GE Digital Energy g imagination at work Transformers are key and expensive components of the electrical grid and knowledge of their health condition is essential to having a reliable network. When a transformer’s insulation system is overstressed, gases are produced that dissolve in the oil. Dissolved Gas-in-oil Analysis (DGA) is recognized as the best indicator of developing faults. The Intellix TM GLA 100 is a small and intuitive transformer “gas level alarm”. It provides a cost-effective transformer warning solution using DGA, specifically tailored monitoring for less critical transformers that would typically be left unmonitored. Critical Generation and Transmission transformers are typically equipped with fully featured multi- gas monitoring systems capable of providing real-time diagnostics. As the criticality decreases, the number of fault gases monitored also decreases, moving away from comprehensive monitoring. The Intellix GLA 100 offers substantial, cost effective monitoring for the over 300,000* significant transformers worldwide that are currently unmonitored. It offers a monitoring solution for important, less critical, less expensive transformers, where the aim is less about protecting the asset and more about avoiding the consequences of an unplanned outage. Entry level price point Continually measures H 2 fault gas 2 gas level alarms, each configurable Colored light indicators and relay outputs Easy to install on 1 inch valve Manual sampling port Small Power Transformers Larger Distribution Pad-mounted Transformers Vacuum type oil-filled OLTCs Oil-filled 'pipe type' cables Oil-filled instrument transformers (CTs and PTs) Product Overview Applications Key Benefits Fault Gas Alarm Straightforward Alerts Configurable Alarms Low Maintenance Gas sensor responds 100% to Hydrogen (general fault gas) and sensitive to Carbon Dioxide (overheated paper) Small form factor easily mounted on a 1 inch valve exposed to the transformer oil. No extra piping or pump required. Weighing only 3.5 Kg No need for PC or software to monitor gas values or trends 4 front, sunlight visible, light indicators for: - each alarm level - service alarm - power 3 dry contact relays available to communicate alerts to a control center: - 2 for the fault gas alarms - one for the service alarm Alarm raised when an abnormal level of fault gas is detected enabling further investigation of the developing fault condition Two gas alarm levels showing increasing severity are available: one for caution and one for alarm. The Intellix GLA 100 comes preset with default alarm settings for simplicity but these are also user configurable using DIP switches. Simple and Reliable No moving parts Vacuum-resistant No consumables: no carrier gases or calibration gases required No field calibration required Regular automatic self-test with service alarm Intellix TM GLA 100 Cost Effective Transformer Warning Solution

Upload: djafri-malin-sati

Post on 12-Nov-2014

33 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Intellix GLA100 - 032911- V2 - Print

GEDigital Energy

g imagination at work

Transformers are key and expensive components of the electrical grid and knowledge of their health condition is essential to having a reliable network. When a transformer’s insulation system is overstressed, gases are produced that dissolve in the oil. Dissolved Gas-in-oil Analysis (DGA) is recognized as the best indicator of developing faults.

The IntellixTM GLA 100 is a small and intuitive transformer “gas level alarm”. It provides a cost-effective transformer warning solution using DGA, specifically tailored monitoring for less critical transformers that would typically be left unmonitored.

Critical Generation and Transmission transformers are typically equipped with fully featured multi-gas monitoring systems capable of providing real-time diagnostics. As the criticality decreases, the number of fault gases monitored also decreases, moving away from comprehensive monitoring.

The Intellix GLA 100 offers substantial, cost effective monitoring for the over 300,000* significant transformers worldwide that are currently unmonitored. It offers a monitoring solution for important, less critical, less expensive transformers, where the aim is less about protecting the asset and more about avoiding the consequences of an unplanned outage.

• Entrylevelpricepoint

• ContinuallymeasuresH2 fault gas

• 2gaslevelalarms,eachconfigurable

• Coloredlightindicatorsandrelayoutputs

• Easytoinstallon1inchvalve

• Manualsamplingport

• SmallPowerTransformers

• LargerDistributionPad-mountedTransformers

• Vacuumtypeoil-filledOLTCs

• Oil-filled'pipetype'cables

• Oil-filledinstrumenttransformers(CTsandPTs)

ProductOverview

Applications

Key Benefits

Fault Gas Alarm

StraightforwardAlerts

Configurable Alarms

Low Maintenance

• Gassensorresponds100%toHydrogen(general fault gas) and sensitive to Carbon Dioxide (overheated paper)

• Smallformfactoreasilymountedona1inchvalve exposed to the transformer oil. No extra piping or pump required. Weighing only 3.5 Kg

• NoneedforPCorsoftwaretomonitorgasvalues or trends

• 4front,sunlightvisible,lightindicatorsfor: - each alarm level - service alarm - power

• 3drycontactrelaysavailabletocommunicatealertstoacontrolcenter: - 2 for the fault gas alarms - one for the service alarm

• Alarmraisedwhenanabnormalleveloffaultgas is detected enabling further investigation of the developing fault condition

• Twogasalarmlevelsshowingincreasingseverityareavailable:oneforcautionandonefor alarm.

• TheIntellixGLA100comespresetwithdefaultalarm settings for simplicity but these are also userconfigurableusingDIPswitches.

• SimpleandReliable

• Nomovingparts

• Vacuum-resistant

• Noconsumables:nocarriergasesorcalibration gases required

• Nofieldcalibrationrequired

• Regularautomaticself-testwithservicealarm

IntellixTM GLA 100CostEffectiveTransformerWarningSolution

Page 2: Intellix GLA100 - 032911- V2 - Print

www.GEDigitalEnergy.com2

Intellix GLA 100

032911-v2

SpecificationsMEASUREMENTSGas in oil measurement range

40–5,000ppm

Accuracy Gas:±20%or±40ppm(whichever is greater)

Relativesensitivity H2:100%ofH2 concentration CO:~15%ofCOlevel1

Responsetime Less than 30 minutes2 (80%ofstepchange)

Samplingmethod Floodedportwith1inchNPTmale thread

External sampling port

For glass syringe, with Luer stop cock

MECHANICALEnclosure rating IP-55

Nema250(Type4X)availableinJune 2011

Enclosure dimension

17.1 x 18.9 x 25.8 cm (6.7x7.4x10.1in) height, width, depth

Weight 3.5 kg (7.7 lb)

OUTPUTSLight Indicators 4sunlightvisibleindicators:

Red–Alarm Amber–Caution Green–Power Blue–Service

Alarm Contact -TwoSPDTalarmrelays(Type C) for gas alarms status (Caution & Alarm levels) -OneSPDTalarmrelay(TypeC)dedicated to system faults

RelayContactRatings

1A@250VACresistiveload, [email protected]@48VDC.

ENVIRONMENTALOperatingtemperature

Ambient:-40°Cto+55°C (-40°Fto+131°F)

Operatinghumidity

0-95%RH(non-condensing)

Oiltemperatureatvalve

-20°Cto+105°C3(-4°Fto+221°F)

Oilpressure 0-700kPa(0-100psia)negativepressure resistant sensor

Powersupplyrequirements

100-120/200-240Vac±10%50-60Hz±5%

STANDARDSType Tests MeetsstandardsCISPR11,EN

61000-4-2,EN61000-4-3,EN61000-4-4,EN61000-4-5,EN61000-4-6,EN61000-4-8,EN61000-4-11,IEC61000-4-12,IEC61000-4-16,IEC61000-3-2,IEC 61000-3-3, IEC 60255-5,

Environmental tests

Meets standards IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-6, IEC 60068-2-30, IEC 60068-2-31,IP55,Nema250(type4x)available in June

CE Approval Meetsstandards: VD:EN61010-1 EMC:EN61326-1

OtherRequirements

cTUVusMark,RoHS

1 No cross reference with other gases at levels up to 5 times IEEEC57.104-2008Condition4

2Ingasphase,at35°C

3Atambienttemperaturegreaterthan40°C(104°F)orwhenoiltemperatureatvalveishigherthan90°C(194°F),afinnedhigh temperature valve adapter is required

SmallPowerTransformers

Fault gas “Alarm” level reached

Fault gas “Caution” level reached

Poweron/operation status

Systemfaultservicealarm

Pad-mountedTransformers

*source:NewtonEvansResearch©2010 General Electric Company. All rights reserved.

Vacuumtypeoil-filledOLTCs Oil-filled'pipetype'cables Oil-filledinstrumenttransformers(CTsandPTs)

CostEffectiveTransformerWarningSolution

GLA100 ** - ** - ** DescriptionValveType V1 InstallationonGateValveorBallValve

V2 InstallationonGlobeValveValveSize S1 1.0" diameter

S2 1.5" diameterS3 2.0" diameter

OperatingTemperature

T1 Ambienttemplessthan40°Candoiltemplessthan90°CT2 Ambienttempgreaterthan40°Coroiltemperaturegreatthan90°C(Finnedheatadaptorrequired)

Ordering