Detailed Inspection & Test Plan ( ITP) for HDPE- Corrugated Sheathing Ducts
(As Per IRC: 18- 2000, IRC - 112-2011 / Fib Bulletin 7 Specifications )
Sr. No.
Inspection & Testing Description
Gra
nu
late
Du
ct
Measuring Technique
Acceptance Criteria
Verifying Document
Test Conducted By
Frequency of Testing Every lot of 7000 mtrs
Remark
A RAW MATERIAL PROPERTIES
1 Density G -- IS : 7328 0.94 - 0.96 gm/cc Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
2 Melt Flow Rate (190 0 c / 5Kg.) G -- IS : 2530 0.4 – 0.6 gm /10 min Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
3 * Shore Hardness D G -- ASTMD 2240 3 sec -60 minimum
15 sec – 58 minimum Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
4 * Charpy Impact Strength of
Notched Specimens at + 23 0
c
G -- ISO 179/1 eA 10 Kj/m2 Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
5 * Charpy Impact Strength of
Notched Specimens at - 30 0
c
G -- ISO 179/1 eA 4 Kj/m2 Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
6 Tensile Impact Strength of Notched Specimens at + 23 0
c G -- ISO 8256 > 130 KJ/m2
Manufacturer’s Test report
Manufacturer 1 Sample per grade of raw
material.
7 Tensile Stress at yield G -- ASTM D 638 (IV) > 22 N/mm2 Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
8 Elongation at yield G -- ASTM D 638 (IV) > 7 % Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
9 E.S.C.R. ( 70 0 c ) G -- ASTM D 1693 > 192 hrs Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
10 Vicat VST B50 G -- ISO 306 > 70 0 c Manufacturer’s Test
report Manufacturer
1 Sample per grade of raw material.
11 Linear expansion – Coefficient between 200c and 800c
G -- --- K -1 To be declared by supplier Supplier’s Typical declared value for
HDPE
Raw Material Supplier
Copy of already declared value.
12 Carbon Content -- D IS : 2530 > 2 % Manufacturer’s Test
report Manufacturer 1 Sample upto 7000 RM
Page-2
Detailed Inspection & Test Plan ( ITP) for HDPE- Corrugated Sheathing Ducts
(As Per IRC: 18:2000, IRC 112-2011 / Fib Bulletin 7 Specifications )
Sr. No. Inspection & Testing
Description
Acceptance
Criteria
Verifying Document
Test Conducted By
Frequency of Testing Remark
B HDPE Sheathing Duct Properties
1 Dimensions
I. D … ID ± 1 % or ± 0.5mm whichever is the greater
Manufacturer’s Test report
Manufacturer 3 Samples upto 7000 RM
2 Wall thickness As per Specified value. – Average ( to be checked at 4 points and average taken )
Manufacturer’s Test report
Manufacturer 3 Samples upto 7000 RM
3 Flexural Behaviour of Duct
Record load at 20 mm deflection & 2 minutes after 20 mm deflection as well as instantaneous deflection after removing load and residual deflection after 2 minutes of removing load.
Manufacturer’s Test report
Manufacturer 3 Samples upto 7000 RM
# 4 * Flexibility of Duct
Deformation preferably ≤ 5% of duct diameter, determined by passing a plunger through the duct at specified minimum bending radius. Internal Duct diameter < 85mm : r = 1800mm Internal Duct diameter > 85mm : r = 2800mm
Manufacturer’s Test report
Manufacturer 3 Samples upto 7000 RM
5 Lateral Load Resistance
of Duct Deformation ≤ 10% or 5mm whichever is lesser after 2 minutes of unloading.
Manufacturer’s Test report
Manufacturer 3 Samples upto 7000 RM.
6 * Longitudinal Load
Resistance
Duct should sustain specified load for 10 minute.
Manufacturer’s Test report
Manufacturer 3 Samples upto 7000 RM
7 * Leak Tightness of
duct system
No visually detectable loss of water during the test period of 5 minutes at Inside pressure of 0.5 bar.
Manufacturer’s Test report
Manufacturer 3 Samples upto 7000 RM
* For conformity of these tests, only butt welded joint or joint with heat shrink sleeves is prescribed.
C System Approval Test
1 Wear Resistance Of Duct Needs to be conducted only once for the project. At times tests conducted for the same
department in the last one year should be accepted and not to be conducted again
2 Bond Behavior of Tendon Should be conducted once for the project and report submitted to the department prior to commencement of supplies. At times tests conducted for the same department in the last one
year should be accepted and not to be conducted again 3 Coefficient of Friction