is 3646-3 (1968): code of practice for interior ... · 2.6 downward coefficient ( abbreviation dc )...

56
Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. इंटरनेट मानक !ान $ एक न’ भारत का +नम-णSatyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” प0रा1 को छोड न’ 5 तरफJawaharlal Nehru “Step Out From the Old to the New” जान1 का अ+धकार, जी1 का अ+धकारMazdoor Kisan Shakti Sangathan “The Right to Information, The Right to Live” !ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह Bharthari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 3646-3 (1968): Code of practice for interior illumination, Part 3: Calculation of coefficients of utilization by the BZ method [ETD 24: Illumination Engineering and Luminaries]

Upload: others

Post on 22-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

Disclosure to Promote the Right To Information

Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public.

इंटरनेट मानक

“!ान $ एक न' भारत का +नम-ण”Satyanarayan Gangaram Pitroda

“Invent a New India Using Knowledge”

“प0रा1 को छोड न' 5 तरफ”Jawaharlal Nehru

“Step Out From the Old to the New”

“जान1 का अ+धकार, जी1 का अ+धकार”Mazdoor Kisan Shakti Sangathan

“The Right to Information, The Right to Live”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता है”Bhartṛhari—Nītiśatakam

“Knowledge is such a treasure which cannot be stolen”

“Invent a New India Using Knowledge”

है”ह”ह

IS 3646-3 (1968): Code of practice for interiorillumination, Part 3: Calculation of coefficients ofutilization by the BZ method [ETD 24: IlluminationEngineering and Luminaries]

Page 2: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the
Page 3: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the
Page 4: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646(Partlll)-1968

Indian Standard CODE OF PRACTICE FOR

INTERIOR ILLUMINATION PART Ill CALCULATION OF COEFFICIENTS OF

UTILIZATION BY THE BZ METHOD

( Sixth Reprint JANUARY 1997 )

UDC 628.972.001.3

Q Copyright 1969

BUREAU OF FNDIAN STANDARDS MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG

NEW DELHI I10002

Gr 10 June 1969

Page 5: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-196S

Indian Standard

CODE OF PRACTICE FOR INTERIOR ILLUMINATION

PART III CALCULATION OF COEFFICIENTS OF UTILIZATION BY THE BZ METHOD

Illuminating Engineering Sectional Committee, ETDC 45

ChUiT7ftUtl Rep”senli/g

Sam N. B. SATARAW.U.A Railway Board, Ministry of Railways

Members

SHRI R. R. ANADA The Ahmedabad Millowners’ Association, Ahmedabad DR G. N. BAUAMI Central iMining Research Station ( CSIR ), Dhanbad SQN LDR H. S. BHATIA Directorate of Technical Development & Production

SHRI N. C. GLXA ( Alternate ) ( Air ) ( Ministry of Defrnce ), New Delhi

SHax S. K. BSATTACHARYA Central Public Works Department, New Delhi SURVEYOR OF WoRKR I

( ELECT ) ( &?rnnlc ) SHRI P. BOSE Eastern Regional Electrical Contractors’ Association

( India ) Ltd, Calcutta SHaI L. N. MATHUR ( Alternote )

Strar B. CUNNINQUAM The General Electric Co of India Private Ltd, Calcutta SHRI D. K. Das ( Alternate )

SARI D. S. Dos~r Bajaj Electricah Ltd, Bombay SHRI S. u. $&ioJWAXI (Afternote)

SHW T. S. GILL Central Public Works Department ( Architect Wing), New Delhi

SRRI M. P. GUPTA Philips India Ltd, Calcutta SHRI P. N. SRINIVASAN (Ahrnnte)

SHRI H. N. JAQTIANI Directorate General Factory Advice Service & Labour Institutes ( Ministry of Labour Employment &

SHRI D. M. JAMINI~AR Rehabilitation )

The Bombay Electric Supply & Transport Undertaking, Bombay

SHRI H. B. NAIK ( Altcrnatc) SHRI A. MITRA

SHRI J. N. VA2 ( Alternntc ) Directorate General of Supplies & Disposals, Sew Delhi

SHRI B. K. MUKAERJEE National Test Hotlse. Calcutta SHRI T. K. KUNnU (,Altemntc )

SHRI J. R. NAHAR SHRI JAYANT R. PARI

The Premier Lighting Industries Private Ltd, Bombay Hindco Lighting Industries Ltd, Bombay

( Continued on page 2 )

BUREAU OF INDIAN STANDARDS MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG

NEW DELHI 110002

Page 6: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

Members R$WWlti?lg

SRRI S. S. RACHAVAN Engineer-in-Chief’s Branch, Army Headquarters, New Delhi

SARI K. S. SARI&A SHRI S. SEN

National Physical Laboratory ( CSIR ), New Delhi

SERI H. SINHA ( Alternnte ) Bharat Electrical Industries Ltd, Calcutta

SARI H. SINAA Illuminating Engineering Socie:tl; of India, Calcutta SHRI K. K. ROHATCI ( Alternnle )

SFRI S. P. TALWAR Crompton &eaves Ltd, Bombay SHRIHARBAJAN SINOH (Alkmat~)

SRRX Y.S. VEBEATESWARAN, Director ( Elec tech 1

Director General, IS1 ( E.x-o,~cio Member )

SHRI T. RAJARAMAN Deputy Director ( Elec tech ), IS1

2

Page 7: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

Indian Standard CODE OF PRACTICE FOR INTERIOR ILLUMINATION

PART III CALCULATION OF COEFFICIENTS OF UTILIZATION BY THE BZ METHOD

0. FOREWORD

0.1 This Indian Standard (Part III ) was adopted by the Indian Standards Institution on 3 December 1968, after the draft finalized by the Illumi- nating Engineering Sectional Committee had been appro:ved by the Electrotechnical Division Council.

0.2 A series of standards on interior illumination is being drawn up and this is the third in the series. This part covers the calculation of coeffi- cients of utilization based on BZ Classification. Part I of this standard covers the principles of good lighting and aspects of design and Part II deals with the schedule for values of illumination and glare index.

0.3 This new method for calculating coefficients of utilization known as British Zonal Method is based on a system of classifying the downward light distribution from lightin, u fittings known as BZ Classification. The basis for the new British Zonal Method is theJones and Neidhart Method of computing coefficients of utilization published in America in 1951. The advantages claimed for this method are that they give more accu- rate designed data, that they are more comprehensive, are produced on a more logical basis and are consistent so that accurate interpolation can be made.

0.4 The coefficients of utilization are derived by applying data calculated from the light distribution curve of the fitting to the tabulated data given in this standard. Twn procedures are given.

0.4.1 The first is the full British Zonal Method which enables coefficients of utilization tn be calculated precisely for any symmetrical light of distri- bution. It is more applicable to the specialized in the photometric laboratory than to practising lighting engineer who will usually rely on the specialist to give him the information he requires.

0.4.2 The second is the simplified British Zonal Classified Method. This relies on the manufacturer providing basic data for his fitting.. If this information (BZ classification and upward and downward light out

3

Page 8: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

put ratios ) is available the coefficients of utilization for particular installa- tion can be calculated by the lighting engineer quickly and simply. The result is not as precise as that given by the full method but it is amply accurate enough for most commercial purposes.

0.5 In preparing this standard, assistance has been derived from I.E.S. Technical Report No. 2. The calculation of Coefficients of Utilization, The British Zonal Method published by the Illuminating Engineering Society, London.

0.6 For the purpose of deciding whether a particular requirement of this standard is complied with, the final value, observed or calculated, express- ing the result of a test, shall be rounded off in accordance with IS : 2-1960*. The number of significant places retained in the rounded off value should be the same as that of the specified value in this standard.

1. SCOPE

1.1 This standard ( Part III j covers the calculation of coefficients of utiliza- tion based on BZ Classification.

2. TERMINOLOGY

2.0 For the purpose of this standard; the following definitions, and defini- tions given in IS: 1885 (Part Xl-I/see 2)-19687 shall apply.

2.1 Downward Light Output Ratio (Abbreviation DLOR, Symbol n”) -The ratio of the downward flux emitted from the fittings to the total lamp flux.

2.2 Upward Light Output Ratio ( Abbreviation ULOR, Symbol n’ ) - The ratio of the upward flux emitted from the fittings to the total lamp flux.

2.3 Direct Ratio (Abbreviation DR, Symbol d) --The proportion of the total downward flux from a conventional installation of lighting fittings which is directly incident on the working plane.

2.4 Lower Flux Utilance (Abbreviation LFU, Symbol 11” ) -The proportion of the total downward flux from the fittings which reaches the working plane, some directly and some after inter-reflection.

2.5 Upper Flux Utilance ( Abbreviation UFU, Symbol p’ )-The proportion of the total upward flux from the fittings which reaches the working plane, after inter-reflection.

*Rules for rounding off numerical values ( revised ). tElectrotechnica1 vocabulary: Part XVI Lighting, Section 2 General illumination,

lighting fittings and light for traffic and signalling.

4

Page 9: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the working plane, some directly and some after inter-reflection, to the total flux from the lamps.

2.7 Upward Coefficient ( Abbreviation UC ) -The ratio of that part of the upward flux from the fittings which reaches the working plane after inter-reflection, to the total flux from the lamps.

2.8 Coefficient of Utilization (Abbreviation CU ) -The ratio of the total flux which reaches the working plane to the total lamp flux.

2.9 Utilance (Abbreviation and Symbol U) -The ratio of the total flux which reaches the working plane to the total flux emitted from the fittings.

2.10 Mounting Height ( Symbol H, )-The height of the fittings above the working plane.

2.11 Suspension Length ( Symbol H, ) -The height of the ceiling above the fittings.

2.12 Spacing ( Symbol S ) - The disthnce between rows of fittings in square arrangement.

2.13 Room Index (Abbreviation RI, Symbol k,) -An index relating to the shape of a rectangular interior, according to the formula:

I‘. 11. ” = (L + IITj. H,,,

where L and 11’ are the length and width rcspertiv+ of the interior, and H,, is the mounting height.

2.14 Cavity Index ( Abbreviation CI, Symbol k,.) -An index relating to the shape of the interior above the level of the lighting fittings, according to the formula:

k, = ,,.,,i”;$;. H, = kr 2

for regular rectangular rooms.

SECTION I GENERAL METHOD OF CALCULATION

3. BZ METHOD

3.1 Basis of the BZ Method-The BZ method can be stated by the equation:

cu = u”.n” + Il’Jz’

or in abbreviations rather than symbols:

CU=DC +UC = LFU x DLOR + UFU x ULOR

The downward and upward light output ratios are obtained from the photometric data for the fitting. The values of the lower

5

Page 10: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3616 (Part III)-1968

flux utilance are read from Tables 1 to 4 accordmg to the values of the direct ratio (see 3.2), room index and the reflection properties of the room surfaces. The values of the upper flux utilance are read from Table 5 according to the values of the room index and the reflection properties of the room surfaces.

3.2 Calculation of Direct Ratio -For any given fitting and spacing or height ratio, the direct ratio depends only on the shape of the polar curve in the lower hemisphere and on the room index of the interior in which the fittings are installed.

Direct ratios are obtained for each room index bv a calculation using zonal multipliers, very similar to the zone factors which are traditionally used for calculating the total flux represented by a polar curve. The derivation of the zonal multipliers tabulated in Table 6 is as follows.

a) As a convention, a regular square arrangement of fittings is assumed, at a uniform spacing/mounting height ratio and at one- half of the normal spacing from each of the walls of a square room of given room index.

b) For each fitting location, the proportion of the Aux in each 10 deg zone in the lower hemisphere which is directly incident on the working plane was calculated and the results were averaged for each zone. These average figures are the zonal multipliers.

c) The calculation was repeated for a range of room indices from 0.6 to 5.0 at each of a range of S H,,, ratios from 0.5 to 1.5 and the results are given in Table 6.

The zonal multipliers have thus been derived mathematically and are dependent only on the <geometry of the room and the layout of the fittings.

The calculation of the direct ratio is the only detailed task in the application of the British Zonal Method or in the determination of BZ Classification for the BZ Classified Method. It is convenient to use a work sheet as given in Table 7. For each 10 deg zone in the lower hemisphere, the product of the actual flux from the fitting in that zone and corresponding zonal multiplier is calculated and these products are added; the sum gives the total flux from the fitting which is directly incident on the working plane. This sum, divided by the total downward flux from the fitting gives the direct ratio for the particular room index and S/H,,, ratio. An example is given in 6.1.

Zonal multipliers may be used for linear sources, su(,h as fittings with tubular fluorescent lamps, provided that the polar cnrve used is the true mean distribution.

6

Page 11: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the
Page 12: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

Room INVtX (4)

TABLE 1 LOWER FLUX UTILANCE: WALL WEPLFCTlON FACTOR 50 PERCENT - Chtd

EOFEC- TlVlC

CEILINQ REPLEO- TION

FACTOR PERCENT

-

DWELT RATIO DIKECT RATIO

.l .2 .3 .4 .5 -6 .7 .8 .9 1.0 .l .2 .3 .4 .5 I

$6 .7 .8 .9 I.0

L.ower Flux Utilance for 10 Percent Reflection

I Additive Correction to LFU for 30 Percent

Factor of Floor or Working Plane Reflection Factor of Floor or Working Plane

2.5 2 ‘62 ‘70 .77 ‘85 ‘91 .98 l-05 6 6 9 10 10 ‘59 ‘67 ‘75 ‘82 90 ‘97 l-03 4 4 6 7 8

I I

3’0 -63 *71 *78 ‘85 -92 99 1’05 10 10 12 00 .60 $8 *75 .83 ‘90 .97 l-04 6 7 8

-71 ‘79 ‘86 ‘93 ‘99 1.05 9 9 10 11 12 14 *68 ‘76 .83 ‘90 .97 l-04 4 67 8 8 9

-72 .79 *87 .93 1’0 1.06 9 10 10 12 12 14 .69 ‘76 -84 ‘91 ‘98 1.04 5 77 8 8 10

Page 13: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

TABLE 2 LOWER FLUX UTILANCE: WALL REFLECTION FACTOR 30 PERCENT

(Clause 3.1 )

Room INDEX ( k,)

1

-

EFFW- TIVE

CRl&lNQ

I~FLEC-

TION

Famon PERCENT

iz 30

-

DIRECT RATIO

.I .2 .3 .4 .5 .G .7 .8 .9 1.0

Lower Flux Utilance for 10 Percent Reflection Factor of Floor qr Working Plane

~18 .27 .36 46 a55 $64 .73 .83 .92 1.01 .I8 -27 ‘36 46 .55 .64 .73 .82 .92 1.01 .17 .26 .36 .45 ‘55 .64 .73 .82 .91 1.01

: / .I9 .I9

/ 18

,28 29 .38 ,38 .47 .47 .57 .56 .66 .65 .75 .74 .84 .83 .92 .92 1.01 1.01

30

!.

.28 ,37 46 .56 *65 .74 .83 .92 1.01

70 .30 .39 .49 .58 .67 .75 .84 .93 1.02 50 .29 .38 48 .57 %6 .75 .84 .93 1.02 30 .28 .38 .47’. .56 .65 .74 .83 .92 1.01

1 pi -

-

.l ,2 .3 .4 .5 .6 .7 .8 .9 1.0 __~. __ _~ ~~_. ~.

Additive Correction to LFU for 30 Percent Reflection Factor of Floor or Working Plane

: 1 1 1 1 1

0 :,;t* f : 11

11 11 23

:,A 11 11 22 11

1 1 1 t 1 1

1 1

.-.__

2 3 3 2 2 2 1 1 1

3 3 3 2 2 2 2 2 2

Page 14: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:

3646(P

artIII)

-1968

——

——

I—

Page 15: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

TABLE 3 LOWER FLUX UTILANCE: WALL REFLECTION FACTOR 18 PERCENT

ROOM INDEX (k,)

-

1

EFFXC-

TIVE CKLLLNU REFLEC- TION

FACTOlt PERCENT

0.6

1.0

1.25

1.5

I I

-

70

z

___-.-

70 50 30

:z 30

-

-

-

L

_-

-!_

( Chuse 3.1 )

1,owcr Flux Utilancc for 10 Wrcrnt ReHrction Additive Correction to I,FU for 30 Pm’ccent Factor of FIoor or Working Plane :

I Reflection Factor of Floor or Working Plane

.]2 ,22 .32 .42 .51 .61 .71 .81 91 l+Kl ’ 0 0 0 1

.I:! .22 .32 .42 .51 .61 .71 .81 91 I+0 ) 0 : .12 .22 .32 .42 .51 .61 ,71 .81 ,91 I*00 i 0 0 : : : 8 8 : 8 8 0 0 0 0 0

.I2 .22 .3’1 .9’L .52 .62 .72 .81 ,91 I.01 0 .12 .22 .32 .+2 .52 .62 71 +I1 .91 I.01 0

:: :, 1 1 I 1 t 1 1

.I” .22 .3y .42 .52 .61 .71 .n1 .91 1m 0 0 0 : :: z:, OL I

’ .23 .:?3 43 .52 .62 .72 .82 .91 I.01 I

,23 .33 .43 .52 .62 .72 .81 .91 1.01

1 1 1 1 I 1 2 ;

.22 .32 .42 .52 .62 -71 -81 .91 1.01 : 0 8l!l A:,:, ; 0 1 ._~ ---__--_

.23 .33 43 .53 .63 .72 .82 +X2 1.01 1 1 112 2 2 3

.23 .33 -43 53 .62 .72 .82 .91 I.01 0

.22 .32 .42 .52 %2 .72 .81 .91 I.01 0 80:,:,1,, :, 1122

I .34 .43 .53 .63 .73 *82 .92 I.02 1 22 22 3 3 4 .33 -43 .53 .63 .72 .82 .92 I.01 .33 -43 052 ,62 .72 .81 .91 1.01 (

ll A:, 11 2 2 1 ; ; ( Continued )

Page 16: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

TABLE 3 LOWER FLUX UTILANCE: WALL REFLECTION FACTOR 10 PERCENT - Cmtd

gl;:: 2 .a ., .* .3 .4 .5 .(i j .8 .I) ,.(, / .I .2 .3 .4 .5 .6 ., .8 .y 1.0

TIOS

Facm)it PERCBX~ Jmwer Flux Utilance for IO Percent Kdlcction Additive Correction to l.FU for 30 Percent

Factor of Floor or Working Plane Jleflection Factor of Floor or \Vorking Planr

- -- --I-

2.0

K 2.5

70 .34 =%‘I .54 .64 .73 .83 .93 I.02 50 .34 .43 .53 .63 .73 .83 .I):! 1.02 30 ,33 ,43 ‘-52 ,62 .72 .82 .91 1.01

.45 .55 .6.5 .74 .84 .93 1.03 44 .54 .64 .73 .83 .93 1.02

30 .43 .53 .63 .72 .82 .92 1.01

70 .45 ,55 .65 .75 .84 .94 1.04 50 .45 .54 .64 .74 .83 .93 I.03

Qo j .43 .53 .63 .73 .82 .92 I.02

4.0 70 .55 .65 .75 .85 .95 1.04 5 7 8 IO 50 .54 .64 .74 .84 93 I.03 3

; 7 4 5 6 7

30 ..53 .63 ,73 .83 .92 I.02 2 JI 7 4 5 6

-

2 2 2 3 4 4 4 6

:, 22 J 1 2 1 2 1 2 2 3 2 4 3

~___ ___-___

2 3 4 4 5 6 7 2 2 2 3 3 4 5 11 22 334

z 3 :< 4 3 5 3 6 4 5 7 5 7

I 2 2 3 3 4 s

-.

5.0 70

/ .56 ,66 .76 .85 ,95 I.05 0 7 9 10 II

50 .54 .64 .74 .84 .94 I.03 30 1 .53 .63 .73 ,83 92 I.02 3

Page 17: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:

3646(P

artIII)

-1968

13

Page 18: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

TABLE 4 LOWER FLUX UTILANCE: WALL REFLECTION FACTOR 0 PERCENT-Conld t:

ROOM INDEX

(k,)

2.0

.+ 2.5

5.0

EFFEC- TIVE

CEILINQ REFLEC-

TION FACTOR PERCENT

__-

:i 30

zi 30

DIRECT RATIO

*l ,2 .3 .4 .5 .6 .7 .8 .9 I.0

Lower Flux Utilance for 10 Percent Reflection Factor of Floor or Working Plane

.32 .42 -52 .62 .7:: .81 .92 1.02

.31 .41 .51 .61 .71 .81 .91 1.01

.30 40 .50 .60 .70 .81 .91 1.01

-

.32 .42 .52 .62 .72 .82 .92 1.02

.31 .4l .51 .61 ,71 .82 .92 1.02

.30 .40 .51 .61 .71 .81 .91 1.01

DIRECT RATIO %

.I .2 .3 ,4 .5 .6 .7 .8 .9 1.0 G Y

Additive Correction to LFU for 30 Percent I

Reflection Factor of Floor or Working Plane 5: zz

: 00 00 12 2 3 3 3 4 4 0 00 :,l 123

___~ .__ _ ~_~~~__~. _.~

0” 1 1 23 2 3 456

0 :,:, 12 2” ; “;

:: .41 .42 .51 .52 .63 .62 .73 .72 .82 .82 .93 .92 1.04 1.02 : 2’23 23 557 4 4 5 30 .40 .51 .61 .71 .81 .92 1.02 00 12 2 3 4

:: .53 .51 .62 .63 .72 .73 .83 .83 .94 .93 1.04 I.03 2 2 3 3 4 ‘1 4 5 6 5 6 7

30 .51 .61 .71 .82 .92 1.02 112 3 4 4

$j .53 .51 .63 .62 .73 .72 .83 .83 ?M .93 1.05 1.03 3 3 4 7 9 9 9 i

30 .51 .61 .71 .82 .92 1.02 1 3 : :

Page 19: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III) - 1968

TABLE 5 UPPER FLUX UTILANCE

i Cl0rr.w 3.1 )

EFFEC- REFLECTION FACTOR OF FLOOR REFLECTION FACTOR 01 FLOOR

10 PERCF.NT 30 PERCRNT TIVE

ROOM CEILINQ INDEX REFLEC- Reflection Factor of Wall Reflection Factor of Wall

( kr ) TION 50% 30% 10% 0 50% 30% 10% 0

FACTOR PERCENT Upper Flux 1Jtilance

0.6 I :I: I .23 .I7 .I2 .09 .24 .I7 a13 .I0 .16 .12 .0a .06 .I7 .I3 .09 .a7

30 W m .05 .04 . IO m .06 .05

.9 1 .24 .20 .I7 I .32 .25 .20 ,I7 0.8 .22 .I7 .I3 .I8 .I4 .I2

.I2 .lO .08 .I1 .09 .08 ~ ~~ .37 .30 .26 .22 .39 .31 .2F .23

1.0 .26 .2’ .18 .16 .27 ,23 .I9 .I7 .I4 .I2 .I0 .n9 .I5 .14 .I2 .I1

.43 .37 .31 .28 .I6 .3a .32 .29 I.25 .30 .26 .22 .20 .32 .27 .24 .22

.I7 .I4 .I2 .I1 .I8 .I5 .I3 .12

I 70

I .47 .41 .36 .33 .51 .43 .3a .34

1.5 50 .33 .29 .26 .24 .35 .30 .27 .25 30 .I9 .I.5 .I3 .13 .21 .I7 . 1.5 .14

I :I: I .53 .48 .44 .41 .5a ..51 .46 .43 2’0 .37 .33 .31 .29 .39 .35 *32 .30

30 .20 .17 .I5 .I4 / .22 .I9 .I7 .I6

..57 .40 .21

%O .41 .22

.53

.37

.19

.56

.39

.20

.49

.34

.I1

.52

.36

.I8

,47 .Y3 .lti

.50

.35

.17

.63 .42 .23

.67 *45 .24

.57 .39 .21

.61

.41

.23

.52

.36

.19

.56

.39

.21

:z .ia

.54

.37

.20

I ;?I I .63 .61 .57 .56 -71 .67 .62 *60 4.0 :z 42 .39 .38 .48 .45 .43 .41

30 .21 .I9 .18 .25 .24 .22 .21

*66

:t;

*60 .59 .74 .70 .66 .65

5.0 .45 .42 .41 -49 .47 ‘45 .24 .22 *20 .I9 -27 .25 .23 :z

15

Page 20: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

I- SPACING/ HEIGHT RATIO

0.5

0.75

l-0

/

.-

-

I

TABLE 6 ZONAL MULTIPLIERS

( Clnurc 3.2 )

~NQI:LAR

ZONE DEGREE

O-10 !O-20 20-30

30-40 40-50 50-60

60-70 70-80 80-90

O-10 10-20 20-30

30-40 40-50 50-60

60-70 70-80 80-90

O-10 10-20 20-30

30-40 40-50 50-60

60-70 70-80 80-90

l-

ROOM INDEX ( k, )

0.6 0.8 1.0 1.25 1.5 2.0 2.5 3.0 4.0 5.0

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 .78 .84 .87 90 .91 *93 .95 96 .97 .97 ..!I2 .63 ‘70 .75 .79 .84 .87 90 -92 94

.39 ‘53 .61 .68 .73 .80 au4 ‘86 ‘90 *92

.13 ‘31 *43 .53 .60 ‘69 ‘75 *79 *84 .87 - ‘10 *24 ‘36 ‘45 .58 ‘65 ‘71 -78 *82

- - .02 ‘11 -22 ‘38 -49 .56 ‘67 *73 - - - - *Ol %I6 .I4 -25 - - - - - - -. _ .iY

.50 *Ol

1.0 1.0 1’0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 t:: 1.0 1.0 1.0 1.0 .52 .63 .71 .77 *81 .85 .88 90 .93 94

- :$ :g

.64 -70 .77 .81 .84 .88 -91 - .57 ‘64 -72 .78 -81 .86 - .08 ,23 .35 44 .56 .65 *71 .77 :E

-- - - al2 -23 ‘39 49 .57 -67 .73 - - - - .Ol .06 .14 *25 40 350 ------___ .02

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1’0 1.0 1.0 1.0 1.0 .84 .88 90 .92 94 .95

.23 *41 *52 .61 ‘68 *76 - *30 942 .52 *59 .69 - - .26 *38 ‘48 ‘60

: :g ::; 1’:; ;:i ,96 *97 '98 98

*80 -84 .88 *75 *79 *84 1: ‘68 .72 *79 -83

- - .Ol .12 *22 *38 49 *56 $6 ‘71 - - - - - *05 .I5 ~24 40 ‘50 ----- - -- - *Ol

( Continued 1

16

Page 21: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

TABLE 6 ZONAL MULTIPLIERS - Cm&

SP4CINO

HEIGHT RATIO

1.25

1.5

IN~WJLAR ROOM INTIEX ( k, )

ZONE DEGREE

0% 0.8 1.0 1.25 1.5 2.0 2.5

O-10 IO-20 20-30

30-40

tit:

60-70 70-80 80-90

O-10 10-20 20-30

ii2 50-60

60-70 70-80 80-90

1.0 1’0 1-o 1.0 1.0 1.0 1.0 1.0 l-0

*41 .56 *64 - -24 .35 - .I6 .28

- - - -, - - - - -

1: 1.0 1.0

.O 1 .o

*72 .76 46 -54 .39 .47

.lO .I9 - - -. -

I.0 1.0 1.0

1.0 1.0 1.0 1.0 l-0 1.0 1.0 1.0 1.0 I.0 1.0 I.0

40 .85 .88 -91 .92 - .14 -28 .16 .55 - - .22 .3? .42

- - .05 .14 .24 -----

1.0 1.0 1.0 1.0 1.0 1.0

-83 .87 .66 ~72 .59 .67

.39 *52 -05 .I4 - -

1.0 . 1.0 i.0” I.0 1.0

:g .72 .95

.55 -64

40 .50 a4 .14

-- -

3.0 4.0 5.0

1’0

;:;

‘89 .77 .72

.58 .25 -

1.0 I.0 1.0

:F .69

:z -

1-o IX 1-o 1’0 1.0

.91 .93

.82 .86

.79 a83

:g -73 .51 - -01

.____~ _

1.0 1’0 ::o” 1.0 1.0

-97 *83 :g -76 .81

-67 *73 -40 *51 - SO1

17

Page 22: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1966

3.3 Calculation of Room Index- As indicated in 2.13, the room index is the ratio which relates the plan dimensions of the whole room to the height between the working plane and the plane of the fittings.

The formula for room index is restricted to a rectangular room, neglecting any small departures from regular shape.

RoomIn;Xe(k.) = cLt*;i)eH,

L = overall length of room, IV = overall width of room, and

Hm = mounting height of fittings above working plane.

3.4 Lower and Upper Flux Utilance for Ceiling-Mounted Fittings - The values of the lower flux utilance and upper flux utilance for ceiling- mounted fittings can be read directly from Tables 1 to 5 which are based on strict mathematical integration of the direct and inter-reflected light for a working plane of 10 percent average reflection factor.

Tables 1 to 4 relate to four different values of the average reflection factor of the walls, and in each table the lower flux utilance shall be read for the appropriate values of the room index, ceiling reflection factor and direct ratio. Correction terms are given for use if the working plane has an effective reflection factor of 30 percent.

Since the whole of the upward light from ceiling-mounted fittings falls on the ceiling, the full range of factors which affect the upper flux utilance can be given in a single table ( Table 5 ).

3.5 Lower and Upper Flux Utilaace for Suspended Fittings --Figure 1 and its caption illustrate the principle adopted in this standard for treating the reflection of light from the ceiling. The inter-reflection calculations are made only in the space between the working plane and the plane of the fittings; the space above the fittings is replaced by an ‘equivalent ceiling ’ which has an effective reflection factor less than that of the actual ceiling.

3.5.1 7%e Cuvi(~~ Method- It can be shown that the light lost by absorption within the space above the plane of the fittings, known as the ‘ ceiling cavity ‘, is the same as that which would be lost on an imaginary ceiling at the same height as the fittings when this equivalent ceiling has an effective reflection factor given by the following formula:

where

Re = A,&

AeRafAt (1-K)

& = effective reflection factor of the equivalent ceiling, A, = plan area of ceiling, R. = average reflection factor of all the actual surf&es within

the ceiling cavity, and At = total area of all surfaces within the ceiling cavity.

18

Page 23: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the
Page 24: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

As in the Original Standard, this Page is Intentionally Left Blank

Page 25: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

CEILING CAVITY-

,-WORKING PLATE \

A-_-----____

f

-+ Hs

-1 7”

1 LFLOOR CAVITY’

IA Ceiling-Mounted Fittings IB Suspended Fittings

FIG. 1 THE CAVITY METHOn

This formula applied to cavities of any shape or contour if they are reasonably uniformly bright and if the span of the cavity does not greatly exceed the aperture of the cavity. The average reflection factor ( Ra ) of the actual surfaces should be carefully estimated or measured, particularly if the cavity height is great or the lighting is mainly indirect.

can For the particular case of regular rectangular rooms, the above formula be simplified by using the Cavity Index as follows:

Cavity Index (k,) = (Ltr)_ HS=s. $” kr

Effective reflection factor of

equivalent ceiling ( Re ) =kc + 2RF;k’_ rc, )

Table 8 gives the effective reflection factor of the equivaiant ceiling for a range of values of the cavity index (kc) and of the average reflection factor of the cavity surface (IZO ).

The cavity index may also be used to estimate tk- average reflection factor of the surfaces within a simple rectangular cavity:

R a = ke.Re+ 2Rw kc + 2

where

R, = is actual reflection factor of ceiling, and

RW =: is actual reflection factor of upper walls.

21

__

Page 26: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

3.5.2 Determination of Lower and Upper Flux Utilance --The values of the lower Aux &lance and upper flux utilance for suspended fittings can be read directly from Tables 1 to 5, using the effective reflection factor of the equivalent ceiling derived from Table 8.

TABLE 8 EFFECTIVE CEILING REFLECTION FACTOR

AVERAGE REFTXCTION FACTOKOF Ac~uar, Cavrm SVRFACES

CEILIIW CAVITY INDEX (kc 1

30 40 5;PERcENT)60

70

Effective Reflection Factor of Equivalent Ceiling ( Percent )

80

:

9 5

f

f :: 20

44 54

6°F 62

63 65

:; 68

3.6 Calculation of Coefficient of Utilization -The full Drocedure of

the BZ

a)

b)

c)

d)

e)

Method is as follows:

Calculate the room index (see 3.3) for the particular interior.

Calculate the direct ratio (see 3.2 ) for this room index from the polar curve or flux distribution data for the fitting, using the zonal multipliers appropriate to the particular S/H, ratio. A work sheet is shown in Table 7.

Calculate the effective reflection factor of the equivalent ceiling ( R, ) for suspended fittings ( see 3.5.1). Data are given in Table 8.

Read the lower flux utilance from the appropriate section of Tables 1 to 4, using the actual reflection factor of the ceiling for ceiling- mounted fittings and the equivalent reflection factor ( Rc) for suspended fittings.

Multiply the lower flux utilance by the downward light output ratio of the fitting, to give the downward coefficient.

22

Page 27: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

f)

R)

h)

IS:3646 (Part IIr)d1968

Read the upper flux utilance from Table 5, using the actual reflection factor of the ceiling for ceiling-mounted fittings and the equivalent reflection factor ( Rd) for suspended fittings.

Multiply the upper flux utilance by the upward light output ratio of the fitting, to give the upward coefficient.

Add the downward and upward coefficients to give the coefficient of utilization.

4. THE APPLICATION OF THE BZ METHOD

4.1 Conventions -The zonal data are strictly valid only for fittings with a light distribution which is symmetrical or nearly symmetrical about a vertical axis and for an installation in which the fittings are equally spread along and across the room (in square arrangement ) with the outer fittings spaced away from the walls at one-half of the spacing from fitting to fitting.

Such precise symmetry is unlikely to occur often in practice but small deviations from complete symmetry will not seriously affect the accuracy of the calculations.

4.2 Calculation of Effective Spacing/Height Ratio-For general lighting layouts with either symmetrical or elongated fittings, the effective spacing/height ratio can be obtained on the basis of the floor area for each fitting.

Effective S/Hm = $ m J Jv

where

AI= total floor area, and

N = number of fittings.

For elongated sources mounted in continuous or nearly continuous lines, the effective spacing S can be taken as the distance between the lines.

4.3 Non-Conventional Arrangement of Fittings -The British Zonal data do not apply strictly to the special case of a known layout in which the outer fittings are very close to the walls. Nevertheless, this situation is often encountered and the following procedure will give a reasonably accurate results:

a) Calculate the room index (see 3.3) for a room enlarged so that the fitting-to-wall spacing is one-half of the fitting-to-fitting spacing,

23

Page 28: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

I3:3646(Part III)-1968

b) Calculate the coefficient of utilization of this enlarged room, and

c) Multiply the value thus obtained by the ratio

Perimeter of actual room Perimeter of enlarged room

to give the actual coefficient of utilization for the actual installation.

Alternatively, it may be desired to calculate the lamp flux require- ments in terms of the actual distance between the fittings themselves rather than on the average area per fitting. This can be done, that is, the same lamp flux requirement will be obtained, if the coefficient of utilization used is the value calculated for the enlarged room, as in above, multiplied by the ratio

Room index of enlarged room __~~ Room index of actual room.

5.. LUMINOUS CEILINGS

51 Light Output Ratio of a Luminous Ceiling - The formula for the light output ratio of a luminous ceiling, formed by a translucent screen across the whole ceiling cavity, is as follows:

Light output ratio ( r] ) = t i y1” + rj’ .R, )

I -.r.R, where

t= total diffuse transmission factor of the translucent ceiling material and its supporting framework;

‘1” = downward light output ratio of the fittings in the cavity;

YJ’ = upward light output ratio of the fittings in the cavity;

R, = effective reflection factor of the cavity (Table 9 may be used for a simple rectangular cavity, but if the cavity is irregular in shape or includes obstructions, the first formula in 3.5.1 should be used); and

r = total reflection factor of the translucent ceiling material and its supporting framework.

5.2 Utilance for a Luminous Ceiling-The utilance for a uniformly diffusing luminous ceiling extending from wall-to-wall can be read from Table 9.

It is necessary to know the value of the effective reflection factor of the ceiling as installed and this may be obtained from the formula:

Effective reflection factor of luminous ceiling = r $ l’::R * c

24

Page 29: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 196@

5.3 Calculation of Coefficient of Utilization for a Luminops Ckiling - The procedure is as follows:

a) Calculate the light output ratio (see 5.1),

1,) Calculate the effective reflection factor of the ceiling .material ( see 5.2 ) ,

c) Read the utilance from Table 9, and

d) Multiply the light output ratio by the utilance to give the coefficient of utilization.

6. EXAMPLES OF THE USE OF THE BZ METHOD

6.1 Calculation of Direct Ratios -For the mean polar curve shown in Fig. 2, the completed work sheet is shown in Table 10. The intensity values were inserted in the second column and multiplied by the usual zone factors to give the flux in each 10 deg zone, entered in the fourth column. Thezonal multipliers used in this work sheet are those appropriate to a spacing or height ratio of 1.5 which was selected as appropriate to this polar curve., The products of flux and zonal multiplier in each zone were added to give’the total at the bottom, this piocess being repeated for each of the values of room index. The total of the products corresponds to the average flux directly incident on the working plane and the ratio of this to the lower hemispherical flux from the fitting (the total of the fourth column) is the direct ratio, for each value of the room index.

These values of the direct ratio apply only to the particular spacingj height ratio, in this case 1.5; the direct ratios for other S’/H,f, ratios within the range O-5 to l-5 could be calculated irr the same way hy using the appropriate znnal multipliers from Table 6.

Where the actual S/Hm ratio is not known, the calculation should be hased on that recommended by the manufacturer of the fitting; this applies particularly to tahles of direct ratio or coefficient of utilization published in catnlngues and the like.

6.2 Ceiling-Mounted Fittings -The coefficient of utilization is required for a ceiling-mounted installation described by the following data:

Room size 11.3 x 7.3 x 3.28 m

Working plane 0.84 m ahnve floor

Reflection factors:

Ceiling 50 percent

Walls 50 percent actual, hut reduced by openings,

furnishings, etc, to an average of 30 percent

Working plane IO percent estimated.

25

Page 30: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

TABLE 9 UTILANCE OF WALL-TO-WALL LUMINOUS CEILING

( mltu< i.2 )

Roolrr INDEX

! kr)

1.29

PERCICNT ~

70 .38 .:il! .27 .25 50 .37 $32 .27 .2.5 30 .3(i .31 .27 .2.i

.49 .42 .36 .35 e-18 +2 .36 .34

30 .47 .41 .36 .34

70 ..;n .,?I 46 ,43 .5O ,.57 .30 .45 .43 30 ..ic, .49 .44 .42

_______...~ ..__ _~ _ __ 70 / %.5 .57 .52 .50

g 1 :(j” 0 I .56 ..5fi .52 ..i 1 ..50 .49

I .71 .64 .58 .5ti

1.5 ; :i .69 .63 .58 56 30 .67 +i2 .57 .55

.78 .72 .67 .65 2.0 .76 .71 .66 .64

.75 .70 .65 .63

I G I .84 .78 .73 .71

2.5 .82 .76 .72 .70 30 a) .7.5 .71 .7O

70 .87 .82 .78 .56 3.0 50 .85 ,80 .77 .75

30 .84 .79 ‘.76 .74

,92 .8R ,n4 ,112 4.0 90 .fX .83 .81

.88 .84 +2 +0

70 / 95 91 .88 .86 5.0 .89 .87 .86

.88 .86 .85

26

.39 .33 .‘7 .26

.3H .32 .27 .25

.:37 .31 .27 ,25

.51 .13 .37 .36

.50 .42 .36 .34

.48 .41 .3fi .34

.61 ..52 .47 +I

.59 .:il .45 .-I-3

..57 .so .44 .43 ,

.69 .tiO .53 .51

.66 .58 ..52 ..%I 43 .57 .51 ..50

.76 .67 .60 .57

.73 .65 .59 .5ti

.70 m .58 .56

.85 .77 .69 66

.82 .74 %8 .G5

.80 .72 .66 -64

.91 .84 .77 .74

.88 .80 .74 .72

.8.5 .78 .72 .70

.96 .88 +I:3 .79

.91 .84 .80 .78

.89 .83 .77 .77

1.03 97 .91 .87 .98 .92 .88 .8G .9.i +39 .Hfi .84

-.-- 147 I.01 37 .9j--

141 .oti .93 .9? .!)I1 .!I:( .91 .90

Page 31: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (@wt III)-1968 I

TABLE 10 EXAMPLE OF COMPIiETED WORK SHEET FOR THE POLAR cmtvk GIVEN IN FIG, 2

(Clause 6.1 )

DFSCRIPTION OF FITTING I x 8OW FLUORESCENT qIRECT/INDIRECT S/H% RATIO 1.5 I

-

PHOTOMETRIC DATA ROOM INDEX ; '

AV

(‘c”D’,

Zone Factor

’ Zonal FIUX

(JM)

0’6 0’8

ZM Prod ZM Prod

565 0095 54 54 1

560 *284 159 1 159 1 464

-i

542 463 251 1 251

i

1.0 1’25 ) 1’5

i ZM Prod ZM Prot

2 3 I 4 i 5 ZONE

(Des)

0 - 10

10 - 20

20 - 30

30 - 40

2.5

ZM Prod ZM Prod

1

1 464

524 -628 329

491

411

-774 380

*897 ’ 369

270 993 1 268

99 I.058 I 105

27 I.091 1 29

ZM Prod

1 ‘1 ~ - _-.. I

1 464 I 464

*88 290

-28 116

Prod

464

__

323

327

1 1 1

1 464 1 464 1

-

464

1

.94

1 1

I----- -91 300 -92

1

310

251

203

107

4

-

-95 313

-72, 274

-64 t36

-50 134

*14 15

- -

~__ __ -t

1339 1436

-- 596

303

209

-96 / 316 / .97 / 319 / -98

;22

‘05

-

-

40-50 .66

*55

-77 293 *83 315 *86

*69 254 *76 280 -81

‘56 155 ‘67 180 *73

-25 .-26 40 42 -51

81

13

155 298 50-60

60 - 70 64 -lo 196

70 - 80 -

-

- .04

-

- - - I 1’ 53

0 7: - - - 80 - 90 -

1195 964 1101 TOTAL or PRODUOTS I 1944

c I( 0:9f/ 0.62 DIHEOT RATIOS 0.31 0’41 0.50 0.69 0.74

ZM = Zonal Multiplier. Prod = Flux x ZM.

27

Page 32: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

As in the Original Standard, this Page is Intentionally Left Blank

Page 33: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

6d

20.

105'

90'

15'

60'

$5'

FIG. 2 MEAN POLAR CURVE OF A FLUORESCENT LAMP FITTING

f’hotometric Data

Polar curve of the same shape as in Fig. 3

Downward light output ratio 40 percent

Upward light output ratio 25 percent

Spacing or height ratio 1.5

The calculation is as follows:

Mounting height ( Hm) = 3.28 - 0.84 = 2.44 m

Room index (k,) = ( 3V2iy,: 5 z 2.44 = 1.8

Dired ratio (interpolating in work sheet, Table 10) RI = 1.8 DR = 0.66

Lower ,flux utilance ( interpolating in Table 2 ) RIs1.8 DR=@66 LFU=@73

Downward coefficient = 073 x 0.40 = 0.29

29

Page 34: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

Is:3646 (Part m)-1!w8

Upper flux utilance ( interpolating in Table 5) RI = l-8 UFU = O-3 1

Upward coefficient = 0.31 x 0.25 = 0.08

Coefficient of utilization = O-29 + O-08 = O-37

90.

60.

60‘

30' 15' 0' 15' 30'

FE. 3 POLAR CURVES IN THE BZ CLASSIFICATION

30

Page 35: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

6.3 Suspended Fittings- In this example the data are the same as in 6.2, except that the room height is 3.89 m and the fittings are suspended at 0.61 m from the ceiling.

Room index ( k, ) = 1.8, and direct ratio = 0.66 as before. The calculation of the effective reflection factor of the ceiling cavity, above the level of the fittings, is as follows:

Ceiling cavity index ( k, ) = k, x & 1.8 x 2.44

= H 0.61

= 7.2 I

Effective reflection factor of equivalent ceiling (interpolating in Table 8 for actual RF of 50 percent)

CI 7.2 Eff. RF = 44 percent

Lower flux utilance (interpolating in Table 2 as in 6.4)

RI = 1.8 DR = @66 Ceiling RF = 44 percent LFU = 0.72

Downward coefficient = 0.72 x 0.40 = 0.29

Upper flux utilance ( interpolating in Table 5 )

RI = 1.8 Ceiling RF = 44 percent UFU = 0.27

Upward coefficient = 0.27 x 0.25 = 0.07

Coefficient of utilization = 0.29 + 0.07 = 0.36

6.4 Interpolation-The foregoing examples show that two-way or three- way interpolation will sometimes be necessary, particularly in the lower flux utilance Tables 1 to 4 and Tables 12 to 21. The interpolation sheet shown in Table 11 is recommended for use where estimation by mental arithmetic is difficult; a similar sheet may be used for interpolation of the initial ‘glare index’ from Tables 1 to 6,8,9, 12 and 13 of IS: 3646 (Part I)- 1966*. In Table 11, the sheet has been completed to show the interpolation required for the lower flux utilance in the previous example in 6.3.

The figures entered in this sheet show the interpolation for lower flux utilance from Table 2 required for the conditions stated in the example in 6.3:

a) Enter the appropriate values of direct ratio, room index and effective ceiling reflection factor in the middle line.

b) Find the nearest tabulated values of the direct ratio, the room index and the ceiling reflection factor and enter them in the first three columns.

c) Enter the values of the lower flux utilance, for each combination of the above tabulated values, in the fourth column.

*Code of practice for interior illumination aspects of design.

: Part I. Principles for good lighting and

31

Page 36: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3616 (Part III)-1968

d) The first stage of interpolation is between the two ceiling reflection factors.

e) The second stage of interpolation is between the two room indices.

f) The third stage of interpolation is between the two direct ratios and gives the required result.

7. TABULATED DATA FOR THE BZ METHOD

7.1 The tables required for calculation of the coefficient of utilization are as follows:

Table 6 <onal Multipliers

To be used for computing the direct ratios from the average polar curve, for each room index and for several values of the S/Hm ratio. The work sheet is shown in Table 7.

Table 8 Effective Ceiling Rejection Factor

To be used for computing the effective reflection factor of the equivalent ceiling as shown in Fig. 1.

Table 1 to 4 Lower Flux Utilance

To be used for computing the total flux on the working plane from the lower hemisphere based on direct flux given by the direct ratio.

Each table gives data for 10 percent or 30 percent reflection factor for the floor or the equivalent working plane, the figures for the 30 percent condition being given as an additive correction to those for the 10 percent condition.

Table 5 up/h?r Flux Utilance

To be used for computing the total flux on the working plane from the upper hemisphere.

The data in Tables 1 to 5 apply to ceiling-mounted fittings when the actual average reflection factor of the ceiling should be used, and to suspended fittings when the effective reflection factor of the ceiling cavity should be used.

Table 9 Utilance of Wall-to-Wall Luminous Ceilings

To be used in conjunction with the light output ratio of the ceiling installation (see 5.1) and its equivalent reflection factor (see 5.2).

32

Page 37: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the
Page 38: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

.--

TABLE 12 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 1

f ~htlnttse 6.4 )

ROOM INDEX

(k,J

E~FIX- TIVF:

CZXLING REFLlCC- TlON

FACTOR PRKCENT

0.6 70

s: 08

1.0

1.25

1.5

2.0

__-

2.5

3.0

40

5-O

70 50 30

70

_-

.- I 70

z --

E ~- :: 30

70 50 30

2 30

70

z

70 50 30

;: 30

REFLECIYCIX FACTOIC OF Fr.oos REFLFXTION FACTOR OF FLOOR 10 PERCEKT 30 PERCENT

Reflection Factor of Wall

50% 30% 10% 0 I

Refkction Fxtor of Wall 50% 36% 10% 0

Lower Flux Utilance

.63 .58 .54 .53

.62 .58 .54 .53

.62 .58 .54 .53

.73 .68 .64 .63

.72 .67 .64 .62

.71 .67 .63 .62

.80 .75 .72 .71

.79 .i5 .72 *71

.78 .74 .71 .70 -

.85 .80 .77 .76

:g .79 .79 .77 .76 .76 .75

.89 .85 .81 .80

.88 .84 .81 .80 *87 .83 -80 .79

.93 .90 .87 .85

.92 .89 .87 .85

.91 .88 .86 .85

.96 .93 -90 a9

.95 .92 94 .91 :8”9 .g

98 .95 .93 .92

:tz .94 .92 .92 .91 .91 .91

1.00 .97 -96 .98

19”: -95 -95

.97 96 94 -94

1.02 .98 .97

1m 1: .97 .98 -96 .95 12

-

-

I

- .65 .59 .54 .54 .63 .59 .53 .62 -58 :z 53

.76 .69 -65 *63

.74 .68 a .62

.73 .68 .63 *62 _____~ __-.___.

.84 .78 .73 .72

.82 ,77 .73 .71 ,81 -75 .72 .70

1: .82 .83 -79 .78 .77 .?6 -86 .81 .77 .f5

.95 .89 .84 .82 *93 .87 .83 .81 .91 .86 .82 *SO

1.01 .95 .91 :88 .98 .93 a9 .87 .96 .91 a8 .86

1.06 1m 96 1.02 .9n 94 19”; 99 94 .91 90

1.08 1.02 la0 -97 1.03 lal .97 -95 1~00 .96 94 -93

1.12 ::z

1.05 1.01 1.06 ,*Ol 1m 1.03 1.01 .99 *98

1.14 1.11 1.08 1.06

fit 1.03 1.01 1.02 99

34

Page 39: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1866

TABLE 13 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 2

( Clause 6.4 )

0.6

0.8

1.0

1.25

1.5

2.0

2.5

3.0

4.0

5.0

EFFEC- TIVF:

CEILIRC REFLIX- TION

FACTON PERCENT

:?I 30

70

ii

70 50 30

:“o 30

:z 30

70 50 30

70 50 30

70 50 30

z:: 30

:: 30

REFLECTION FACTOROFFLOOR REFLRCTIONFACTOHOFFLOOR 10 PERCXNT 30 PERCENT

Reflection Factor of Wall Reflection Factor of Wall 50% 30% 10% 0

I 50% 30% 10% 0

Lower Flux Utilancc

.5ti ,51 .47 :‘z I -57 .52 .47 .56 .51 .47 .57 .52 .47 :z

.56 .50 .47 .45 .57 .51 .4i -45

.67 .62 .57 .55 ei .61 .57 .55 .65 .61 .57 ..55

.70 .63 .58 *55 a .62 -5; .55 *66 .61 .57 *55

.74 .70 .65 .64 -78 .72 .66 .65

.73 .69 .ti5 .M .76 .71 .66 .64

.72 .68 .65 .63 .74 .69 -65 ~63

~~~ .80 .75 .71 .70 .85 .78 .73 .71 .79 .74 .71 .70 -83 .77 *72 .70 .78 -74 .70 .69 -81 .76 .71 -69

.85 .81 .77 .7fi .91 .85 .79 .84 .80 .76 .75 .89 .83 .78 :;; .83 .79 .76 .74 -87 ‘81 .77 ,74

.91 .87 .83 .81

.89 .85 .83 .81

.88 .84 .82 .81 .99 .92 .87 .95 -89 .85 :z .93 .87 -83 .82

.93 .90 .87 .85 1.02 .97 .92 -89

.92 .88 .86 .85 .98 .93 .89 -87

.91 .87 -85 .84 -95 .89 -87 -86

2 .91 -93

.93 90

-98 96

1% :Zi

90 .89 .89 .88 ,88 +38

34 .93 .92 .92 .91 *91

::tZ .98

la0 *97 -97 94 :z 94 .91 -90

1.10 1.04 l+lO

1.06 1.02 1.01 :Z .98 -95

1.01 .98 .96 *95 l-13 1.10 1.06 -99 -97 ,95

:Z l-07 1.04 1.02 ::g

-98 .95 -93 1.02 1.00 98 -97

35

Page 40: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Port III)-1968

TABLE 14 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 3

(clnurc 6’4)

EFPEC- REELECTIONFACMROFFLOOR REFLRCT~ONFACTOROF FLOOR

IOPERC~NT 30 IWZCENT TIFE p-

ROOM clm.1x0 IXDICC REFLEC-

Reflection Factor of Wall Reflection Factor of Wall

(k,j TION 5oo/

Cl 30% loo/, 0 50% 3(196 loo! 0

FACTOR PERCENT Laum Flux Utilance

.49 -44 .43

-77 :; :E -83

*77 -81 :E -77 -89 *a4 -79 .7a

-82 l+m -86 aa2

E a89

-81 :g -85

.a8 :z

-83

-85 1.04 -85

-85 -84 :E

:z :g :g *91 -87 -86

I 70

I -97 -95 092 90 1.09 1.05 I*00 -95

4-O 50 95 :: :g :g I.03 -95 30 *93 .B

1xJo :z .95 -92

g +99 *!x *93 1.11 l*oR 1-w 1.02

5.0 *97 a95 1% -92 1.05 1.02 +!J +a 30 .95 -93 -91 *91 1.01 -97 -95 94

36

Page 41: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

TABLE 15 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 4

( Clausq 6.4 )

ROOM INDEX

(k, 1

14

1.25

1.5

2.0

2.5

3.0

4.0

5.0

EFPEC- REFTJCCTION FACTOROF FLOOR

I

REFLECTION FACTOR OR FLOOR 10 PERCENT 30 PERCENT

TIVE ___ CElLrNa REFLICC-

Reflection Factor of Wall Reflection Factor of Wall

TION 50% 30% 10% 0 I 50% 30% 10% 0

FACTOR PERCENT Lmuer Flux Utilance

70 .48 42 .38 .3J *49 .43 .38 .37 .47 .42 .38 .36 .4a *43 .38 .36 .4J .41 .38 .36 -48 .42 .38 ~36

70

i:

zoo 30

:% .54 .53 .49 .49 47 .47 .62 .61 -55 .54 .50 .49 49 -47 .59 .53 .49 .47 *SO .54 .49 *47

.66 .60 .54 .53 *69 .61 .55 .65 .59 -54 e.53 .6J .60 .55 -+&i +‘I .58 .54 .52 -65 -59 ,54 .52

70 .72 .65 .61 .59 .76 -62 z: .70 .69 .65 .64 .60 .60 .59 .58 -70 -73

:z :z *65 .61 .61 -58

:i 30

ii 30

.77 .71 -66 .65 .82 .75 %a 66

.75 .70 .66 .79 .73 *67 -65

.74 -69 .65 :z

.76 .Jl .66 +4 .84 .78 .J3 .72 -91 .84 .77 -75

.a1 .J7 .J3 -71 *a7 .80 .75 -73

.79 -75 .72 .70 -82 *77 *73 *71

:i

30

2 30

z

30

70 50 30

.89

.a6

.84

:z .a6

::

.89

.97 *95 .93

.83

.a2

.81

.a6 .a4 -83

.91

.a9

.87

.93

.92 90

.J9

.J8

.77

*a2 .81 .80

.a7 *86 .85

:z .a8

.77

.77

.76

-80 .80 ,79

-85 *a5 .84

.a9 *a8 .a7

*97 .89 -83 *92 *86 *81 *a7 .83 -79

1fIlI .a9 .92 *aa -85 :z .86 $4

l-05 1.00 94 .91

$7 :g .a8

l-09 l-04 1$ci l-03 ?xl .95 *97 -94 -91

37

Page 42: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

TABLE 16 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 5

( clauss 6.4 )

EFFEC- ’ REFLECTION FACTOR 08 FLOOR REFLECTION FACTOR OF FLOOR

10 PERCENT 30 PERCENT TIVE i

Room CEILING-4 INDEX REFLEC-

Reflection Factor of Wall Reflection Factor of Wall

( kr ) TION 50% 30% 10% 0 50% 30% 10% 0

FACTOR PERCENT Lower Flux Utilance

.43 .36 .32 .31 0.6 .42 .36 .32 .30

.41 .36 .32 .30

*56 .49 44 .43 0.8 -55 :z :g .42

.54 .42

.64 .58 -52 .51 1.0 I 2: ! *63 .57 .52 *51

30 *62 *56 .52 .50

1.25 i zl 30

1 .70 -63 .58 .56 .68 -63 .58 .56 .66 -62 -57 .55

.67 .62 .61 1.5 .66 -62 *60

.65 -61 .59

I :8 I .81 .74 .69 .68

2.0 .78 .73 .69 -67 30 *76 .72 -68 -66

I 70

2.5 :i I .85 .79 .74 .72 -82 .77 .73 -72 *80 .76 .72 “71

70 .89 .80 .78 3.0 i!l 1 .87 :z *79 .77

.85 -81 .78 .76

.93 .89 .85 .83 4.0 :: -87 .84 .83

.85 -83 *82 .g5 .91 .88 .86 5.0 i :: I .93 90 .87 *86

30 .91 *a8 -86 -85

-

-

4 ,37 .32 .43 .36 .32 .42 .36 .32

.58 .50 .45

.57 -50 .44

.56 49 44

.67 -59 .53

.65 .58 .53

.63 .57 .52

.74 -66 .59

.71 ~65 .59

.68 .64 .58

.79 .71 *64

.76 -69 .63

.73 .67 -62

.88 .79 .73 .84 .76 .71 -80 .74 -69

.92 .85 .78

.88 .81 .76

.84 .77 *74

.98 90 .85

.92 .86: .82 -90 +J2 .79

1.04 .98 392 .98 .93 *89 .92 -87 -85

1.07 1 .Ol ,97 1.01 .97 -9s .95 90 .88

.31

.:a0

.30

.44

.42

.42

.52 -51 .51

.57

.56 -55

*63 *61 -60

ii: .67

.75

.75 J73

.82

.80

.78

.88

.87 +4

-95 -91 -87

38

Page 43: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

TABLE 17 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 6

( Qause 6.4 )

Roox INDEX i k,)

0%

0.8

1.0

1.25

1.5

-

,

-

EFFEC- RRFIJCCTION FACTOR OF FLOOR RRPJJCCTION FACTOR OF FLOOR

10 PERCENT 30 PERCENT TIPE

Cl?ILlNG REFL.EC- Reflection Factor of Wall Reflection Factor of Wall

TlON 50% 30% IO?/, 0 50% 30% 10% 0

FACTOR PERCBNT Lower Flux Utilance

70 .38 .31 .26 .25 .39 .32 .26 .25 50 .37 .31 .26 .24 .38 .31 .26 .24 30 .36 .30 .26 .24 .37 .30 .26 .24

70 .48 .41 .35 .34 50 .42 .36 .35 50 .47 .41 .35 ,33 .48 .42 .35 .33 30 .46 .40 .35 .33 .47 .41 .35 .33

70 50 I :g .48 .42 ,40 I .58 .49 .42 .47 .42 .48 .42 :;

30 ’ .53 .46 .41 1;; 1 :$

.47 .41 .39

70 .61 .53 .47 .45 .64 .55 .48 .46 50 .58 .52 .47 45 .61 .54 .47 .45 30 .57 .52 .46 .44 .58 .53 4.6 .44

70 ’ .67 .59 .53 .51 .72 .62 ,55 .52 50 .65 .58 .53 .51 .69 .60 .54 .51 30 .63 .57 .52 ,50 .65 .5a .53 .50

70 j

.73 .64 .60 ,58 .80 .69 .63 2.0 50

! .71 .64 .59 57 .76 .67

‘59 .61 .58

30 .69 .63 .58 ,56 .72 .65 .59 .57

1

! 70 / .78 .71 .65 ,63 .85 .76 .69 .65

2.5 3: .76 .70 -65 .62 ; .72 .68 ‘6’ .62 j :!A ::: ::5’ 1:; _ _~ ~~ -___- __

.82 .75 .-IO .68 .89 .79 .73 .71 3.0 .79 .74 .69 ,67 .84 .78 .72 .70

.76 .72 .68 +66 .80 .76 .71 -68

) 70 .a7 .81 .76 .74 .97 .89 .83 .78 4.0 ! 50 .84 .79 .75 .73 .92 .85 .79

1 .77

30 .81 .77 .74 .72 .86 .81 .76 .75 I

5.0 j I

I

5: .91 .87 12 .85 .a3 .81 .79 .78 .78 1.02 .96 .97 .91 .85 .83

30 .86 .81 .77 .77 .91 .85 .80 .79

39

Page 44: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

TABLE 18 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 7

( Clause 6.4 )

- REFLECTION FACTOR OFFLOOR REFLECTION FACTOROPFLOOR

~OPERCENT ~OPERCENT ~________

Reflection Factor of Wall Reflection Factor ofWall 50% 30% 10% 0 50% 30% 10% 0

Lawn Flux 1Jtihuc

EFFEC- TIVE

CEILING REFLEC- TION

FACTOR PERCENT

ROOM INDEX (kr)

-i- - -34 -27 *22 ‘21

‘33 *27 *22 ‘20 -32 -26 .22 .20

;; 30

.35 .2a *22 *21

.34 -27 -22 .20 -33 .27 *22 -20

*45 -36 ‘30 .29 .43 *36 .29 *27 -42 *35 *29 *27

.52 .43 -36 .34

.51 .42 .36 *34 -50 e-12 -35 .33

%O ‘51 .43 .511 49 -42 :z

‘56 48 .42 *39

-66 -56 -62 *54

1: .45 -44

.60 ‘52 -47 -44

.74 *64 ‘56 -52

.70 .62 .55 .52 *67 %O .53 .51

__- ‘31 -71 ‘64 -59 ‘76 -68 ‘61 -58 .72 ‘65 ‘59 ‘57

.a5 -74 064 -80 -73 :iz ‘76 -71 %4 1:;

-93 ‘84 -76 *72 ‘86 -78 -73 ‘70 .81 ‘74 -70 -68

‘96 .89 *a2 -79 ‘90 -84 *7a .75 *a5 ‘79 -74 ‘72

I

r ‘43 .35 .29 .28 -42 *35 .29 -27 .41 .34 -29 .27

70 0.8 ’

;2

.50 .42 ‘36 ‘34

:z -41 .41 -35 .36 ‘33 ‘34 70 50 30

5: 30

I.0

1.25

1’5

2.0

2.5

3.0

4.0

5’0

-!- --

-

‘57 .49 -42 .55 .47 .42 :g

.54 .47 *41 .39

70

3”:

.62 *53 ‘46 ‘44 ‘59 -52 46 ‘57 051 ‘46 :‘z

I

.A_ -

--

-

--

1

:: 30

‘69 .54 ‘52 ‘66 :ti .53 -51 ‘64 *58 .52 ‘50

2 30

.74 ‘66 ‘6o ‘57 -71 .65 ‘59 ‘56 .69 ‘63 ‘58 ‘56

-

-

-

‘77 ‘70 -64 062 .75 ‘69 .63 ‘73 ‘67 -62 :E

ii 30

zi 30

-83 -76 -70 ‘68 -80 -74 -69 -67 -78 *72 %a ‘66

:i 30

‘86 ‘80 ‘75 ‘72 .83 .7a .73 ‘71 -81 -76 -72 ‘70

40

Page 45: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

TABLE 19 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 8

( Clnuse 6.4 )

REFLECTIUN FACTOR OF Fmolt REIWRCTION FACTOR OF FLOOR EFFRC- 10 PEKCENT 30 PERCENT

: TlVE I .~

Rook / CEILINO INDEX i Rmmw- Reflection Factor of Wall Reflection Factor of Wall (b,) / FT~~~, ) 50% 30% 10% 0 __ 50% 30% _ ‘0% 0

0.6

0.8

1 .o

1.25

I.5

-

I :: .3 .30 I ‘24 .24 ‘19 .19 .I8 .17 .32 .31 .25 .24 ‘19 ‘19 *I8 017 30 .29 .23 *19 ‘17 -30 .23 ‘19 -17

z: .41 .40 .33 .32 -26 .26 .25 .24 .43 ‘41 ‘34 ‘33 .27 .26 .24 30 .3Y .32 .26 .24 .40 ‘33 :if > -24

70 .49 .40 .34 .32 ‘51 .41 .34 .32

z:: .4i .4t1 .39 .39 -34 .33 ‘32 .31 ‘47 .49 -40 .40 .34 .33 .3:: .31

70 ..54 .45 .3(3 .37 j ‘57 ‘47 .3Y .38

:I: .52 .50 +4 .4J .38 .37 .35 .3ti .51 .54 :z .38 ..37 .3ti *35

70 ~ .59 .49 .42 .+0 ‘63 .52

50 1

‘41

.56 ‘48 42 ‘40 ‘59 .50 :z 30 ‘53 ‘47 .42 .39 .55 .48 ‘42 :“;r

70 2 . D 50

90

70 3.0 50

30

‘6G ‘56 .50 ‘48 .71 ‘60 ‘52 +8 .G3 .55 .49 ‘47 .67 -58 .51 ‘48 wl .54 .48 ‘46 ‘63 .56 ‘49 ‘47

‘71 .63 ‘56 ‘53 I ‘77 ‘67 .59 .54 ?i8 .61 .55 .52 ‘72 .64 .57 ‘53 ?i5 .59 .54 .52 .67 .61 .55 .53

_

.75 ‘67 .61 .59 .83 .71 ‘65 ‘61

.72 ?i5 ‘60 ‘57 .77 -69 .63 w

.6Y %3 .59 ‘57 .71 .65 .61 ‘5Y

70 .L)O ‘74 ‘ti7 .05 -89 .a1 .73 .68 4.0 50 ‘77 .72 .66 ?i4 ‘83 .76 .70 ‘67

30 .;4 .70 .65 ?i3 ‘77 .i2 .ti7 .66

! 70

I .83 ‘77 .71 .68 .Y3 -85 .77 .73

5.0 .50 ‘80 ‘75 .69 .27 ‘87 ‘80 ,74 .70 Yt) .77 ‘73 .68 ?i6 .82 .75 .71 .68

41

Page 46: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

TABLE 20 LOWER FLUX UTlLANCE FOR CLASSIFICATION BZ 9

( Clause 6.4 )

ROOM INDEX

(k,)

0.6

0.8

1’0

1.25

--

1.5

2.0

2.5

3.0

40

5.0

EFFEC- TIVE

CEILING REFLEC- TION

FACTOR PERCENT

-.

i

:Fl 30

_‘L

2 30

_

-

:: 30

:: 30

70 50 30

70

:

ci 30

REFLECTIONFACTOR OFFLOOR ’ REFLECTIONFACTOROFFLOOR 10 PERCENT 30PERCEXT

Reflection Factor of Wall Reflection Factor of Wall 50% 30% 10% 0 50% 30% 10% 0

/

Lower Flux Utilance

.28 *21 ‘1.5 -13 ‘27 *21 ‘15 .13 -26 -20 ‘15 *I3

-37 -29 *22 *21 -36 -28 -22 -20 -35 -28 -22 *20

‘44 -35 -29 -27 ‘43 -34 -29 ‘27 .42 -34 -28 -26

‘50 ‘41 *34 *32 .48 ‘39 ‘34 -32 ‘46 ‘39 *33 ‘31

*55 .45 .38 -36 -52 ‘37 ‘35 -50

:z .37 -34

-61 ‘51 .44 *42 .58 .50 -43 ‘41 -56 -49 -43 ‘40

-67 .58 ‘51 -48 *64 ‘56 -50 ‘47 ‘62 ‘54 -49 .47

*72 ‘63 .56 ‘53 .69 ‘61 ‘55 .52 $66 .59 *54 -52

*77 ‘69 -62 %O .74 .67 .61 .59 .7: ~65 ‘60 .58

G .80 .77 -73 .71 .65 .67 G 30 *7ci .69 %4 062

42

‘28 .21 .15 ‘13 -28 *21 ‘15 ‘13 ‘27 *20 *15 ‘14

‘39 :zi .23 *22 .37 *22 -20 ‘36 *28 *22 *20

:zz *35 *36 -29 -29 -27 *27 ‘43 -35 ‘28 *26

.53 ‘43 -35 -32 ‘50 ‘41 -34 *32 ‘47 40 *34 -31

-59 *47 -39 *36 .54 ‘46 ‘38 ‘35 -51 44 *38 ‘34

‘66 ‘55 46 -42 ‘6% -52 -45 ‘41 -58 ‘50 44 ‘41

‘73 -62 .54 -68 ‘59 *52 :z

‘64 ‘56 -50 48

-79 -67 -59 ‘55 -73 ‘65 -58 -54 -68 -62 56 -53

-86 -76 .63 *80 ‘71

vi?! .62

-74 G3 -62 -60

90 .81 -73 -68 -84 .76 -70 .66 .78 -72 ‘67 .64

Page 47: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

TABLE 21 LOWER FLUX UTILANCE FOR CLASSIFICATION BZ 10

( Clazrsc 6.4 )

ROOM IP*‘DEX (k,\

0.8

EFFEC- RBFT.ECTTON FACTOT~ OF FLOOR REFLECTION FACTOR OF FLOOR

10 PERCPNT

TI”E _-_ I 30 PERCENT _

Cl.xLI~Q REFLISC-

Rrfktion Factor of Wall Reflection Factor of Wall

TTOY 50% 30% 10% 0 I 50% 30% 10% 0

5: .23 .22 .I6 .16 .lO .lO .08 .08 30 .21 .15 .lO .08

5:: .32 .33 .24 .24 .17 .17 *I6 .I5 30 .31 .?3 .17 .15

_I 70 .39 .30 .23 .22

1.0 i ii - .38 .29 .23 -21 I .37 .28 .22 .20

k.25

l-5

2.0

2.5

3.0

4.0

5.0

I--_, I

70 46 .36 .28 .27 2:: .44 42 .34 .35 .28 .28 .25 .‘6

zi .51 .49 .41 .34 -33 .32 .31 30 .47 :: -33 .30

._

i0 .57 .47 .40 .38 50 .54 .46 .39 -37 30 .52 .45 .39 -36

-.

70 .64 .55 .47 :“o .61 .59 -51 .53 .46 .45

:z -42

70 .69 .59 .52 .50

z: .66 .64 .57 .55 .50 .51 .48 .48 -___.

70 .74 .67 *59 .57

5: .71 .GG .65 .63 .58 .57 .55 .55

70 .78 .71 .65 .62 50 .75 .69 .63 .61 30 .73 .67 .62 -60

43

I

-

_-

-

-23 .16 .lO .08 .23 .16 .lO .08 .22 .I5 .lO al

.35 .25 .18 .17

.33 .25 *I7 .15 032 .24 .I7 *I5

*41 .31 a23 -22 -39 .30 .23 -21 -38 .29 .22 *20

.49 .38 -29 -27

.46 .36 .28 -26

.43 .35 .28 .25

.55 .43 .35 .32 -51 .42 .34 *31 048 40 .34 .31

.62 .51 342 .38 058 ,48 .41 .37 .53 *45 4tJ .37

*70 .59 -49 *65 .56 .48 :g

-60 .54 .45 .43

.76 .63 .53 -52

.70 .61 .54 .50 WI .57 .52 .49

.81 .74 .64 -59

.76 .69 .61 .58

.71 .65 .59 .57

-88 .79 .71 a2 .74 .68 1: .76 .69 .65 .62

Page 48: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

SECTION 2 CLASSIFICATION OF LIGHT DISTRIBUTIONS

8. THE BZ CLASSIFICATION

8.0 The objects of the British Zonal Classification are to define the down- ward light distribution characteristics of lighting fittings, to simplify the calculations of coefficients of utilization for installations of fittings for which the classification is known and to facilitate the initial stages of lighting design by enabling a realistic estimate of the coefficient to be made before the final selection of fittings.

8.1 Basis of BZ Classification-The method of classification is based on the fact that, in any given interior, the direct ratio of the fittings determines the lower flux utilance. The downward light utilization characteristics of lighting fittings can, therefore, be expressed by the relation between their direct ratio and the geometry of the interior and of the installation layout, that is, the room index. Thus, for any particular fitting, a curve that can be drawn relating direct ratio to room index is also characteristic of the downward lighting performance. It is thus possible to evolve a system of classification by producing curves of direct ratio against room index for a range of basic polar distributions and allotting a code number (the BZ number) to each curve. An actual fitting can then be classified by the code number of the direct ratio curve with which its own curve most clearly coincides.

Fig. 3 shows the ten basic polar distributions selected. They are each mathematically derived so as to be,simply and accurately reproducible and they cover the range of beam spreads, from narrowest to widest, likely to be met in practice. For the purpose of classification, each distribution is associated with a spacing or height ratio which is related to the dispersive angle and which was adopted in accordance with the values generally given in manufacturers’ recommendations.

Fig. 4 shows the family of reference direct ratio curves corresponding to the ten basic polar curves, calculated by the zonal multipliers given in Table 6. Table 6 gives the figures from which Fig. 4 was drawn.

6.2 Procedure for Classification - In order to classify a fitting, the direct ratio is computed for the full range of room indices as has been done in 6.1. These values are then either compared directly with the reference values given in Table 22 or preferably by plotting the direct ratio curve on the same sheet as the reference curves (Fig. 4 ). The fitting is then given the BZ number of the nearest set of values or the nearest curve.

As an example of the latter method, the direct ratio curve of the fitting used in 6.1, as illustrated in Fig. 2 and Table 10 is shown in Fig. 5 plotted with the ten BZ reference curves. It will be seen that the curve is closest to BZ 5 up to a room index of I.5 and is closest to BZ 4 at higher

44

Page 49: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

TABLE 22 DIRECT P4TIOS FOR BZ CLASSIFICATIONS

CLASSI- ASSOCIA-

FICA- TED S/H, TION RATIO

BZ 1 BZ 2 BZ 3 BZ 4 BZ 5

RZ 6 BZ 7 BZ 8 BZ 9 BZ 10

-

ii: 1.25 : 1 1.25 : 1 1.5 :1

1.5 :1 1.5 :I 1.5 :I 1.5 :1 1.5 :l

( &use 8.2 )

ROOM INDEX ( k, )

-

O-6 0.8 1.0 1.25 1.5 2.0 2.5 3.0 4.0 50

.528 .625 .696 *742 .786 *835 *866 a890 ,915 .929

.453 .554 .630 -690 ,737 .795 .831 -858 +892 907

.430 .530 .590 .616 ,687 -758 .803 -832 .869 .892

.380 -467 .532 ~582 *630 -701 .750 .781 -824 -852

.313 *411 .490 -548 .595 -663 .713 a750 *796 .833

.244 .327 *391 -444 .494 *560 .612 -654 .708 -742 -202 .271 .326 a380 .432 -497 .552 .594 -652 .692 .174 .240 .296 .351 .395 .456 .510 -557 .613 .657 .135 .I91 .250 -300 347 -415 .472 .520 .581 &625 .085 .140 .I93 ~245 .291 ~361 .42,1 -472 .54O 585

room indices. It will frequently be the case that actual polar distributions will cause the direct ratio curve of a fitting to cross one of the BZ reference curves, but it is unusual for the curve to tinder among them.

The fitting can then he given a stepped classification related to room index and the example in Fig. 5 is classified:

BZ5forRIupto 1.5

BZ 4 for RI greater than l-5

The shorthand form of this classification is : BZ 5/1*5/BZ 4.

Cases may arise where the fitting direct ratio curve is too erratic for simple comparison with the BZ reference curves and in such cases no attempt should be made to apply a BZ number.

SECTION 3 CALCULATION FOR CLASSIFIED DISTRIBUTIONS

9. THE BZ CLASSIFXED METHOD

9.0 The British Zonal Classification of a fitting determines its direct ratio for any given value of the room index. As already indicated, the lower flux utilance in any given interior is determined in turn by the direct ratio of the fittings and it follows that the lower flux utilance can be calculated and tabulated for each BZ class for a wide range of values of the room index and of the reflection factors of ceiiing, walls, and floor. This has been done in Tables 12 to 2 1. The upper flux utilance is handled in the same way as in the Section 1 and the data are repeated in Table 19 for convenience.

45

Page 50: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

833646 (Part III)-1968

o-5

0.L

0.3

0:2

0.1

ROOM INDEX I

0 Z",Z%Z =: z :: 0 0 ;,&I:& (Y ; 4 m

FIG. 4 BZ CLASSIFICATION REFERENCE CURVES

(see also TABLE 6 )

9.1 Calculation of Coefficients of Utilization for BZ Classified Fittings- It may be expected that the BZ Classification and the down- ward and upward light output ratios of a lighting fittings are available from the manufacturer. Alternatively, these data may be obtained from an average polar curve by the methods already described.

The procedure for calculating the coefficient of utilization is then as follows:

a)

b)

Calculate the room index for the particular interior ( 3.3);

Calculate the effective reflection factor of the eqiivalent ( R,) for suspended fittings (3.5.1);

46

ceiIing

Page 51: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (PartIII)-1968

1.0

DIRECT I I I 1 I

I I I 1

’ I

RATIO 825/1~5/82L+----- B2,

0.9 BZ2 BZ3

BZL B25

0.8

BZ6

0.1 827

BZ.3

BZ9 0.6

8210

0.5

0.2

0.1

ROOM INDEX I I

,111, I I I I 0 000rnO 0

o(Doc-4 ul Q =: =: 8 z &.A_> I & & ; - IA

FK. 5 EXAMPLE SHOWING THE BZ CLASSIFICATION OF THE POLAR CURVE GIVEN IN FIG. 2

c) Read the lower flux utilance from the appropriate section of Tables 9 to 18 using the actual reflection factor of the ceiling for ceiling-mounted fittings and the equivalent reflection factor (R,) for suspended fittings;

d) Multiply the lower flux utilance by the downward light output ratio of the fitting to give the downward coefficient;

e) Read the upper flux utilance from Table 22 using the actual reflection factor of the ceiling for ceiling-mounted fittings and the equivalent reflection factor ( R,) for suspended fittings;

f) Multiply the upper flux utilance by the upward light output ratio of the fitting to give the upward coefficient; and

g) Add the downward and upward coefficients to give the coefficient of utilization.

47

Page 52: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS : 3646 ( Part III ) - 1968

9.2 Accuracy of the BZ Classified Method -Tables 12 to 2 1 are derived with no loss of accuracy from Tables 1 to 4 and the only source of error additional to that of the full method is that due to the method of classification. Reference to Fig. 4 shows that the maximum interval between BZ curves, expressed as a percentage of the lower value, occurs with curves BZ 9 and 10 at RI = 0.6, the interval here being approximately 50 percent of the value of the direct ratio for BZ 10. This leads to a 25 percent error in direct ratio at this point if the fitting direct ratio is midway between the values for BZ 9 and BZ 10. The corresponding calculation error in lower flux utilance is considerably less than this due to the compensating effect of inter-reflection.

A comparison between the lower flux utilance tables for consecutive BZ Classifications shows that the maximum error in any practical case due to the method of classification is unlikely to exceed 10 percent and the error in normal lighting practice is unlikely to exceed 5 percent. In view of this relatively high order of accuracy, the BZ Classified Method and data can be used with confidence not only for making preliminary estimates of the coefficient of utilization but also for its final determination when data derived from the full procedure are not available.

10. TABULATED DATA FOR THE BZ CLASSIFIED METHOD

10.1 The data in Tables 9 to 19 apply to ceiling-mounted fittings when the actual average reflection factor of the ceiling should be used, and to suspended fittings when the effective reflection factor of the ceiling cavity should be used.

Tables 12 to 21 Lower Flux Utilance

To be used for computing the total flux on the working plane from the lower hemisphere, based on the BZ Classification.

Each table gives data for ranges of the room index, of the effective reflection factor of ceiling, of the reflection factor of walls and for 10 percent and 30 percent effective reflection factor of the working plane.

‘Table 8 Upper Flux Utilance

To be used for computing the total flux on the working plane from the upper hemisphere.

11. EXAMPLES OF THE USE OF THE BZ CLASSIFIED METHOD

11.1 The coefficient of utilization is required for an installation of suspended fittings described by the following data:

Room size 15.2 x 9.14 x 3.05 m high

Working plane 0.84 m above floor

48

Page 53: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-1968

Reflection factors:

Ceiling 70 percent

Walls 30 percent (effective value after allowing for windows, furnishings, etc)

Working plane 30 percent

Suspension length 0.38 m below ceiling

Photometric data (pro. vided by manufac- turers )

Classification BZ 6

Downward L.O.R. 40 percent

Upward L. O.R. 30 percent

The calculation is as follows:

Mounting height ( Hm) = 3.05 m - 0.84 m - 0.38 m = 1.83 m

Room index (k,) = -(&$&: ,If.,, = 3.1

3.1 x 1.83 Ceiling cavity index (k,) = ---F38p = .

15

Average reflection factor of the surfaces within the ceiling

cavity = k, R, t 2&o 15 X 0.70 + 2 x 0.3

kc+2 =-- _- ~

15+2 = 65 percent

Effective reflection factor of ceiling cavity ( interpolating in Table 9) 62 percent

I.ower flux utilance (interpolating in Table 14 ) 0.79

Downward coefficient 0.79 x 0.4 = 0.32

Upper flux utilance (interpolating in Table 23) 0.54

Upward coefficient 0.54 x 0.3 = 0.16

Coefficient of utilization 0.32 + 0.16 = 0.48

If the actual reflection factor of the ceiling (70 percent) had been used instead of the effective reflection factor of the ceiling cavity (62 percent), the lower flux utilance and upper flux utilance would have been 0.80 and 0.62 respectively and the apparent coefficient of utiliaa- tion would have been O-51. The need to allow for the effect of suspension length is more marked for fittings with a greater proportion of upward light.

49

Page 54: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (PartHI)-

12. THE BZ METHOD AND LIGHTING PRACTICE

12.0 Although the primary reason for the production of the BZ Method is to rationalize the calculation of coefficients of utilization, the method is capable of application with equal facility to the determination of average luminances in an interior and to the predetermination of discomfort glare, which are of increasing importance in lighting design.

12.1 Calculation of Interior Luminances -Just as the direct ratio indicates the light flux directly incident on the working plane from the installation, so the value ( l- direct ratio) indicates the flux from the installation which is directly incident on the walls between the ceiling cavity and the working plane. Data ( 7 ) for the inter-reflected component of flux on walls and ceiling are also available and the predetermination of average interior luminances is thus practicable at the same time and as easily as the coefficient of utilization.

12.2 Predetermination of Discomfort GlaFe -Data in Part I of this code have enabled discomfort glare indices to be predetermined for any general lighting installation on the ‘Glare Index Scale’. The reduction of the great mass of computed data has been made possible by the adoption of the BZ Classification both for calculating the adaptation and luminance levels which enter into each computation and for presenting the results in a few simple and easily used tables.

12;3 The BZ Method and the Manufacturer - It will be apparent from this part that the British Zonal Method provides a means by which the results of a great deal of research and investigation into lighting technology can be applied to general lighting practice without calling for elaborate or costly calculation procedures. Accurate tables of coefficient of utilization can be prepared, with no more photometry or labour than formerly and by relatively unskilled staff. On the other hand, the means are provided for manufacturers who do not wish to publish such tables to give adequate design information for a fitting in the form of the BZ Classification and the light output ratios.

It is fundamental to the successful adoption of the BZ Method that all manufacturers of fittings should make freely available the BZ Classification and the downward and upward light output ratios of their fittings, whether or not they publish tables of coefficients, since these data are required not only for calculations of coefficients but also for the Glare Tables [see IS : 3646 ( Part I )-I 966* 1. In addition, these data are likely to be of value as a convenient basis for luminance data which will undoubtedly become generally ‘available in the near future.

*Code of practice for interior illumination: Part I Principles for good lighting and aspects of design.

50

Page 55: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

IS:3646 (Part III)-l!m

TABLE 23 UPPER FLUX UTILANCE FOR ALL BZ CLASSIFICATIONS

(Clause 11.1 )

EFBEC- TIVE

ROOM CEILINQ IXOEX REFLEC- (4) TION

FACTOR PERCENT

1-O 4 30

1.25 :“o 30

70 1.5

z:

2-o :;: 30

2.5 :8 30

70 3.0 50

30

70 4.0

z:

70 5.0

z:

REFLECTION FACTOR OFFLOOR I REFLECTIONFACTOR OF FLOOR

10 PERCENT 30 PERCENT

Reflection Factor of Wall Reflection Factor of Wall 50% 30% 10% 0 I 50% 30% 10% 0

.23 -17 *12 a09 -24 -17 *13 *lo

.16 *12 .08 *06 -17 a13 -09 -07

.09 -07 $05 -04 -10 -09 *06 -05

.32 *23 .13

-25 .18 *ll

.2d -14 a9

-17 *12 *08

-31 .20 *22 *13

.12 .08

-37 .30 *26 .22 *39 *31 *26 -23 -26 -22 *18 .16 -27 .23 -19 .17 .14 -12 *lo .09 .15 -14 -12 -11

-43 .37 .31 .28 -46 -38 -32 .30 .26 .22 .20 .32 .27 .24 ::

*17 .14 .12 .ll -18 *15 *13 *12 .47 .41 .36 *33

*33 .29 .26 .24 .19 .15 -13 .I3

.53 -48 44 *41

.37 .33 .31 *29 -20 .17 .15 .14

.57 .53 -49 .47

1: .37 -34 .33 .19 -17 -16

.51 *43 -38 -34

.35 *30 .27 -25 -21 -17 *15 -14

*58 -51 a43

-39 *35

:z

.22 *19 *17 :2

-63 .57 .52 .42 .39 .36 :g

*23 .21 -19 -18

60 .56 -52 .50 -67 .61 -56 .41 -39 .36 .35 -45 .41 -39 :z .22 .20 .18 -17 -24 -23 -21 .20

.63 .61 .57 -56 -71 -67 *62 .44 .42 *39 -38 -48 .45 .43 1: -23 -21 .19 -18 .25 .24 .22 -21

-66 .64 :i! -59 -74 .70 -66 -65 .45 .43 .41 .49 .47 .45 -44 .24 .22 .20 -19 -27 .25 *23 -22

51

Page 56: IS 3646-3 (1968): Code of practice for interior ... · 2.6 Downward Coefficient ( Abbreviation DC ) -The ratio of that part of the downward flux from the fittings which reaches the

BUREAU OF INDIAN STANDARDS

HeadqumMrs Manak Shavan, 9 Bahadur Shah Zafar Marg, NEW DELHI 110002 Tabphones: 323 0131,323 3375,323 9402 Fax : 91 11 3234062,91 11 3239399, 91 11 3239362

Centml Labtntory :

Plat No. 20/9, Sita IV, Sahibabad industrial Area, Sahibabad 201010

Regh?Ml omce8:

Tebgrams : Manaksanstha (Common to ail Cffii)

Telephone

0-77 00 32

Cenfral : Manak Bhavan. 9 Bahadur Shah Zafar Mug, NEW DELHI 110002 323 76 17

%astam : 1114 CtT Schema VII M, V.I.P. Road, Maniktob, CALCUTTA 700054 3376662

Northern : SC0 335336, Sector 34-A, CHANDIGARH 160022 603643

Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113 235 23 16

‘We&n&- E9, Behind Mud Tebphone Exchange, Andheri (East), 632 92 95

Brmch Offfces::

‘Pushpak’, Nurmohamed Shaikh Marg, Khanpur, AHMEDABAD 360001

$Paenya Industrial Area, 1 st Stage, Bangalore-Tumkur Road, BANGALORE 560056

5501346

639 49 55

Gangotri Compbx+ 56’1 Floor, Bhadbhada Roti, T.T. Nagar, BHOPAL 462003 55 40 21

plot No. 62-63, Unit VI. Ganga Nagar. BHUBANESHWAR 751001 40 36 27

j&bfk&& Buildings. 670 Avfnashi Road, COfMBATORE 641037 21 01 41

plot No. 43. Sector 16 A. Mathura Road, FARIDABAD 121001 6-26 66 01

Savitri Complex, 116 G.T. Road, GHAZIABAD 201001 6-71 1996

5315 Ward No.29, R.G. Barua Road, 5ti By-lute. GUWAHATI 761003 541137

S-6-56C. L.N. Gupta Marg, Nampally Statfon Road, HYDERABAD 500001 201063

E-52, Chftaranjan Marg. C-Scheme, JAIPUR 302001 37 29 25

117/416 8. Sarvodaya Nagar, KANPUR 206065 21 66 76

Seth Bhawan. 2nd Floor, Behind Leek Cinema, Naval Kbhore Road, 236923 LUCKNOW 226001

NIT Building, Second Floor, Gokulpat Market NAGPUR 440010 52 51 71

Patliputra Industrial Estate, PATNA 600013 26 23 05

Institution of Engineers (India) Building 1332 Shivaji Nagar, PUNE 411005 32 36 35

T.C. No. 14/l 421, Uniwmity P. 0. Palayam, THIRUV ANANTHAPURAM 695034 621 17

‘Sales Cffiie is at 5 Chowringhee Approach, P.O. Princep Street, CALCUTA ?00072

271065

tSabs Oflice is at Novslty Chambers, Grant Road, MUMBAI 400007

SSabs Of%e is at ‘F’ Bkxk, Unity Building, Narcrshimaraja Square, BANGALORE 560002

309 65 26

222 39 71

Printed at Simco Printing Press, Delhi. India