inspection date: 11/16/2010 rc: 53 bin: 1022710 bridge …...rc: 53 bin: 1022710 bridge ratings...

41
Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671 RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 Inspection Agency: 10 - NYSDOT Type of Inspection: 1 - BIENNIAL GTMS: 302 -- Steel - Stringer/Multi-Beam or Girder POSTINGS: See Gen Rec Page 1 for Postings at time of inspection. Further Investigation Needed: No State Highway Number: 000000 Milepoint: 0 AADT/Yr: 1420 / 2000 Orientation: 1 - North Political Unit: 2007 - City of BUFFALO Year Built: 1968 Total Spans: 2 Ramp Bridge Attached To Span: NA BIN: NA General Recommendation: 5 Computed Condition Rating: 4.641 Abutment Ratings: Beg Abut End Abut Joint with Deck 4 8 Bearings, Bolts, Pads 5 5 Seats and Pedestals 6 6 Backwall 5 5 Stem (Breastwall) 8 8 Erosion or Scour 6 6 Footings 6 5 Piles 8 8 Recommendation 6 6 Wingwall Ratings: Beg Abut End Abut Walls 6 6 Footings 9 9 Erosion or Scour 6 6 Piles 8 8 Channel Ratings: Channel Stream Alignment 8 Erosion and Scour 8 Waterway Opening 8 Bank Protection 8 Approach Ratings: Approaches Drainage 6 Embankment 6 Settlement 4 Erosion 6 Pavement 6 Guide Railing 5 Number of Flags Issued: RED: 0 Yellow: 0 Safety: 0 Vulnerability Reviews Recommended: 1=Yes, 2=No, 3=NA, X=NotActive Hydraulic: 3 Overload: X Steel: 2 Collision: 2 Concrete: X Seismic: X Inspector's Signature: CheckValue: 1,745,863,671 Date: 11/16/2010 Naeem A. Abbasi,PE () (Inspector ID:5000003) Signed copy of this inspection report is available in the appropriate NYSDOT Regional Office Reviewed By: Date: 1/19/2011 Richard J. Kotecki,PE () (QC ID:5000015) Signed copy of this inspection report is available in the appropriate NYSDOT Regional Office

Upload: others

Post on 23-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Bridge Ratings

Inspection Date: 11/16/2010

Inspection Agency: 10 - NYSDOT Type of Inspection: 1 - BIENNIALGTMS: 302 -- Steel - Stringer/Multi-Beam or GirderPOSTINGS: See Gen Rec Page 1 for Postings at time of inspection.Further Investigation Needed: NoState Highway Number: 000000 Milepoint: 0 AADT/Yr: 1420 / 2000Orientation: 1 - North Political Unit: 2007 - City of BUFFALO Year Built: 1968Total Spans: 2 Ramp Bridge Attached To Span: NA BIN: NAGeneral Recommendation: 5 Computed Condition Rating: 4.641

Abutment Ratings: Beg Abut End Abut Joint with Deck 4 8 Bearings, Bolts, Pads 5 5 Seats and Pedestals 6 6 Backwall 5 5 Stem (Breastwall) 8 8 Erosion or Scour 6 6 Footings 6 5 Piles 8 8 Recommendation 6 6

Wingwall Ratings: Beg Abut End Abut Walls 6 6 Footings 9 9 Erosion or Scour 6 6 Piles 8 8

Channel Ratings: Channel Stream Alignment 8 Erosion and Scour 8 Waterway Opening 8 Bank Protection 8

Approach Ratings: Approaches Drainage 6 Embankment 6 Settlement 4 Erosion 6 Pavement 6 Guide Railing 5

Number of Flags Issued: RED: 0 Yellow: 0 Safety: 0

Vulnerability Reviews Recommended: 1=Yes, 2=No, 3=NA, X=NotActive Hydraulic: 3 Overload: X Steel: 2 Collision: 2 Concrete: X Seismic: X

Inspector's Signature: CheckValue: 1,745,863,671 Date: 11/16/2010

Naeem A. Abbasi,PE () (Inspector ID:5000003)

Signed copy of this inspection report is available

in the appropriate NYSDOT Regional Office

Reviewed By: Date: 1/19/2011

Richard J. Kotecki,PE () (QC ID:5000015)

Signed copy of this inspection report is available

in the appropriate NYSDOT Regional Office

Page 2: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

RC: 53 BIN: 1022710 Span Ratings

Inspection Date: 11/16/2010

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

Deck Element Ratings: 001 002 Wearing Surface 6 6 Curbs 5 6 Sidewalks, Fascias 5 5 Railings, Parapets 6 6 Scuppers 8 8 Gratings 8 8 Median 8 8 Mono Deck Surface 8 8

Superstructure Ratings: 001 002 Structural Deck 4 4 Primary Members 5 5 Secondary Members 5 5 Paint 7 7 Joints 4 8 Recommendation 5 5

Pier Ratings: 001 002 Bearings, Bolts, Pads 4 8 Pedestals 4 8 Top of Cap or Beam 6 8 Stem Solid Pier 8 8 Cap Beam 5 8 Pier Columns 4 8 Footings 9 8 Erosion or Scour 7 8 Piles 8 8 Recommendation 5 8

Utility Ratings: 001 002 Lighting 8 8 Sign Structure 6 6 Utilities and Support 4 4

Field Notes:Field Date Arrival Departure Temp (C) Temp (F) Weather Conditions 10/16/2010 10:00:00 AM 11:30:00 PM 49 Clear10/17/2010 9:30:00 AM 11:30:00 AM 45 Clear11/16/2010 8:00:00 AM 11:30:00 AM 37 Cloudy

Page 3: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

RC: 53 BIN: 1022710 Inspection Notes

Inspection Date: 11/16/2010

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

Note ID: 5C1010227100000 Beg Abut -- Abutment: Joint with Deck -- Rated 4, Was 4 Referenced Photos: "15" Above deck, the joint seal is covered with dirt and debris. Below deck, there is evidence of active joint leakage within all 4 bays. Condition rating of 4 is retained.

Note ID: 5C1010227100001 Approaches: Settlement -- Rated 4, Was 4 Referenced Photos: "13", "16" The sidewalks at all 4 corners of the bridge show settlement across the transition between the bridge and the approach. The end left sidewalk settlement is is measured to vary between 1-1/4 and 1-1/2". The begin right sidewalk settlement is measured to vary between 1/2 and 1". The begin left sidewalk settlement is measured to vary between 0 and 1-1/2". The end right sidewalk settlement is measured to vary between 0 and 3/4". At end left 2 feet of sidewalk slab is missing. This is filled by asphalt and is about 1/2" lower. Condition rating of 4 is retained.

Note ID: 5C1010227100002 Approaches: Pavement -- Rated 6, Was 6 Referenced Photos: "14", "18", "19" End approach has full length transverse crack which has been sealed however the seal is poping out at few spots. Begin approach is in good condition except few cracks were noted along the joint header. These cracks are sealed. Condition rating is downgraded to 5.

Note ID: 5C1010227100003 Span 001 -- Superstructure: Structural Deck -- Rated 4, Was 4 Referenced Photos: "11" Note: Previous description is retained with slight modification because no significant change in deck condition was noted. In the left fascia bay in both spans, the S.I.P. forms are heavily corroded over large areas. The corroded forms extend for the full width of the bay and reach up to 5 feet long. Additionally, the forms are heavily corroded for 1.5 ft wide strip along the left side of girder G-2. The largest areas of formwork corrosion are located at L/5, L/2 and near the end of Span 1 as well as at L/2 and 2L/3 in Span 2. These areas show large sections of the formwork that is rusted through where the underside of the deck is exposed. The exposed concrete is either honeycombed or spalled. The worst areas of spalling were noted near the end of Span 1. The spalling reaches 1" deep and exposes the "chairs" for the reinforcement. There is no exposed main reinforcement. The forms are corroded for the length of both spans along the left side of girder G-2. There are stalactites hanging from the formwork adjacent to the top flange of the girder. The right fascia bay shows similar corrosion along the right side of girder G-4. There are areas where the formwork is corroded thru. The formwork in Bay 4 is in slightly better condition than the formwork in Bay 1. The formwork within the 2 interior bays show significantly less corrosion. There are only narrow strips along the girders. Overall, the corrosion to the formwork appears to affect approximately 25% of the total exposed surface of the bridge. The corroded thru areas appear to affect less

Page 4: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

RC: 53 BIN: 1022710 Inspection Notes

Inspection Date: 11/16/2010

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

Note ID: 5C1010227100003 - continued than 5% of the entire deck surface.

Note ID: 5C1010227100006 Span 001 -- Superstructure: Primary Members -- Rated 5, Was 5 Referenced Photos: "12" The end diaphragms support the structural deck and are considered primary members. The end diaphragm in Bay 4 at the end of Span 1 shows heavy corrosion with heavy delaminations, section loss and 4 rust perforations. The rust perforations are near the lower right corner and are scattered along a length of 1'-6". The largest hole reaches 2" in diameter. The bottom flanges have been thinned by corrosion. The bottom flange shows section loss that is estimated to range between 40 and 45%. Other primary members in span 1 are in good condition. Internal redundancy is provided in the design. Rating is based on composite behavior of primary members

Note ID: 5C1010227100008 Span 001 -- Superstructure: Joints -- Rated 4, Was 4 Referenced Photos: "5", "9", "17" Below deck, active leakage was noted throughout. The concrete headers in Bays 1 and 4 show spalled concrete that reaches 5" deep. Above deck, the joint components appear to be in good condition. The joint seal is covered with roadway dirt and debris. The exposed portions appear to be in good condition.

Note ID: 5C1010227100009 Span 001 -- Pier: Bearings, Bolts, Pads -- Rated 4, Was 4 Referenced Photos: "8" Note: Bearings condition at pier 1 remains almost unchanged. Previous note is retained with slight modification. The Span 2 expansion bearings show packrust between the sole plate and the load plate that appears to somewhat restricting girder end rotation. The worst conditions were noted on the fascia bearings. The packrust between the masonry plate and the bronze sliding surface has caused the sheet to slightly bulge upward approximately 3/16 inches. There is also pack rust forming between the load plates and the side keeper plates. The right keeper plate on the G-1 bearing and the left keeper plate on the G-5 bearing are nearly corroded away. The interior Span 2 bearings are in better condition and would rate "5". The Span 1 fixed bearings show some packrust between the rocker and the masonry plate. There is very little other corrosion to the anchor bolts or either plate and would rate "5".

Note ID: 5C101022710000A Span 001 -- Pier: Pedestals -- Rated 4, Was 4 Referenced Photos: "3", "7" Right fascia pedestal is severely spalled and reinfircement bar is exposed. It sounds very hollow on outside faces. Left fascia pedestial is moderately spalled and bars are exposed. Rest of the pedestials are in good shape and would rate 5.

Page 5: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

RC: 53 BIN: 1022710 Inspection Notes

Inspection Date: 11/16/2010

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

Note ID: 5C101022710000B Span 001 -- Pier: Pier Columns -- Rated 4, Was 4 Referenced Photos: "6" Pier Column 3 shows a small 12" diameter concrete spall at the top of the end face that reaches 1-1/2" deep. There is a 2.5 foot wide by 3 foot high area of cracked and hollow sounding concrete adjacent to the spall. Pier Column 2 shows a 8 SF area of cracked and hollow concrete. Pier Column 1 is in good condition.

Note ID: 5C101022710000C Span 001 -- Utilities: Utilities and Support -- Rated 4, Was 4 Referenced Photos: "10" The 12" diameter watermain in Bay 4 shows that the insulation has been removed from its entire length in both spans. There were no leaks noted. The waterline appears to be in satisfactory condition.

Note ID: 5C1010227100004 Span 002 -- Superstructure: Structural Deck -- Rated 4, Was 4 Referenced Photos: "2" Note: Previous description is retained with slight modification because no significant change in deck condition was noted. In the left fascia bay in both spans, the S.I.P. forms are heavily corroded over large areas. The corroded forms extend for the full width of the bay and reach up to between 4 and 5 feet long. Additionally, the forms are heavily corroded for a 1 to 1.5 wide strip along the left side of girder G- 2. The largest areas of formwork corrosion are located at L/5, L/2 and near the end of Span 1 as well as at L/2 and 2L/3 in Span 2. These areas show large sections of the formwork that is rusted through where the underside of the deck is exposed. The exposed concrete is either honeycombed or spalled. The worst areas of spalling were noted near the end of Span 1. The spalling reaches 1" deep and exposes the "chairs" for the reinforcement. There is no exposed main reinforcement. The forms are corroded for the length of both spans along the left side of girder G-2. There are stalactites hanging from the formwork adjacent to the top flange of the girder. The right fascia bay shows similar corrosion along the right side of girder G-4. There are areas where the formwork is corroded thru. The formwork in Bay 4 is in slightly better condition than the formwork in Bay 1. The formwork within the 2 interior bays show significantly less corrosion. There are only narrow strips along the girders. Overall, the corrosion to the formwork appears to affect approximately 25% of the total exposed surface of the bridge. The corroded thru areas appear to affect less than 5% of the entire deck surface.

Note ID: 5C1010227100007 Span 002 -- Superstructure: Primary Members -- Rated 5, Was 5 Referenced Photos: "4" The end diaphragms support the structural deck and are considered primary members. The end diaphragm at the begin of Span 2 in Bay 4 also shows heavy corrosion with heavy delaminations, section loss and numerous rust perforations. The rust perforations are near the lower center and are scattered along a length of 2'. The largest hole reaches 1' wide and 1-1/2" high. The bottom flanges have been thinned by corrosion. Other primary

Page 6: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

RC: 53 BIN: 1022710 Inspection Notes

Inspection Date: 11/16/2010

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

Note ID: 5C1010227100007 - continued members in span 1 are in good condition. Internal redundancy is provided in the design. Rating is based on composite behavior of primary members

Note ID: 5C101022710000D Span 002 -- Utilities: Utilities and Support -- Rated 4, Was 4 Referenced Photos: "1", "10", "13" As the utilities conditions are unchanged bsince 2008, previous description is retained. The 12" diameter watermain in Bay 4 shows that the insulation has been removed from its entire length in both spans. There were no leaks noted. The waterline appears to be in satisfactory condition. The utility pipe adjacent to the waterline is separated at 2/3L of the span. Additionally, the light standard at the end left shows a small 1/2" diameter rust perforation. The section loss appears to be less than 15% overall. �

Page 7: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Bay 4, span 2 - separated utility pipe

Photo Number: 1 Photo Filename: 10_ 001.jpg

Bay 1, span 2 - all bays similar - underside of the structural deck rusted

Photo Number: 2 Photo Filename: 10_ 002.jpg

Page 8: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Pier, right fascia pedestal spalled

Photo Number: 3 Photo Filename: 10_ 003.jpg

End diaphragm in bay 4 at begin of span 2 over Pier - rust holes at bottom of web

Photo Number: 4 Photo Filename: 10_ 004.jpg

Page 9: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Joint over Pier in Bay 4 - rust and leakage

Photo Number: 5 Photo Filename: 10_ 005.jpg

End face of pier column C3 - cracks and spall along column

Photo Number: 6 Photo Filename: 10_ 006.jpg

Page 10: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Pedestal below the left fascia girder - spall at top of pedestal to rebar

Photo Number: 7 Photo Filename: 10_ 007.jpg

Bearing below girder G1 at the begin of span 2 - pack rust between sole plate and load plate

Photo Number: 8 Photo Filename: 10_ 008.jpg

Page 11: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Joint over Pier in bay 1 - active leakage

Photo Number: 9 Photo Filename: 10_ 009.jpg

Bay 4, span 1, utilities - Span 2 similar

Photo Number: 10 Photo Filename: 10_ 010.jpg

Page 12: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Bay 1, span 1, underside of structural deck - deck SIP crodded typical in fascia bays and other locations.

Photo Number: 11 Photo Filename: 10_ 011.jpg

End diaphragm in bay 4 at the end of span 1 over Pier - rust holes at bottom of web

Photo Number: 12 Photo Filename: 10_ 012.jpg

Page 13: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

End left sidewalk missing (2'1"x4'2" section) and utility pole

Photo Number: 13 Photo Filename: 10_ 013.jpg

End approach pavement

Photo Number: 14 Photo Filename: 10_ 014.jpg

Page 14: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Begin joint

Photo Number: 15 Photo Filename: 10_ 015.jpg

Begin left sidewalk settlement (1.5")

Photo Number: 16 Photo Filename: 10_ 016.jpg

Page 15: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Pier joint at the top

Photo Number: 17 Photo Filename: 10_ 017.jpg

Begin approach

Photo Number: 18 Photo Filename: 10_ 018.jpg

Page 16: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Photos in Photo Number Order

Inspection Date: 11/16/2010

Begin approach

Photo Number: 19 Photo Filename: 10_ 019.jpg

Page 17: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100001 Sketch Filename: BinMap.10.wpd General Sketch for Bridge Referenced Photos: Map to Bridge

Page 18: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100002 Sketch Filename: SpecialEmphasis.10.wpd General Sketch for Bridge Referenced Photos: Special Emphasis

Page 19: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100003 Sketch Filename: VerticalClearance.10.wpd General Sketch for Bridge Referenced Photos: Vertical Clearance

Page 20: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100004 Sketch Filename: 1022710VIRTIS.10.wpd General Sketch for Bridge Referenced Photos: Load Rating

Page 21: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100005 Sketch Filename: MPT_Form.10.wpd General Sketch for Bridge Referenced Photos: MPT form

Page 22: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100005 Sketch Filename: MPT_Form.10.wpd General Sketch for Bridge Referenced Photos: MPT form

Page 23: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100006 Sketch Filename: Photolog.10.wpd General Sketch for Bridge Referenced Photos: Photo log form

Page 24: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100006 Sketch Filename: Photolog.10.wpd General Sketch for Bridge Referenced Photos: Photo log form

Page 25: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Sketches in Sketch SysID Order

Inspection Date: 11/16/2010

Sketch ID: 5C1010227100008 Sketch Filename: Deck Det in Span 1-2.10.wpd Span 001 -- Superstructure: Structural Deck -- Rated 4, Was 4 Span 002 -- Superstructure: Structural Deck -- Rated 4, Was 4 Referenced Photos: "11", "2" Deck Deterioration in Span 1 and 2.10.wpd

Page 26: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

RC: 53 BIN: 1022710 Gen. Rec., Postings, Federal Ratings, etc.

Inspection Date: 11/16/2010

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

Overall Condition: GENERAL RECOMMENDATION: 5 Computed Condition Rating: 4.641

Problems Requiring Action: NO Further Investigation Needed NO Flags Issued

POSTINGS: Inspector Confirmed existing Posting data as correct. Posted Vertical Clearance ON the bridge is: No Posting Posted Vertical Clearance UNDER the bridge is: No Posting No Load Restriction is posted on this bridge

Overloads Observed: NO Overload Vehicles were observed on this bridge

FEDERAL RATINGS: NBI Deck Condition: 5 NBI Superstruct Condition: 7 NBI Substruct Condition: 7 NBI Channel Condition: N NBI Culvert Condition: N

Diving Inspection Needs: Diving Inspection Required? No Date of Last Diving Inspection: No Date

Inventory Problems: Inventory Problems Exist? No

Miscellaneous: Time Required to Inspect Bridge: 9 Hours Lane Closure Needs: By Contract for 2.5 Hours No Railroad Flagging Required There is a Pedestrian Fence 6.00 Feet High No Snow Fence The BIN Plate is in DAMAGED condition

Page 27: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

RC: 53 BIN: 1022710 Gen. Rec., Postings, Federal Ratings, etc.

Inspection Date: 11/16/2010

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

Special Emphasis Inspection Required: Non-Redundant/Fracture Critical Members - No Pin and Hangers - No Fatigue-Prone Welds - Yes Non-Categorized Fatigue-Prone Details - No Other (Specified in Text) - No

Special Emphasis Details: The connection welds at the ends of the partial length cover plates on the bottom flanges of all 5 girders in both Span 1 and Span

General Notes To the Next Inspector: The BIN Plates are attached to the begin pedestals below G-3 and G-5. Maintenance & Protection of Traffic was combined among the 9 overhead bridges between the NY198 split and the NYS Thruway (I-90), requiring a single, continuous Lane closure for the inspection of the WB Abutments/Piers, EB Abutments/Piers and the Center Median Piers for all 9 bridges on 3 separate dates. For the EB & WB Right lane closures, it is strongly recommended to rent 2 variable message boards to warn Route 33 traffic of stopped/merging traffic. Sign may read - "CAUTION MERGING TRAFFIC AHEAD" or "MERGING TRAFFIC AHEAD - SLOW DOWN".

Improvements Observed: No improvements noted.

Page 28: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Review Progress and Personnel Present at Inspection

Inspection Date: 11/16/2010

Inspection Submission Status: Submitted to QC Engineer on: 1/19/2011 QC Submission Number: C5502702 QC Review Completed: 1/19/2011 QC Engineer: Richard J. Kotecki Submitted to Liaison Engineer on: 1/19/2011 Liaison Submission Number: 55043 Liaison Review Completed: 2/2/2011 Liaison Engineer: Mike S. Crislip Submitted for BIIS Processing on: 2/2/2011 BIIS Submission Number: .kp1 Current Status: Keypunched, Sent to BIIS Check Value: 1,745,863,671

Personnel Present During Inspection: Naeem A. Abbasi - Team Leader Mohammad j. Soltanieh - Assistant Team Leader Michael - MPT Nimish Shah - Help inspect bridge

Page 29: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Inspection Access Requirements

Inspection Date: 11/16/2010

Equipment Required for Inspection No Access Requirement Changes Noted During This Inspection. This Listing is from the Inventory Database. ACCESS CATEGORIES FOR ENTIRE BRIDGE Required: Walking, Extension Ladder, Small Lift, Shadow Vehicle ACCESS CATEGORIES FOR SPAN 1 Required: Walking, Extension Ladder, Small Lift, Shadow Vehicle ACCESS CATEGORIES FOR SPAN 2 Required: Walking, Extension Ladder, Small Lift, Shadow Vehicle

Page 30: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047 CheckValue: 1,745,863,671

RC: 53 BIN: 1022710 Culvert Measurements

Inspection Date: 11/16/2010

Culvert Measurements NO CULVERT DATA FOR BIN 1022710

Page 31: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

1022710_LOCATION_MAP.JPG

Page 32: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

1022710_QUAD_MAP.JPG

Page 33: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

AbutWingwall.02.jpg

Page 34: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

ApproachBegin.02.jpg

Page 35: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

ApproachEnd.02.jpg

Page 36: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

CrossedSpan1Left.02.jpg

Page 37: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

CrossedSpan2Right.02.jpg

Page 38: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

ElevationLeft.02.jpg

Page 39: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

ElevationRight.02.jpg

Page 40: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

FramingSpan2.02.jpg

Page 41: Inspection Date: 11/16/2010 RC: 53 BIN: 1022710 Bridge …...RC: 53 BIN: 1022710 Bridge Ratings Inspection Date: 11/16/2010 ... of formwork corrosion are located at L/5, L/2 and near

Carried: HOSPITAL DRIVE Crossed: 33 33 53011047

RC: 53 BIN: 1022710 Standard Photos

Pier1.02.jpg