail addresses for a maximum of four recipients. (See “E-mail recipients” on page 44.)

Note: You can use the To Address setting of the recipients option to send e-mail to a text-based pager.

SMTP.

Path: Administration > Notification > E-mail > server

Setting Description

Local SMTP Server

The IP address or DNS name of the local SMTP server.

NOTE: This definition is required only when SMTP Server is set to Local. See “E-mail recipients” on page 44.

From Address

The contents of the From field in e-mail messages sent by the PDU:• In the format user@ [IP_address] (if an IP address is specified as Local SMTP Server)• In the format user@domain (if DNS is configured and the DNS name is specified as Local

SMTP Server) in the e-mail messages.

NOTE: The local SMTP server may require that you use a valid user account on the server for this setting. See the server’s documentation.

43InfraStruXure PDU User’s Guide

Page 50: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

E-mail recipients.

Path: Administration > Notification > E-mail > recipients

Identify up to four e-mail recipients.

E-mail test (Administration > Notification > E-mail > test). Send a test message to a configured recipient.

SNMP traps

Trap Receivers.

Path: Administration > Notification > SNMP Traps > trap receivers

View trap receivers by NMS IP/Host Name. You can configure up to six trap receivers.

• To open the page for configuring a new trap receiver, click Add Trap Receiver.

• To modify or delete a trap receiver, first click its IP address or host name to access its settings. (If you delete a trap receiver, all notification settings configured under Event Actions for the deleted trap receiver are set to their default values.)

• To specify the trap type for a trap receiver, select either the SNMPv1 or SNMPv3 radio button. For an NMS to receive both types of traps, you must configure two trap receivers for that NMS, one for each trap type.

Setting Description

To Address The user and domain names of the recipient. To use e-mail for paging, use the e-mail address for the recipient’s pager gateway account (for example, [email protected]). The pager gateway will generate the page.

To bypass the DNS lookup of the mail server’s IP address, use the IP address in brackets instead of the e-mail domain name, e.g., use jsmith@[xxx.xxx.x.xxx] instead of [email protected]. This is useful when DNS lookups are not working correctly.

NOTE: The recipient’s pager must be able to use text-based messaging.

SMTP Server Select one of the following methods for routing e-mail:• Local: Through the PDU’s SMTP server. This setting (recommended) ensures that the e-mail

is sent before the PDU’s 20-second time-out, and, if necessary, is retried several times. Also do one of the following: • Enable forwarding at the PDU’s SMTP server so that it can route e-mail to external SMTP

servers. Typically, SMTP servers are not configured to forward e-mail. Check with the administrator of your SMTP server before changing its configuration to allow forwarding.

• Set up a special e-mail account for the PDU to forward e-mail to an external mail account.• Recipient: Directly to the recipient’s SMTP server. With this setting, the PDU tries to send

the e-mail only once. On a busy remote SMTP server, the time-out may prevent some e-mail from being sent.

When the recipient uses the PDU’s SMTP server, this setting has no effect.

E-mail Generation

Enables (by default) or disables sending e-mail to the recipient.

Format The long format contains Name, Location, Contact, IP address, serial number of the device, date and time, event code, and event description. The short format provides only the event description.

InfraStruXure PDU User’s Guide44

Page 51: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

SNMPv1 option.

SNMPv3 option. Select the identifier of the user profile for this trap receiver. (To view the settings of the user profiles identified by the user names selectable here, choose Network on the top menu bar and user profiles under SNMPv3 on the left navigation menu.)

See “SNMPv3” on page 38 for information on creating user profiles and selecting authentication and encryption methods.

SNMP Trap Test

Path: Administration > Notification > SNMP Traps > test

Last Test Result. The result of the most recent SNMP trap test. A successful SNMP trap test verifies only that a trap was sent; it does not verify that the trap was received by the selected trap receiver. A trap test succeeds if all of the following are true:

• The SNMP version (SNMPv1 or SNMPv3) configured for the selected trap receiver is enabled on this device.

• The trap receiver is enabled.

• If a host name is selected for the To address, that host name can be mapped to a valid IP address.To. Select the IP address or host name to which a test SNMP trap will be sent. If no trap receiver was ever configured, a link to the Trap Receiver configuration page is displayed.

SyslogPath: Logs > Syslog > options

The PDU can send messages to up to four Syslog servers when an event occurs. The Syslog servers record events that occur at network devices in a log that provides a centralized record of events.

This user’s guide does not describe Syslog or its configuration values in detail. See RFC3164 for more information about Syslog.

Item Definition

Trap Generation Enable (the default) or disable trap generation for this trap receiver.

NMS IP/Host Name The IP address or host name of this trap receiver. The default, 0.0.0.0, leaves the trap receiver undefined.

Community Name The name (public by default) used as an identifier when SNMPv1 traps are sent to this trap receiver.

Authenticate Traps When this option is enabled (the default), the NMS identified by the NMS IP/Host Name setting will receive authentication traps (traps generated by invalid attempts to log on to this device). To disable that ability, unmark the checkbox.

45InfraStruXure PDU User’s Guide

Page 52: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Identifying Syslog Servers.

Path: Logs > Syslog > servers

Syslog Settings.

Path: Logs > Syslog > settings

Setting Definition

Syslog Server

Uses IP addresses or host names to identify from one to four servers to receive Syslog messages sent by the PDU.

Port The user datagram protocol (UDP) port that the PDU will use to send Syslog messages. The default is 514, the UDP port assigned to Syslog.

Setting Definition

Message Generation

Enables (by default) or disables the Syslog feature.

Facility Code Selects the facility code assigned to the PDU’s Syslog messages (User, by default).

NOTE: User best defines the Syslog messages sent by the PDU. Do not change this selection unless advised to do so by the Syslog network or system administrator.

Severity Mapping

Maps each severity level of PDU or Environment events to available Syslog priorities. You should not need to change the mappings.

The following definitions are from RFC3164:• Emergency: The system is unusable• Alert: Action must be taken immediately• Critical: Critical conditions• Error: Error conditions• Warning: Warning conditions• Notice: Normal but significant conditions• Informational: Informational messages• Debug: Debug-level messages

Following are the default settings for the four Local Priority settings:• Severe is mapped to Critical• Warning is mapped to Warning• Informational is mapped to Info

NOTE: To disable Syslog messages, see “Configuring event actions” on page 41.

InfraStruXure PDU User’s Guide46

Page 53: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Syslog Test and Format example.

Path: Logs > Syslog > test

Send a test message to the Syslog servers configured through the servers option.

1. Select a severity to assign to the test message.2. Define the test message, according to the required message fields

– The priority (PRI): the Syslog priority assigned to the message’s event, and the facility code of messages sent by the PDU.

– The Header: a time stamp and the IP address of the PDU.– The message (MSG) part:

• The TAG field, followed by a colon and space, identifies the event type.• The CONTENT field is the event text, followed (optionally) by a space and the event

code.

For example, APC: Test Syslog is valid.

Queries (SNMP GETs)

See “SNMP” on page 37 for a description of SNMPv1 and SNMPv3 settings that enable an NMS to perform informational queries. With SNMPv1, which does not encrypt data before transmission, configuring the most restrictive SNMP access type (READ) enables informational queries without allowing remote configuration changes.

47InfraStruXure PDU User’s Guide

Page 54: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Administration: General Options

Identification Path: Administration > General > Identification

Define values for Name (the device name), Location (the physical location), and Contact (the person responsible for the device) used by the PDU’s SNMP agent. These settings are the values used for the MIB-II sysName, sysContact, and sysLocation Object Identifiers (OIDs).

For more information about MIB-II OIDs, see the PowerNet® SNMP Management Information Base (MIB) Reference Guide, available on the APC Web site, www.apc.com.

Set the Date and TimeMethod

Path: Administration > General > Date & Time > mode

Set the time and date used by the PDU. You can change the current settings manually or through a Network Time Protocol (NTP) Server:

• Manual Mode: Do one of the following:

– Enter the date and time for the PDU.

– Mark the check box Apply Local Computer Time to match the date and time settings of the computer you are using.

• Synchronize with NTP Server: Have an NTP Server define the date and time for the PDU.

Daylight saving

Path: Administration > General > Date & Time > daylight saving

Enable traditional United States Daylight Saving Time (DST), or enable and configure a customized daylight saving time to match how Daylight Saving Time is implemented in your local area. DST is disabled by default.

Setting Definition

Primary NTP Server Enter the IP address or domain name of the primary NTP server.

Secondary NTP Server Enter the IP address or domain name of the secondary NTP server, when a secondary server is available.

Time Zone Select a time zone. The number of hours preceding each time zone in the list is the offset from Coordinated Universal Time (UTC), formerly Greenwich Mean Time).

Update Interval Define how often, in hours, the PDU accesses the NTP Server for an update. Minimum: 1; Maximum: 8760 (1 year).

Update Using NTP Now Initiate an immediate update of date and time by the NTP Server.

InfraStruXure PDU User’s Guide48

Page 55: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

When customizing Daylight Saving Time (DST):

• If the local DST always starts or ends on the fourth occurrence of a specific weekday of a month (e.g, the fourth Sunday), choose Fourth/Last. If a fifth Sunday occurs in that month in a subsequent year, the time setting still changes on the fourth Sunday.

• If the local DST always starts or ends on the last occurrence of a specific weekday of a month, whether it is the fourth or the fifth occurrence, choose Fifth/Last.

Format

Path: Administration > General > Date & Time > date format

Select the numerical format in which to display all dates in this user interface. In the selections, each letter m (for month), d (for day), and y (for year) represents one digit. Single-digit days and months are displayed with a leading zero.

Use an .ini File Path: Administration > General > User Config File

Use the settings from one PDU to configure another. Retrieve the config.ini file from the configured PDU, customize that file (e.g., to change the IP address), and upload the customized file to the new PDU. The file name can be up to 64 characters, and must have the.ini suffix.

To retrieve and customize the file of a configured PDU, see “How to Export Configuration Settings” on page 54.

Instead of uploading the file to one PDU, you can export the file to multiple PDUs by using an FTP or SCP script or a batch file and the APC .ini file utility, available from www.apc.com/tools/download.

Temperature UnitsPath: Administration > General > Unit Preference

Select the temperature scale (Fahrenheit or Celsius) in which to display all temperature measurements in this user interface.

Status Reports the progress of the upload. The upload succeeds even if the file contains errors, but a system event r reports the errors in the event log.

Upload Browse to the customized file and upload it so that the current PDU can use it to set its own configuration.

49InfraStruXure PDU User’s Guide

Page 56: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Reset the Interface Path: Administration > General > Reset/Reboot

Configuring Links Path: Administration > General > Quick Links

Select the Administration tab, General on the top menu bar, and Quick Links on the left navigation menu to view and change the URL links displayed at the bottom left of each page of the interface.

By default, these links access the following Web pages:

• Link 1: The home page of the APC Web site.

• Link 2: A page where you can use samples of APC Web-enabled products.

• Link 3: The home page of the APC Remote Monitoring Service.To reconfigure any of the following, click the link name in the Display column:

• Display: The short link name displayed on each interface page

• Name: A name that fully identifies the target or purpose of the link

• Address: Any URL—for example, the URL of another device or server

About the PDU Path: Administration > General > About

The hardware information is especially useful to APC Customer Support to troubleshoot problems with the PDU. The serial number and MAC address are also available on the PDU itself.

Firmware information for the Application Module and APC OS (AOS) indicates the name, the firmware version, and the date and time each firmware module was created. This information is also useful in troubleshooting and enables you to determine if updated firmware is available at the APC Web site.

Management Uptime is the length to time the interface has been running continuously.

Action Definition

Reboot Management Interface

Restarts the interface of the PDU.

Reset All1 Select Exclude TCP/IP to reset all values except TCP/IP; clear Exclude TCP/IP to reset all configuration values.

Reset Only1 TCP/IP settings: Set TCP/IP Configuration to DHCP & BOOTP, its default setting, requiring that the PDU receive its TCP/IP settings from a DHCP or BOOTP server. See “TCP/IP and Communication Settings” on page 29.

Event configuration: Reset all changes to event configuration, by event and by group, to their default settings.

1. Resetting may take up to a minute.

InfraStruXure PDU User’s Guide50

Page 57: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

APC Device IP Configuration Wizard

Capabilities, Requirements, and InstallationHow to use the Wizard to configure TCP/IP settings

The APC Device IP Configuration Wizard configures the IP address, subnet mask, and default gateway of one or more PDUs. You can use the Wizard in either of the following ways:

• Remotely over your TCP/IP network to discover and configure unconfigured PDUs on the same network segment as the computer running the Wizard.

• Through a direct connection from a serial port of your computer to the PDU to configure or reconfigure it.

System requirements

The Wizard runs on Microsoft Windows 2000, Windows 2003, and Windows XP operating systems.

Installation

To install the Wizard from the Utility CD, if one is provided with your PDU:

1. If autorun is enabled, the user interface of the CD starts when you insert the CD. Otherwise, open the file contents.htm on the CD.

2. Click Device IP Configuration Wizard and follow the instructions.To install the Wizard from a downloaded executable file:

1. Go to www.apc.com/tools/download.

2. Download the Device IP Configuration Wizard.

3. Run the executable file in the folder to which you downloaded it.

51InfraStruXure PDU User’s Guide

Page 58: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Use the WizardNote: Most software firewalls must be temporarily disabled for the Wizard to discover unconfigured PDUs.

Launch the WizardThe installation creates a shortcut link in the Start menu to launch the Wizard.

Configure the basic TCP/IP settings remotely

Prepare to configure the settings. Before you run the Wizard:

1. Contact your network administrator to obtain valid TCP/IP settings.

2. If you are configuring multiple unconfigured PDUs, obtain the MAC address of each one to identify it when the Wizard discovers it. (The Wizard displays the MAC address on the screen on which you then enter the TCP/IP settings.)

– The MAC address is on a label on the PDU.

– You can also obtain the MAC address from the Quality Assurance slip that came with the PDU.

Run the Wizard to perform the configuration. To discover and configure unconfigured PDUs over the network:

1. From the Start menu, launch the Wizard. The Wizard detects the first PDU that is not configured.

2. Select Remotely (over the network), and click Next >.

3. Enter the system IP, subnet mask, and default gateway for the PDU identified by the MAC address. Click Next >.

On the Transmit Current Settings Remotely screen, if you select the Start a Web browser when finished check box, the default Web browser connects to the PDU after the Wizard transmits the settings.

4. Click Finish to transmit the settings. If the IP address you entered is in use on the network, the Wizard prompts you to enter an IP address that is not in use. Enter a correct IP address, and click Finish.

5. If the Wizard finds another unconfigured PDU, it displays the screen to enter TCP/IP settings. Repeat this procedure beginning at step 3, or to skip the PDU whose MAC address is currently displayed, click Cancel.

InfraStruXure PDU User’s Guide52

Page 59: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Configure or reconfigure the TCP/IP settings locally

1. Contact your network administrator to obtain valid TCP/IP settings.

2. Connect the serial configuration cable (which came with the PDU) from an available communications port on your computer to the serial port of the card or device. Make sure no other application is using the computer port.

3. From the Start menu, launch the Wizard application.

4. If the PDU is not configured, wait for the Wizard to detect it. Otherwise, click Next>.

5. Select Locally (through the serial port), and click Next >.

6. Enter the system IP, subnet mask, and default gateway for the PDU, and click Next >.

7. On the Transmit Current Settings Remotely screen, if you select the Start a Web browser when finished check box, the default Web browser connects to the PDU after the Wizard transmits the settings.

8. Click Finish to transmit the TCP/IP settings. If the IP address you entered is in use on the network, the Wizard prompts you to enter an IP address that is not in use. Enter a correct IP address, and click Finish.

9. If you selected Start a Web browser when finished in step 7, you can now configure other parameters through the Web interface of the device.

53InfraStruXure PDU User’s Guide

Page 60: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

How to Export Configuration Settings

Retrieving and Exporting the .ini FileSummary of the procedure

An Administrator can retrieve the .ini file of a PDU and export it to another PDU or to multiple PDUs.

1. Configure one PDU to have the settings you want to export.

2. Retrieve the .ini file from that PDU.

3. Customize the file to change at least the TCP/IP settings.

4. Use a file transfer protocol supported by the PDU to transfer a copy to one or more other PDUs. For a transfer to multiple PDUs, use an FTP or SCP script or the APC .ini file utility.

Each receiving PDU uses the file to reconfigure its own settings and then deletes it.

Contents of the .ini file

The config.ini file you retrieve from the PDU contains the following:

• section headings and keywords (only those supported for the device from which you retrieve the file): Section headings are category names enclosed in brackets ([ ]). Keywords, under each section heading, are labels describing specific PDU settings. Each keyword is followed by an equals sign and a value (either the default or a configured value).

• The Override keyword: With its default value, this keyword prevents the exporting of one or more keywords and their device-specific values, e.g., in the [NetworkTCP/IP] section, the default value for Override (the MAC address of the PDU) blocks the exporting of values for the SystemIP, SubnetMask, DefaultGateway, and BootMode.

Detailed procedures

Retrieving. To set up and retrieve an .ini file to export:

1. If possible, use the interface of a PDU to configure it with the settings to export. Directly editing the .ini file risks introducing errors.

2. To use FTP to retrieve config.ini from the configured PDU:

a. Open a connection to the PDU, using its IP address:

ftp> open ip_address

b. Log on using the Administrator user name and password.

c. Retrieve the config.ini file containing the PDU’s settings:

ftp> get config.ini

The file is written to the folder from which you launched FTP.

To retrieve configuration settings from multiple PDUs and export them to other PDUs, see Release Notes: ini File Utility, version 1.0, available on the APC Web site, www.apc.com.

InfraStruXure PDU User’s Guide54

Page 61: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Customizing. You must customize the file before you export it.

1. Use a text editor to customize the file.

– Section headings, keywords, and pre-defined values are not case-sensitive, but string values that you define are case-sensitive.

– Use adjacent quotation marks to indicate no value. For example, LinkURL1="" indicates that the URL is intentionally undefined.

– Enclose in quotation marks any values that contain leading or trailing spaces or are already enclosed in quotation marks.

– To export scheduled events, configure the values directly in the .ini file.

– To export a system time with the greatest accuracy, if the receiving PDUs can access a Network Time Protocol server, configure enabled for NTPEnable:

NTPEnable=enabled

Alternatively, reduce transmission time by exporting the [SystemDate/Time] section as a separate .ini file.

– To add comments, start each comment line with a semicolon (;).

2. Copy the customized file to another file name in the same folder:

– The file name can have up to 64 characters and must have the .ini suffix.

– Retain the original customized file for future use. The file that you retain is the only record of your comments.

Transferring the file to a single PDU. To transfer the .ini file to another PDU, do either of the following:

• From the Web interface of the receiving PDU, select the Administration tab, General on the top menu bar, and User Config File on the left navigation menu. Enter the full path of the file, or use Browse.

• Use any file transfer protocol supported by PDUs, i.e., FTP, FTP Client, SCP, or TFTP). The following example uses FTP:

a. From the folder containing the copy of the customized .ini file, use FTP to log in to the PDU to which you are exporting the .ini file:

ftp> open ip_address

b. Export the copy of the customized .ini file to the root directory of the receiving PDU:

ftp> put filename.ini

Exporting the file to multiple PDUs. To export the .ini file to multiple PDUs:

• Use FTP or SCP, but write a script that incorporates and repeats the steps used for exporting the file to a single PDU.

• Use a batch processing file and the APC .ini file utility.

To create the batch file and use the utility, see Release Notes: ini File Utility, version 1.0 on the APC Web site, www.apc.com.

55InfraStruXure PDU User’s Guide

Page 62: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

The Upload Event and Error MessagesThe event and its error messages

The following event occurs when the receiving PDU completes using the .ini file to update its settings.

Configuration file upload complete, with number valid values

If a keyword, section name, or value is invalid, the upload by the receiving PDU succeeds, and additional event text states the error.

Messages in config.ini

A device associated with the PDU from which you download the config.ini file must be discovered successfully in order for its configuration to be included. If the device is not present or, for another reason, is not discovered, the config.ini file contains a message under the appropriate section name, instead of keywords and values.

If you did not intend to export the configuration of the device as part of the .ini file import, ignore these messages.

Errors generated by overridden values

The Override keyword and its value will generate error messages in the event log when it blocks the exporting of values.

See “Contents of the .ini file” on page 54 for information about which values are overridden.

Because the overridden values are device-specific and not appropriate to export to other PDUs, ignore these error messages. To prevent these error messages, you can delete the lines that contain the Override keyword and the lines that contain the values that they override. Do not delete or change the line containing the section heading.

Event text Description

Configuration file warning: Invalid keyword on line number.

Configuration file warning: Invalid value on line number.

A line with an invalid keyword or value is ignored.

Configuration file warning: Invalid section on line number.

If a section name is invalid, all keyword/value pairs in that section are ignored.

Configuration file warning: Keyword found outside of a section on line number.

A keyword entered at the beginning of the file (i.e., before any section headings) is ignored.

Configuration file warning: Configuration file exceeds maximum size.

If the file is too large, an incomplete upload occurs. Reduce the size of the file, or divide it into two files, and try uploading again.

InfraStruXure PDU User’s Guide56

Page 63: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Related TopicsOn Windows operating systems, instead of transferring .ini files, you can use the APC Device IP Configuration Wizard to update the basic TCP/IP settings of PDUs and configure other settings through their user interface.

See “APC Device IP Configuration Wizard” on page 51.

57InfraStruXure PDU User’s Guide

Page 64: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

File Transfers

Upgrading FirmwareBenefits of upgrading firmware

When you upgrade the firmware on the PDU:

• You obtain the latest bug fixes and performance improvements.

• New features become available for immediate use. Keeping the firmware versions consistent across your network ensures that all PDUs support the same features in the same manner.

Firmware files (PDU)

A firmware version consists of two modules: An APC Operating System (AOS) module and an application module. Each module contains one or more Cyclical Redundancy Checks (CRCs) to protect its data from corruption during transfer.

The APC Operating System (AOS) and application module files used with the PDU share the same basic format:

apc_hardware-version_type_firmware-version.bin

• apc: Indicates that this is an APC file.

• hardware-version: hw0x identifies the version of the hardware on which you can use this binary file.

• type: Identifies whether the file is for the APC Operating System (AOS) or the application module for the PDU.

• version: The version number of the file.

• bin: Indicates that this is a binary file.

Obtain the latest firmware versionAutomated upgrade tool for Microsoft Windows systems. An upgrade tool automates the transferring of the firmware modules on any supported Windows operating system. Obtain the latest version of the tool at no cost from www.apc.com/tools/download. At this Web page, find the latest firmware release for your APC product and download the automated tool. Never use the tool for one APC product to upgrade firmware of another.

Manual upgrades, primarily for Linux systems. If no computer on your network is running a Microsoft Windows operating system, you must upgrade the firmware of your PDUs by using the separate AOS and application firmware modules.

Obtain the individual firmware modules by downloading the automated tool from www.apcc.com/tools/download, then extracting the firmware files from the tool.

InfraStruXure PDU User’s Guide58

Page 65: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

To extract the firmware files:

1. Run the tool.

2. At the prompts, click Next>, and then specify the directory location to which the files will be extracted.

3. When the Extraction Complete message displays, close the dialog box.

Firmware File Transfer MethodsTo upgrade the firmware of a PDU, use one of these methods:

• From a networked computer running a Microsoft Windows operating system, use the firmware upgrade tool downloaded from the APC Web site.

• From a networked computer on any supported operating system, use FTP or SCP to transfer the individual AOS and application firmware modules.

• For a PDU that is not on your network, use XMODEM through a serial connection to transfer the individual firmware modules from your computer to the PDU.

Caution: When you transfer individual firmware modules, you must transfer the APC Operating System (AOS) module to the PDU before you transfer the application module.

Use FTP or SCP to upgrade one PDU

FTP. For you to use FTP to upgrade one PDU over the network:

• The PDU must be connected to the network, and its system IP, subnet mask, and default gateway must be configured

• The FTP server must be enabled at the PDU

• The firmware files must be extracted from the firmware upgrade tool (see “To extract the firmware files:” on page 59)

To transfer the files:

1. Open a command prompt window of a computer on the network. Go to the directory that contains the firmware files, and list the files:

C:\>cd\apcC:\apc>dir

For the listed files, xxx represents the firmware version number:

• apc_hw03_aos_xxx.bin

• apc_hw03_application_xxx.bin

2. Open an FTP client session:

C:\apc>ftp

59InfraStruXure PDU User’s Guide

Page 66: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

3. Type open and the PDU’s IP address, and press ENTER. If the port setting for the FTP Server has changed from its default of 21, you must use the non-default value in the FTP command.

– For Windows FTP clients, separate a non-default port number from the IP address by a space. For example:ftp> open 150.250.6.10 21000

– Some FTP clients require a colon instead before the port number.

4. Log on as Administrator; apc is the default user name and password.

5. Upgrade the AOS. In the example, xxx is the firmware version number:

ftp> binftp> put apc_hw03_aos_xxx.bin

6. When FTP confirms the transfer, type quit to close the session.

7. After 20 seconds, repeat step 2 through step 6. In step 5, use the application module file name.

SCP. To use Secure CoPy (SCP) to upgrade firmware for a PDU:

1. Identify and locate the firmware modules described in the preceding instructions for FTP.

2. Use an SCP command line to transfer the AOS firmware module to the PDU. The following example uses xxx to represent the version number of the AOS module:scp apc_hw03_aos_xxx.bin [email protected]:apc_hw03_aos_xxx.bin

3. Use a similar SCP command line, with the name of the application module, to transfer the second firmware module to the PDU.

How to upgrade multiple PDUs

Export configuration settings. You can create batch files and use an APC utility to retrieve configuration settings from multiple PDUs and export them to other PDUs.

See Release Notes: ini File Utility, version 1.0, available on the APC Web site, www.apc.com.

Use FTP or SCP to upgrade multiple PDUs. To upgrade multiple PDUs using an FTP client or using SCP, write a script which automatically performs the procedure.

InfraStruXure PDU User’s Guide60

Page 67: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Use XMODEM to upgrade one PDU

To upgrade the firmware for one PDU that is not on the network, you must extract the firmware files from the firmware upgrade tool (see “To extract the firmware files:” on page 59).

To transfer the files:

1. Obtain the individual firmware modules (the AOS module and the application module) from www.apc.com/tools/download.

2. Select a serial port at the local computer and disable any service that uses the port.

3. Connect the provided configuration cable to the selected port and to the serial port at the PDU.

4. Run a terminal program such as HyperTerminal, and configure the selected port for 2400 bps, 8 data bits, no parity, 1 stop bit, and no flow control.

5. Press ENTER to display the User Name prompt.

6. Enter the Administrator user name and password (apc by default for both).

7. From the Control Console menu, select System, then Tools, then File Transfer, then XMODEM; and type Yes at the prompt to continue.

8. Select a baud rate, change the terminal program’s baud rate to match your selection, and press ENTER. A higher baud rate causes faster upgrades.

9. From the terminal program’s menu, select the binary AOS file to transfer using XMODEM-CRC. After the XMODEM transfer is complete, set the baud rate to 2400. The PDU automatically restarts.

10.Repeat step 4 through step 9 to install the application module. In step 9, use the application module file name, not the AOS module file name.

11. For information about the format used for firmware modules, see “Firmware files (PDU)” on page 58.

Verifying Upgrades and UpdatesVerify the success or failure of the transfer

To verify whether a firmware upgrade succeeded, use the Network menu in the control console and select the FTP Server option to view Last Transfer Result, or use an SNMP GET to the mfiletransferStatusLastTransferResult OID.

61InfraStruXure PDU User’s Guide

Page 68: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Last Transfer Result codes

Verify the version numbers of installed firmware.

Use the Web interface to verify the versions of the upgraded firmware modules by selecting the Administration tab, General on the top menu bar, and About on the left navigation menu, or use an SNMP GET to the MIB II sysDescr OID.

Code Description

Successful The file transfer was successful.

Result not available There are no recorded file transfers.

Failure unknown The last file transfer failed for an unknown reason.

Server inaccessible The TFTP or FTP server could not be found on the network.

Server access denied The TFTP or FTP server denied access.

File not found The TFTP or FTP server could not locate the requested file.

File type unknown The file was downloaded but the contents were not recognized.

File corrupt The file was downloaded but at least one Cyclical Redundancy Check (CRC) failed.

InfraStruXure PDU User’s Guide62

Page 69: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Index

AAbout options

for information about the Management Card 50Access

enabling or disabling methods of accessto the control console 36to the Web interface 34

priority for logging on 2to the control console

locally 6remotely 5

AdministrationNetwork menu 29Notification menu 41

Apply Local Computer Time 48Authenticating users through RADIUS 25Authentication Traps setting 45Automatic log-off for inactivity 28

BBOOTP

BOOTP server providing TCP/IP settings 29

CCertificates, how to create, view, or remove 35Community Name

for trap receivers 45config.ini file. See User configuration files.Configuring

RADIUS authentication 26Contact identification (whom to contact) 48Control console

configuring access 36Device Manager menu 8navigating menus 8refreshing menus 8structure 8

DData log

importing into spreadsheet 23Log Interval setting 22rotation (archiving) 22using FTP or SCP to retrieve 23

Date & Time settings 48Date format, configuring 49Daylight saving time 48Device IP Configuration Wizard

installation and system requirements 51using the wizard

for local configuration. 53for remote configuration 52

Device Manager menu, control console 8DHCP

APC cookie 31DHCP server providing TCP/IP settings 29

Disablee-mail to a recipient 44encryption algorithms for SSH 36reverse lookup 21SSL cipher suites 34Telnet 36

DNSdefining host and domain names 33query types 33specifying DNS servers by IP address 32

EE-mail

configuring notification parameters 43configuring recipients 44test message 44using for paging 44

Enablee-mail forwarding to external SMTP servers 44e-mail to a recipient 44encryption algorithms for SSH 36reverse lookup 21SSL cipher suites 34Telnet 36versions of SSH 36

InfraStruXure PDU User’s Guide 63

Page 70: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

Error messagesfrom overridden values in .ini file 56

Ethernet port speed 32Event actions 41

configuring by event 42configuring by group 42

Event logaccessing 8displaying and using 20errors from overridden values in .ini file 56filtering by date or time 20filtering by event 20using FTP del command 24using FTP or SCP to retrieve 23

event.txt filecontents 23importing into spreadsheet 23

FFacility Code (Syslog setting) 46Firmware

benefits of upgrading 58file transfer methods

automated upgrade tool 58FTP or SCP 59XMODEM 61

obtaining the latest version 58upgrading multiple Management Cards 60versions displayed on main screen 6

From Address (SMTP setting) 43FTP

server settings 40transferring firmware files 59using to retrieve event or data log 23

GGeneral menu, Administration tab 48

HHelp

on control console 8Host keys

adding or replacing 37status 37

Host name of trap receivers 45

IIdentification (Name, Location, and Contact)

in Web interface 48on control console main screen 6

Inactivity timeout 28ini files, See User configuration filesInitial setup 1

JJavaScript, required to launch log in new

window 20, 21

KKeywords in user configuration file 54

LLast Transfer Result codes 62Launch Log in New Window, JavaScript

requirement. 20, 21Links, configuration 50Local SMTP Server

defining by IP address or DNS name 43recommended option for routing e-mail 44

Local Users, setting user access 25Location (system value) 48Logging on

control console 5Web interface 10

Login date and time, control console 7Loopback address not to be used as default

gateway 1

MMain screen of control console

information fields displayed 6status fields displayed 7

MenusControl Console 8General 48Logs 20Network 29Notification 41top menu bar 13

Message Generation (Syslog setting) 46

64 InfraStruXure PDU User’s Guide

Page 71: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

NNetwork menu 29Network Time Protocol (NTP) 48Network timer, resetting 4NMS IP/Host Name for trap receivers 45Notification menu 41Notification, delaying or repeating 41

OOverride keyword, user configuration file 54

PPaging

by using e-mail 44Passwords

default for each account type 10defining for each account type 25for data log repository 22recovering from lost password 3

Port speed, configuring for Ethernet 32Ports

FTP server 40HTTP and HTTPS 34RADIUS server 26Telnet and SSH 36

Primary NTP Server 48

QQuick Links, configuration 50

RRADIUS

configuration 26server configuration 27supported RADIUS servers 27

Reboot Management Interface 50Recipient SMTP server 44Remote Monitoring Service 50Remote Users

authentication 26setting user access 25

Reset All 50Reset Only 50Restart for inactivity, preventing 4Reverse lookup 21

SSCP

for high-security file transfer 40transferring firmware files 59using to retrieve event or data log 23

Secondary NTP Server 48Section headings, user configuration file 54Severity Mapping (Syslog setting) 46SMTP server

selecting for e-mail recipients 44SNMP

access and access controlSNMPv1 38SNMPv3 38

authentication traps 45disabling SNMPv1 for high-security systems 37

SSHencryption algorithms 36host keys 37

SSLcipher suites 34configuring cipher suites 34how to create, view, or remove certificates 35

Statuson control console main screen 7

Synchronize with NTP Server,(Date & Time) 48

Syslogidentifying the Syslog server and port 46mapping event severity to Syslog priorities 46settings 46test 47

System Name 48

TTCP/IP configuration 29Temperature units (Fahrenheit or Celsius) 49Test

DNS query 33e-mail recipient settings 44RADIUS server path 26Syslog 47trap receiver 45

Time setting 48Time Zone, for synchronizing with NTP

server 48Timeout setting for RADIUS 26

InfraStruXure PDU User’s Guide 65

Page 72: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

To Address, e-mail recipients 44Trap generation, for trap receivers 45Traps

trap receivers 44Troubleshooting

RADIUS only setting when RADIUS isunavailable 26

UUnit Preference 49Up Time

control console main screen 6in Web interface 50

Update Interval, Date & Time setting 48Update Using NTP Now, Date & Time

setting 48Upgrading firmware 58Upload event 56User configuration files

contents 54customizing 55exporting system time separately 55messages for undiscovered devices 56overriding device-specific values 54retrieving and exporting 54upload event and error messages 56using file transfer protocols to transfer 55using the file as a boot file with DHCP 32

User namesdefault for each account type 10defining for each account type. 25maximum number of characters for RADIUS 25

WWeb interface 10

configuring access 34logging on 10

XXMODEM to transfer firmware files 61

66 InfraStruXure PDU User’s Guide

Page 73: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings
Page 74: InfraStruXure PDU User’s Guide -  · PDF fileInfraStruXure PDU User’s Guide i ... How to Recover from a Lost Password ... Viewing and editing branch circuit breaker settings

8/2009990-0819A

APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following ways:

• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com (Corporate Headquarters)

Connect to localized APC Web sites for specific countries, each of which provides customer support information.

– www.apc.com/support/Global support searching APC Knowledge Base and using e-support.

• Contact the APC Customer Support Center by telephone or e-mail.– Local, country-specific centers: go to www.apc.com/support/contact for contact information.

For information on how to obtain local customer support, contact the APC representative or other distributors from whom you purchased your APC product.