klima 2 600 active chilled beams - barcol- · pdf filesystem technology barcol-air active...
TRANSCRIPT
KLIMA 2 600
Active Chilled Beams
Subject
Index
Introduction
General description
Product features
Dimensions
Performance data
Section example
Guide specifications
Page
1
2
3-4
5-6
7
8-11
12
13
Index
1Rev 140910
The Barcol-Air chilled beam systems are designed to achieve a comfortable indoor climate with low energy consumption and
a low ceiling void height. The systems provide cooling, heating, ventilation and humidity control with low noise and minimal
maintenance.
Introduction
Figure 1: KLIMA Active Chilled Beam
System Technology
Barcol-Air active chilled beams integrate the primary air distribution function with the secondary air heat exchange using a
proprietary air nozzle technology to induce secondary room air into the unit and through the heat exchanger before mixing
with the primary air. The resulting mixture of primary air and induced secondary room air is then supplied to the room through
the contoured diffusers which are designed to keep the air close to the ceiling using the Coanda effect.
Barcol-Air's KLIMA 2 600 series active chilled beams units are designed with a nominal width of 600 mm to integrate with the
ceiling grids of the more popular ceiling configurations. Standard unit lengths are nominally 1,200 mm to 3,000 mm in 300 mm
increments but special lengths are also available to match with specific ceiling requirements.
2
Figure 2: Operating Principle of the Active Chilled Beam
Primary Air
Room air Discharge AirDischarge Air
Rev 140910
The principle of the active chilled beam system is to use terminal chilled water heat exchangers in the ceiling to offset the
room sensible cooling loads or to provide sensible heating. The ventilation and humidity control requirements are taken care
of by using separate primary conditioned air supplied by a central air handling unit.
Due to the relatively high supply chilled water temperatures, about 16 deg C, the heat exchangers operate dry, avoiding many
of the maintenance and health concerns that are associated with other systems that use terminal heat exchangers such as
fan coil units.
The system provides large energy savings because the amount of air to be circulated around the building can be reduced to
close to that required for ventilation and humidity control only, resulting in large reductions in air handling unit fan power and
energy consumption.
Further energy savings result from the use of high chilled water temperatures serving the heat exchangers. This can allow the
water chiller to operate at higher water temperatures, giving the opportunity to improve chiller operating efficiency and
energy consumption.
Figure 3: Active Chilled Beam System
7-12°C
Active Chilled Beam System
- +
16-19°C
System Concept
3Rev 140910
Figure 4: KLIMA – Air Distribution
The specific shape of the supply slot diffusers creates two opposing discharge air flows from the active chilled beam along
the ceiling. The velocity of the supply air along the ceiling creates the Coanda-effect whereby velocity differences in the cool
air stream press the air stream against the ceiling, thereby extending the air throw and preventing the cool air from dropping
into the comfort zone prematurely. It is important, with such air patterns, that the ceiling is flat and free of any obstacles,
especially light fixtures situated close to the slots, because these can disturb the Coanda-effect.
Aesthetics (fitting into the pattern of the ceiling).
Level of flexibility to create offices within the floor plan. Number of active chilled beams required. Available distance for the air throw. The air must have the opportunity to mix with the room air before impinging on a wall or an opposing air stream from another chilled beam. Disturbances in the suspended ceiling which might influence air pattern, like lighting fixtures. Disturbances in the facade or floor, like radiators or floor convectors that could influence the air pattern.
Figure 6: Parallel to FacadeFigure 5: Perpendicular to Facade
Comfort zone
1.8m
1.0m 0.5m
Facade-orientation
Orientation of the active chilled beam with regard to the facade has no influence on the operation. There are two common
installation arrangements, perpendicular or parallel to the facade. The choice between perpendicular and parallel will be
determined by:
Air distribution
4Rev 140910
Product Features
Figur 7: High Efficiency Air Nozzles
Low Height:
The KLIMA 600 series has a maximum height of 200 mm allowing the use of reduced height ceiling voids to maximize ceiling
heights. Alternatively the building slab to slab height can be reduced allowing more floors in a given building height.
Flexible Sizes
Units are available with lengths between 1200 mm and 3000 mm to match with most ceiling configurations. Unit lengths can
also be tailored to match exact installation requirement.
Aesthetic Choices
The KLIMA 600 series can be supplied with perforated return air diffusers or linear slot diffusers to match the aesthetic
requirements of the building. Exposed metal surfaces are powder painted. The standard finish colour is RAL 9010 with 20%
gloss. Other RAL colours can be supplied to match project requirements.
Simple mounting:
Units can be easily suspended from the concrete slab above using threaded rod or hanging wire support systems to match
with metal panel, fiber board or plaster ceilings. Units can also be installed without ceilings.
High capacity with multi choice nozzles
The KLIMA 600 series active chilled beams have a choice of 8 nozzle configurations designed to provide high induction rates
for the secondary room air and thereby high cooling and heating capacities. This makes them suitable for application in a
building’s perimeter zones requiring higher cooling capacites as well as internal zones. Nozzles are factory installed and can
be blanked if one side discharge is required.
5Rev 140910
Low noise:
The efficiently shaped nozzles create maximum induction with low sound levels.
Low maintenance:
The KLIMA 600 series active chilled beam has no filter, fan, drain pan or any other moving parts and maintenance is limited to
cleaning the exposed metal surfaces and cleaning any dust from the heat exchanger every 2 to 5 years depending on the
cleanliness of the supply air. The heat exchanger can be easily accessed by dropping down the centre perforated diffuser
which is equipped with a safety hanging wires, and then removing any dust with a vacuum cleaner.
Controls:
The active chilled beam can be supplied with constant air volume controllers for the primary air, water control valves with room
control sensors as well as balancing and isolation valves and condensation sensors.
Air Distribution Control (Optional)
To allow selection of the air discharge pattern KLIMA 600 series units can be supplied with optional air discharge deflectors.
These air deflectors can be independently adjusted to provide different air distribution patterns.
Figure 7 : Air Distribution Control
6Rev 140910
Dimension KLIMA 2 600
Table1: Dimensional data KLIMA 600
Size
A
B
C
D
D1
E
F
K4Weight (kg)
1200
1195
595
62
1 x ø123
1 x ø123
1090
312
200
25
1500
1495
595
62
1 x ø123
1 x ø123
1390
312
200
30
1800
1795
595
62
1 x ø123
1 x ø123
1690
312
200
34
2400
2395
595
62
2 x ø123
1 x ø158
2290
312
200
44
3000
2995
595
62
2 x ø123
1 x ø198
2890
312
200
54
Water Connection Diameters in mm
Unit Size
Chilled water
Hot water
1200-1800
12
12
2400-3000
15
12
1. Dimensions in mm.2. Air connectors can be provided on the short side of the
plenum on request.3. Intermediate lengths are available on request.
7
Duct connection on the side
2 duct connections for models 2400 and 3000
Duct connection on top
Rev 140910
Performance Data KLIMA 2 600
8
dBA
73 97 121 146 170
97 121 146 170 194
146 182 218 255 291
218 267 315 364 412
291340388437485
340400461522582
388461534607679
534631728825922
CoolingTroom minus T entering water temperature = 10 deg C
Cooling Water Flow 1 Cooling Water Flow 2 Cooling Water Flow 3 Heating Water Flow 1 Heating Water Flow 2 Heating Water Flow 3
Waterflow
l/s l/s l/s l/s l/s l/sdeg C deg C deg C deg C deg C
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
4.84.84.84.84.8
4.84.84.84.84.8
4.84.84.84.84.8
4.84.84.84.84.8
4.84.84.84.84.8
4.84.84.84.84.8
4.84.84.84.84.8
4.84.84.84.84.8
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
10.810.810.810.810.8
10.810.810.810.810.8
10.810.810.810.810.8
10.810.810.810.810.8
10.810.810.810.810.8
10.810.810.810.810.8
10.810.810.810.810.8
10.810.810.810.810.8
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
19.219.219.219.219.2
19.219.219.219.219.2
19.219.219.219.219.2
19.219.219.219.219.2
19.219.219.219.219.2
19.219.219.219.219.2
19.219.219.219.219.2
19.219.219.219.219.2
0.020.020.020.020.02
0.020.020.020.020.02
0.020.020.020.020.02
0.020.020.020.020.02
0.020.020.020.020.02
0.020.020.020.020.02
0.020.020.020.020.02
0.020.020.020.020.02
0.30.30.30.30.3
0.30.30.30.30.3
0.30.30.30.30.3
0.30.30.30.30.3
0.30.30.30.30.3
0.30.30.30.30.3
0.30.30.30.30.3
0.30.30.30.30.3
0.70.70.70.70.7
0.70.70.70.70.7
0.70.70.70.70.7
0.70.70.70.70.7
0.70.70.70.70.7
0.70.70.70.70.7
0.70.70.70.70.7
0.70.70.70.70.7
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
1.21.21.21.21.2
1.21.21.21.21.2
1.21.21.21.21.2
1.21.21.21.21.2
1.21.21.21.21.2
1.21.21.21.21.2
1.21.21.21.21.2
1.21.21.21.21.2
A1
B1
C1
E1
F1
G1
H1
deg C
A1
B1
C1
E1
F1
G1
H1
1200
1200
1200
1200
1200
1200
1200
deg C
Performance table notes1) Air cooling capacities are based on Troom minus T primary air = 10 deg C. For other conditions multiply the table air cooling capacity by the required (Troom minus Tprimary air) divided by 10. Alternatively the air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (Troom minus T primary air)2) Water cooling capacities are based on Troom minus T entering water temperature = 10 deg C. For other conditions multiply the table water cooling capacity by the required (Troom minusT entering water) divided by 10.3) Water heating capacities are based on 4 pipe chilled beams with T room minus T entering water temperature = 35 deg C. For other conditions multiply the table water heating capacity by the required (Troom minusT entering water) divided by 35.
10C
384475546604653
415506581643698
451535604662712
517585641689731
556607651690724
558608651689723
562616663704740
641676707733757
2.32.93.33.63.9
2.53.03.53.84.2
2.73.23.63.94.2
3.13.53.84.14.4
3.33.63.94.14.3
3.33.63.94.14.3
3.33.73.94.24.4
3.84.14.24.44.5
440545626692749
476581666738800
517613692759817
593670734790838
638696746791830
640697747790829
644707760807848
735776810841868
1.82.12.52.73.0
1.92.32.72.93.2
2.12.42.73.03.3
2.32.72.93.13.3
2.52.83.03.13.3
2.52.83.03.13.3
2.52.83.03.23.4
2.93.13.23.33.5
468579665736795
506617707784850
549652735806868
630712780839890
677739793840882
680741793839880
685751808857901
781824861894922
1.41.72.02.22.4
1.51.92.12.32.5
1.61.92.22.42.6
1.92.12.32.52.7
2.02.22.42.52.6
2.02.22.42.52.6
2.02.22.42.62.7
2.32.42.62.72.7
679 902107912251350
8461021116612891397
9281075119813051400
9641092120112971383
10671166125313301399
10731173125913341401
11031183125313151371
11661238130013551404
8.110.712.914.716.1
10.212.214.015.416.7
11.112.814.315.616.7
11.513.014.315.516.5
12.814.014.915.916.7
12.814.015.015.916.7
13.114.114.915.816.4
14.014.815.516.116.7
8591142136615511709
10711292147516321768
11751360151716521772
12211382152116421750
13501476158616831771
13581485159416891774
13971497158616651736
14761567164617151777
6.8 9.110.912.313.6
8.510.311.813.014.1
9.410.812.113.114.1
9.711.012.113.113.9
10.711.812.713.414.1
10.811.812.713.514.1
11.111.912.713.213.9
11.812.513.113.614.2
9451256150217061880
11781422162317951945
12931496166818171949
13431520167318071926
14851624174418521948
14931633175318581951
15361647174418311910
16231723181018861955
5.6 7.5 9.010.211.2
7.0 8.5 9.710.711.6
7.7 9.010.010.911.6
8.0 9.110.010.811.5
8.9 9.710.411.011.6
8.9 9.710.411.111.6
9.2 9.910.410.911.4
9.710.310.811.311.6
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
Water
KLIMA 600-1200
6 8101214
810121416
1215182124
1822263034
2428323640
2833384348
3238445056
4452606876
36 64100144196
42 66 95129169
47 73105143186
57 85119158203
58 79103130160
50 70 93119148
52 73 97126158
47 66 88113142
≤15≤15≤15≤15 17
≤15≤15≤15≤15 18
≤15≤15 18 22 26
≤15 20 25 28 31
20 24 28 31 33
22 27 30 34 37
25 30 34 38 41
31 37 41 43 46
≤15≤15≤15 18 22
≤15≤15 16 20 23
≤15 17 23 27 31
19 25 30 33 36
25 29 33 36 38
27 32 35 39 42
30 35 39 43 46
36 42 46 48 51
9
Performance Data KLIMA 2 600
dBA
CoolingTroom minus T entering water temperature = 10 deg C
Cooling Water Flow 1 Cooling Water Flow 2 Cooling Water Flow 3 Heating Water Flow 1 Heating Water Flow 2 Heating Water Flow 3
Waterflow
l/s l/s l/s l/s l/s l/sdeg C deg C deg C deg C deg C
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
0.080.080.080.080.08
A1
B1
C1
E1
F1
G1
H1
deg C
A1
B1
C1
E1
F1
G1
H1
deg C
1800
1800
1800
1800
1800
1800
1800
1800
40 68103145195
45 68 96129166
52 75102133168
55 77102131163
58 78101126155
50 69 93119148
59 77 98122149
51 69 90114141
≤15≤15 20 26 29
≤15 18 23 27 31
21 26 30 34 37
28 32 36 39 41
34 38 40 44 47
36 40 44 47 50
40 44 47 49 51
46 48 51 53 56
≤15≤15≤15 21 24
≤15≤15 18 22 26
16 21 25 29 32
23 27 31 34 36
29 33 35 39 42
31 35 39 42 45
35 39 42 44 46
41 43 46 48 51
5.85.85.85.85.8
5.85.85.85.85.8
5.85.85.85.85.8
5.85.85.85.85.8
5.85.85.85.85.8
5.85.85.85.85.8
5.85.85.85.85.8
5.85.85.85.85.8
13.113.113.113.113.1
13.113.113.113.113.1
13.113.113.113.113.1
13.113.113.113.113.1
13.113.113.113.113.1
13.113.113.113.113.1
13.113.113.113.113.1
13.113.113.113.113.1
23.323.323.323.323.3
23.323.323.323.323.3
23.323.323.323.323.3
23.323.323.323.323.3
23.323.323.323.323.3
23.323.323.323.323.3
23.323.323.323.323.3
23.323.323.323.323.3
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.030.030.030.030.03
0.90.90.90.90.9
0.90.90.90.90.9
0.90.90.90.90.9
0.90.90.90.90.9
0.90.90.90.90.9
0.90.90.90.90.9
0.90.90.90.90.9
0.90.90.90.90.9
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
1.51.51.51.51.5
1.51.51.51.51.5
1.51.51.51.51.5
1.51.51.51.51.5
1.51.51.51.51.5
1.51.51.51.51.5
1.51.51.51.51.5
1.51.51.51.51.5
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
2.42.42.42.42.4
2.42.42.42.42.4
2.42.42.42.42.4
2.42.42.42.42.4
2.42.42.42.42.4
2.42.42.42.42.4
2.42.42.42.42.4
2.42.42.42.42.4
Performance table notes1) Air cooling capacities are based on Troom minus T primary air = 10 deg C. For other conditions multiply the table air cooling capacity by the required (Troom minus Tprimary air) divided by 10. Alternatively the air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (Troom minus T primary air)2) Water cooling capacities are based on Troom minus T entering water temperature = 10 deg C. For other conditions multiply the table water cooling capacity by the required (Troom minusT entering water) divided by 10.3) Water heating capacities are based on 4 pipe chilled beams with T room minus T entering water temperature = 35 deg C. For other conditions multiply the table water heating capacity by the required (Troom minusT entering water) divided by 35.
10C
121 158 194 230 267
158 194 230 267 303
243 291 340 388 437
340 400 461 522 582
461 534 607 679 752
534 631 728 825 922
655 752 849 946 1043
873 1019 1164 1310 1456
585 706 802 881 949
623 746 848 9351011
687 787 872 9451010
747 827 896 9561010
812 882 943 9981047
811 885 94910051054
850 914 97010201065
945 992103410701103
3.54.24.85.35.7
3.74.55.15.66.0
4.14.75.25.66.0
4.55.05.45.76.0
4.85.35.66.06.3
4.85.35.76.06.3
5.15.45.86.16.3
5.65.96.16.46.6
670 809 91910111088
714 855 97210721159
787 902 99910831158
856 948102710961158
9311011108211441200
9301015108811521209
9741047111211691221
10831138118512271265
2.73.23.74.04.3
2.83.43.94.34.6
3.13.64.04.34.6
3.43.84.14.44.6
3.74.04.34.54.8
3.74.14.34.64.8
3.94.24.44.74.9
4.34.54.74.95.0
712 860 97710741156
759 909103311391231
837 959106211511230
9101007109111651230
9891075114912151275
9881079115612241284
10351113118112421297
11511209125913041344
2.12.62.93.23.5
2.32.73.13.43.7
2.52.93.23.43.7
2.73.03.33.53.7
3.03.23.43.63.8
3.03.23.53.63.8
3.13.33.53.73.9
3.43.63.83.94.0
10701422170119322129
13341610183820332202
14641694188920582207
15211722189520462181
16821839197620972206
16911850198521042210
17401865197620742163
18391952205021362214
8.511.313.515.417.0
10.612.814.616.217.5
11.613.515.016.417.6
12.113.715.016.317.4
13.414.615.816.717.6
13.514.715.816.717.6
13.914.915.816.517.2
14.615.516.317.017.6
13541800215324462695
16892038232725732788
18532145239226052794
19252180239825902760
21292328250126542792
21412341251326632797
22022361250126252737
23272471259527042802
8.110.712.814.616.1
10.112.213.915.316.7
11.012.814.315.616.7
11.513.014.315.516.5
12.713.914.915.816.7
12.814.015.015.916.7
13.114.114.915.716.4
13.914.715.516.116.7
14901980236926902964
18582242255928303066
20382359263128663073
21172398263828493036
23422560275129203071
23552576276529303077
24232597275128883011
25602718285429753083
7.1 9.511.312.814.1
8.910.712.213.514.7
9.711.312.613.714.7
10.111.512.613.614.5
11.212.213.113.914.7
11.312.313.214.014.7
11.612.413.113.814.4
12.213.013.614.214.7
Water
KLIMA 600-1800
10 13 16 19 22
13 16 19 22 25
20 24 28 32 36
28 33 38 43 48
38 44 50 56 62
44 52 60 68 76
54 62 70 78 86
72 84 96108120
10
Performance Data KLIMA 2 600
dBA
CoolingTroom minus T entering water temperature = 10 deg C
Cooling Water Flow 1 Cooling Water Flow 2 Cooling Water Flow 3 Heating Water Flow 1 Heating Water Flow 2 Heating Water Flow 3
Waterflow
l/s l/s l/s l/s l/s l/sdeg C deg C deg C deg C deg C
A1
B1
C1
E1
F1
G1
H1
deg C
A1
B1
C1
E1
F1
G1
H1
deg C
2400
2400
2400
2400
2400
2400
2400
2400
Performance table notes1) Air cooling capacities are based on Troom minus T primary air = 10 deg C. For other conditions multiply the table air cooling capacity by the required (Troom minus Tprimary air) divided by 10. Alternatively the air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (Troom minus T primary air)2) Water cooling capacities are based on Troom minus T entering water temperature = 10 deg C. For other conditions multiply the table water cooling capacity by the required (Troom minusT entering water) divided by 10.3) Water heating capacities are based on 4 pipe chilled beams with T room minus T entering water temperature = 35 deg C. For other conditions multiply the table water heating capacity by the required (Troom minusT entering water) divided by 35.
14 18 22 26 30
19 23 27 31 35
28 33 38 43 48
37 44 51 58 65
48 58 68 78 88
60 72 84 96108
70 82 94106118
90110130150170
43 70105147196
51 75104137174
55 76101129161
52 73 99127160
50 72 99131166
50 72 97127161
53 73 95121150
43 64 90119153
≤15 16 21 25 29
≤15 20 25 28 32
22 26 30 33 36
27 32 35 39 42
31 36 40 44 47
35 40 44 47 51
39 43 46 49 52
42 47 51 55 60
≤15≤15 16 20 24
≤15≤15 20 23 27
17 21 25 28 31
22 27 30 34 37
26 31 35 39 42
30 35 39 42 46
34 38 41 44 47
37 42 46 50 55
170 218 267 315 364
230 279 328 376 425
340 400 461 522 582
449 534 619 704 788
582 704 825 946 1067
728 873 1019 1164 1310
849 995 1140 1286 1431
1092 1334 1577 1820 2062
10C
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
3.23.23.23.23.2
3.23.23.23.23.2
3.23.23.23.23.2
3.23.23.23.23.2
3.23.23.23.23.2
3.23.23.23.23.2
3.23.23.23.23.2
3.23.23.23.23.2
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
7.17.17.17.17.1
7.17.17.17.17.1
7.17.17.17.17.1
7.17.17.17.17.1
7.17.17.17.17.1
7.17.17.17.17.1
7.17.17.17.17.1
7.17.17.17.17.1
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
12.712.712.712.712.7
12.712.712.712.712.7
12.712.712.712.712.7
12.712.712.712.712.7
12.712.712.712.712.7
12.712.712.712.712.7
12.712.712.712.712.7
12.712.712.712.712.7
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
1.91.91.91.91.9
1.91.91.91.91.9
1.91.91.91.91.9
1.91.91.91.91.9
1.91.91.91.91.9
1.91.91.91.91.9
1.91.91.91.91.9
1.91.91.91.91.9
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
2.92.92.92.92.9
2.92.92.92.92.9
2.92.92.92.92.9
2.92.92.92.92.9
2.92.92.92.92.9
2.92.92.92.92.9
2.92.92.92.92.9
2.92.92.92.92.9
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
4.24.24.24.24.2
4.24.24.24.24.2
4.24.24.24.24.2
4.24.24.24.24.2
4.24.24.24.24.2
4.24.24.24.24.2
4.24.24.24.24.2
4.24.24.24.24.2
8421007113812471340
9371097123213471449
9901117122713231408
10321152125413431421
10941222133014231505
11451260135714411515
11671270135914381508
12961384145715201575
3.34.04.55.05.3
3.74.44.95.45.8
3.94.54.95.35.6
4.14.65.05.35.7
4.34.95.35.76.0
4.65.05.45.76.0
4.75.15.45.76.0
5.25.55.86.16.2
9571144129214161523
10641246139915311646
11241269139415031600
11731309142415251615
12431389151116171710
13011431154116371721
13251443154416331713
14731572165617271789
2.53.03.43.84.0
2.83.33.74.14.4
3.03.43.74.04.2
3.13.53.84.14.3
3.33.74.04.34.5
3.43.84.14.44.6
3.53.84.14.34.5
3.94.24.44.64.8
2.02.42.72.93.2
2.22.62.93.23.4
2.32.62.93.13.3
2.42.73.03.23.3
2.62.93.13.43.5
2.73.03.23.43.6
2.73.03.23.43.6
3.13.33.43.63.7
14611943232426392908
18232199251127763008
20002314258128113014
20772352258827952978
22972512269828643013
23102527271228743018
23762548269828332954
25112666280029183024
8.711.613.915.817.4
10.913.115.016.618.0
11.913.815.416.818.0
12.414.015.516.717.8
13.715.016.117.118.0
13.815.116.217.118.0
14.215.216.116.917.6
15.015.916.717.418.0
18502459294133403681
23072784317835143808
25312930326635583816
26292977327635373770
29083179341636253814
29243198343336383820
30083225341635863739
31793375354436943828
8.811.814.016.017.6
11.013.315.216.818.2
12.114.015.617.018.2
12.614.215.716.918.0
13.915.216.317.318.2
13.915.316.417.418.2
14.415.416.317.117.9
15.216.116.917.618.3
20352705323536744049
25383062349638664188
27843223359339144197
28923275360338914147
31993497375739884195
32173518377640024202
33093548375739444113
34973712389940634210
8.110.812.914.616.1
10.112.213.915.416.7
11.112.814.315.616.7
11.513.014.315.516.5
12.713.915.015.916.7
12.814.015.015.916.7
13.214.115.015.716.4
13.914.815.516.216.8
9981193134814771588
11101300145915961717
11731324145415671669
12231365148615911684
12961448157616861783
13571493160817071795
13821505161017031786
15361640172718011866
Water
KLIMA 600-2400
11
Performance Data KLIMA 2 600
dBA
CoolingTroom minus T entering water temperature = 10 deg C
Cooling Water Flow 1 Cooling Water Flow 2 Cooling Water Flow 3 Heating Water Flow 1 Heating Water Flow 2 Heating Water Flow 3
Waterflow
l/s l/s l/s l/s l/s l/sdeg C deg C deg C deg C deg C
A1
B1
C1
E1
F1
G1
H1
deg C
A1
B1
C1
E1
F1
G1
H1
deg C
3000
3000
3000
3000
3000
3000
3000
3000
Performance table notes1) Air cooling capacities are based on Troom minus T primary air = 10 deg C. For other conditions multiply the table air cooling capacity by the required (Troom minus Tprimary air) divided by 10. Alternatively the air cooling capacity can be calculated from the formula: Air cooling capacity W = 1.213 x Airflow (l/s) x (Troom minus T primary air)2) Water cooling capacities are based on Troom minus T entering water temperature = 10 deg C. For other conditions multiply the table water cooling capacity by the required (Troom minusT entering water) divided by 10.3) Water heating capacities are based on 4 pipe chilled beams with T room minus T entering water temperature = 35 deg C. For other conditions multiply the table water heating capacity by the required (Troom minusT entering water) divided by 35.
10C
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.090.090.090.090.09
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.120.120.120.120.12
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.040.040.040.040.04
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.050.050.050.050.05
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
0.060.060.060.060.06
17 22 27 32 37
24 29 34 39 44
34 41 48 55 62
50 58 66 74 82
62 74 86 98110
75 90105120135
86104122140158
120145170195220
39 65 98138185
51 75102135172
50 73100131167
59 79103129159
52 73 99129162
48 70 95124157
50 72100131167
48 69 95125160
1618242933
1824283235
2530343741
3336404347
3541454952
3945495255
4147515458
4953565863
≤15≤15 19 24 28
≤15 19 23 27 30
20 25 29 32 36
28 31 35 38 42
30 36 40 44 47
34 40 44 47 50
36 42 46 49 53
44 48 51 53 58
206 267 328 388 449
291 352 412 473 534
412 497 582 667 752
607 704 801 898 995
752 898 1043 1189 1334
910 1092 1274 1456 1638
1043 1262 1480 1698 1917
1456 1759 2062 2365 2669
3.53.53.53.53.5
3.53.53.53.53.5
3.53.53.53.53.5
3.53.53.53.53.5
3.53.53.53.53.5
3.53.53.53.53.5
3.53.53.53.53.5
3.53.53.53.53.5
7.87.87.87.87.8
7.87.87.87.87.8
7.87.87.87.87.8
7.87.87.87.87.8
7.87.87.87.87.8
7.87.87.87.87.8
7.87.87.87.87.8
7.87.87.87.87.8
13.913.913.913.913.9
13.913.913.913.913.9
13.913.913.913.913.9
13.913.913.913.913.9
13.913.913.913.913.9
13.913.913.913.913.9
13.913.913.913.913.9
13.913.913.913.913.9
2.22.22.22.22.2
2.22.22.22.22.2
2.22.22.22.22.2
2.22.22.22.22.2
2.22.22.22.22.2
2.22.22.22.22.2
2.22.22.22.22.2
2.22.22.22.22.2
3.43.43.43.43.4
3.43.43.43.43.4
3.43.43.43.43.4
3.43.43.43.43.4
3.43.43.43.43.4
3.43.43.43.43.4
3.43.43.43.43.4
3.43.43.43.43.4
4.94.94.94.94.9
4.94.94.94.94.9
4.94.94.94.94.9
4.94.94.94.94.9
4.94.94.94.94.9
4.94.94.94.94.9
4.94.94.94.94.9
4.94.94.94.94.9
9461142129714261536
10851269142415581675
11111280142215451653
12501369147315651647
12861425154416461737
13201453156616631749
13311476159717011793
15321628170917791840
3.84.55.25.76.1
4.35.15.76.26.7
4.45.15.76.16.6
5.05.55.96.26.6
5.15.76.16.66.9
5.35.86.26.67.0
5.35.96.46.87.1
6.16.56.87.17.3
10941321150016491777
12551468164718021938
12851480164517871912
14461584170418101905
14871648178519042010
15271681181119242024
15401707184719682074
17721883197720572128
2.93.54.04.44.7
3.33.94.44.85.1
3.43.94.44.85.1
3.84.24.54.85.1
4.04.44.85.05.3
4.14.54.85.15.4
4.14.54.95.25.5
4.75.05.35.55.7
11861432162717891927
13611592178619542101
13931605178319372073
15681718184819632066
16131787193620652179
16561823196420862194
16701851200321342249
19212042214322312308
2.42.83.23.63.8
2.73.23.63.94.2
2.83.23.53.94.1
3.13.43.73.94.1
3.23.63.94.14.3
3.33.63.94.24.4
3.33.74.04.24.5
3.84.14.34.44.6
18532463294633463687
23112788318335203814
25352934327235643822
26332982328135433776
29123184342136313820
29293203343836443826
30133230342135913745
31843380355037003834
10.814.417.219.621.6
13.516.218.520.522.2
15.417.419.220.722.1
17.218.820.221.522.6
17.519.120.521.822.9
17.719.320.722.023.1
18.219.520.621.722.6
18.920.121.122.022.8
2299 3055 3654 4150 4573
2852 3441 3928 4344 4707
3267 3699 4070 4395 4685
3650 3990 4287 4551 4787
3705 4051 4352 4620 4860
3745 4095 4396 4658 4892
3852 4130 4374 4592 4788
4010 4257 4471 4660 4829
11.014.717.620.022.0
13.816.719.021.022.7
15.217.519.521.322.8
15.717.819.621.122.6
17.419.020.421.722.8
17.519.120.521.722.9
18.019.320.421.422.4
19.020.221.222.122.9
25803430410246585133
32183882443249015310
35304086455649635322
36674152456849335258
40554434476450565319
40784460478750735328
41954498476450015215
44334706494351525338
10.313.716.318.520.4
12.815.417.619.521.1
14.116.318.219.721.2
14.616.518.219.620.9
16.217.618.920.121.2
16.217.819.120.221.2
16.717.918.919.920.7
17.618.719.720.521.3
Water
KLIMA 600-3000
Selection example
Specified data:
Office (LxWxH) 7.2 (L) x 5.4 (W) x 2.7 (H) m
Occupants: 4
Minimum Ventilation 4 x 10 l/s = 40 l/s
Preferred size of chilled beams 1800 x 600 mm ( 2 units )
Summer room design condition ( Troom ) 24 deg C with 50% Relative Humidity (dew point 13.0 deg C)
Chilled Water temperature (Tw,in ) 15 deg C (Room Dew Point 13 deg C + 2 deg C)
Summer supply air temperature (T1 ) 12 deg C
Summer sensible room cooling load 2 700 W or 1350 W per chilled beam
Winter room design condition ( Troom ) 20 deg C with 50% Relative Humidity (dew point 9.0 deg C)
Heating water temperature (Tw,in ) 45 deg C
Winter supply air temperature (T1 ) 20 deg C
Winter heating requirement 2600 W or 1300 W per unit
Calculation:
The temperature differences required to make Determine required airflow for humidity control:
the cooling selection are: Room latent load = 4 people x 55W = 220W
ΔTAC = Troom - T1 = 24 – 12 = 12 deg C = 3.0 x Airflow l/s x ∆ humidity g/kg
ΔTWC = Troom - Tw,in = 24 -15 = 9 deg C Room condition 24 deg C 50% RH and humidity = 9.33 g/kg
The temperature differences required to make Supply air condition 12 deg C. Allow 1 deg C heat gain for
the heating selection are: AHU motor and duct heat gain so required off coil temp = 11
ΔTAH = T1 - Troom = 20 - 20 = 0 deg C deg C and with 98% RH and humidity = 8.03 g/kg
ΔTWH = Tw,in - Troom = 45 - 20 = 25 deg C Required primary airflow for humidity control
= 220 / [3.0 x(9.33 – 8.03)] = 56 l/s or 28 l/s per beam which is
more than the 40l/s or 20l/s per beam required for ventilation
Selection:
Model: Width: 600 mm
Length: 1800 mm
Performance table: Page 9
Primary airflow: 28 l/s per beam
Nozzle: B1
Static air pressure in plenum: 102 Pa
Cooling Performance
Available cooling from primary air: 1.213 x 28 x 12 = 407 W per unit
Required cooling from chilled water: 1350 – 407 = 943 W per unit
From page 9 select water cooling capacity: 1062 W per unit at ΔTWC = 10 deg C with water flow = 0.08 l/s
With ΔTWC = 9 deg C water cooling equals: 1062 x 9 deg C / 10 deg C = 956 W per unit
and water flow is: 0.08 l /s
water pressure drop is: 23.3 K pa
water temperature difference is: 956 W / ( 4.187 x 0.08 l/s x 1000) = 2.9 deg C
And total cooling capacity is: 407W + 956W = 1363W per unit x 2 units = 2726 W
This satisfies the total sensible cooling requirement of 2700 W for the room
Heating Performance
Available heating from primary air: 1.213 x 28 x 0 = 0 W per unit
Required heating from heating water: 1300 – 0 = 1300 W per unit
From page 9 select water heating capacity 1889 W per unit at ΔTWH = 35 deg C with water flow = 0.03 l/s
So water heating capacity for ΔTWC = 25 deg C 1889 x 25 deg C / 35 deg C = 1349 W per unit
and water flow is: 0.03 l /s
water pressure drop is: 0.9 K pa
water temperature difference is: 1349 W / ( 4.187 x 0.03 l/s x 1000) = 10.7 deg C
So total heating capacity is: 0W + 1349W = 1349 W x 2unit = 2698 W per unit
This satisfies the total sensible heating requirement of 2600 W
For non standard applications and/or selections, please contact our technical staff.
12Rev 140910
Guide Specifications
Barcol-Air KLIMA 600 series active chilled beams shall be used to compensate for the external and internal heat loads of the
building and shall maintain the thermal comfort in the room within the specified comfort and noise criteria.
Functional description
Primary air will be supplied by the fresh air handling unit to the chilled beam air plenum box. The primary air shall then
pass through the induction nozzles into the mixing section to mix with the induced room air before being distributed into the
room by two slot diffusers.
Induction nozzles shall induce air from the room through the inlet air diffuser and then through the fin and tube
cooling/heating heat exchanger before mixing with the primary air and being supplied to the room. The induction nozzles
shall be factory installed to provide the required unit capacity with the specified primary airflow, air inlet pressure and noise
level.
Heat exchangers shall be 2-pipe type for cooling only or cooling/heating changeover systems or 4 pipe type for systems
with separate cooling and heating circuits.
The units shall incorporate two linear slot air supply diffusers and shall be designed so that the supply air is discharged
horizontally under the ceiling using the “Coanda” effect to increase the air throw and to ensure the air mixing with the room air
above the occupied zone. The centre diffuser shall be perforated to allow the room air to flow in to the heat exchanger and
shall be easily removable to allow for any accumulated dust to be removed from the heat exchanger with a vacuum cleaner.
The centre diffuser shall be provided with safety hanging wires.
Construction of the chilled beam:
The primary air plenum box shall be manufactured from galvanized sheet steel and shall have one or more circular air
spigot connectors to ensure the inlet air velocity does not exceed 2.5 m/s. The plenum should be internally insulated to
prevent condensation if the primary supply air temperature is less than the surrounding air dew point temperature.
The nozzle plate and chilled beam body shall be manufactured from galvanized steel with a minimum thickness of 0.8mm.
The heat exchangers shall be made from seamless copper tubes with aluminum fins and shall have 12 or 15 mm diameter
water connections depending on unit's size and connections. The heat exchangers shall be suitable to operate at 15 bar
working pressure and shall be factory pressure tested at 20 bar pressure.
The supply air diffuser and room air inlet diffuser shall be manufactured from galvanized steel with a minimum thickness
of 1.0 mm and shall be finished with polyester powder paint to RAL9010 with 20% gloss or with an alternative finish to be
specified.
Dimensions
Width: The chilled beam shall be 595 mm wide.
Length: The units shall be 1200, 1500, 1800, 2400 and 3000 mm long or any intermediate length by special order.
Height: The height of the chilled beam (including distribution plenum) shall not be more than 200mm.
Installation
The chilled beam shall have 7 mm diameter mounting holes for suspension by 6mm diameter threaded rod or suspension
wires.
13Rev 140910