instruction leaflet neutral current sensors - pxr trip ......eaton 5 instructional leaflet...

6
Instruction Leaflet IL012302EN Effective March 2019 Power Defense – MCCB Power Defense™ WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION. (3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO THE DISCONNECT POSITION. (4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND MECHANISM SPRINGS DISCHARGED. FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY DAMAGE. WARNING THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES: DISCONNECTING; ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED; VERIFY ISOLATION FROM THE SUPPLY; EARTHING AND SHORT-CIRCUITING; AND COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS. DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED MAINTENANCE INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR AND EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT INJURY TO PERSONNEL AND DAMAGE TO THE SWITCHBOARD. Instructions apply to: Neutral Current Sensors - PXR Trip Units, Frames 2, 3, 4, 5 & 6

Upload: others

Post on 17-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Instruction Leaflet Neutral Current Sensors - PXR Trip ......EATON 5 Instructional Leaflet IL012302EN Effective March 2019 Neutral Current Sensors - PXR Tr ip Un ts, Frames 2, 3,

Instruction Leaflet IL012302EN Effective March 2019 Power Defense – MCCB

Power Defense™

WARNING(1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK

ON THE EQUIPMENT.(2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT

BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION. (3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO THE

DISCONNECT POSITION. (4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND

MECHANISM SPRINGS DISCHARGED.FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY DAMAGE.

WARNINGTHE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES: – DISCONNECTING;– ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED;– VERIFY ISOLATION FROM THE SUPPLY;– EARTHING AND SHORT-CIRCUITING; AND– COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS. DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZEDSPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED MAINTENANCEINTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR AND EXCHANGE MUSTBE STRICTLY ADHERED TO PREVENT INJURY TO PERSONNEL AND DAMAGE TOTHE SWITCHBOARD.

Instructions apply to:

Neutral Current Sensors - PXR Trip Units, Frames 2, 3, 4, 5 & 6

Page 2: Instruction Leaflet Neutral Current Sensors - PXR Trip ......EATON 5 Instructional Leaflet IL012302EN Effective March 2019 Neutral Current Sensors - PXR Tr ip Un ts, Frames 2, 3,

2 EATON www.eaton.com

Instructional Leaflet IL012302ENEffective March 2019

Section 1: Neutral Current Sensor InstallationGround Fault Trip Units detect ground fault currents through Residual Sensing. If the system neutral is grounded and residual ground faultis desired, but no phase to neutral loads are used, a neutral currentsensor is not necessary. In that case, a jumper is required between the circuit breaker's gray and white wires. If the system neutral is grounded and phase to neutral loads are used, then the neutral current sensor (see Figure 1) must be used to account for this load in the residual ground fault sensing. It has the same turns ratio as the phase current sensors in the circuit breaker. The factory installed jumper wire must be removed before installing the neutral current sensor. For all neutral sensors, primary connections should be made by routing or connecting the source neutral connection on the side or terminal where the dot is placed. Note: the dot must face the current source. Secondary connections are made by terminating the gray and white colored wires from the trip unit to the terminals labeled with those colors. Refer to Figure 2, 3, 4, or 5 for dimensional and labeling details.

Table 1. Catalog Number and Use Details

Neutral Current Sensors - PXR Trip Units,Frames 2, 3, 4, 5 & 6

Frame

PD2

PD2

PD2

PD2

PD3

PD4

PD5

PD6

Cable Type

Cable Type

Busbar Type

Busbar Type

Busbar Type

Busbar Type

Busbar Type

Busbar Type

PDG2XNCTD0100

PDG2XNCTD0225

PDG2XNCTB0100

PDG2XNCTB0225

PDG3XNCTB0600

PDG4XNCTB0800

PDG5XNCTB1200

PDG6XNCTB2500

60A, 63A, 100A

150A, 160A, 225A, 250A

60A, 63A, 100A

150A, 160A, 225A, 250A

125A, 250A, 400A, 600A, 630A

800A, 1000A

800A, 1200A, 1600A

1600A, 2000A, 2500A

Figure 2

Figure 2

Figure 3

Figure 3

Figure 3

Figure 3

Figure 4

Figure 5

Application Catalog#Trip Unit Rating

Where Used Details

Figure 1. Neutral Current Sensor Application

NSource L C R

Neutral Sensor

Load

Source

Gra

yW

hite

Load

Page 3: Instruction Leaflet Neutral Current Sensors - PXR Trip ......EATON 5 Instructional Leaflet IL012302EN Effective March 2019 Neutral Current Sensors - PXR Tr ip Un ts, Frames 2, 3,

3EATON www.eaton.com

Instructional Leaflet IL012302ENEffective March 2019

Figure 3. PD2, PD3 and PD4 Busbar Type Dimensions

Neutral Current Sensors - PXR Trip Units,Frames 2, 3, 4, 5 & 6

(2.000)

(1.000)

(.617) (.617)

(5.610)

1.09

2.443.04

2.19

2X n.281 THRU HOLES

1.19

6.00

(4.376)

1.44

5.87

3.04

2.33

2.19

1.121.12

GRAY WIRE

WHITE WIRE

POLARITY MARKS

TORQUE TO20 lb-in.

TORQUE TO 50 lb-ft.

#10 RING TERMINAL AND HARDWARE (2X)

1/2X1.5" L HEX BOLT (2X)

2.60

2.12

.47

.81 .81

n 1.1

R.11

.22

1.53

POLARITY MARKS

GRAY WIRE

WHITE WIRE

#10 RING TERMINAL AND

HARDWARE (2X)

TORQUE TO

20 lb-in.

Figure 2. PD2-Cable type Dimensions

Page 4: Instruction Leaflet Neutral Current Sensors - PXR Trip ......EATON 5 Instructional Leaflet IL012302EN Effective March 2019 Neutral Current Sensors - PXR Tr ip Un ts, Frames 2, 3,

4 EATON www.eaton.com

Instructional Leaflet Effective March 2019

IL012302EN

Figure 5. PD6 Busbar Type Dimensions

Neutral Current Sensors - PXR Trip Units,Frames 2, 3, 4, 5 & 6

1.58

n

Figure 4. PD5 Busbar Type Dimensions

.32

.94

.144 .50

.541.08

3.59

.50

1.00

.79

.49

.98

8X n.4403.94

1.572.64

3.70

POLARITY MARK

#10 RING TERMINAL AND HARDWARE (2X)TORQUE TO 20 lb-in.

GRAY WIREPOLARITY MARK

WHITE WIRE

(2.000)

(.532) (.532)

(5.440)

1.09

1.44

6.00

2.753.34

3.04

2.33

2.19

(4.376)

2X n.281 THRU HOLES

1.25

5.87

(.469)

(1.062)

(1.000)

1.141.14

GRAY WIRE

WHITE WIRE

POLARITY MARKS

TORQUE TO20 lb-in.

TORQUE TO 50 lb-ft.

#10 RING TERMINAL AND HARDWARE (2X)

1/2X1.5" L HEX BOLT (4X)

Page 5: Instruction Leaflet Neutral Current Sensors - PXR Trip ......EATON 5 Instructional Leaflet IL012302EN Effective March 2019 Neutral Current Sensors - PXR Tr ip Un ts, Frames 2, 3,

5EATON www.eaton.com

Instructional Leaflet IL012302ENEffective March 2019

Neutral Current Sensors - PXR Trip Units,Frames 2, 3, 4, 5 & 6

Note: Since the ground fault circuit breakers derive their operating power from the phase current and not from the neutral current, passing current through the neutral sensor only will not properly test the ground fault feature.

IMPORTANTTHE POLARITY OF THE SENSOR CONNECTIONS IS CRITICAL. ALWAYS OBSERVE THE POLARITY MARKINGS ON THE INSTALLATION DRAWINGS. THE POLARITY MARKINGS ARE IDENTIFIED AS WHITE DOTS ON THE TRANSFORMERS. TO INSURE CORRECT GROUND FAULT EQUIPMENT PERFORMANCE, CONDUCT FIELD TESTS TO COMPLY WITH NATIONAL ELECTRIC CODE REQUIREMENTS UNDER ARTICLE 230-95-C. SEE PERFORMANCE TESTING INSTRUCTIONS ON IL012125EN.

Section 2: Performance Testing For Ground Fault Circuit Breakers

General Test Instructions

The

Please consult Instruction Leaflet number IL012125EN for general instructions to aid you in ground fault testing of Power Defense circuit breakers with PXR electronic trip units.

interconnect system shall be evaluated in accordance with the equipment assembler’s detailed instruction by qualified personnel.

The polarity of the neutral sensor connection (if used) must agree with equipment assembler’s detailed instructions to avoid improper operations following apparently correct simulated test operations. Where a question exists, consult the specifying engineer and/or equipment assembler.

The grounding points of the system shall be verified to determine that ground paths do not exist that would bypass the sensors. High-voltage testers and resistance bridges may be used.

Page 6: Instruction Leaflet Neutral Current Sensors - PXR Trip ......EATON 5 Instructional Leaflet IL012302EN Effective March 2019 Neutral Current Sensors - PXR Tr ip Un ts, Frames 2, 3,

Eaton is a registered Trademark.

All other trademarks are property of their respective owners.

EatonElectrical Sector1000 Eaton BoulevardCleveland OH 44122United States877-ETN-CARE (877-386-2273) Eaton.com

© 2019 EatonAll Rights ReservedPrinted in USAPublication No. IL012302ENPart Number: IL012302ENH01March 2019

Instructional Leaflet IL010302ENEffective March 2019

Disclaimer of warranties and limitation of liability

The information, recommendations, descriptions, and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted.

Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.

THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein.

The information contained in this manual is subject to change without notice.

Neutral Current Sensors - PXR Trip Units,Frames 2, 3, 4, 5 & 6