izbor opreme ok
DESCRIPTION
Kako je sta imaTRANSCRIPT
-
IZBOR ELEMENATA PRIMARNE OPREMEPROJEKTIRANJE ELEKTRINIH POSTROJENJA
-
ELEKTRINA POSTROJENJAUNUTARNJA IZVEDBAVANJSKA IZVEDBAOTVORENA POSTROJENJAZATVORENA POSTROJENJAPLINOM IZOLIRANA POSTROJENJA
OTVORENA POSTROJENJAZATVORENA POSTROJENJA
-
PRIMARNA OPREMA ELEKTRINOG POSTROJENJA
-
I. NAPREZANJA PRIMARNE OPREME ELEKTRINOG POSTROJENJA (HRN-HD 637)NAPONSKA NAPREZANJASTRUJNA NAPREZANJAMEHANIKA NAPREZANJA (POTRESI I SL.)KLIMATSKI UTJECAJUTJECAJ OKOLIA KOJI SE OEKUJE NA LOKACIJI POSTROJENJA
-
ELEKTRINI ZAHTJEVINAINI POSTUPANJA S NEUTRALNOM TOKOMRAZREDBA NAPONASTRUJA U NORMALNOM POGONUSTRUJA KRATKOG SPOJANAZIVNA FREKVENCIJAKORONA
-
PRORAUN STRUJA KS-a(HRN HD 533)VRSTE KRATKIH SPOJEVA:TROPOLNI KSDVOPOLNI KSZEMLJOSPOJDVOPOLNI KS S ISTODOBNIM SPOJEM SA ZEMLJOMDVOSTRUKI ZEMLJOSPOJ
-
JEDNOPOLNI KS
-
DVOPOLNI KS
-
DVOPOLNI KS S ISTOVREMENIM SPOJEM SA ZEMLJOM
-
TROPOLNI KS
-
PRORAUN STRUJA KS-a (2)U struji kratkog spoja razlikujemo tri struje presudne za dimenzioniranje i odabir elemenata rasklopnog postrojenja:UDARNA STRUJA KS-a,PREKIDNA STRUJA KS-a iSTRUJA MJERODAVNA ZA UGRIJAVANJE
-
ODREIVANJE NAJVEE STRUJE ZA RAZLIITE VRSTE KS-a
-
ODREIVANJE UDARNE STRUJE KRATKOG SPOJA
JEDNOPOLNI KSTROPOLNI KSIk'' efektivna vrijednost struje neposredno nakon nastanka kratkog spoja,Zd'' zbroj subtranzijentne (poetne) reaktancije generatora i impedancije u direktnom sustavu od generatora do mjesta kratkog spoja,V efektivna vrijednost faznog napona mree, k faktor u ovisnosti o omjeru R/X zadane mree.
-
ODREIVANJE PREKIDNE STRUJE KRATKOG SPOJA
-EFEKTIVNA VRIJEDNOST STRUJE KOJA PROTIE KROZ PREKIDA U TRENUTKU ODVAJANJA KONTAKATA-Ia VRIJEDNOST ISTOSMJERNE KOMPONENTE U TRENUTKU ODVAJANJA KONTAKATA
-
ODREIVANJE STRUJE MJERODAVNE ZA UGRIJAVANJE
-
MEHANIKI ZAHTJEVINORMALNO OPTEREENJEOPTEREENJE USLIJED ZATEZANJAOPTEREENJE USLIJED IZVOENJAOPTEREENJE USLIJED LEDAOPTEREENJE USLIJED VJETRASILE USLIJED SKLAPANJASILE USLIJED KRATKOG SPOJAOTPUTANJE VODIAVIBRACIJEDIMENZIONIRANJE NOSIVIH KONSTRUKCIJA
-
KLIMATSKI UVJETI IUVJETI OKOLIATEMPERATURANADMORSKA VISINA I TLAKVLANOSTOBORINEONEIENJESUNEVO ZRAENJE
-
POSEBNI ZAHTJEVIPOSTROJENJA NA VELIKIM NADMORSKIM VISINAMAUINCI MALIH IVOTINJA I MIKROORGANIZAMARAZINA BUKEUINCI POTRESA
-
II. IZOLACIJAKOORDINACIJU IZOLACIJE USKLADITI S EN 60071-1 I EN 60071-2EN 60071-1 DEFINIRA VRIJEDNOSTI NAJVIEG NAPONA OPREME UmEN 60071-2 DEFINIRA ODGOVARAJUE MINIMALNE RAZMAKE
-
NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (1)
-
NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (2)
-
NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (3)
-
III. OPREMASABIRNICEPREKIDAIOSIGURAIRASTAVLJAIMJERNI TRANSFORMATORIODVODNICI PRENAPONAIZOLATORI
-
1. SABIRNICEDIMENZIONIRANJE:OBZIROM NA MAKSIMALNU STRUJU U NORMALNOM POGONUOBZIROM NA DOZVOLJENO POVIENJE TEMPERATURE ZA VRIJEME KRATKOG SPOJAOBZIROM NA MEHANIKA NAPREZANJA ZA VRIJEME KRATKOG SPOJA
-
MAKSIMALNA STRUJA U NORMALNOM POGONULOCIRATI NAJVIE OPTEREENI DIO SABIRNICA U NORMALNOM POGONU, ALI I U SLUAJU n-1
VODITI RAUNA O PROPISIMA KOJI ODREUJU MINIMALNE PRESJEKE ODNOSNO PROMJERE CIJEVNIH SABIRNICA
PROVJERITI TRAJNU STRUJU ODABRANIH SABIRNICA TE IZVRITI KOREKCIJE U OVISNOSTI O DOZVOLJENOJ NADTEMPERATURI
-
KONTROLA PRESJEKA OBZIROM NA UGRIJAVANJE ZA VRIJEME KS-aRAUNSKIM PUTEM ODREDITI PRESJEK SABIRNICA TE GA USPOREDITI S PRESJEKOM ODABRANOG TIPA SABIRNICEZA ALUMINIJ
ZA BAKAR
-
KONTROLA PRESJEKA SABIRNICA OBZIROM NA MEHANIKA NAPREZANJA ZA VRIJEME KS-aODREDITI RAZMAK SABIRNICA POJEDINIH FAZA TEMELJEM PROPISA, A U OVISNOSTI O NAPONSKOJ RAZINIODREDITI RAZMAK POTPORNIH IZOLATORAIZRAUNATI MAKSIMALNI MOMENT SAVIJANJA U UPORITIMAODREDITI LINIJSKI OTPORNI MOMENTODREDITI MAKSIMALNO NAPREZANJE I USPOREDITI GA S DVOSTRUKOM VRIJEDNOSTI GRANICE TEENJA ODABRANOG MATERIJALA SABIRNICA
-
2. PREKIDAIDIMENZIONIRANJE:OBZIROM NA NAZIVNI NAPONOBZIROM NA MAKSIMALNU STRUJU U NORMALNOM POGONUOBZIROM NA VRIJEDNOST PREKIDNE STRUJE IprKONTROLA OBZIROM NA UDARNU STRUJU KS-a
-
VRSTE PREKIDAAULJNIMALOULJNIHIDROMATSKIPNEUMATSKI (KOMPRIMIRANI ZRAK, SF6)VAKUUMSKI PREKIDAIZRANI PREKIDAI
-
3. OSIGURAIZATITA OD KS-a I PREOPTEREENJAUPORABA VN OSIGURAA DO 35 kVUGRADNJA NA MJESTU SMANJENJA PRESJEKA I POETKU TIENOG VODIASELEKTIVNOST - OMJER NAZIVNIH STRUJA SUSJEDNIH OSIGURAA >= 1,6IZBOR - PREMA NAZIVNOM NAPONU I STRUJI
-
4. RASTAVLJAIVIDLJIVO ODVAJANJE DIJELOVA POD NAPONOM OD OSTALIH DIJELOVA KOJI NISU POD NAPONOM
DIMENZIONIRANJE OBZIROM NA:NAZIVNI NAPON RASTAVLJAAMAKSIMALNU STRUJU U NORMALNOM POGONUKONTROLA OBZIROM NA UDARNU STRUJU KS-a I STRUJU MJERODAVNU ZA UGRIJAVANJE
-
5.MJERNI TRANSFORMATORI5.1 STRUJNI MJERNI TRANSFORMATORI
PRIKLJUAK ZATITNIH I MJERNIH UREAJA NA SEKUNDARNE STEZALJKEIZBOR PRIMARNE STRUJE PREMA MAKSIMALNOJ STRUJI U NORMALNOM POGONUSEKUNDARNA STRUJA 5A ILI 1ABROJ PRIKLJUENIH INSTRUMENATA ODREUJE SNAGU STRUJNOG TRANSFORMATORAKLASA STRUJNOG TRANSFORMATORA
-
5.2 NAPONSKI MJERNI TRANSFORMATORIIZVEDBA KAO U TRANSFOMRATORA SNAGEINDUKTIVNI ILI KAPACITIVNI TRANSFORMATORIPRIMARNI NAPON ODGOVARA LINIJSKOM ILI FAZNOM NAPONU POSTROJENJASEKUNDARNI NAPON IZNOSI 100V ILI 100/3VSNAGU DEFINIRAJU PRIKLJUENI INSTRUMENTI NA SEKUNDARU
-
6. ODVODNICI PRENAPONANAZIVNI NAPON ODVODNIKA VEI OD NAJVEEG POVREMENOG POVIENJA POGONSKOG NAPONA UP0UP0=cu*cf*Um/3 cu=1,07 cf=1,3 izravno uzemljena mrea cf=1,74 izolirana ili gaena mrea Um-najvea vrijednost linijskog pogonskog naponaPRORADNI NAPON - DJELOVANJE ODVODNIKAPREOSTALI NAPON - MANJI OD NAPONSKE RAZINE IZOLACIJE TIENOG UREAJA (POSTROJENJA)VENTILNI ODVODNICI, CIJEVNI ODVODNICI, BROJAI PRORADE ODVODNIKA
-
7. IZOLATORI7.1 POTPORNI IZOLATORIODABIR SE VRI PREMA:NAZIVNOM NAPONU I VELIINI SILE KOJA SE PRENOSI NA IZOLATORTIPOVI: PORCULAN, UMJETNA SMOLA
7.2 PROVODNI IZOLATORIODABIR SE VRI PREMA:NAZIVNOM NAPONUMAKSIMALNOJ STRUJI U NORMALNOM POGONUMEHANIKIM NAPREZANJIMA ZA VRIJEME KS-aUGRIJAVANJU ZA VRIJEME KS-a