28 DOORS AND HARDWARE £ JUNE 2007 FOR MANY MONTHS YOU HAVE READ AND HEARD INFORMATION regarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007 edition will have on new and existing buildings and facilities. Most notably, its requirements for the annual inspection of all types of fire-rated door assemblies will have a direct impact on the architectural openings industry. As is oſten the case, rumors and myths abound as to when these inspections will go into effect, how these inspections will take place, who is responsible for performing the inspections, and if these inspections are necessary. It is also rumored that these inspections are virtually unenforceable due to the wide range of products these openings are comprised of. Some may interpret the new inspection requirements to mean that these inspectors can coerce building owners into compliance by threatening to “shut down” their building until corrections are made. Others worry that unscrupulous individuals will force owners to unnecessarily replace doors and hardware in order to increase their own profits. Still others are concerned about the potential liability the inspectors will bear for performing these safety inspections. Previous editions of NFPA 80 contained requirements for the ongoing maintenance and care of fire-rated door assemblies, but the language used was ambiguously phrased, which made it virtually unenforceable. More importantly, the majority of property owners and management companies were not aware of these responsibilities or how to go about making the necessary repairs to fire-rated door assemblies. Chapter 5, titled Care and Maintenance, of the 2007 edition of NFPA 80 contains specific requirements for the ongoing maintenance and repair of fire-rated door assemblies. Section 5.2, titled Inspections, outlines the inspection process, its documentation, and the repairing of fire-rated door assemblies. by Keith E. Pardoe, DAHC/CDC, CDT Inspection of FIRE-RATED Door Assemblies This article will attempt to explain the new inspection requirements and allay these concerns.

Upload: others

Post on 24-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

28 DOORSANDHARDWARE £ June 2007

For many months you have read and heard inFormation regarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007 edition will have on new and existing buildings and facilities. Most notably, its requirements for the annual inspection of all types of fire-rated door assemblies will have a direct impact on the architectural openings industry. As is often the case, rumors and myths abound as to when these inspections will go into effect, how these inspections will take place, who is responsible for performing the inspections, and if these inspections are necessary. It is also rumored that these inspections are virtually unenforceable due to the wide range of products these openings are comprised of. Some may interpret the new inspection requirements to mean that these inspectors can coerce building owners into compliance by threatening to “shut down” their building until corrections are made. Others worry that unscrupulous individuals will force owners to unnecessarily replace doors and hardware in order to increase their own profits. Still others are concerned about the potential liability the inspectors will bear for performing these safety inspections.

Previous editions of NFPA 80 contained requirements for the ongoing maintenance and care of fire-rated door assemblies, but the language used was ambiguously phrased, which made it virtually unenforceable. More importantly, the majority of property owners and management companies were not aware of these responsibilities or how to go about making the necessary repairs to fire-rated door assemblies. Chapter 5, titled Care and Maintenance, of the 2007 edition of NFPA 80 contains specific requirements for the ongoing maintenance and repair of fire-rated door assemblies. Section 5.2, titled Inspections, outlines the inspection process, its documentation, and the repairing of fire-rated door assemblies.

by Keith E. Pardoe, DAHC/CDC, CDT

Inspection of FIrE-rATED Door Assemblies

this article will attempt to explain the new inspection requirements and allay these concerns.

Page 2: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

June 2007 £DOORSANDHARDWARE 29

NFPA 80, Standard for Fire Doors and Other Opening Protectives—2007 edition, requires documented inspections of fire-rated door assemblies on an annual basis. NFPA 80 requires these inspections to be performed by persons who are knowledgeable of the types of door assemblies being inspected. Swinging doors with builders hardware are the most common type of fire door assembly, and are among the most complex due to the myriad of materials and products that are used to create them. These assemblies often provide accessibility, security and life-safety functions in addition to their fire-safety protection, also increasing their complexity. Inspectors must thoroughly understand the dynamics of these assemblies in order to correctly evaluate them in the field.

Understanding the role and responsibilities of the inspectors is equally as important as understanding what is being inspected. Interacting with the building owner and the Authority Having Jurisdiction (AHJ) is paramount to ensuring the respective parties clearly understand the inspection documentation and follow through with necessary corrections in order to improve safety in their buildings and facilities.

This class will teach you how to perform and record these inspections as well as provide tips for interacting with the owners and AHJs. In addition, upon passing this class, you will be invited to enroll in Intertek’s Certified Inspectors of Swinging Doors with Builders Hardware to NFPA 80 program.

Note: In preparation for the Intertek Certified Fire Door Inspector program, ALL students are required to bring photo identification (e.g., valid driver’s license) and be prepared to have their photograph taken for their inspector credentials. Notification of successfully passing the FDAIC will be sent to each student and Intertek within 30 days of completion of the class.

Learning Outcome Statements:Upon successful completion of this class, students will:

n Understand inspection requirements of the 2007 edition of NFPA 80

n Understand the inspector’s role and responsibilities

n Be able to conduct safety inspections of swinging fire door assemblies with builders hardware

n Be able to create inspection records and summary inspection reports

n Be eligible to enroll in the Intertek/Warnock Hersey Certified Fire Door Inspection program

Student Materials:Each student will receive an Inspection Guidelines Kit that includes:

n NFPA 80, Standard for Fire Doors and Other Opening Protective—2007 edition

n 2007 Guidelines for Inspections of Fire-Rated Door Assemblies (published by the Foundation for the Advancement of Life Safety and Security)

n Sample Inspection forms

n Sample Contract templates for inspection and service agreements

n Application for Errors and Omissions insurance for inspectors

Prerequisites:Individuals certified as Architectural Hardware Consultants (AHCs), Certified Door Consultants (CDCs), Electrified Hardware Consultants (EHCs) and/or Architectural Openings Consultants (AOCs) are eligible to enroll in the FDAIC. All other individuals must have successfully completed each of the following DHI classes prior to enrolling in the FDAIC:

n Self-Study Course: Fundamentals of Architectural Doors and Hardware

n COR110 Basic Hardware

n COR115 Hardware Applications

n COR140 Using Codes and StandardsNFPA 80

Fire Doors Assembly Inspection Class (FDAIC)(24 hours, 72 CEP Points)

It is important to remember that NFPA 80 is a product standard, it is not a code per se. As such, NFPA 80 establishes the minimal level of qual-ity for the products used to create

fire-rated door assemblies and their installation. Consequently, NFPA 80 requires individuals performing the inspections of fire-rated door assem-blies to be knowledgeable of the

types of assemblies being inspected. However, it does not attempt to define what constitutes an accept-able level of knowledge (e.g., experi-ence, training, certification, etc.) for

Page 3: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

30 DOORSANDHARDWARE £ June 2007

these individuals. Instead, NFPA 80 relies on the Authority Having Jurisdiction (AHJ) to determine if the individuals performing inspections in their region have the requisite level of knowledge to perform these safety inspections.

The AHJ community at large recognizes they, themselves, are not adequately trained to perform these inspections (with few excep-tions), nor do they have the time to dedicate to performing these inspec-tions given their responsibilities for the entire structure. As is the case with inspections for fire alarm and sprinkler systems, as well as eleva-tors and fire extinguishers, AHJs rely on the expertise of industry

personnel to perform and document the inspections. Building owners and facility management companies are required to retain written proof of the inspections, which will be presented to the AHJ for its approval at a later date. Inspections of fire-rated door assemblies will follow the same process and the AHJs will be looking toward personnel in our industry to lead the way.

A portion of the role our industry is playing in this process is the development of a new training program, which will be open to all interested parties. Large facilities and institutions (e.g., hospitals, universities, etc.) already have trained personnel who are respon-

sible for the care and maintenance of their buildings. In some cases, they have established door main-tenance programs and it would be a natural extension of their programs to train their personnel to perform these inspections.

Ultimately, the building owner is the party who is responsible for making sure the inspections take place and that the fire-rated door assemblies within the structure are properly maintained. AHJs will confirm the inspections have occurred by reviewing the documentation and verifying that necessary corrective actions were taken to repair assemblies that were found to have deficiencies.

FireDoorInspectionInitiativeOnNovember28,2006,JerryS.Heppes,Sr.

CAE,andJeffTurcotterepresentingIntertek,

signedanagreementtocreatetrainingand

certificationtosupporttheinspectionsrequired

byNFPA80.Intertekisagloballeaderintesting,

inspectionandcertificationofdoorandhardware

products,undertheWarnockHerseymark.

Page 4: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

PLEASE SIGN HERE Artist Copy EditorAccount

ExecProject Mgr Art Director

Creative

Director

Print

ProducerArt Producer QC

Approved As Is

Approved With Change

Change and Resubmit

von069891_mch_mag_ladrs.inddJob Type: Standard Studio Child Number 073042

Job Name: Von Duprin Resize/Pub Materials R2 Number -

Element: Magazine Ad - Doors & Hardware Current Proof Date & Version: 02.27.07 (load)

Built Scale: 100% Approval Due: 02.23.07

Print Scale: 100% Mechanical Released: -

Live: 8.0416” x 10.5416” Material Ship Date: -

Trim: 8.375” x 10.875” Material Arrive Date: -

Bleed: 8.625” x 11.125” Ad Closing Date: -

Colors: 4C Contact Name - Phone: Nigel Lowrie - 214.259.4330

Operator: ASIERRA QTY: 1

Program/Version: InDesign CS2 Special or Kitting Instructions -

LOS ANGELES

UNIFIED SCHOOL DISTRICT

L O S A N G E L E S

Few things can hold up under the pressure of several hundred kids headed for freedom. Which is why the

L.A. Unifi ed School District uses Von Duprin® exit devices. Because they’re built to endure the highest levels of

abuse, installing Von Duprin now means you won’t have to worry about unnecessary repairs and maintenance

later. If Von Duprin can survive some of the most rough-and-tumble kids

in the country, then you can be sure it will take whatever you throw at it.

© 2007 Ingersoll-Rand Company Limited vonduprin.ingersollrand.com

58882r1cs_DDB_VONladrs.indd 1 3/2/07 7:10:08 PM

58882r1cs_DDB_VONladrs_1-1.pgs 03.02.2007 18:45BLACK YELLOW MAGENTA CYAN

FREEADVERTISERINFORMATIONAT:www.thru.to/dhi

Page 5: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

BREAKING NEWS!!!

Join DHI for the release of the FIRE DOOR ASSEMBLY INSPECTION CLASS (FDAIC) at this year’s 32nd Annual Conference and Exposition in Nashville, TN, October 13th - 20th, 2007.

� e inaugural presentation of this program will include education sessions on the new inspection process guidelines as well as the certifi cation process for companies and individuals. � e Forum for the Future will address busi-ness issues that will speak to the insurance, staffi ng, marketing and fi nancial ramifi cations of this initiative.

Fire Door Assembly Inspection Program

Na� vi� eNa� vi� e

Watch www.dhi.org for further details!

NashvilleFDIP_Ad2.indd 1 4/23/07 4:57:23 PM

FREEADVERTISERINFORMATIONAT:www.thru.to/dhi

Page 6: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

June 2007 £DOORSANDHARDWARE 33

The role of the inspector is to simply record and report the condition of the door assemblies to the owner. The owner will have to decide if, when, and what corrective actions will be taken; otherwise, they will run the risk of being cited for violations by the AHJ. Understand, inspectors are not passing or failing door assemblies, nor are they approving them. Only the AHJ has the authority to approve, in this case, the door assemblies and building elements within their jurisdiction. Accordingly, inspectors will not be permitted to threaten to shut down a building as leverage to force compliance. Similarly, inspectors will not be authorized to issue citations or monetary fines when openings with deficiencies are discovered.

Liability for the maintenance and care of fire-rated door assemblies rests solidly on the shoulders of the building owners and/or their representatives. However, in today’s society no one is immune from being sued and an inspector is a possible candidate, especially if problems arise subsequent to an inspection. Proper documentation of the inspections will help to protect the inspectors should legal proceedings be initiated. Likewise, being able to document a certain level of train-ing specific to the types of fire-rated door assemblies will alleviate some of the potential liability. DHI is developing an errors and omissions insurance program specifi-cally designed to insulate the inspectors from financial loss resulting from performing these inspections.

The majority of fire-rated door assemblies are classified as swinging doors with builders hardware (see chapter 6 of NFPA 80), which can also be the most complex type of fire-rated door assemblies due to their locations within buildings and facilities. In addition to their fire-protection properties, these door assemblies often provide accessibility, life-safety and security functions, which can increase their complexity dramatically. Inspectors have to be extremely knowledgeable of a broad range of products that can, and cannot, be used on these types of openings; this depth of knowledge can only be gained through experience.

Another frequently raised issue regarding the inspection of swinging doors with builders hardware concerns the number of existing openings and the high number of possible product combinations used to create them. The sheer number of possibilities makes inspections both overwhelming and virtually unenforceable. It is certainly true that the number of

Our strength and achievements are grown from the inside out.

To learn more about Arc One and AOU, visit our website at www.arcdoors.com

What Color is

Your Door?

At Arc One, we view employee relationships as successful partnerships. The more knowledge our employees gain - the better we service our customers. Arc One University, our unique in-house training facility, is dedicated to employee development through year-round course offerings. Where are you headed in the door and hardware industry? Arc One is a great place to advance your door and hardware career to the next level What color is your door?

Arc One, an industry leader, wants you to be a leader too.

FREEADVERTISERINFORMATIONAT:www.thru.to/dhi

Page 7: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

34 DOORSANDHARDWARE £ June 2007

installed fire-rated swinging doors with builders hard-ware is extremely large and growing every year. Modern day assemblies have different capabilities and limitations than yesterday’s assem-blies. However, when you look

at the criteria for inspecting them (see section 5.2.4 of NFPA 80), you will see the base elements are the lowest common denominator that all of these assemblies must meet.

Fortunately, it will take some time for these inspections to be universally required across the country. As with

other significant changes (e.g., posi-tive pressure fire testing, accessibility requirements, etc.) that have affected our industry, inspections will begin slowly as AHJs and their respective jurisdictions adopt the 2007 edition of NFPA 80 and its inspection require-ments. Remember, NFPA 80 does not require the inspections to be performed by third-party inspectors, nor does it require professional certifi-cation for the inspectors; only that the inspectors are knowledgeable about the types of openings being inspected. While certification is not a require-ment of NFPA 80, the AHJ community looks to the industry experts, in our case DHI, for training and informa-tion to facilitate the inspections.

The important accomplishment of having NFPA 80 Standard for Fire

Doors and Other Opening Protectives language requiring the annual inspection of fire doors has been achieved and the development of the DHI training and certifica-tion program is well underway.

To thoroughly explain and support these multiple efforts in moving forward, at this year’s annual Conference & Exposition in Nashville, TN., in October, the Foundation is featuring an in-depth presentation at the Forum for the Future. This exclusive Industry event devoted to this initiative will highlight all of the business issues that speak to the insurance, staffing, marketing, and financial parameters of becoming engaged in this effort.

n mid-October, at DHI’s 32nd annual convention and tradeshow, DHI will be

launching the first training class for fire door inspectors. The Fire Door Assembly

Inspection Class (FDAIC)—see course description on page 29—is designed to train

inspectors in performing and documenting the inspections. Additionally, upon

passing this class, the students will be eligible to participate in Intertek’s Certified

Inspectors of Swinging Doors with Builders Hardware to NFPA 80 program.

Architectural Hardware Consultants (AHCs), Certified Door Consultants (CDCs),

Electrified Hardware Consultants (EHCs) and Architectural Openings Consultants

(AOCs) are immediately eligible to enroll in this class. Others, whether from our

industry or related industries (e.g., locksmiths, access control installers, AHJs, etc.),

need to learn basic product and technical information (see course prerequisites on

page 29) before being eligible to enroll in this class.

Note: Class size is limited and registrations will be entered in the order they are received.

Watch the DHI website and Doors & Hardware magazine for the enrollment application.

For more information on this new training program, contact the DHI Education and Technical Services department at 703-222-2010 or [email protected].

Icontinues on page 92

Page 8: Inspection of FIrE-rATEDregarding the affect the National Fire Protection Association’s (NFPA) publication number 80, Standard for Fire Doors and Other Opening Protectives, 2007

92 DOORSANDHARDWARE £ June 2007

Topics specifically addressed at this year’s Forum will cover:

n An overview of the inspection guidelines, checklists, reports, and model contractual agreements that will be used to support anyone performing these inspections.

n The Risk management and insurance aspects of this program.

n Long-term maintenance agreements.

n Classes and Certifications through DHI and Intertek.

n Important perspective from a retired state fire marshal.

“This inspection requirement means that functional testing must be performed by individuals with knowledge and understanding of the operating components of the fire rated openings,“ said Jerry Heppes, CAE, and Chief Executive Officer of DHI. “Currently, DHI members are the most qualified professionals to perform these inspections—and will be even more so once they are certified and understand the business aspects of what this initiative brings.”

Those attending this year’s Forum will gain a clear understanding of the leadership role this industry will play in carrying out these inspections and the business opportunities that will follow. Make sure that you and your company are in the know—Register to attend this year’s Conference and annual Forum for the Future online at www.dhi.org.

About the Author: Keith E. Pardoe, DAHC/ CDC, CDT is the Director of Education and Technical Services for DHI. He can be reached at [email protected].