1 T M Brochure NAE2091481 / 04.2016 Isolated Power Planning Guide System options for isolated power in healthcare facilities

Upload: others

Post on 11-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

1

T M

BrochureNAE2091481 / 04.2016

Isolated Power Planning GuideSystem options for isolated power in healthcare facilities

Page 2: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

2

Standards such as NFPA 99 and CSA Z32 require isolated power systems in all areas deemed “wet procedure locations” in healthcare facilities. Isolated power systems offer an invaluable advantage - early detection of ground faults allows for critical systems to remain online in a single fault condition.

Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest in technology, Bender equipment ensures that electrical ground faults are detected and located fast and automatically, in compliance with the latest standards and code requirements.

Bender provides advanced electrical safety technology to the healthcare industry, including:

�� The latest in line isolation monitoring technology, providing advanced warning of faults to help reduce downtime and increase operational efficiencies

�� Supplimental alarms including transformer load, temperature, and voltage to mitigate risk of electrical shock and fire

�� Branch location of ground faults, fast and automatically - locate faulty equipment while the system remains online

�� Fast notification to facility staff with modern digital remotes and communication gateways to connect to Ethernet and Modbus networks

�� Complete, modular panel solutions for ease of customization and installation

�� Equipment designed in strict compliance with many electrical codes and standards, including NFPA 99, NFPA 70, CSA Z32, RETIE, AEA 90364-7-710, UL 1047, and more

PROTECT PATIENTS AND STAFFWith isolated power solutions from the leader in electrical safety.

Page 3: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

3

Standard Configuration

System Load Monitoring

Branch Ground Fault Location

Branch Load Monitoring

Central Monitoring Station

Technician Visualization and Remote Integration

Page 4

Page 5

Page 6

Page 7

Page 8

Page 9

Bender.org/tools/isolated-power/Build panels using our easy-to-use online tool.

Page 4: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

4

MK2000P-G1 remote indicator

Basic configurationIncludes required equipment for NFPA 99 compliance

Standard isolated power panel

Key system components:

Isolation transformer2

Secondary branch circuit breakers (provisionable up to 16 branches)3

LIM2010 line isolation monitor4

MK2000P remote indicator (with visual and audible indication, remote LIM test)5

System notes:�� Minimum equipment required for com-

pliance with NFPA 99

�� Remote indication required when panel is not installed inside OR / ICU

Basic panel and system configuration

P

L1 L2

1

34

5

Panel configuration:�� Standard panel configuration

�� One (1) LIM2010 line isolation monitor

�� Provisions for up to 16 branch circuit breakers

�� Options for built-in hospital grade receptacles and ground jacks

�� Option for PLC controlled circuit lockout

Sample part numbers:(ex. 10 kVA, 208/120V)�� Transformer: XM10BA

�� Backbox: B432408

�� Front trim: T4526

�� Interior: IP10BASP

Additional equipment:�� MK2000P-G1 remote indicator

Primary circuit breaker1

2

Page 5: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

5

MK2000CBM digital remote indicator

Load monitoringIncludes capability of monitoring transformer load

STW3 current transformer

Transformer load monitoring

L1 L2

1

2

Key additional components:

STW3 load monitoring current transformer1

MK2000CBM digital remote indicator2System notes:�� Adds capability of system load monitor-

ing (for entire system)

�� Load monitoring indicated on both LIM2010 and MK2000CBM remote

�� MK2000CBM provides digital readout of both THC and transformer load

Panel configuration:�� Standard panel configuration with inte-

grated system load monitoring

�� Options for built-in hospital grade receptacles and ground jacks

�� Option for PLC controlled circuit lockout

Sample part numbers:(ex. 10 kVA, 208/120V)�� Transformer: XM10BA

�� Backbox: B432408

�� Front trim: T4526

�� Interior: IP10BASP-LM

Additional equipment:�� MK2000CBM remote indicator

Page 6: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

6

Branch ground fault locationIncludes automatic indication of individual branches with ground faults

EDS461 and W-8000 series

Key additional components:

EDS461 ground fault location module (integratable into panel)1

W-8000 series current transformers (integratable into panel or retrofittable)2

MK2430 remote indicating station3

System notes:�� Automatic detection and indication of

faulty branch circuit

�� Digital display clearly shows faulty branch circuit

�� Modular current transformer sizes allow for simple installation

�� EDS module and current sensors can be built into the panel

�� MK2430 remote provides alarm indica-tion for both LIM and EDS module

�� Simple RS-485 connectivity between LIM, EDS, and remote

�� MK2430 can monitor multiple systems / panels

�� Allows for future integration of other rooms and central nurses' desk monitor-ing

Addition of ground fault location and digital remote station

1

2

3

L1 L2

MK2430 remote indicating station

Included in panel beyond standard:�� Two (2) EDS461 ground fault location

modules

�� Sixteen (16) W-8000 series current transformers

Sample part numbers:(ex. 10 kVA, 208/120V)�� Transformer: XM10BA

�� Backbox: B482408

�� Front trim: T5026E

�� Interior: IP10BASP-D6

Additional equipment:�� MK2430 remote station

Page 7: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

7

L1 L2

W series current transformers

Branch load monitoringAdds load monitoring for individual branch loads

CMS460 branch current module

Key additional components:

CMS460 branch current monitoring module1

W series current transformers (integratable into panel or retrofittable)2

System notes:�� Automatically detects and alarms on

overload for individual branches

�� Displays load current values in real-time on digital display

�� Integrates into RS-485 network with other equipment

�� Load current alarms also displayed on MK2430 remote station

Addition of branch load current monitoring

12

Included in panel beyond standard:�� Two (2) EDS461 ground fault location

modules

�� Two (2) CMS460 load current modules

�� Sixteen (16) W-8000 series current trans-formers for ground fault location

�� Sixteen (16) W series current transform-ers for load current monitoring

Sample part numbers:(ex. 10 kVA, 208/120V)�� Transformer: XM10BA

�� Backbox: B522408

�� Front trim: T5426EC

�� Interior: IP10BASP-D6LMC

Additional equipment:�� MK2430 remote station

Page 8: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

8

L1 L2

Central monitoring stationProvides a central point for monitoring system alarms

MK800RS (as shown) remote station

Key additional components:

MK800 remote station1

System notes:�� All components connected by same two-wire RS-485 network

�� MK800 provides large screen for notification of alarms for hundreds of systems

�� Nurses' desk able to see alarms from multiple rooms and a central point

�� Compatible with any panel type

Addition of central monitoring station at nurses' desk

1

Page 9: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

9

L1 L2

COM465IP communication gateway

Technician visualization and remote integrationIncludes advanced technical visualizations and communication

Key additional components:

COM460IP Ethernet and Modbus/TCP communication gateway2

Bender TCP series HMI station3

System notes:�� All components connected by same

two-wire RS-485 network

�� Technicians view all systems from a centralized point

�� COM465IP provides centralized, brows-er-based interface for viewing device status

�� COM465IP provides integration into building management systems via Modbus/TCP

�� TCP series station provides advanced touchscreen visualizations of system along with integration other system controls into unified control screen

�� Compatible with any panel type

Addition of technician monitoring station for all systems

1

2

3

TCP series HMI station

Page 10: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

10

Complete systems for multiple roomsA complete solution for multiple operating rooms, centrally monitored

L1 L2 L1 L2 L1 L2

Modbus/TCPnetwork

OR 1 OR 2

System features:�� All systems connect to each other with simple, two-wire RS-485 network

�� Nurses' desk monitors multiple systems from single location

�� Integratable into existing Modbus/TCP networks

�� Central visualizations for technicians and maintenance personnel for all systems

Page 11: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

11

L1 L2 L1 L2 L1 L2

Modbus/TCPnetwork

ICU 1 Nurse Desk Central Maintenance

Sample part numbers as shown in example: (ex. 10 kVA, 208/120V)

�� 3x Transformer: XM10BA

�� 3x Backbox: B522408

�� 3x Front trim: T5426EC

�� 3x Interior: IP10BASP-D6LMC

Other equipment:

�� 3x MK2430

�� 1x MK800

�� 1x COM465IP

�� 1x TCP series HMI station

Page 12: Isolated Power Planning Guide - Bender...Bender isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas. Utilizing the latest

Doc

umen

t N

AE2

0914

81 /

04.2

016

/ © B

ende

r Inc

. A

ll Ri

ghts

Res

erve

d.

T M

USA • Exton, PA • 800-356-4266 / 610-383-9200Mexico and Central America • Tampa, FL • +1 [email protected] • www.bender.org

Canada • Mississauga, ON • 800-243-2438 / [email protected] • www.bender-ca.com

South America • Santiago de Chile • +56 2 2933 [email protected] • www.bender-latinamerica.com

Your local contact: