installation design guide 09/2010 - schneider · pdf fileroombox' installation design...
TRANSCRIPT
Final low voltage control, Distribution & Protection
Roombox
Installation Design Guide09/2010
PB
1065
56-5
0
3
ContentsRoombox Installation Design Guide
Energy efficency regulation p. 6
Overview of the Roombox concept p. 7
Roombox functions p. 16
Roombox range p. 23
Roombox implementation and architecture p. 26
Roombox installation p. 28
Energy distribution to the Roombox p. 32
Communication port characteristics p. 37
Input and sensor characteristics p. 40
Feeder characteristics p. 44
Conformity with standards p. 46
Physical characteristics p. 47
Location p. 48
Appendices p. 50
Roombox' Installation Design Guide
4
The Roombox concept presented in this guide is a new-generation of electrical distribution installation promoting:
> Optimum energy efficiency for powered devices, by using them only as and when they are required;
> Flexible low-cost workspace;
> Comfort and productivity of the occupants through the use of "intelligent" control and monitoring methods.
Building projects that are better controlled over time and less expensive than conventional projects, offering an excellent level of comfort and improving the energy balance, are the ideal configuration building promoters, investors and specifiers are now seeking.
E00
3262
-90
P11
7489
-60
5
Throughout the logical approach to the electrical installation design phases, you can discover the principle of the concept and its many advantages:
In addition, Schneider Electric's Roombox concept uses innovative technology to protect goods and people against electrical faults: overloads, short circuits and earth leakage monitoring.
> Manageable packages electrical distribution by electrical contract on providing best value.
> Energy provided via a "power bus", reducing cable lengths and installation time
> More flexibility protection, distribution, monitoring, and control, as close as possible to the loads, and users.
> Space saving, by reducing the panel boards, and cable tray sizes.
Roombox' Installation Design Guide
6
Energy efficiency regulations
This standard specifies a method of calculating building energy performance. It assigns performance indicators to the automated functions, which include heating, cooling, ventilation, lighting, venetian and roller blinds.
Heating, cooling and ventilation control: although the Roombox does not deal directly with these functions, it nevertheless makes it possible to access high indicators by using the appropriate controllers.
The Roombox functions that come within the scope of EN 15232 - performance indicator A (the highest) Lighting Natural light control Blind control
Automatic start up and adjustment by dimmable output on presence detection and light level sensing;
Automatic start up and automatic switch off by dimmable or switching output on presence and absence detection;
Manual start up and adjustment by dimmable output on presence detection and light level sensing;
Manual starts up and automatic switch off by dimmable or switching output on absence detection.
Automatic. Combined lighting, blind and HVAC system control.
The European EN 15232 standard
Thermal regulations RT 2010 – for application in 2012
Each new thermal regulation reinforces the need for more accurate monitoring, from general metering to metering by function and by lot (storey, occupant, etc.) for buildings > 400 m².
They involve the heating, cooling, ventilation, and lighting functions.
BREEAM (BRE Environmental & Sustainability Standard) Certification
This originally British certification is the oldest and most commonly used throughout the world. It was established by the BRE - the Research, Testing, Consultancy and Training organisation - for use in the building sector.
After an assessment has been completed, it assigns a grade based on the quality of the design and a building's ability to be used in accordance with the environmental criteria affecting the health and comfort of its users.
LEED Certification (Leadership in Energy and Environmental Design)
LEED certification is the BREEAM's rival. It is a North-American standardisation system for high environmental quality buildings, which was developed by the US Green Building Council in 1998.
The assessment criteria include: energy efficiency, water consumption efficiency, heating system efficiency, the use of locally sourced materials and the reuse of any surplus materials.
According to its performance point evaluation, a building can qualify for one of four levels of certification: "certified-silver", "gold" or "platinum".
Schneider Electric Services and Solutions have a 50% direct impact on the LEED evaluation, which is sufficient to obtain Silver Certification.
7
Overview of the Roombox conceptContribution to conformance with energy regulations
Roombox and EN 15232European standard for the classification of automation solutions in terms of improving the Energy Efficiency of Buildings. This standard specifically recommends the use of the BMS and multi-application controls (scenarios).
These easy-to-configure controls are available in the Roombox.
Roombox and the European Energy Performance Building Directive (EPBD), the purpose of European Directive n° 2010/31/CE dated 19/05/2010.Is to promote the improvement of building energy performance in the European Community, by taking account of the outdoor climate conditions, particular local characteristics and the requirements in terms of the indoor climate and the cost/efficiency ratio. In particular, the directive requires the installation of a consumption measurement system.
The Roombox incorporates 3 energy meters measuring: the total electrical energy consumption of the Roombox and its loads; the total electrical energy consumption of the lighting loads.
Roombox and RT2010 (under development) It specifies a minimum performance level for building solutions and thermal systems. The trend is towards more accurate consumption monitoring, maximum permitted consumption, real-time analyses, etc.
The Roombox incorporates 3 energy meters measuring: the total electrical energy consumption of the Roombox and its loads; the total electrical energy consumption of the lighting loads.
Roombox and Building environmental and energy certification Apart from conforming to the current regulations, adopting a Roombox architecture makes it easier to obtain certification.
Protection and control are decentralised to reduce the use of copper (cables),
Automated control systems meet the energy management requirements,
The energy meters are integrated into each Roombox (several Roomboxes can represent a lot) making RT 2010 easier to apply and more economically advantageous.
The Roombox concept provides installation design solutions in conformance with present and fore secable future energy guidelines:
Roombox' Installation Design Guide
8
Zone D
The Roombox
FunctionsA Roombox is an all-in-one protection, metering and control device with a power supply input and 12 feeders for the equipment.
Front panel
The function of a feeder is determined at the factory and can be as follows:
Protected power supply, measurement of air-conditioning cassettes;
Protected power supply, motorised valve measurement and control;
Protected power supply, On/Off lighting measurement and control;
Protected power supply, lighting measurement and control, Dali ballast dimmer;
Protected power supply and Motorised venetian or roller blind control (230 V).
Each feeder has an input for a wired pushbutton or a wired window contact.
The Roombox has 4 inputs for the "Roombox" specific presence and light level sensors.
As an alternative to wired pushbuttons, the Roombox has a "remote-controlled radio receiver" function designed to receive orders from Zigbee wireless pushbuttons. Moreover, pressing the pushbutton generates the electricity necessary for transmission and no battery is required.
The Roombox provides its energy meter values: total energy consumed on its 16 A supply, total energy supplied to the lighting circuits, total energy supplied to the heating/air-conditioning circuits.
The Roombox can communicate with a Building Management System (BMS) via a LON or KNX network, depending on its version.
PB and LED: PB Zone combination
RJ12 connector for combined light/presence sensor
LON or KNX bus connector
RJ45 connector for link with local diagnostic PC
Supply 230 V
PB and LED in teach mode; and "presence on LON indication"
3 pushbutton connectors zone B
3 pushbutton connectors zone B
3 output connectors zone D
3 output connectors zone D
Switchboard isolation, resetting
Output status indicator lights: fault, voltage, presence.
Programming button / status change / ON / Reset / OFF
3 output connectors zone A
3 pushbutton connectors zone A
3 output connectors zone C
3 pushbutton connectors zone C
Zone A
Zone C
Zone B
Overview of the Roombox concept
LED Power Supply 230 V
LED Status DALI
LED Metering calibration
PB
1065
57-4
5
9
Roombox electrical distribution The 12 Roombox feeders are divided into 3 or 4 groups - or zones - each of which can control a complete or incomplete set of air-conditioning + lighting devices + motorised blinds.
The zone is usually assigned to a building module, i.e. the equivalent of an area of around 13 m².
The example below shows a space with four zones, A, B, C, D controlled by a Roombox:
zones B and D are assigned to separate offices;
zones A+C are combined functionally and assigned to a large collective office.
Operation in a separate zone:
One lighting circuit: controlled by one local pushbutton or presence + light detector or by one pushbutton + detector for switching off only. Two lighting circuits: controlled by one
pushbutton or by one pushbutton per circuit, or by one pushbutton + detector for switching off only.
Zone B
Zone D
Operation in zones combined by configuration:
Lighting: all circuits of the same type (general-purpose, corridor, window) operating as a single circuit, with their respective buttons then generating joint orders.
Roller blinds: all the pushbuttons generate joint orders. HVAC: the window contacts and movement
detectors generate joint orders.
Zone A
Zone C
Zone A and C combination
Caption: sensor actuator
Zones A and C Zone B Zone D
PB
1065
57-2
9
PB
1065
60
PB
1065
59-4
0
PB
1065
61P
B10
6561
Roombox' Installation Design Guide
10
Advantages of the Roombox solution throughout the project
Efficient designUltra selective output electrical protection due to static breaking technology
Terminal electronic breaking resulting from Schneider Electric's research complements upstream circuit breaker breaking capability.
Individual protection: each of the 12 Roombox feeders is protected by a static breaking unit.
Tripping: tripping can be caused by an overload, a short circuit or by detection of a leakage current of more than 10 mA.
Discrimination: there is total discrimination between all forms of individual protection and any upstream protection device ≥16 A , thus ensuring optimum continuity of service.
Short-circuit current breaking ("Ultra Limitation"): the response time before the actual breaking is one hundred times less than that of an electromechanical circuit breaker, i.e. 20 ms. Consequently, up to an Isc of 10 kA, the short-circuit current never reaches values higher than 140 A.
Remote reset: As opposed to electromechanical circuit breakers that require additional accessories for remote resetting, terminal electronic breaking offers various possibilities as standard, according to its parameter settings: room-mounting: resetting via the equipment control pushbutton, by the front panel "CLEAR" buttons, or via the building management system.
Resetting is only possible if the fault has disappeared.
Universality of protection and control through "zero current" electronic switching'
Switching the feeder ON at zero voltage and OFF at zero current allows any type of load, whether it be a resistive, inductive or capacitive impedance load, to be interrupted for protection and control.
This is specifically useful for lighting feeders, whatever the type of ballast.
This switching mode removes operating interference and extends the life of the equipment powered. Mechanical and electrical endurance are unlimited: no wear, etc.
Silent operation.
Economical designFewer power cables
A single "power bus" cable from a sub-distribution board supplies several Roomboxes, the number of which depends on the cross-section of the cable used.Example: 6 Roomboxes tapping off a 3P+N / 2.5 mm² cable.
Shorter control cables
The pushbutton cables converge on the Roombox with which they are associated, which is generally the nearest one. In addition, the inter-Roombox KNX or LON communication bus can be used to combine certain lighting sensors and pushbuttons.
Wireless and batteryless radio buttons ensure more flexible and faster installation.
Energy meters incorporated in the Roombox
More and more regulations require electrical load consumption to be monitored by type: lighting, ventilation. This differentiated metering is integrated into each Roombox.
The saving with respect to modular meters is obvious, as is the amount of space saved.
The meter values are regularly notified to the Building Management System via the communication bus.
They can therefore be monitored by groups of circuits with the same function, by geographical zone (storey, building, etc.).
Overview of the Roombox concept
11
Easier organisationMore logical, better defined electrical lot
As the lighting and roller blinds are controlled by the Roombox, their deployment is entirely the responsibility of the electrician.
During the learning phase, the Roombox recognises the pushbuttons and/or sensors and automatically assigns them to the lighting feeders and to the roller blinds.
Therefore, even before the building management system is implemented, the electrician can check each electrical control function in local mode and modify it if required.
The next phase, which consists of fine-tuning the BMS, will be more "fluid", since all circuits will have been checked.
Standard easy-to-procure connectors
The pushbuttons and loads are connected to the Roombox using standard polarised connectors (Wieland).
The use of preconnectorised cables shortens cabling times, prevents cabling errors and improves the safety of the power supply.
Easier installationSmaller switchboard footprint
The switchboards on each floor or in each zone only include protection for socket-outlet circuits and a limited number of 3P+N "buses" supplying "clusters" of Roomboxes.
The latter include the protection of terminal load cables (lighting, HVAC terminals, roller blind motors, depending on the version).
Frees up wall space
The Roomboxes should preferably be installed in a suspended ceiling.
PB
1065
56-6
0
Roombox' Installation Design Guide
12
Conventional electrical distribution architecture
Principle Main General Distribution Board
The MGDB receives the power supply for the building and controls the various sources.
It supplies the high-power equipment in the building, the feeders to the sub-distribution boards and some local loads and electrical network measurement and control devices.
Sub-distribution boards
The sub-distribution boards are installed throughout different buildings or different zones of a building and distribute energy to the safety, control and monitoring equipment and to each local load via dedicated feeders: lighting, connectors, HVAC terminals, etc.
Upgradeability
A large number of lines now converge at the sub-distribution boards. They generally follow the service ducts through the suspended ceilings and/or false floors of the buildings.
Changing the location of the loads with this conventional architecture which is appropriate for "fixed" buildings (hotels, educational establishments, hospitals, etc.) is very tricky: unsuitable cables have to be replaced, cables removed from controls, reassigned, etc.
The cost is generally high and the work takes a long time to complete. Solutions based on busbar trunking systems help to improve the flexibility of the working areas.
Overview of the Roombox concept
Power outlets
Main General Distribution Board
> Protection> Measurement
Sub-distribution board
> Protection> Measurement> Control
Sub-distribution board
> Protection> Measurement> Control
Sub-distribution board
> Protection> Measurement> Control
Luminaire
Roller blind
Fan coil module
Pushbutton
DB
1237
44
13
Roombox electrical distribution architecture
Principle Main General Distribution BoardThe upstream distribution remains standard, a MGDB supplies the sub-distribution boards.
Sub-distribution boards They supply: the circuits, the safety and control and monitoring equipment and the loads
situated in zones whose use is not likely to change: passage areas, service rooms, toilet facilities; the column circuits via the fast connectivity busbar, or trunkings making the
high and low current connectors available. This infrastructure is generally only finalised when the occupier's installation requirements are known, i.e. when the building is almost completed. The luminaires, air-conditioning cassettes and any motorised blinds will already be in place; the "busbar" feeders of the Roombox serving the zones where flexibility is
required: in general, open space (open plan) areas, office zones.
Roombox Preferably located in the suspended ceilings of corridors or open spaces, the Roomboxes can be regarded as mini protection and local control switchboards. Each Roombox protects and controls 12 circuits: lighting, HVAC cassettes, motorised blinds.
Although the air-conditioning terminals, luminaires and motorised blinds remain in place when dividing walls are moved, their electrical control generally changes: new control regulations, new pushbutton arrangements. The power cables and pushbutton cables are fitted with plug-in connectors that allow changes to be made quickly and easily, hence limiting any new electrical design to a simple layout change request. Wireless and batteryless pushbuttons also provide greater flexibility.
Main Roombox electrical characteristicsSupply voltage / frequency 230 V CA – 50 Hz
Max. input current 16 A
Output voltage 230 V
Max. permissible load per feeder, (max. 16 A for all the feeders) 600 VA (2.6 A)
MGDB
1P+N 2.5 mm²
1P+N1.5 mm²
Roombox switchboard
3P+N – 2.5 mm² busbar southern open space
3P+N – 2.5 mm² busbar northern open space 200 to 300 m²
Sub-distribution board
Floor Level X
Terminal equipment: luminaires, cassettes, motorised blinds
Passage area lighting circuits
Connector column circuits
Fan coil module
Roller blind
Luminaire
pushbutton
Power outlets
DB
1237
45
Roombox' Installation Design Guide
14
Example of a KNX configuration
Roombox communication network architectures
Information exchange The Roombox provides status information on each loads that it supplies and control. These information can be used in turn for monitoring purpose and control process. They can also be shared with other devices on the communication network for two way control purpose, central command, time management, display and analysis.
KNX architectureThe KNX architecture is highly appropriate for small and medium-sized buildings, where extremely decentralised control, mainly focused on electrical applications, is required. Its design is easily accessible to "Automation" or "Electrical" design offices.
The Roomboxes are directly interconnected in a "daisy chain" configuration or in parallel with a KNX bus. They are in fact similar to devices installed on a network and communicate with sensors, actuators and man/machine interfaces from the KNX product family. Schneider Electric provides a large range of KNX components, the ETS programming software and Technical support.
Bus power supply
4 pushbutton thermostat unit
Outdoor sensor (temperature and luminosity)
Touch screen4-channel annual programmable clock
Management of zones not covered by the Roomboxes
8-pushbutton unit 8-relay actuator
The main shared KNX functions
The ETS software is used to set the function parameters.
Time programming: using the 4-channel annual programmable clock (ref. MTN677029 or MTN 677129). This clock can for example control the lighting feeders of several Roombox by switching them on or off.
General controls: using multi-function pushbuttons (ref. MTN 623xyz and MTN 628xyz). The lighting on each floor is switched on and off from the entrance, with LED status indication. The blinds are all lowered collectively.
Temperature control: the multi-function pushbuttons (ref. MTN 623xyz and MTN 628xyz) incorporate a sensor and a thermostat that can send ON/OFF orders to a KNX actuator or an HVAC feeder on a Roombox connected to a two-way valve. The user has an LCD screen for setting the commands and displaying the temperature.
Equipment, meter and temperature status display and general controls: the 10" touch screen (ref. MTN 683090) provides the operator with simple, easily understandable communication (example: a photo associated with a particular event may appear). The touch screen is installed on the wall, at the reception or security desk. The operator can easily control the status of the lighting, the blinds, the outdoor and indoor temperature, turn everything off and close all the blinds with one touch of a button. He can check the lighting and air-conditioning energy consumption for each zone or overall.
KNX bus
Overview of the Roombox concept
PB
1065
57-1
0
P11
6030
-18
P10
5935
-20
P11
5993
-15
P11
0081
-22
P11
6006
-20
P11
5870
-15
P11
5960
-17
15
Example of a LON configuration
LON architectureThe LON architecture is highly suitable for medium-sized and large buildings where management via a single monitoring system and interactivity between various systems: fire safety, access control, HVAC, electrical distribution, etc. is required. It is designed and configured by specialised design offices, generally in close association with the "Heat" and "Utilities" lots.
The LON connection is generally used to allow the supervision PCs to monitor the electrical distribution and for centralised control, control by occupancy times and to "transmit" the metering values, etc.
The Roombox are directly interconnected in a "daisy chain" configuration or in parallel with the LON bus.
Schneider Electric has designed a range of "VISTA" BMS systems based on "Xenta" controllers.
Vista station or server
Xenta HVAC terminal controller
Xenta HVAC terminal controller
Xenta HVAC terminal controller
Touch screenXenta PLC – Web page server
Xenta input / output module
Shared LON functionsThese functions are similar to the KNX architecture functions.
Bus Lon
Stand-alone architectureIn this case, each Roombox operates independently, without a bus communication link with the others or with a central control system, after having been configured individually.
Note: the use of addressable radio pushbuttons allows several Roombox in close proximity to react to common manual orders: general switching ON/OFF in an open space (open plan area), for example.
@
P11
0081
-22
DE
4015
33
PB
1065
62
PB
1065
63
PB
1065
64-3
5
PB
1065
57-1
0
Roombox' Installation Design Guide
16
ON/OFF lighting
Roombox functions
> Local automatic controlA Roombox "presence and light" sensor can be associated with the lighting in one or more zones.
Depending on the Roombox parameter settings, the lighting can simply come on after a presence is detected and remain on for an adjustable time or it can be switched on when a light threshold is detected or even when a presence and light threshold are detected.
> Mixed local controlThe pushbutton is used to switch the lighting on and off.
The "presence and light" detector: inhibits or switches off the lighting when the
brightness exceeds a predetermined threshold. switches off the lighting when no presence has been
detected for fifteen minutes.
ou
> Local manual control Pressing the local pushbutton controls the associated output as follows: immediate ON/OFF control or time-delay control (timer function)
A wired or batteryless radio button can also be used.
Local control authorisation/inhibition: they can be provided by a light sensor installed locally or on another Roombox or by a time program in a remote controller.
ou
Nota: IEC 60081 and IEC 60901 norms impose a burn in phase of a 100 hours for dimmable fluorescent tubes in order to stabilise them and improve life cycle.
PB
1065
58-2
4
PB
1065
70P
B10
6570
PB
1065
70
PB
1158
99
PB
1158
99
PB
1065
74P
B10
6574
PB
1065
58-2
4P
B10
6558
-24
17
> Automatic control via the BMS busBuilding Management System bus In this example, a touch screen KNX room-mounted terminal connected by a communication bus is used to control the luminaires managed by the various Roombox. It can also include time programming functions and lighting scenarios.
A LON building management controller connected to the bus can be used for the same time of functions.
Terminal
PB
1065
56-2
4
PB
1065
65
PB
1065
56-2
4
PB
1065
70
PB
1065
70P
B10
6570
Roombox' Installation Design Guide
18
DALI dimmer lighting The Roombox contains "DALI Lighting" feeders that allow fluorescent lamps fitted with DALI ballasts to be powered and dimmed. Each connector has 230 V supply terminals and DALI communication.
The DALI feeder operates in broadcast mode: the command sent to the DALI bus is executed in the same way by all the ballasts. The ballast diagnosis return is, however, individual. The automatic addressing system makes it much easier to implement.
> ScenarioA scenario is the automatic combination of simultaneous actions on several devices in the same room. Example: in a meeting room, pressing a "projection" button switches off two lighting circuits and lowers the blinds. Another press cancels the action
A scenario can also be started up by a presence sensor in an office. Example: the occupant's arrival is detected and switches on the lighting (if it is dark) and the air-conditioning; after the occupant has been absent for fifteen minutes, the sensor will switch the lighting off and set the air-conditioning to "unoccupied" mode.
The Roombox incorporates scenarios that can be predefined and selected by the electrician, thus releasing the BMS from having to perform these tasks.
> Local manual control The ON/OFF/Dimming ± functions are controlled by wired buttons or by radio battery less pushbuttons. DALI power supply
+ Bus
DALI ballast luminaires
> Local automatic controlAdding the "presence and light" detector allows the brightness to be regulated according to the following principle: the user can adjust the lighting level and switch it
ON / OFF. the lighting level is then kept constant, in proportion
with the ambiant natural lighting level.
or
or
DALI power supply + Bus
DALI ballast luminaires Light sensor
Roombox functions
PB
1065
58-2
4P
B10
6558
-24
PB
1065
70P
B10
6570
PB
1065
74P
B10
6574
19
HVAC (heating, venting, Air-conditioning)
> Air-conditioning terminal power supply
Compatibility with With air-treatment units and terminals
Mono-split or multi-split systems and terminals
Cassettes 2 tubes, 4 tubes, 2 tubes / 2 wires (P ≤ 600 W)
Chilled beams 2 tubes, 4 tubes, 2 tubes / 2 wires (P ≤ 600 W)
Fan coil units 2 tubes, 4 tubes, 2 tubes / 2 wires (P ≤ 600 W)
Indoor wall units
Depending on its version, the Roombox can be used to supply 230 V to the air-conditioning system terminals up to 2.6 A (600 VA) per circuit. This voltage is required: for the terminal controller, for the fan, for any additional electrical heating element.
The production units (heat pumps, air-treatment units, etc.) are not covered.
> Regulation equipment power supply / controlLocal controller power supply (HVAC management by separate system)
The Roombox only supplies power to the local controller, it does not perform a control function. However it has a protection and switching function allowing the power supply to the HVAC regulator and terminal unit.
Controller
230 V 2.6 A max.
Fan coil unit
Bus
PB
1065
56-2
4
PB
1065
66
PB
1065
67
PB
1065
68-7
0
PB
1065
69
PB
1065
68
PB
1065
64-4
0
Roombox' Installation Design Guide
20
Zone controller
Window contact NC type
230 V two-way valve
> Regulation equipement power supply / control (cont.)Valve supply / control (the HVAC system and the Roombox share the same bus)
The Roombox behaves as a KNX or LON output interface by executing the orders received from the zone controller via the common bus.
It opens/closes the valve according to the control requirements.
Energy management can be optimised by wiring a window contact to the input associated with the HVAC feeder. The status of the window is sent via the network to the zone controller concerned that can then trip the "Stop" mode (cut off the valve supply) if the window is open.
HVAC (heating, venting, Air-conditioning)
Roombox functions
230 V two-way valves
Building Management System bus
By default, the Roombox is configured for normally-closed window contacts (Open when the window is Closed). This parameter can be modified via the BMS.
The zone control function can also be provided by any other BMS system or controller using a communication mode that is KNX or LON compatible.
PB
1065
56-2
4
P10
5935
-20
PB
1065
73
PB
1065
73
PB
1065
75
21
> Roller blinds (230 V motors)
> Venetian blinds (230 V motors)
A zone controller can be implemented on the BMS bus to coordinate the control of the lighting, air-conditioning and light-exclusion motors according to a general schedule, a central manual control, etc.
Besides the up/down functions, the direction of the slats can be accessed locally via a pushbutton and also via a communicating automated device that will adjust it according to the sunlight and/or the occupancy schedule.
The up/down action is controlled by a "long" (>600ms) pulse on the corresponding button.
Shutter control
Zone controller
Local control PB
Building Management System bus
Locally, the user has an up/down button to adjust the position of the blind, as required.
The Roombox provides the continuous neutral and applies the phase to the up or down wire of the motor according to the order sent. Consequently, the motor stops remain effective.
The order is maintained by the Roombox during a customisable time delay (depending on the window height and speed of the motor).
An intermediate stop is obtained by a "short" (<600ms) pulse on the opposite button. Slat angle change (rotation) is achieved through a serie of short pulses up or down.
Zone controller
Communicating sunlight sensor
Local control PB
Building Management System bus
PB
1065
56-2
4
PB
1065
56-2
4
PB
1065
56-2
4
PB
1065
56-2
4
P10
5935
-20
P10
5935
-20
P11
5993
-11
PB
1065
71
PB
1065
71
PB
1065
71
PB
1065
74
PB
1065
74
PB
1065
74
PB
1065
74
PB
1065
72
PB
1065
72P
B10
6572
Roombox' Installation Design Guide
22
Energy metering
Roombox functions
> Roombox internal meters3 energy metering functions are integrated in each Roombox:
Metering Accuracy - class (according to IEC 61557-12)
Unit Number of digits
Cooling period
All consumption totaliser 1% - 1 1 kwh 10 programmable from 1 to 3600 secondsTotal lighting 2.5% - 2 1 kwh 10 programmable from 1 to 3600 secondsTotal HVAC 2.5% - 2 1 kwh 10 programmable from 1 to 3600 seconds
The values are transmitted by the bus to the BMS for display, archiving and potential threshold alert processing.
23
Roombox range
Roombox:
common LON - KNX versions
Number of Zones x Number of Feeders
Equipment Blinds ON/OFF lighting 4x2 DALI lighting 4x2 HVAC 4x1 4x1
Cat. noWired LON ORBL8L0S4HW ORBL8D0S4HWWired KNX ORBK8L0S4HW ORBK8D0S4HWRadio LON ORBL8L0S4HR ORBL8D0S4HRRadio KNX ORBK8L0S4HR ORBK8D0S4HR
Roombox:
LON specific versions
Number of Zones x Number of Feeders
Equipment Blinds 4x1 4x1 Lighting TOR 2x2, 2x1 Lighting DALI 2x2, 2x1 3x3 HVAC 2x1 2x1 3x1
Cat. noWired LON ORBL6L4S2HW ORBL6D4S2HW ORBL9D0S3HWRadio LON ORBL6L4S2HR ORBL6D4S2HR ORBL9D0S3HR
Roombox:
KNX specific versions
Number of Zones x Number of Feeders
Equipment Blinds 4x1 4x1 Lighting TOR 4x1 Lighting DALI 4x1 HVAC 4x1 4x1
Cat. noWired KNX ORBK4L4S4HW ORBK4D4S4HWRadio KNX ORBK4L4S4HR ORBK4D4S4HR
The 18 Roombox
PB
1065
57-1
2P
B10
6557
-12
PB
1065
57-1
2
Roombox' Installation Design Guide
24
Roombox buttons and sensors
Roombox range
Wireless, batteryless pushbuttonsAs an alternative to the wired pushbuttons, wireless, batteryless pushbuttons bring exceptional upgradeability to the Roombox concept the buttons being battery less completely release the operator from the constraints of maintenance.
These buttons are used to control the lighting and motorised blinds.
They communicate by radio with the Roombox to which they are assigned. The Zigbee communication standard used provides highly reliability for a moderate cost in local remote-control applications.
A micro-generator powered by the energy used to press the button makes it possible to dispense with the use of battery.
Transmission power < 1 mWRange In free field appromatively 100 m
Through a light plaster wall up to 30 mThrough a concrete block wall approximately 10 m
The values given are for information only, since radio propagation changes when metal surfaces or steel reinforcing bars are present, according to the thickness of the materials, etc.
Schneider Electric Zigbee pushbuttons are available with M-Smart range covers:
Single pushbutton
P11
7489
P10
5916
-48
25
Presence / light level sensorTwo sensors are integrated into one box:
Presence sensor, closes its contact briefly when a movement, even a slight movement (such as that made by a person sitting in front of a desk, etc.) is detected.> Detection characteristics: 360°; range with a radius of 7 m and a max. height of 2.40 m.
Light level sensor: its output voltage varies according to the intensity of the light perceived.> 0 V = 0 lux and 10 V = 900 lux.
Type Cat. no.
Sensor
Flush-mounted sensor MTN6901-0000
Base for surface-mounting MTN6901-0001
Cable
15 m original cable (RJ12 and M8 connectors)
MTN6901-0003
15 m intermediate cable (M8/M8) MTN6901-0005
Movement detection in large rooms and corridors:
Two sensors can be associated in a "daisy chain" to cover the detection zone, each sensor is fitted with two M8 connectors for this purpose. The light is measured only by the nearest sensor to the Roombox.
Intermediate cable Original cable
MTN6901-0002 MTN6901-0004
Example:
PB
1065
57-1
5
P11
2750
-70
P11
5899
-15
P11
9792
-12
Roombox' Installation Design Guide
26
Roombox implementation and architecture"Budget envelope" approach
> The number of Roombox, i.e. the prospective budget envelope, should quickly be assessed. The method is approximate, based mainly on a breakdown of the building modules.
Building module concept One floor of a building consists of the horizontal juxtaposition of building modules of identical dimensions, generally two windows wide, i.e.
For example: in France: usually 2 x 1.35 m; in the Netherlands: 2 x 1.60 m.
A module is fitted with the following standard equipment:
one or two motorised or manual blinds (they generally have combined controls);
one or more luminaires (with combined manual control; the row on the window side can be fitted with an inhibiting automated control);
an HVAC terminal;
The number of devices per module depends on the quality specified and the modularity required for any half-module assembly.
Precautions to be taken when defining packagesThe Roombox equipment will be integrated logically in the "Strong current – Low current" lot.
Caution! > Impact on the HVAC equipment (HVAC): the Roombox supply the controllers, the 230 V two-way valves, the HVAC terminals (cassettes, fan coil units, etc.). Those responsible for the HVAC equipment must therefore be informed that the total power of the Controller + Fan + possibly a backup resistor is limited to 600 VA (2.6 A).
> Impact on the various installations/woodwork is as follows: the Roombox supply 230 V and power the automated motor control.
Two examples of modules:
> The type A module is the most common.
> The type B module can be split into half-modules.
The corridors and other specially designated rooms are designed without reference to the module, as their equipment will be specifically arranged to suit each location.
Other types of modules are possible.
2 x 1.35 m
Type A module
2 x 1.35 m
Type B module
Motorised blind
HVAC terminal
T5 fluo luminaire
Pushbutton
27
Roombox implementation and architectureAssessing the number of Roombox on each floor> Step 1: Identify the building modules on the drawing.
> Step 2: Count the modules with motorised blinds: N1 Count the modules without blinds: N2
Number of Roombox R = (N1: 2) + (N2: 4)
Building module with its equipment:
Luminaire
HVAC terminal
Motorised blind
PB
1065
29-2
7
Roombox' Installation Design Guide
28
Roombox installationPrinciple
1- Installing the Roombox distribution structure
The optimum type(s) of Roombox must be determined and the feeders routed to the equipment in one or more modules.
The optimum arrangement is achieved when: minimum cable lengths are used; the Roombox cover one or more complete rooms,
as the operating scenarios can then be configured for these rooms.
2- Determining the building module equipmentIdentify the basic building module on the drawing.
Count the type and number of Roombox feeders it will require.
Motorised blinds: they can be wired to a single feeder and will operate simultaneously.
HVAC terminal: the power available on each feeder was limited to 600 VA (2.6 A). Good coordination with those responsible for the HVAC lot is required to ensure that the total power of the Controller + Fan + possibly a backup resistor is less than this value. The trend is for the major manufacturers to provide low power consumption terminals.
Luminaries: they are generally powered by two separate feeders so that only the luminaire on the window side is controlled by daylight.
Three to six feeders may be required for each building module, depending on the degree of flexibility and comfort required.
3- Optimising the roomsA room consists of building modules and possibly half-modules.
The optimum arrangement may be achieved by envisaging the connection of identical devices on several modules in the room in parallel on the same feeder. This solution will only be appropriate if there is no plan to divide the room up at a later date.
Otherwise, this room must be dealt with module by module. Combine the equipment from any half-module used with the appropriate adjacent module.
4- Optimising open space or an entire storey
A Roombox can cover several offices. Supplying offices on both sides of a corridor limits the length of the cables and makes it easier to carry out work on the Roombox which will be fitted in the centre of the suspended ceiling in the corridor.
It will be sensible to have a few spare feeders so that modifications can be made at a later date.
5-Corridors and service roomsThere is generally no intention to change the lighting in these zones. The luminaires in one zone should therefore be grouped together over a minimum number of Roombox outputs not exceeding the maximum available power (600 VA).
29
Offices on both sides of a corridor are supplied by the same Roombox.
The remaining available Roombox lighting outputs were assigned to passage areas in an attempt to optimise resources.
The Roombox chosen is:
A: ref. ORBL8L0S4HW
: 8 ON/OFF lighting outputs
: 4 HVAC outputs
A certain switchboard zone corresponds to each room.
The corridor luminaires are powered via a free channel in zones C and D.
Office width: 1 module
Office width: 2 modules
Example: Installation in a suite of "module A" offices
PB
1065
57-1
0
BBBA A
Roombox' Installation Design Guide
30
The Roombox chosen are:
A: ref. ORBL8L0S4HW : 8 ON/OFF lighting outputs: 4 HVAC outputs
B: ref. ORBL6L4S2HW : 4 motorised blind outputs : 6 ON/OFF lighting outputs: 2 HVAC outputs
The corridor luminaires are powered by a conventional circuit.
The pushbuttons are wired buttons.
Office width: 1 module
Office width: 1 module
Roombox installationExample: "Module A" version with blind control
PB
1065
57-1
0
B A B A
31
The Roombox chosen are:
A: ref. ORBL8L0S4HR : 8 ON/OFF lighting outputs: 4 HVAC outputs
B: ref. ORBL6L4S2HR : 4 motorised blind outputs : 6 ON/OFF lighting outputs: HVAC outputs
The corridor luminaires are powered by type B Roombox (2 lighting outputs remain available, the links are not shown).
The pushbuttons are radio batteryless buttons.
Office width: 1 module
Office width:1.5 module
Office width: 2 modules
As module B can be split, it is possible to create intermediate-sized rooms.
Example: Installation in a suite of "module B" officesP
B10
6557
-10
Examples of supply distribution architecture
LT
LT
LT
LT
Roombox' Installation Design Guide
32
Energy distribution to the RoomboxDistribution design elements
Roombox power supply characteristics
Supply voltage 230 Vac, +10% -15% Frequency 50 Hz, ±2%Integrated input protection rating 16 A
The best technico-economic optimisation is obtained with the two 2.5 mm² 4-pole bus cables:This solution is the one that offers the cheapest upstream cabling + protection, considering:
The low cost of the 20 A upstream circuit breakers to be used,
The relative ease with which the 2.5 mm² cables and tap-off accessories can be implemented.
> The additional cost of the solution with 1 x 6 mm² 4-pole bus is in the region of 25%.
Roombox
Tap-off unit
Cable tray
2 x 2.5 mm2 4-pole bus cable
1 x 6 mm2 4-pole bus cable
3 x 6 mm2 single-phase bus cable
6 x 2.5 mm2 single-phase cable
DB
1237
46
DB
1237
47D
B12
3749
DB
1237
48
L
N
PE
Bus cable and tap-off unit
2 Roombox max. on a 3 x 2.5 mm² cable (assuming 16 A max. per Roombox)
C20A 2P + vigi 300 mA or 30 mA
3 x 2.5 mm²
3 x 2.5 mm² (or 3 x 1.5 mm² with L ≤ 3 m)
C32A 2P + vigi 300 mA or 30 mA
Max. 4 Roombox on a 3 x 6 mm² cable (assuming 16 A max. per Roombox)
L
N
PE
3 x 6 mm²
L ≤ 3 m3 x 2.5 mm² or 3 x 1.5 mm²
Bus cable and tap-off units
33
Bus cables and tap-off unit protection regulations
Protection against overvoltages caused by lightning strikes Degree of Roombox protection: OVC3 (4 kV).
Bus cable protection against overloads and short circuits depends on the cable cross-section.
Protection against earth leakage currents is achieved: by 300 mA or 30 mA Vigi modules.
The protection used for the bus cable will also protect the tap-off unit with the same core diameter / cross section. For economic optimisation purposes, a tap-off cable with a smaller cross-section than that of the main cable may be used. This changes the risk characteristics and logically, appropriate protection is required at the tap-off connection.
This protection is not mandatory when its length does not exceed 3 metres according to IEC 60364-4-43, sub-clause 434.2.
The 16 A incoming circuit breaker incorporated in the Roombox also protects the tap off cable against overload, which combined with the 3M rule makes safe and compliant.
Power supply circuit via a single-phase bus cable
DB
1237
50D
B12
3751
L1 L2 L2 L3 L3L1
Bus cable and tap-off units
L1
L2
L3
N
PE
3 x 2 Roombox max. on a 5 x 2.5 mm² cable (assuming 16 A max. per Roombox)
C20A 4P
cable 5 x 2.5 mm²
3 x 2.5 mm² (or 3 x 1.5 mm² with L ≤ 3m)
C32A 4P + vigi 300 mA
4 x 3 Roombox max. on a 5 x 6 mm² cable (assuming 16 A max. per Roombox)
L1 L1 L1 L1 L2 L2 L2 L2 L3 L3 L3 L3
L1
N
PE
5 x 6 mm²
L ≤ 3m3 x 2.5 mm² or 3 x 1.5mm²
Bus cable and tap-off units
L2
L3
Roombox' Installation Design Guide
34
Power supply circuit via a three-phase bus cable
Practical example of Roombox power analysis
Roombox selected: Ref. ORBL8L0S4HW (8 lighting feeders + 4 HVAC terminals) to supply four 12 m² offices.
Equipment per office Total power Total current2 x 62 W luminaires (4 x T5 14 W) 124 W 0.54 A1 x HVAC terminal (no backup R) 150 W 150 W 0.65 ATotal 1 office 274 W 1.19 ATotal 1 Roombox (4 offices) 1096 W 4.76 A
As in this example, the Roombox inrush current will frequently be in the region of 5 A (T5 lighting + 2-tube or 4-tube fan coil).
Under such conditions, each phase of a 5 x 2.5 mm² bus cable can supply up to three Roombox, i.e. 9 per bus cable: > i.e. 36 x 12 m² offices> as a summary calculation, select one 5 x 2.5 mm² cable for 450 to 500 m².
Energy distribution to the RoomboxD
B12
3752
DB
1237
53
PE N L3 L2 L1
LoadLoad
LoadLoad
LoadLoad
LoadLoad
LoadLoad
LoadLoad
35
Roombox power supply connections and internal protection devices
230 V power supply
Removable connector ref.: ORBCM50
Ultimate protection by DT40 16A C curve circuit breaker – 10 kA
Protection device status control and display
"Powered output" tripping indicator led
"Powered output" indicator led
Individual electronic protection In = 2.6 A Icu = Ics = 10 kA Idn = 10 mA
PB
1065
77
PB
1065
78
PB
1065
79
DB
1237
54
Roombox' Installation Design Guide
36
> Schneider Electric's solution: Canalis KDP busbar trunking system.
> Another solution: Wieland – Gesis flat cable and accessories
Canalis KDP is a busbar trunking system that uses a flat cable with factory-installed tap-off units to ensure the quality of the connection:
either at 1.20 m or 2.40 m intervals suitable for 0.60 m wide suspended ceiling tiles;
or at 1.35 m or 2.70 m intervals suitable for 1.35 m module facades.
> It is available in 3 x 2.5 mm² and 5 x 2.5 mm² versions.
A rack-out connector for 1.5 mm² cable allowing the supply phase to be selected is used to connect the switchboards to the main cable. http://www.e-catalogue.schneider-electric.fr/navdoc/catalog/ca/index.htm
The communication bus (not shown) is separate from the busbar.
Connectors on the flat cable are available to the installer, as required. The phase is selected by piercing the insulating material. Some cables also incorporate a data bus.
Five-conductor cable with bus: flat cable 5G2.5+2*1.5QMM FR/LSOH ref.: 00.709.0323.9 Wieland male 3P connector + bus:
MALE C.W.STR-REL. EST2I3FSS1 Z GN/SW; ref.: 93.502.0553.1
Wieland connector on the Roombox side: WIELAND GESIS GST 18i3
The length of the tap-off cables must not exceed 3 m.
http://ecat.wieland-electric.com/search-engine/showProductDetails.do?productSN=7784
Energy distribution to the RoomboxD
B12
3759
DB
1237
60
37
Communication port
Building management system port
The management network is connected via the fast connection terminal block, whatever the protocol used.
LonTalk (LON) Protocol: in conformance with EN14908 - 1, 2, 3, 4
This protocol allows exchanges between Roombox via a LonWorks network and, in particular Vista, an original Schneider Electric management system based on Xenta controllers.
KNX protocol: in conformance with ISO/IEC 14543
It is used to communicate over a network of room-mounted devices (control panels, room terminals, KNX-compatible sensors) and Roombox.
Schneider Electric has a complete range of KNX components and the ETS configuration software.
Characteristics:P
B10
6557
-45
PB
1065
80
Roombox' Installation Design Guide
38
Building management system port
Permissible architectureLon KNX
Network consisting of segments, each of which is controlled by a Router connecting it to the main segment.
Segment topology: free (see illustration) or pure bus.
Network consisting of lines, each with a power supply and a coupler connecting it to the main "zone line" (15 lines max./zone line).
The zone lines can be connected to a 'backbone" via a coupler (15 zone lines max./ "backbone").
Line topology: free, but loops are not permitted (see illustration).
STN 2 STN 4
STN 1 STN 3
STN 5 STN 6
STN 7
STN 9
STN 18
STN 17STN 16
STN 15
STN 3
STN 10
STN 11
STN 12 STN 13 STN 14
STN 8
STN 2 STN 4
STN 1 STN 3
STN 5 STN 6
STN 7
STN 9
STN 18
STN 17STN 16
STN 15
STN 3
STN 10
STN 11
STN 12 STN 13 STN 14
STN 8
Type of cable
Belden 7703; 1 pair 0.64 mm Belden YE00820; 2 pairs 0.8 mm
Maximum length
500 m of cable used in free topology 1000 m in pure bus topology
1000 m of cable used per line. 350 m max. between the supply and the furthest point.
Max. no. of points
60 nodes max. per segment (1 Roombox = 1 node)
64 participants max. per line. (1 Roombox = 1 participant)
Polarised bus
No Yes
Terminator impedance to be cabled to a segment or line
Yes No
Power supply
Via the router Via the 29 V power supply module + inductor
Communication portCharacteristics:
Router
Linear topology
Star topology
Extended Star topology
Power supply 230V
Linear topology
Star topology
Extended Star topology
DB
1237
55
DB
1237
56
39
Ethernet port for local configuration PC
TCP / IP protocol This universal protocol is available on the RJ45 connector on the front of the Roombox. It is used to upgrade its microprogram (Operating System) by connecting it to a PC. The connection requires a CAT5e RJ45 cable ("network cable").
DALI lighting management system ports (depending on the version)
DALI protocol: in conformance with IEC 62 386
This protocol is available on two of the five DALI Lighting output connector terminals. It allows lighting commands and ON/OFF orders to be sent via a two-wire bus to luminaires fitted with DALI ballasts. Each "DALI lighting" power output of the Roombox supplies power to a ballast or group of ballasts that reacts collectively to each order issued ("broadcast" mode) via the Roombox DALI output.
Maximum length of each DALI bus: 25 m.
Energy-saving: the 230 V ballast power supply can be desable when the DALI control is set to 0%.
Maximum: 6 ballasts per line.
Radio receiver port for ZIGBEE sensors (depending on the version)
Zigbee protocol: in conformance with the IEEE 802.15.4 standard
Some Roombox incorporate a radio receiver supporting the Zigbee protocol which allows them to process orders from Schneider Electric wireless, batteryless pushbuttons.The antenna is built into the Roombox.
Frequency: 2.4 GHz
PB
1065
57-2
9
PB
1065
81
P11
9792
-16
Roombox' Installation Design Guide
40
Input and sensor
The input circuits are designed to receive orders from lighting pushbuttons and venetian or roller blind pushbuttons, as well as the status of a window contact.
A 3-pin connector accepts a single or double gang pushbuttons; in the case of a double gang pushbuttons, one pin is common.
This 3 pin connector is also used for window contacts. By default, the type of contact used is normaly open.
Input electrical characteristics
The input circuits inject a direct current into the sensors; the power supply is built into the Roombox.
+ -> Roombox output rated voltage, open circuit contact: 24 Vcc
> Rated current in a closed circuit: 6 mA
Switching limit values in conformance with IEC 61131-2 for type 2 PLC inputs
The voltage available is classed as ELV, supporting, for example, the installation of ELV multipair cables for pushbuttons.
Characteristics:
PB
1065
57-2
9
PB
1065
85
PB
1065
84
PB
1065
86
41
Recommended sensors and pushbuttons
The button and sensor contacts must ensure correct operation under the following conditions:
> Switching voltage: 24 Vcc
> Current: 6 mA
Window sensor: preferably NO type (open when idle). Opening the window closes the contact. The use of a NC type contact requires a Roombox parameter to be modified via the configuration tool.
Sensor connection diagram Sensor power supply:
+24 V DC supplied by the Roombox to terminal C.
Connection to the Roombox input terminal blocks:
Check with your pushbutton manufacturer the compatibility of his material with ELV switching more specifically if you're planning to use standard 230 V push buttons.
In fact, depending on their technology, the contacts may get dirty over time, with the result that their conductivity becomes increasingly random.
Schneider Electric guarantees that its pushbuttons meet these requirements.
Caution!
Sensor cable connector Schneider Electric Reference: ORBCI50
Sensor cables Pushbuttons: cable cross-section 0.75 to 1.5 mm²
Connection of a single pushbutton (ON/OFF PB) or NO contact (open when a window is open) to a three-pin terminal block
Connection of a double PB to a three-pin terminal block
ON + OFF up + down
ON/T C OFF ON/T C OFF Up C Down
Installation examples
Roombox' Installation Design Guide
42
Input and sensor
Installation of an ALBO65222 raising/lowering button on ALBO6501 mechanism.
Alvaïs finishEmbedded in masonry: Modulo box ALB71301Or for dry partition: Alfix box ALB71340+ Quadra mechanism holder ALB81010 + ELV control ALB06601+ Anthracite Alvaïs Design finish frame ALB83010.
Alvaïs finish 4-pushbutton control: ELV control ALB06612+ mechanism holder ALB81010+ finish plate ALB86050.
IHC finishDirect mounting on wood panelELV control ALB06512 with finish frame supplied (50 x 50 mm).
IHC finishDirect mounting on wood panelELV control ALB06501 on frame ALB06563 (65 x 65 mm).
Schneider Electric's pushbutton range: ELV Alvaïs ELV controls
Type To be composed for Alvaïs or IHC finish To be composed for IHC finish Complete with Aline finish
No. of pushbuttons 2 4 6 4
No. of indicator lamps 0 0 0 0
Cat. No. White ALB06501 ALB06502 ALB06503 ALB06502
Anthracite ALB06601 ALB06602 - -
Characteristics
Thickness 12 mm
Accessories supplied White IHC finish frame with white controls Transparent plastic covers, with label-holder buttons
Connection Self-stripping contacts
Recommended mounting With 3 x 40 mm plasterboard type screws
Accessories Cat. No.
45x45 mm Quadra mechanism holder for Alvaïs mounting
ALB81010 - -
White raising/lowering buttons for roller blinds (set of 10)
ALB06522 ALB06522 ALB06522 -
Working voltage: 5 – 24 V DC Acceptable current: 1 to 50 mA
Characteristics:A
LB06
501d
ALB
0660
1d
ALB
0650
2d
ALB
0650
3d
ALB
9150
2d
ALB
0660
2d
E97
924d
ALB
0652
2d
E97
923d
E97
928d
E98
201r
E97
915
E97
916
E97
914
1 2
3 4
5 6
RJ12
43
Presence / light sensor inputs4 inputs (1 per zone) on RJ12 connectors are available on the Roombox front panel for connecting Roombox-specific sensors.
1: + 24 V output2: 0 V3: free4: 0-10 V input (light level)5: free6: +24 V input (presence detected)
PB
1065
83
Roombox' Installation Design Guide
44
Feeder
Permissible power
Maximum permissible unit power per feederOutput voltage: 230 Vac +10% -15% Frequency 50 Hz ±2%Maximum current 2.6 AMaximum power 600 VAMin. ϕ cos 0Protection characteristics Class 10 overload protection to Nema ICS2 Standard *Technology Static output with electronic protection
*Protection meeting the needs of blind motors and HVAC terminals.
Maximum total permissible powerMaximum permissible power 3665 VA Max. derating according to the temperature 2285 VA à 50°C*
* The derating is maximum when the Roombox is in the most unfavourable position (see the Roombox location chapter).
ConnectionsType of feeder Roombox terminal block Removable connector
References Schneider ElectricON/OFF lightingAir-conditioning terminalTwo-way valve
3 terminals ORBCL50
Motorised venetian and roller blinds 4 terminals ORBCS50
DALI ballast 5 terminals ORBCD50
Power cables Minimum cross-section: 1.5 mm².
Power capacity of lighting circuits by lamp typeStandard luminaire characteristicsOffice zones
Based on T5 14 W to 80 W fluorescent lamps with 3 to 5 W electronic ballast. 1 to 4 tubes per luminaire. Most commonly used luminaire: 60 W (2 x 28 W tubes + ballast).
Based on T8 16 W to 58 W fluorescent lamps with 2 to 4 W electronic ballast. 1 to 4 tubes per luminaire. Most commonly used luminaire: 75 W (2 x 36 W tubes + ballast).
The sum of the effective powers controlled by the feeders must not exceed the maximum total permissible power.
Caution!
Characteristics:
45
Max. number of luminaires per feeder = 600 VA / (P luminaire x 2)*
* to be rounded up
The constraints of ageing and preheating are taken into account.
Any Cos ϕ due to Roombox output technology.
> i.e. 5 x 60 W T5 luminaires.
Power capacity of roller blind circuits according to the type of motor230 V motor: Power W /Torque mN Number
135 / 15 4200 / 30 3285 / 35 2310 / 45 1
Caution: capacity expressed within the limit of the Maximum total permissible power.
Power capacity of HVAC cassettes and two-way valvesTerminal Nombre
2 tubes, 4 tubes: 230 V / 50 to 100 W 6 to 122 tubes / 2 wires: 230 V / 600 W max. 1230 V / 6 W two-way valve 100
Passage areas
Based on 9 to 55 W compact fluorescent lamps with separate 2 to 4 W electronic ballast. 1 to 2 lamps per luminaire.
Based on 20 to 150 W sodium iodide lamps with 5 to 15 W electronic ballast.
1 to 2 lamps per luminaire.
Constraints of preheating – Ageing
Type Preheating current End-of-life current
Fluorescent lamps, compact fluorescent lamps
1.5 to 1.6 In for a few tenths of a second to a few seconds
Up to 2 In
Metal-iodide lamps 1.5 to 1.6 In for a few minutes Up to 2 In
Power capacity of fluorescent and metal iodide lamps
Roombox' Installation Design Guide
46
Conformity with standards Switchgear and overload protection standardsStatic breaking protection products are only covered by general standards:
IEC 60439-1 for low voltage switchgear and controlgear assemblies,
IEC 60947 for protection against overloads,
IEC 60669-2-1 switches for fix domestic networks,
EN 50090-HBES Home & Building Electronic Systems.
The Roombox design fully complies with these standards.
Quality marksCE mark: conformance with European safety and consumer protection directives, etc.
Installation Installations that integrate Roombox fully comply with CEI 60364 and NF C 15-100 (France).
P10
2068
47
Physical characteristics
Environmental conditionsAmbient air operating temperature 0°C to +50°CMax. operating temperature without derating +30°CStorage temperature -15°C to +65°CRelative humidity 5… 95% without condensation
Physical dimensions, Weight
Height 280 mm
Depth 88.5 mm
Weight: 2 500 g
Width 344.5 mm
Protection class IP20 (EN 60 529/IEC 144) without connectors.
IP30 with all connectors fitted.
Degree of pollution: III (EN60 730/ IEC 1036).
Electrical insulation class Class II according to NF C 71-000
(NF EN 60598-1).
PB
1065
57-2
9
P10
2048
Roombox' Installation Design Guide
48
LocationPreferred installation zones
Enclosure
Suspended ceiling
False floor
The Roombox must not be installed in an enclosure as there is not sufficient ventilation.
It should preferably be installed in the vertical position, as this position optimises its natural cooling capacity.
DB
1237
57
13 cmmin.
Screw-fixed installation
Fixed to a DIN rail against dividing wallor other support (better ventilation)
PB
1065
57-1
5
49
Total power derating according to the position of the Roombox
Roombox Imax Ambient temperature(Total Pmax available but limited to 600 VA/feeder)
30°C 40 °C 50 °C
Installation Fitted on the ceiling 16 A
(3600 VA) 15 A
(3400 VA) 13 A
(3000 VA)
Recommended
Acceptable
Mounting
DB
1237
58
Roombox' Installation Design Guide
50
AppendicesInstallation Design Guide: ref. S1A2688201Available on our websit site www.schneider-electric.com
COM-POWER-RBX-GUI1-EN
Schneider Electric Industries SAS35, rue Joseph MonierCS 30323F- 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439Capital social 896 313 776 www.schneider-electric.com
Printed on ecological paper
09-2010
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
© 2
010
- S
chne
ider
Ele
ctric
- A
ll rig
hts
rese
rved
.
Publishing: Schneider ElectricPrinting: