    JABATAN KERJA RAYA MALAYSIA

    UNIT STANDARD ,PENGU.IIAN & MAKMALCAWANGAN ELEKTRIK

    TECHNICAL INFORMATION ON STANDARD CABLE TRUNKINGS I CABLEMANAGEMENT SYSTEM

    A. COMPANY1. Name o f Company2. Address

    3. Telephone N o ...............................................................4. Faxs No . .............................................................5 . S.T Registration No . ...............................................................6 . Validity Date of Registration : ..............................................................7. SIRIM Test Report ............................................. -(If related)8. SIRIM Test C ertificate No : .............................................. (If related)9. Other A ccredicted T est R eport/Certificate: ...................................................

    B. PRODUCT SPECIFICATIONI . Brand's Nam e ................................................................2. Model No .............................................................3. Approval Standard . ...............................................................

  • 7/27/2019 JKR Standard on Trunking

    2/5

    Catatan Pe'abatk31 0 Kandas 1

    5.0 CABLE TRUNKING (METALLIC)

    5.1 Comply with IEC 61084 q y es q NO 05.2 Fabricated from galvanished sheet steel and finished with 2 coats

    of standard orange enamel q y es NO 05.3 Equipped with removable covers at suitable intervals q Yes No 0

    6.0 Shall have the following minimun wall thicknessNomiilal Size(m11x mrn) Minimun Wall Thickness(mm )i) 50 x50 and below 1.0 yes q NO 0ii) 75 x 50 to 100x100 1.2 Yes q No 0

    iii) 150 x 50 to 300 x150 1.6 q y es q NO 0iv) Above 300 x 150 2.0 O ~ e s NO0

    If others from the above please specify.. . . . . . . . . . . . . . . ... . .. ..6.5 All truilking elbows,offsett & combinatioll elbow ,adaptors & tee shall have the same thickness a s

    the straight trunking q y es NO 06.6 Shall be maufactured by the same manufacturer Yes No 06 .7 Sha ll be suppo rted by fixing brackets i.e not be in contact with

    wall or floor slabs y es NO 06.8 Th e brackets shall be installed at interval not greater 1500mm

  • 7/27/2019 JKR Standard on Trunking

    3/5

    Informative to be used together during installation:

    8 . 1 When conduit is tapped from the trunking ,suitable brass type smoother bushes shall befitted at all conduit termination . q Yes q No 0

    ...nformation CPC For Site Installation:9 .0 A1 1 trunkings shall have either tinned copper tape of dimension not less than 25mm x 3

    mrn as circuit protector conductor orearth cable of approriate D y e s D N O O

    10.0 Others (please specify)

    11.0 Under Floor Trunking (i.e Raised Floor, Flushed Floor.. .etc)i ) Please give details of the test report :. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ii) The Dimensions - Please used Lam piran :

  • 7/27/2019 JKR Standard on Trunking

    4/5

    12.0 Cable trunking-uPVC(Cab1e trunking made of insulating material)12 .1 Comply to BS 4678 :Part 4:1982 : O Y e s ~ N O O

    Others standard,please specify.. . . . . . . . . . . . .Have an approval letter from Jabatan Bomba: q Yes q No 012.2 Comply to Clause 4 : Classification e.g

    : Trunking for heavy mechanical stresses : O Y e s O N O O: Comply according to resistance against ingress of solid ob je c t: n Yes q No 0

    . . . . . . . . . . . . . . .2.3 Dimension -Width.. . . .x Heigh t.. Thickn ess.. .(mm)

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Please specify !If needed arise please used additional paper-12.4 Clause 9.3-

    (i) Impact Test Data - Heavy Duty (3.3 kg mass of hammer & impact Energy 10 J )-12.5 Clause 10-Resistance to heat- Ball pressure test. q Yes q No 012.6 Clause 11-Resistance to burning.. . . . . . . . . . n ~ e s N O O12.7 Marking - code of marking e.g 425 plus additional marking code-/. . . . .Please specify .13.0 Others for uPVC trunking -(If ther e is a deviation from 12.0 & Please explain)-

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    (Note : The above clauses to be tested is just an example of the important clauses thatmalufa cture rs should be done but manufacturers also can do full type test .)