1. INTRODUCTION 1.1 The Great East Japan Earthquake At 14:46 on March 11, 2011, the East Japan Earthquake of magnitude 9.0 occurred off Sanriku coast of Japan. It caused tremendous tsunami hazard in the pacific coast of eastern Japan, killing more than 15,000 people, destroying and washing away cities. The epicenter was 129km from Sendai, the largest city in the northeast of Japan. The depth of the hypocenter was 24 km. The recorded magnitude  places the earthquake as the fourth largest in the world since 1900, following 1960 Chile Earthquake M9.5, 1964 Alaska Earthquake M9.2, 2004 Sumatra Earthquake M9.2, and it is the largest in Japan since modern instrumental recording began 130 years ago. The earthquake has recorded the seismic intensity 7, highest in the Japan Meteorological Agency scale, in the north of Miyagi prefecture. There were many strong earthquake observation networks in operation under the management of research institutes, universities and companies. A large amount of data was well recorded during the earthquake. Figure 1 shows the distribution of peak ground acceleration (PGA) recorded during the earthquake, summarized by Earthquake Research Institute (ERI), the University of T okyo. K-NET Tsukidate, located in Kurihara city, Miyagi prefecture, is the only station that recorded Intensity 7 during the main shock. A maximum acceleration in the N-S direction reached almost 2699 cm/s 2 , representing that the main shock caused excessively severe earthquake motions. Strong motions with PGA larger than 200 cm/s 2  were observed over a very wide area from Ibaraki to South Iwate. Toky o is located 300 km away from the epicenter (Figure 1), and its stations recorded PGA of 50 to 150 cm/s 2 . The records from stations close to epicenter, such as Sendai, show two wave groups with a time interval of about 50 seconds, and those from southern station such as Ibaraki and Tokyo areas show one large wave group. Such phenomenon occurred due to difference of focal rupture process and the wave propagation to recording stations in the northern and southern portions of the fault area of 500 km long. 1.2  Building r esponses an d rec ords Where ground acceleration was large, except for some areas of soft ground, the response spectrum indicates short dominant period, which was probably the main reason for relatively small seismic damage. On the other hand, Tokyo relatively far from the epicenter was subjected to the ground motion of short to long period components. Many tall  buildings have been constructed for the last 40 years in Tokyo, and the shaking they experienced is much stronger than those in the past. Therefore, the response observed are believed to be the precursors for the performance of the tall buildings against the stronger shaking that will definitely occur in future. Since some tall buildings were instrumented with accelerometers, acceleration records obtained during the earthquake would be one of the best resources to study the building responses (Kasai, 2011a). Responses of Tall Buildings in Tokyo during the 2011 Great East Japan Earthquake K. Kasai, W.C. Pu & A. Wada Tokyo Institute of Technology, Yokohama, Japan ABSTRACT: Many tall buildings in Tokyo metropolitan area were strongly shaken during the Great East Japan Earthquake, March 11, 2011 . Most of them are less than 40 years old, and have not experienced the shaking of such a strong level. The tall buildings are of steel construction, concrete construction, or hybrid construction, and those less than 15 years old, constructed after the 1995 Kobe Earthquake, are installed with dampers due to the increased concern about serious consequence of seismic damage in major buildings. Some tall buildings are instrumented with sensors and their motions were recorded during the event. This paper discusses the responses of the Japanese tall buildings based on their motions recorded in Tokyo during the 2011 Great East Japan Earthquake.

Upload: kaiserasrael

Post on 03-Apr-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 1/10

1.  INTRODUCTION

1.1 The Great East Japan Earthquake

At 14:46 on March 11, 2011, the East JapanEarthquake of magnitude 9.0 occurred off Sanrikucoast of Japan. It caused tremendous tsunami hazardin the pacific coast of eastern Japan, killing more

than 15,000 people, destroying and washing awaycities.

The epicenter was 129km from Sendai, the largestcity in the northeast of Japan. The depth of thehypocenter was 24 km. The recorded magnitude

 places the earthquake as the fourth largest in theworld since 1900, following 1960 Chile EarthquakeM9.5, 1964 Alaska Earthquake M9.2, 2004 SumatraEarthquake M9.2, and it is the largest in Japan sincemodern instrumental recording began 130 years ago.The earthquake has recorded the seismic intensity 7,

highest in the Japan Meteorological Agency scale, inthe north of Miyagi prefecture.There were many strong earthquake observation

networks in operation under the management ofresearch institutes, universities and companies. Alarge amount of data was well recorded during theearthquake. Figure 1 shows the distribution of peakground acceleration (PGA) recorded during theearthquake, summarized by Earthquake ResearchInstitute (ERI), the University of Tokyo.

K-NET Tsukidate, located in Kurihara city,Miyagi prefecture, is the only station that recorded

Intensity 7 during the main shock. A maximumacceleration in the N-S direction reached almost2699 cm/s2, representing that the main shock causedexcessively severe earthquake motions. Strongmotions with PGA larger than 200 cm/s2  were

observed over a very wide area from Ibaraki toSouth Iwate. Tokyo is located 300 km away from theepicenter (Figure 1), and its stations recorded PGAof 50 to 150 cm/s2.

The records from stations close to epicenter, suchas Sendai, show two wave groups with a timeinterval of about 50 seconds, and those from

southern station such as Ibaraki and Tokyo areasshow one large wave group. Such phenomenonoccurred due to difference of focal rupture processand the wave propagation to recording stations inthe northern and southern portions of the fault areaof 500 km long.

1.2  Building responses and records 

Where ground acceleration was large, except forsome areas of soft ground, the response spectrum

indicates short dominant period, which was probablythe main reason for relatively small seismic damage.

On the other hand, Tokyo relatively far from theepicenter was subjected to the ground motion ofshort to long period components. Many tall

 buildings have been constructed for the last 40 yearsin Tokyo, and the shaking they experienced is muchstronger than those in the past. Therefore, theresponse observed are believed to be the precursorsfor the performance of the tall buildings against thestronger shaking that will definitely occur in future.

Since some tall buildings were instrumented withaccelerometers, acceleration records obtained duringthe earthquake would be one of the best resources tostudy the building responses (Kasai, 2011a).

Responses of Tall Buildings in Tokyo during the 2011 Great East JapanEarthquake

K. Kasai, W.C. Pu & A. WadaTokyo Institute of Technology, Yokohama, Japan

ABSTRACT: Many tall buildings in Tokyo metropolitan area were strongly shaken during the Great EastJapan Earthquake, March 11, 2011. Most of them are less than 40 years old, and have not experienced theshaking of such a strong level. The tall buildings are of steel construction, concrete construction, or hybridconstruction, and those less than 15 years old, constructed after the 1995 Kobe Earthquake, are installed withdampers due to the increased concern about serious consequence of seismic damage in major buildings. Sometall buildings are instrumented with sensors and their motions were recorded during the event. This paper

discusses the responses of the Japanese tall buildings based on their motions recorded in Tokyo during the2011 Great East Japan Earthquake.

Page 2: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 2/10

1.3 Objectives and scopes

Pursuant to these, the objective of the present

 paper is to clarify behavior of tall buildings in Tokyo, based on the responses recorded during the 2011Great East Japan Earthquake. The paper will analyzeacceleration records of a typical seismically-resistant

 building with a low damping ratio, andresponse-controlled buildings whose damping ratiosare increased by the new technology using varioustypes of dampers.

Virtually, most Japanese tall buildings constructedafter the 1995 Great Hanshin Earthquake areresponse-controlled in order to protect not only the

human lives but also the structural components,

nonstructural components, and building functions.Therefore, effectiveness of the new technology inachieving the above-mentioned performance will bediscussed.

Because of constraints of preparation time and page length, the paper will concentrate on severaltall buildings only. More information will be

 presented in the STESSA conference, based on the

extensive study being conducted at Tokyo Instituteof Technology.

2.  OVERVIEW OF BUILDINGS EXAMINED

2.1  Nine tall buildings selected  

We select one conventional seismically-resistant building and eight response-controlled buildings thathave various types of dampers for seismic energydissipation. All the selected buildings are over 60

meters high, commonly considered as the lowerlimit of height of high-rise buildings in Japan. Timehistory analysis is compulsory for these buildingswhen performing structural design. The number offloors of the buildings ranges from 19 to 54. Notethat some of the buildings will be anonymous in this

 paper, due to the request of building owners.In Table 1, structural types of buildings,

fundamental periods of x- and y-directions, peakaccelerations of top and base are given. Hereinafter,the top means the highest floor where theaccelerometer is installed, and the base means the

lowest floor in structure closest to the ground level.The vibration periods are obtained from the transferfunction of acceleration of top to base; the frequencyat the peak value of transfer function is defined asthe vibration period of structure.

The peak acceleration at the base ranged from 52to 142 cm/s2, and their average is about 80 cm/s2.The peak acceleration response at top of the buildingranged from 113 to 251 cm/s2, and the average storydrift angle (ratio of peak displacement of top to itsheight) is 1/300 rad. at most.

Figure 1. Peak ground accelerations recorded in eastern Japanduring the 2011 Great East Japan Earthquake (From ERI, the

University of Tokyo).

Tokyo

Iwate

Chiba

Miyagi

Fukushima

Ibaraki

Table 1. Basic information on buildings examined.

 Note: S = Steel structure, CFT = Concrete-filled tube columns.

X Y X Y X Y X Y

1 No Damper S 29 127.8 2.96 3.09 235 316 91 89 2.58 3.55

2 Steel+Viscous S 14 66.0 1.21 1.66 217 155 112 127 1.94 1.22

3 Viscous S 19 79.5 1.83 1.58 142 154 75 71 1.89 2.17

4 Steel+Viscous S 21 99.6 1.83 1.97 113 128 75 71 1.51 1.80

5 Viscous CFT+S 37 178.0 4.96 5.21 99 145 108 92 0.92 1.58

6 Oil CFT+S 41 186.9 3.97 4.10 118 124 53 52 2.23 2.38

7 Oil CFT+S 42 157.3 4.78 4.31 147 152 47 68 3.13 2.24

8 Steel+Viscous CFT+S 43 152.5 4.75 4.23 136 199 72 78 1.89 2.559 Oil S 54 223.0 5.37 6.43 236 161 94 142 2.51 1.13

Amplif. Factor Height

(m)

Period (s) Top Acc. (cm/s2) Base Acc. (cm/s2) No. Type of Damper 

  Type of 

Frame

 Number 

of Floors

Page 3: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 3/10

2.2 Spectral responses at building sites

Figure 2 shows the response spectra of the base

acceleration records of both x- and y-directions, thedamping ratio of 5% is used. The nine buildings arelocated in Shinjuku ward, Chiyoda ward, Bunkyoward, Minato ward, and Meguro ward of Tokyo. Ascan be seen from Figure 2, response spectra havesmall coefficient of variation of about 0.2 at themiddle to long period range.

In view of the strong randomness of earthquakemotions, the intensity and characteristics of theseinput earthquake motions may be considered assimilar ones. Consequently, it is reasonable to usethe average to represent the input earthquake level inthis area. In one sense, it could be considered thatall the nine buildings were subjected to a commonground shaking characterized by the averagespectral plots.

It should be also noted that in Tokyo and Osakacity relatively far from the epicenter, long-periodearthquake motions were observed during the 2011Great East Japan Earthquake. The spectralcharacteristics in Tokyo differed considerably fromthe well-known motion recorded during the 2004

 Niigata Chuetsu Earthquake. As partly shown byFigure 2b, the spectral velocity was almost uniform

for the vibration periods from 0.5s and 20s, and itsmagnitude exceeded even the largest spectral valuedue to the 2004 Niigata Chuetsu Earthquake thatconcentrated at the period about 7s (not shown).

Thus, unlike the responses during the 2004 quake,the responses of the tall buildings in Tokyo weredominated by not only the long period motion butalso the shorter period motions during the 2011Great East Japan Earthquake.

2.3  Amplification of acceleration

The ratio of accelerations of top to base will benamed as “acceleration amplification ratio”. InFigure 3, its value is shown with respect to each

 building height. In addition to the nine buildings of14-story or higher discussed above (Table 1), twoshorter response-controlled buildings with steeldampers and ten short to tall seismically-resistant

 buildings (Kasai, 2011a) are added for comparisonover wide range.

As stated in Sec. 2.2, the response spectra for the

 buildings are similar, and the vibration period of the building is well correlated to its height. However,acceleration amplification ratio in Figure 3 does notfollow the trend of acceleration spectra in Figure 2a:It is very high for taller buildings, in contrast to lowspectral accelerations in Fig. 2a (Kasai, 2011a,b).

This is due to significant contribution of highermodes as will be explained in later sections, and, incase of seismic-resistant buildings, their dampingratios below the value of 5% used in the spectra ofFigure 2. Note also the shorter response-controlled

 buildings with steel dampers show similar trend asthe seismically-resistant building, since damper waselastic or yielding very little for the level of theground shaking in Tokyo.

In Japanese practice to-date, design criteria for

Figure 2. Response spectra generated from the base motions of

the nine buildings (damping ratio = 5%).

0

5

10

15

20

25

30

35

0 1 2 3 4 5

T(s)

   D   i  s  p   l  a  c  e  m  e  n   t   (  c  m   )

0

10

20

30

40

50

60

0 1 2 3 4 5

T(s)

   P  s  e  u   d  o  v  e   l  o  c   i   t  y   (  c  m   /  s   )

0

100

200

300

400

500

0 1 2 3 4 5

T(s)

     P   s   e   u     d   o  -   a   c   c   e     l   e   r   a    t     i   o   n     (   c   m     /   s     /   s     )

 Average Average ± Standard deviationIndividual motion

   P  s  e  u   d  o  -   A  c  c .   (  c  m   /  s   2   )

   P  s  e  u   d  o  -   V  e   l  o  c   i   t  y   (  c  m   /  s   )

   D   i  s  p   l  a  c  e  m  e  n   t   (  c  m   )

(a)

(b)

(c)

0 10 20 30 40 50 60

0

1

2

3

4

5

 

  加  速  度  増  幅  比

   (  頂  部  /  基  部  )

耐震構造

制振構造

   A  c  c .   A  m  p   l   i   f   i  c  a   t   i  o  n   (   T  o  p   /   B  a  s  e   ) ● Seismic-resistant building

□ Response-controlled building 

Figure 3. Acceleration amplification factor vs. number of

stories of buildings.

Number of Stories

Page 4: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 4/10

response-controlled buildings have been set fordisplacement control, and rarely for accelerationcontrol. In spite, excessive accelerations have beenfound to cause large economic loss due to thedamage on non-structural components and facilities.Thus, acceleration amplification such as shown inFigure 2 should be taken in structural design moreseriously. By this reason, the following discussion

will refer to both displacement and acceleration

2.4 Calculation of displacements

By using the following two different methods, thedisplacements of structure are calculated from therecorded accelerations. The results are comparedwith each other in order to confirm their reliability(Kasai, 2011a).

Method 1 performs double integration togetherwith hi-pass filtering in frequency domain. The

cut-off frequency is typically 0.05 or 0.1Hz. Method2 first obtains modal properties such as vibration

 period, damping ratio, and participation vector, byapplying a basic system identification technique forthe story where recording was done. Then, the timehistories of accelerations and displacements of mode1 to 3 are calculated by using the base accelerationrecorded, and modal superposition is performed.

For all the nine buildings considered, thedisplacements from method 2 agreed well with thosefrom method 1, and accelerations from method 2

agreed with those recorded. Thus, the modal properties obtained are considered valid, and thecontribution of each individual mode to the totalresponse of system, and the effect of damping can befurthermore examined.

 Note that method 2 is based on the assumption oflinear response, proportional damping, and realnumber mode. The agreement between the twomethods suggests that the buildings had linear orslightly nonlinear behavior during the earthquake aswell as moderate amount of damping. In Chapter 3,four selected buildings will be described in detail.

3.  PERFORMANCE EXAMPLES

3.1 Seismically-resistant building 1

Building 1 is a seismically-resistant 29-story steel building constructed in 1989. It is a school buildingof Kogakuin University, located in Shinjuku ward ofcentral Tokyo. Figure 4 shows the elevation and planof the building as well as locations of sensorsinstrumented (Hisada, 2011).

As indicated in Table 1, the peak accelerations inx- and y-directions were 91 and 89 cm/s2 at the base,and 235 and 316 cm/s2 at the top floor, respectively.The acceleration amplification ratios are 2.58 and3.55, respectively. The average drift angle (i.e., top

floor displacement divided by the height) is 1/350rad., and the structure remained elastic. The

vibration periods for the first three modes are 2.96s,1.00s, and 0.52s for x-direction, and 3.10s, 0.94s,and 0.47s for y-direction, respectively. Likewise,damping ratios are 1.7%, 1.8%, and 3.4% forx-direction, and 2.1%, 1.6%, and 3.4% fory-direction, respectively. Prof. Hisada of theUniversity reported damping ratio of 0.01, based onthe small amplitude vibration test which heconducted before 2011 ( Hisada, 2011).

Figure 5a shows y-direction pseudo-accelerationresponse spectra  S  pa  of Building 1 (buildingacceleration spectrum, solid line) and a componentat building top floor (component accelerationspectrum, broken line) due to the y-directionaccelerations recorded at the building base and topfloor, respectively. Damping ratios are set to 2% and3%, considering responses of building andnon-structural component such as ceiling (Kasai 2011b), respectively. Similarly, Figure 5b showsdisplacement spectra S d   of Building 1 (buildingdisplacement spectrum, solid line) and a component(component displacement spectrum, broken line),respectively. The two vertical axes on two sides of

each figure are in reference to responses of theBuilding 1 and the component, respectively.

S  pa’s of Building 1 at the 2nd (0.94s) and 3rd(0.47s) mode periods are large, suggesting possiblehigher mode contributions to the accelerations in the

Figure 4. Seismically-resistant 29-story building (Building 1).

(a) X-direction frame 

(c) Typical floor plan

(b) Y-direction frame 

127.8m

25.6m38.4m

NS1 NS2

EW

UD

 Accelerometer BraceX

Y

Page 5: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 5/10

 building. Also, S  pa’s of components resonant withthe 1st (3.09s) and 2nd (0.94s) modes are extremelyhigh, and their values are 1,600 and 2,400 cm/s2,respectively. Time history analyses of suchcomponents have indicated many cycles of largeaccelerations.

On the other hand, S d ’s of both Building 1 andcomponent are highly dependent on the building’s1st mode period (3.09s). Note that broken line inFigure 5b indicates the component may move

400cm, if it is flexible and resonate with the building’s 1st mode.Figure 6 shows situations of the rooms just after

the earthquake, and move of furniture, falling ofceiling and books occurred due to the highacceleration. The control of building’s higher moderesponses is a problem that needs to be resolved incase of a conventional seismically-resistant tall

 building (see also Sec. 4.1).Figure 7a compares acceleration records at top

floor and base in y-direction. The earthquakeduration is long, and is considered to be about 200

seconds (Fig. 7a). For the first 90 seconds of thefigure, high frequency response of the top floor isapparent, as confirmed by the large number ofcycles per unit time. These are caused by thehigh-frequency ground shaking, as shown by the

 base accelerations. In contrast, f or the last 110seconds, low frequency response is dominant. Theground shaking is weak (Fig. 7a), but its lowfrequency contents excited the first mode and causedresonated response.

Figures 7b compares the top floor acceleration

recorded with that calculated by method 2. The goodagreement suggests that the mode method iseffective, and the first three modes are adequate inresponse calculation for this case. Figure 7ccompares relative displacement of top floor obtained

 by double integration of the record (method 1) withthat calculated by method 2. In some cycles the peakvalues by the both method differ a little, but thedisplacements agree well overall.

As is known, the contribution of each vibrationmode depends on the type of response as well as the

story level determining participation vector. Sincethe properties and responses of each vibration modehave been obtained, it is possible to discuss suchcontributions:

Figure 8a shows the acceleration of each mode atthe top floor. As mentioned earlier, it is dominated

 by the 2nd, 1st, and 3rd modes in the order of weightfor the first 90 seconds. For the later 110 seconds,the 1st mode response increases and becomedominant, with slight contribution from the 2ndmode. As Figure 8b shows, for the 16th floor the2nd mode is much more dominant, developingalmost the same acceleration as top floor. As for thedisplacement at top floor (Fig. 8c), the 1st modedominates throughout the entire duration.

3.2 Response-controlled buildings 4, 6, and 9Building 4 is a 21-story government office

 building (Koyoma and Kashima 2011, Kasai 2011b).It consists of a steel frame and 336 low yield pointsteel (wall) dampers and 284 viscous (wall) dampers(Fig. 9a). For seismic energy dissipation, the steeldamper utilizes yielding of steel material, and

viscous damper utilizes flow resistance of the polymer liquid with high viscosity (Kasai et al.2009).

 Note that a contrasting case of using only steeldampers lead to large accelerations like the

Figure 6. Damage to nonstructural components and contents

of Building 1. (From Prof. Hisada) 

(a) Falling of ceilings 

(b) Falling of books 

BuildingSpa (cm/s2)

T(s)

Figure 5. Response spectra of building (solid lines) andcomponent at top floor (broken lines) of Building 1. 

   T   1  =   3 .   0   9  s   T

   2  =   0 .   9   4  s

   T   3  =   0 .   4   7  s

   T   1  =   3 .   0   9  s

   T   2  =   0 .   9   4  s

   T   3  =   0 .   4   7  s

ComponentSpa (cm/s2)

BuildingSd (cm)

ComponentSd (cm)

T(s)

a

Page 6: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 6/10

seismically-resistant building in Sec. 3.1, since thedamper remained elastic for the level of shaking in

Tokyo (Kasai et al. 2011b). Building 4 had beendesigned to avoid such a situation, expecting thatviscous damper would dissipate energy from a smallearthquake, and steel damper, the most economicalamong all types, would dissipate considerable

amount of energy at a large quake, respectively.Building 6 is a 41-story office building (Kasai et

al. 2009, 2011b). It consists of a frame usingconcrete-filled tube columns and steel beams, and688 oil dampers (Fig. 9b). For energy dissipation,the damper utilizes flow resistance of oil with lowviscosity. The valve placed at orifice is shaped to

(b) Comparison: acceleration obtained by mode superposition vs. actual recorded acceleration.

Figure 7. Acceleration records and accuracy of mode superposition method. 

Mode superposition Actual Acc.

To acceleration Base acceleration

(a) Accelerations recorded at top and base.

Mode superpositionDouble inte ral of actual acc.

(c) Comparison: dispt. obtained by mode superposition vs. dispt. from double integral of recorded acceleration.

Hi h Fre uenc Low Fre uenc

2nd mode1st mode3rd mode

Figure 8. Contributions of the first three modes to acceleration and displacement of Building 1. 

(c) Modal contributions to top floor displacement.

2nd mode1st mode3rd mode

2nd mode

1st mode3rd mode

(a) Modal contributions to top floor acceleration.

(b) Modal contributions to 16th floor acceleration.

Page 7: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 7/10

 produce the force linearly proportional to velocity, but a relief mechanism to limit the force is provided,making the hysteresis to switch from an ellipticalshape to a rectangle shape. Most likely, the relief didnot occur for the level of shaking.

Building 9 is a 54-story office steel buildingconstructed in 1979. It was retrofitted in 2009(Maseki et al. 2011) by attaching 288 oil dampers(Fig. 9c). 12 dampers per floor were attached tomiddle 24 stories of the building. The oil damper issimilar to those used for Building 6, except that itsrelief mechanism is modified to reduce forces near

 peak responses. This aims to reduce the axial forceof the column transmitting the damper force, and

consequently uplift force of foundation. Most likely,however, the relief did not occur for the level ofshaking.

As indicated in Table 1, average of accelerationamplification ratios of Buildings 4, 6, and 9 is lessthan 2, well below those of Building 1 (Sec. 3.1),and they remained elastic. Modal properties areobtained from method 2, and estimated 1st modedamping ratios are about 4%, and those of the 2ndand 3rd modes are almost equal or larger. The 1stmode vibration periods are indicated in Table 1, andthose up to the 3rd mode will be mentioned later.

For all the three buildings, their accelerations anddisplacements are obtained from superposition up tothe 3rd mode, and accuracies are confirmed as in to

 be even better than those shown in Figures 7b and c

shown earlier (Sec. 3.1). Such responses at top floorare shown by black lines in Figures 10, 11, and 12for buildings 4, 6, and 9, respectively. In these three

 buildings, the acceleration (Figs. 10 to 12) isdominated by the 2nd and 3rd modes for about 100seconds, and by the 1st mode for later 200 seconds.Whereas, the displacement (Figs. 10 to 12) isdominated by the 1st mode throughout the shaking.

This trend is like that of seismically-resistant building 1, but the amplitudes are believed to besmaller due to the supplemental damping. Thus, theresponses are compared with those of lower but

 possible damping ratio representing a hypotheticalcase of not using the dampers. The modal period is

unchanged, assuming small stiffness of the damper.The 1st to 3rd mode damping ratios are uniformlyset to 1% and superposition is repeated. The resultsare shown by gray lines in Figures 10, 11, and 12 forBuildings 4, 6, and 9, respectively.

In all the three buildings, their responses areconsiderably smaller (black lines) than those withlow damping (gray line). The peak accelerations anddisplacements are about 0.5 and 0.7 times those ofthe low damping case. Moreover, betweensignificant ground shakings, the responses decaymuch faster, and number of large cycles is reducedconsiderably. These help reducing damage andfatigue of structural and non-structural componentas well as fear or discomfort of the occupants. Inorder to quantify such an effect, root mean square of

Figure 9. Response-controlled buildings and dampers considered (Buildings 4, 6, 9 from left). 

ViscousDamper

SteelDamper

(a)

Damper

(c)

Damper

(b) XY

99.6m

21-story Building:

Steel Frame +336 Steel Dampers +284 Viscous Dampers

41-story Building:

Steel Frame +688 Oil Dampers

223m

54-story Building:

Steel Frame + 288 Oil Dampers

186.9m

XYXY

52m96m

45.4m45.4m

42m63m

Page 8: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 8/10

the acceleration and displacement at top arecalculated, and their values appear to be about 0.4and 0.5 times those with low damping, respectively.

4.  DISCUSSIONS

4. 1 Component acceleration spectrum

Inertia forces against structural and non-structural

components including equipment and building

content are produced by accelerations in the building.

Large accelerations typically developed at upper

stories cause falling, overturning, shifting, crashing,rapture, and excessive vibration of a variety of

non-structural components.

As a matter of fact, economic loss due to damage

of non-structural components is much more than that

of structural damage. Falling of ceilings and other

components may also cause death of occupants.

Such failures due to the 2011 Great East Japan

Earthquake were enormous.Figure 13 shows component acceleration spectra

for the top floors of the four buildings 1, 4, 6, and 9.Damping ratio of the component is assumed to be3%. The value attached to “original damping” is thefirst mode damping ratio. For Building 1 (Fig. 13a)that is seismically resistant, the broken line is basedon the recorded top floor acceleration of the original

 building having low damping ratios (Sec. 3.1), andsolid line shows a case where the building dampingratios of the first three modes are increased to 4%. Incontrast, for Buildings 4, 6, and 9 (Fig. 13b-d) that

Original damping

Decreased damping (1%)

Decreased damping (1%)

Figure 11. Building 6 with different damping ratios (x-dir.). 

(a) Acceleration of top floor  

(b) Displacement of top floor   Original damping

Figure 12. Building 9 with different damping ratios (y-dir.). 

Original dampingDecreased damping (1%)

Original damping

Decreased damping (1%)(a) Acceleration of top floor  

(b) Displacement of top floor  

Figure 10. Building 4 with different damping ratios (y-dir.). 

Original dampingDecreased damping (1%)

Decreased damping (1%)(a) Acceleration of top floor  

(b) Displacement of top floor  

Original damping

Page 9: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 9/10

are response-controlled, the solid line is based onrecorded top floor acceleration of the original

 building (Sec. 3.2), and the broken line shows whenthe first three modal damping ratios of the buildingare reduced to 1%. These examine a merit ofincreasing building modal damping ratios for

 protecting the acceleration-sensitive components.According to Figure 13, the past belief that

short-period components are safer in a tall buildingis incorrect. They are as vulnerable as thelong-period components due to multiple resonance

 peaks created by different modes of the building.The peaks are extremely high, even greater than2,000 cm/s2 (≈2G). Thus, the resonant accelerationof the components may be greater than 8G at aso-called major quake 4 times or stronger. The

 problem may become more serious when damageand softening of components cause period shiftingfrom one resonance peak to others. Note that three

 peaks for each building are shown in Figure 13,

since the first three modes were identified (Sec. 2.4).But more peaks may emerge in an actual lowdamping case,

As a rule of thumb, facilities may overturn whenfloor acceleration exceeds 0.3G, and ceiling whose

vibration period typically ranges from 0.3s to 1smay fall when its acceleration response exceeds 1G.These indicate the needs for an immediate attentionto component responses at a major quake that willoccur in Tokyo. Figure 13 also clearly indicates thateven moderately increasing the building dampingratio by 3% or so would reduce the componentacceleration considerably.

4.2 Effect of long-period earthquakeThe soil base of Tokyo plains is composed of soft

sedimentary layers, and the specific long periodcomponents of earthquake wave may be amplified

 by these soft layers, and subsequently causeundesirable resonance of long period structures suchas tall buildings and base-isolated buildings.

The supposed velocity spectrum of thelong-period earthquake at damping ratio of 5% is 80to 120 cm/s, 3 to 4 times than recorded in Tokyoduring the 2011 Great East Japan Earthquake. TheJapanese government is striving to find social andtechnical solutions to the long period earthquakes.

The accurate time history analyses superposingthe modal response (Chapter 3) are utilized toexamine the effects of the long period earthquake. Awell-known EW-direction ground motion recordedin Tomakomai during the 2003 TokachiokiEarthquake is used (Figure 14).

From Figure 15a where damping ratio is 2%, theS  pa exceeds the PGA (72.9 cm/s2) in a wide periodrange up to 9s, suggesting significant higher mode

contributions to the building accelerations. The S d  onthe other hand shows mostly the 1st modecontribution to the building displacement.

These are in conformity with the peak responsessummarized in Table 2: In case of Building 1 havinglow damping, high acceleration amplification ratioof 3.65 is obtained, and acceleration history containsmultiple mode contributions. Compared with thevalues from the 2011 Great East Japan Earthquake,the average drift angle is 1/212 and 1.65 times,although PGA is smaller and 0.82 times.

More significant responses are found fromBuilding 9. Due to the vibration period of 6.43s(Table 1) and increasing S d   for the longer period,large average drift angle 1/79 is obtained, indicating

 possibility of frame yielding. Top floor accelerationis 335 cm/s2  that is very high and contains highermodes, as found from time history. Note that theBuilding 9 is response-controlled by using oildampers (Sec. 3.2). Even much larger responses areexpected when Building 9 had not been retrofitted

 by dampers (e.g., Sec. 3.2).Based on these, it is important to realize the

 possible large accelerations during the long periodearthquake due to excitation of multiple modes, in

addition to commonly concerned large displacement

due to the 1st mode excitation.

0.1 1 100

500

1000

1500

2000

2500

0.1 1 10

0

500

1000

1500

2000

2500

0.1 1 10

0

500

1000

1500

2000

2500

0.1 1 10

0

500

1000

1500

2000

2500

Figure 13. Component response spectra (damping ratio = 3%).

   S  p  a   (  c  m

   /  s   2   )

    S  p  a   (  c  m   /  s   2   )

   S  p  a   (  c  m   /  s   2   )

   S  p  a   (  c  m   /  s   2   )

Decreased Bldg.Damping (1%)

T s

(a) Bldg. 1

(b) Bldg. 4

(c) Bldg. 6

(d) Bldg. 9

T s

T s

T s

Decreased Bldg.Damping (1%)

Decreased Bldg.Damping (1%)

Original Bldg.Damping (2.1%)Increased Bldg.

Damping (4%)

Original Bldg.Damping (3.7%)

Original Bldg.Damping (3.4%)

Original Bldg.Damping (3.9%)

Page 10: Kasai 20111031

7/28/2019 Kasai 20111031

http://slidepdf.com/reader/full/kasai-20111031 10/10

4.3  Effect of near-field earthquake  Near-field earthquake is another major concern in

Tokyo. It has a short duration but strong intensity, andthe pulse-like ground motion destroyed numerousinfrastructures and buildings during the 1995 Great

Hanshin Earthquake. One of the three strongest groundmotions recorded during the 1995 quake, the NScomponent of JMA Kobe record (PGA 821 cm/s2) isused here. As Figure 14 shows, its duration is muchshorter than the long-period motion (Sec. 4.2).

In Figure 15a, S  pa of JMA Kobe record is comparedwith that of Tomakomai record, where much higher S  pa at short period suggests strong higher modecontribution to the building acceleration. The trend ofS  pa makes S d  the largest at the period of about 1.5s, andsmaller at longer periods. These suggest the averagedrift angle, similar to S d  divided by effective height of

the building, decreases for a taller building.The above observations match well with the peak

responses summarized in Table 2: Building 1 havinglow damping shows high acceleration of 1,532 cm/s2 at top floor, and time history indicated by far the

strongest contribution of the 2nd mode, followed bythe 3rd mode. Similar trend is observed from the threetaller buildings response-controlled. But very highaccelerations of Building 4 may be offset, since thesteel dampers (Sec. 3.2) should yield at average driftangle 1/151 tabulated, which cannot be simulated bythe present modal superposition approach. The taller

 buildings also show much less drift angles (Table 2),as discussed above.

In summary, the near-field motion did not excitethe 1st mode of the tall buildings, since it has mainlyshort to medium long period contents. This resulted in

relatively small story drift, but large accelerations ofhigher modes. The responses could be more significantwithout the supplemental damping provided by thevelocity-dependent dampers used.

5. CONCLUSIONResponses of the tall buildings in Tokyo during the

2011 Great East Japan Earthquake are discussed basedon the strong motions recorded. By successfullyanalyzing contributions of multiple vibration modes,various shaking phenomena in the tall building thathad not been experienced are clarified.

Based on this approach, the merit of dampingtechnology for occupants and contents in the tall

 building is explained. Immediate attention must begiven to the acceleration-induced hazard in tall

 buildings, considering much stronger shaking likely tooccur in the near future.

REFERENCESKasai, K. 2011a. 4.2.3 Acceleration records of buildings, 4.4.5.

Behavior of response controlled buildings, PreliminaryReconnaissance Report of the 2011 Tohoku-Chiho Taiheiyo-OkiEarthquake, Architectural Institute of Japan, pp.280-284, pp.345-347.

Kasai, K. 2011b. Chapter 4. Performance of Response-ControlledBuildings, The Kenchiku Gijutsu, No.741, pp.118-123.

Hisada, Y., Kubo, T., and Yamashita, T., Shaking and Damage of theShinjuku Campus Building and Shinjuku Campus Report fromKougakuin University, Internet Access: http://kouzou.cc.kogakuin.ac.jp/Open/20110420Event/20Apr11_K ogakuin01.pdf

Koyama, S., and Kashima, T. 2011. Prompt Report on StrongMotions Recorded during the 2011 Tohoku Pacific OceanEarthquake, Report 5, Building Research Institute (BRI).

Kasai, K., Motoyui, S., Ozaki, H., Ishii, M., Ito, H., Kajiwara, K., andHikino, T. 2009. Full-Scale Tests of Passively-Controlled 5-StorySteel Building Using E-Defense Shake Table; Part 1 to Part 3, Proc.

Stessa2009, Philadelphia.Maseki, R., Nii, A., Nagashima, I., Aono, H., Kimura, Y., and

Hosozawa, O. 2011. Performance of Seismic Retrofitting of SuoerHigh-Rise Building Based on Earthquake Observation Records,International Symposium on Disaster Simulation and StructuralSafety in the Next Generation (DS’11), Japan

1995 JMA Kobe

NS

Figure 14. Normalized acceleration time histories of Tomakomai (black) and JMA Kobe (gray) records. 

2003 Tomakomai

EW

Figure 15. Pseudo-acc. spectra and displacement spectra forJMA Kobe and Tomakomai records (damping ratio = 2%).

2003 Tomakomai

2003 Tomakomai

1995 JMA Kobe

1995 JMA Kobe

(a) Pseudo-Acc.

(b) Displacement

   S  p  a   (  c  m   /  s   2   )

   S   d

   (  c  m   )

T(s)

T(s)

Table 2. Response of buildings subjected to JMA Kobemotion and Tomakomai motion.

Bldg.  Dispt.

(cm)

Avg. Drift

Angle

Acc.

(cm/s2)

Dispt.

(cm)

Avg. Drift

Angle

Acc.

(cm/s2) No.1 72.7 1/176 1532 60.4 1/212 266

 No.4 65.9 1/151 1860 15.1 1/659 170

 No.6 71.9 1/260 997 88.9 1/210 184

 No.9 56.8 1/393 927 283.3 1/79 335

 Note: Avg. Drift Angle = Top Floor Displacement/Height

JMA Kobe NS (1995) Tomakomai EW (2003)

 Note: Avg. Drift Angle = Top Floor Displacement / Height