• REFER TO PLANS FOR PARTITION TAGS, NOT ALL PARTITION ASSEMBLIES ARE USED.• WHERE A PARTITION IS SHOWN WITHOUT A TAG, USE PARTITION TYPE P3, FULL HEIGHT WITH SOUND ATTENUATION.• WALL AND PARTITION TYPE ARE FOLLOWED BY A LETTER DESIGNATION INDICATING THE FOLLOWING REQUIREMENTS
WHERE USED (MORE THAN ONE LETTER MAY BE USED):
*ALL FIRE RATED WALLS ARE FULL HEIGHT, CONTINUOUS
A = NON RATED FIRE SEPARATIONB = 30 MINUTE FIRE SEPARATIONC = 45 MINUTE FIRE SEPARATIOND = 60 MINUTE (1 HR) FIRE SEPARATIONE = 90 MINUTE (1.5 HR) FIRE SEPARATIONF = 120 MINUTE (2 HR) FIRE SEPARATIONG = 180 MINUTE (3 HR) FIRE SEPARATIONH = FULL HEIGHT PARTITIONJ = WALL HEIGHT TO MIN. 150MM ABOVE CEILINGSK = WALL TO FINISH AT U/S CEILING, TAPEABLE L MOLD @ T-BAR, TAPE @ GYPL = LOAD BEARING WALLM = WALL HEIGHT TO U/S FLOOR/CEILING JOISTSN = LOW WALL TO HEIGHT AS INDICATEDP = INFILL CONSTRUCTION TO MATCH EXISTING PARTITION THICKNESSS = SOUND ATTENUATION INSULATION, ACOUSTIC SEAL TO AND BOTTOM TRACK CONTINUOUS
Wall and Partition Type Legend
Interior Partition Assemblies - New Construction - Metal Stud
TAG ASSEMBLY THICKNESS
P3
16 GYPSUM BOARD92 METAL STUDS @ 400 O/CSOUND ATTENUATION BATT INSUL16 GYPSUM BOARD
124
4 7/8"
5/8" GYPSUM BOARD3 5/8" METAL STUDS @ 16" O/CSOUND ATTENUATION BATT INSUL5/8" GYPSUM BOARD
UNITSVISUAL
M
SI
ULC
P9
108
4-1/4"5/8" GYPSUM BOARD3 5/8" METAL STUDS @ 400 O/C5/8" GYPSUM BOARD
M
SI
16 GYPSUM BOARD92 METAL STUDS @ 16" O/C16 GYPSUM BOARD
25 GYPSUM SHAFTWALL LINER PANEL (TYPE 'X')
64 CH STUDS @ 400 O/C16 TYPE 'X' GYPSUM BOARD
ULC REFERENCE: ULC W446
1 HOUR MAXIMUM FIRE RESISTANCE RATING (F.R.R.) BASED ON ULC DESIGN. REFER TO FIRE RATING DESIGNATIONS AND FIRE SEPARATION PLANS FOR REQUIRED RATING & LOCATIONS.
FIRE STOP CAULKING AT TOP AND BOTTOM OF WALL + PENETRATIONS
4-1/4"M
SI
P401" GYPSUM SHAFTWALL
LINER PANEL (TYPE 'X')3-1/8" CH STUDS @ 400 O/C5/8" TYPE 'X' GYPSUM BOARD
3-1/8"
BUILDING CODE REF.
11.01 PROJECT TYPE
11.02 MAJOR OCCUPANCY CLASSIFICATION
11.03
ONTARIOBUILDING CODEDATA MATRIX
PART 11RENOVATION OF EXISTING BUILDING
BUILDING CODE VERSION: O. REG. 332/12
LAST AMMENDMENT: O. REG. 191/14
SUPERIMPOSED MAJOR OCCUPANCIES
11.05
11.06
BUILDING HEIGHT
11.07
NUMBER OF STREETS / FIREFIGHTER ACCESS
BUILDING SIZE
[A] 1.1.2
3.1.2.1.(1)
ADDITION RENOVATION ADDITION & RENOVATION CHANGE OF USE
DESCRIPTION:
OCCUPANCY:
USE:
NO YES
DESCRIPTION:
3.2.2.7
STOREYS ABOVE GRADE2
STOREYS BELOW GRADE1
(m) ABOVE GRADEUNKNOWN [A] 1.4.1.2 & 3.2.1.1
STREET(S)1 3.2.2.10 &3.2.5
SMALL MEDIUM LARGE > LARGE T.11.2.1.1.B-N
11.08 EXISTING BUILDING CLASSIFICATION
CHANGE IN MAJOR OCCUPANCY: NOT APPLICABLE (NO MAJOR CHANGE OF OCCUPANCY)YES
CONSTRUCTION INDEX:
HAZARD INDEX:
11.10 OCCUPANT LOAD
11.11 PLUMBING FIXTURE REQUIREMENTS
11.12
11.13 REDUCTION IN PERFORMANCE LEVEL
BARRIER-FREE DESIGN
11.14
11.15
COMPENSATING STRUCTURE
11.16
COMPLIANCE ALTERNATIVESPROPOSED
NOTES
3.1.17
3.7.4RATIO:
NO YES
EXPLANATION: POWER DOOR OPERATORS PROVIDED / BARRIER-FREE PATH OF TRAVEL
11.3.3.2.(2)
11.4.2.111.4.2.211.4.2.311.4.2.411.4.2.511.4.2.6
11.4.3.111.4.3.211.4.3.311.4.3.411.4.3.511.4.3.611.4.3.7
11.5.1.1
11.5.1.1
IMPORTANCE CATEGORY: LOW NORMAL
HIGH POST-DISASTER
11.09 RENOVATION TYPE BASIC RENOVATION EXTENSIVE RENOVATION
FLOOR LEVEL / AREA OCCUPANCY TYPE BASED ON OCCUPANT LOAD
N/A
FLOOR LEVEL / AREA OCCUPANCY TYPE BASED ON OCCUPANT LOAD
DESIGN OF SPACE 59OFFICESMAIN FLOOR / 200m2
N/A N/AN/AN/A
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
STRUCTURAL:
BY INCREASE IN OCCUPANT LOAD:
BY CHANGE OF MAJOR OCCUPANCY:
PLUMBING:
SEWAGE-SYSTEMS:
EXTENSION OF COMBUSTIBLE CONSTRUCTION:
NO YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
STRUCTURAL:
BY INCREASE IN OCCUPANT LOAD:
BY CHANGE OF MAJOR OCCUPANCY:
PLUMBING:
SEWAGE-SYSTEMS:
EXTENSION OF COMBUSTIBLE CONSTRUCTION:
NO YES (LIST NUMBERS AND DESCRIBE)
(LIST NUMBERS AND DESCRIBE)
(LIST NUMBERS AND DESCRIBE)
NOTES: ALL REFERENCES ARE TO DIVISION B OF THE OBC UNLESS PRECEDED BY [A] FOR DIVISION A AND [C] FOR DIVISION C
11.3.3.111.3.3.2
11.2.1.1
T11.2.1.1AT11.2.1.1 B TO N
4.2.1.(3)5.2.2.1.(2)
"
"
"
"
"
"
INTERIOR RENOVATION
OFFICES
GROUP D OCCUPANCY
N/A
N/A
N/A
NAME OF PRACTICE:CERTIFICATE OF PRACTICE:NAME OF PROJECT:PROJECT LOCATION:
CORY R STECHYSHYN INC - O/A I4ARCHITECTURE4394LAKEHEAD UNIVERSITY ABORIGINAL INITIATIVES INTERIOR RENOVATION955, OLIVER ROAD, THUNDER BAY
D1001
W1
STRUCTURAL GRID & BUBBLE
ROOM NAME & NUMBER TAG
ELEVATIONS
CEILING HEIGHT
DOOR NUMBER TAG
INTERIOR/EXTERIOR WALL TYPE TAG
WINDOW TYPE TAG
CEILING MATERIAL
DETAIL NUMBER
SHEET NUMBER WHEREDETAIL REFERENCE FOUND
SHEET NUMBER WHEREDETAIL IS DRAWN
EXTERIOR & INTERIOR BUILDING ELEVATION
CEILING TAG
SHEET NUMBER WHERE DRAWN
Level NameElevation
PARTITION TYPEPARTITION FIRE RATING / LEGEND DESIGNATION
ROOM NAME101
ROOM NAME, NUMBER & AREA TAGROOM NAME
101150 m²
CURTAIN WALL TAG
Symbol Legend
0
A101
1
1
1
1
R1
ENLARGED PLANS & DETAILS
F1
P????
XXXXXXXXX
Ref
XXXXXXXXX
Ref
XXAX.XX AX.XX
RefBUILDING SECTION
DETAIL NUMBER
SPOT ELEVATIONS
REFERENCE SIMILAR/ TYPICAL DETAIL
ROOF TYPE TAG
FLOOR TYPE TAG
SCREEN TAG
ACT 1' - 0"
S1
C1
Abbreviations
ATNUMBER, POUNDABOVEACOUSTIC CEILING TILEABOVE FINISHED FLOORALUMINUMACOUSTICAL METAL CEILINGSACOUSTICAL WOOD CEILINGSANODIZEDARCHITECTURALAIR/VAPOUR BARRIER
BOTTOM OFBOARDBEDROOMBARRIER FREEBULKHEADBUILDINGBASEMENTBEYOND
CENTER TO CENTERCLEAR OPENINGCHANNELCENTER LINECEILINGCLEARCONCRETE MASONRY UNITCOLUMNCONCRETECONSTRUCTIONCONTINUOUSCARPET CERAMIC WALL TILE
DOUBLEDEMOLISH, DEMOLITIONDEPARTMENTDOUBLE GLAZINGDIAMETERDIMENSION/DIMENSIONSDOWNDRAWING/DRAWINGS
EPOXY FLOOR COATINGEXTERIOR INSULATION AND FINISH SYSTEMELEVATORELECTRICALETHYLENE PROPYLENE DIENE MONOMER EQUALEACH WAYEXISTINGEXPOSEDEXTERIOR
@#ABVACTAFFALUMAMCAWCANODARCHAVB
B/OBDBDRMBFBLKHDBLDGBSMTBYND
C/CC/OCHNLCLCLGCLRCMUCOLCONCCONSTCONTCPTCWT
DBLDEMODEPTDGLDIADIM/DIMSDNDWG/DWGS
EFCEIFSELEVELECEPDMEQE/WEX/EXISTEXPEXT
ON CENTEROUTSIDE FACEOVERHEADOPENING
PLASTIC LAMINATEPERIMETERPERPENDICULARPLYWOODPLUMBINGPRE-CAST CONCTRETEPRE-FINISHEDPAINTPAINTEDPRESSURE TREATED LUMBERPARTITIONPOLYVINYL CHLORIDE
REFLECTED CEILING PLANROOF DRAINRECEPTACLEREQUIREDROOMROUGH OPENINGRUBBER BASE
SALVAGESCHEDULE SCUPPER DRAINSQUARE FOOTSAFETY GLASSSHOWERSIMILARSPECIFICATIONSPEAKERSQUARESTAINLESS STEELSOUND TRANSMISSION CLASSSTANDARDSTEELSTORAGESTRUCTURE, STRUCTURALSTAIRWAYSHEET VINYL FLOORING
O/CO/FO/HOPNG
PLAMPERIMPERPPLYWDPLUMBPRECASTPREFINPTPTDPTLPTNPVC
RCPRDRECEPREQDRMR/ORUB
SALVSCHEDSDSFSGLSHWRSIMSPECSPKSQSSSTCSTDSTLSTORSTRUCTSTWYSV
FACE TO FACEFACE OFFLOOR DRAINFIRE HOSE CABINETFIXTUREFLOORFOUNDATIONFOOT
GUAGEGALVANIZEDGLASS, GLAZINGGYPSUM BOARD
HOLLOW COREHOLLOW METALHORIZONTALHOURHEATING, VENTILATING
AND AIR CONDITIONING
INSIDE FACEINCHESINSULATIONINTERIOR
JANITORJANITOR’S CLOSET
LAMINATELINOLEUMLANDINGLOUVER
METERMATERIALMAXIMUMMECHANICALMEDIUMMEMBRANEMEZZANINEMANUFACTURERMINIMUMMILLIMETERMOUNTEDMETALMULLIONMILLWORK
NORTHNOT IN CONTRACTNUMBERNOMINALNOT TO SCALE
F/FF/OFDFHCFIXTFLRFNDNFT
GAGALVGLGYP
HCHMHORIZHRHVAC
I/FININSTINSUL
JANJC
LAMLINLNDGLVR
MMATLMAXMECHMEDMEMBMEZZMFRMINMMMTDMTLMULMWK
NNICNONOMNTS
TOP OFTONGUE AND GROOVETELEPHONETERRAZZOTELEVISIONTYPICAL
UNDERSIDEUNFINISHED
VACUUMVAPOURVINYL COMPOSITION TILEVERTICALVESTIBULE
WITHWITHOUTWATER CLOSETWOODWASHROOM
T/OT>ELTERRTVTYP
U/S UNFIN
VACVBVCTVERTVEST
W/W/OWCWDWR
AREA OF WORK
LAKETAMBLYN
EXIT
AGORA CIRCLE
EXIT
EXIT
27.1m +/- TRAVEL DISTANCE
21.6m +/- TRAVEL DISTANCE
COPYRIGHT NOTICE:
Copyright of this electronic document belongs to Cory R. Stechyshyn Architect
Inc o/a i4architecture.
This electronic document may not be forwarded to others, transmitted,
downloaded or reproduced in any format, whether print or electronic, without the
express, written permission of the copyright owner.
Scale
Drawn by
Project No.
12 St Paul St.Thunder Bay, ON, CAP7A 4S5
807.346.2277 (office)8555.558.1459 (fax)i4a.ca
Project Name
Project Address
Sheet Name
Sheet Number
Professional Seal
DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION UNLESS ARCHITECTS SEAL IS AFFIXED, SIGNED AND DATED.
As indicated
955 Oliver Road, Thunder Bay, ON, P7B 5E1
Cover Sheet,Drawing Sheet List,Wall Assemblies,Wall Type Legend,OBC Matrix,Symbol Legend,Abbreviations &Key Plan
Lakehead UniversityAboriginalInitiatives - InteriorRenovation
A0.0
2017-68
TNG / NCM
955 Oliver Road,Thunder Bay, ON,P7B 5E1
Lakehead University Aboriginal Initiatives - Interior Renovation
Architectural Sheet List
Sheet Number Sheet NameCurrentRevision
A0.0 Cover Sheet, Drawing Sheet List, Wall Assemblies, Wall Type Legend, OBC Matrix, Symbol Legend, Abbreviations & Key Plan DA0.1 Room Finish Schedule, Door & Frame Schedule, Door & Frame Type Legend, Fire Seperation Legend, Fire Seperation Plan & Furniture / Finish Plan CA2.0 Renovated Floor Plan & Reflected Ceiling Plan, Construction Notes & Existing Plan & 3D View DA5.0 Interior Elevations & Typical Millwork Section Details C
Electrical Engineering Sheet ListSheet No. Sheet Name
E1 Electrical Specifications & Power Layout
Mechanical Engineering Sheet ListSheet No. Sheet Name
MP-1 New Plumbing Layout, Notes & DetailsMV-1 New Ventilation Layout, Notes & DetailsMS-1 Mechancial Specifications
PRIME CONSULTANT:
i4architecture12 St. Paul StreetThunder Bay, Ontario, P7A 4S5
Tel: (807) 346.2277Fax: (855) 558.1459www.i4a.ca
MECHANICAL ENGINEER:
Cuthbertson Engineering
ELECTRICAL ENGINEER:
AG Engineering111 Victoria Ave EThunder Bay, ONP7C 1B7
Tel: (807) 622-3654Fax: (807) 622-3633www.agpeng.com
Scale = 1" = 40'-0"A0.01 Key Plan
111 Victoria Ave EThunder Bay, ONP7C 1B7
Tel: (807) 622-3600www.manta.com/ic/mtzml2l/ca/cuthbertson-ltd
Rev. No. Description DateA ISSUED FOR 75% REVIEW 23-JUL-2018B ISSUED FOR 95% REVIEW 12-SEP-2018C ISSUED FOR 100% REVIEW 19-SEP-2018D ISSUED FOR PERMIT &
CONSTRUCTION20-SEP-2018
20-SEP-2018
1. LEVER HANDLE2. CLOSER3. BARN DOOR HARDWARE4. CLEAR SWING HINGES5. OVERHEAD STOP6. WALL STOP7. WEATHERSTRIPPING & AUTO BOTTOM
Notes - Door and Frame Schedule
HM PROFILE - WRAP
THIC
KNES
S
SEE
SCHE
DULE
FO
R PA
RTIT
ION
51 20
10
51.
51
VARIES
HM PROFILE - BUTT
THIC
KNES
S
SEE
SCHE
DULE
FO
R PA
RTIT
ION
51 20
51.
51
VARIES
Door Frame Profile
Door Type Legend
VARIES
VARI
ES
VARIES
VARI
ES
3'-0"
VARI
ES6"
6" VARIES 6"VARIES 8" 6"
3'-0"
VARI
ES6"
VARIES
VARI
ES
6" VARIES 6"
10"
1'-6"
8"VA
RIES
5 7/8"
VARIES
VARI
ES
DOORTYPE 'D3'
DOORTYPE 'D2'
DOORTYPE 'D4'
NOTE:
1. REFER TO DOOR AND FRAME SCHEDULE FOR DOOR DIMENSIONS.
2. REFER TO SPECIFICATIONS FOR APPROVED MANUFACTURERS. DIMENSIONS MAY VARY TO SUIT FRAME MATERIAL AND PROFILES AVAILABLE.
3. REFER TO DOOR AND FRAME SCHEDULE FOR TYPE OF GLAZING OR INSERTS.
4. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF DOOR LOUVERS.
5. REFER TO PLANS AND INTERIOR ELEVATIONS FORSWING OR OPERATION OF DOOR.
VARI
ES
VARIES
DOORTYPE 'D1'
GLGL
3'-0"
GL
GL
DOORTYPE 'D5'
GL
DOORTYPE 'D6'
VARI
ES
VARIES
GL
6"VA
RIES
10"
6" VARIES 6"
MANAGER OFFICE103
RECEPTION101
COMMUNITY PARTNERPROGRAM ROOM
108
STORAGE109
LOUNGE AREA105
COMPUTER WORK STATIONS (10)
FHC
TV ABOVE
SEATING AREA110
MULTI PURPOSE AREA111
COUNSELOR'S OFFICE106
ELDER'S ROOM107
TEL
MEDI
CINE
CA
BINE
T
FILE
SHEL
VING
PRINTER NIC
FAXNIC
LAMP
PRINTERNIC
WHITEBOARD / SCREEN (NIC) - SEE ELEV
STOR
AGE
SHEL
VING
SHEL
VING
SHELVING
HOOKS
DISPLAY CABINET
STORAGE CABINETS W/ PULL OUT SHELVES
MICROWAVE
RELOCATED BULLETIN BD CABINET
FILE
FILE
CLOTHES TREE
SVEX
IST
EX TILE SV
WAITING AREA100
JAN / ELEC RM102
FILE RM104
FRIDGE
DISHWASHER
0 min FIRE RESISTANCE RATING (F.R.R.) ON WALL
30 min FIRE RESISTANCE RATING (F.R.R.) ON WALL
1 h FIRE RESISTANCE RATING (F.R.R.) ON WALL
TRAVEL DISTANCE (METERS)
EXIT LOCATION
45 min FIRE RESISTANCE RATING (F.R.R.) ON WALL
1.5 h FIRE RESISTANCE RATING (F.R.R.) ON WALL
2 h FIRE RESISTANCE RATING (F.R.R.) ON WALL30 30 3030
0 00
60 6060 60
9090 90
120 120 120
Fire Separation Legend
FRAME TYPE "F1"
50 VARIES 50
VARI
ES50
FRAME TYPE "F2"
50 500 50 VARIES 50
VARI
ES50
FRAME TYPE "F4"FRAME TYPE "F3"
Frame Type Legend
FOLD
LIN
E
FOLD
LIN
E
FOLD
LIN
E
8'-0"
7'-0"
1'-0"
10"
8'-0"
5'-1 5/8"
1'-6"
1'-0"
7'-0"
10"
3'-0"
2"1'-7 5/8"2"
2" 1'-10" 2" 1'-10" 4 7/8" 3'-2 1/4" 4 7/8" 6'-8" 4 7/8" 3'-4 1/8" 4 7/8"1'-10 1/8"2"
8"10
"
MANAGER OFFICE103
RECEPTION101
COMMUNITY PARTNERPROGRAM ROOM
108
STORAGE109
LOUNGE AREA105
SEATING AREA110
MULTI PURPOSE AREA111
COUNSELOR'S OFFICE106
ELDER'S ROOM107
TRAVEL DISTANCE = 18.24m
6060
6060
6060
60
6060
60
WAITING AREA100
JAN / ELEC RM102
FILE RM104
MECH CHASE
60
60
60 60
60
606060
60
60
NEW SHAFT WALL C/W 1-HR FIRE RATING
6060
60
60 60 60 60 60 60 60 60
COPYRIGHT NOTICE:
Copyright of this electronic document belongs to Cory R. Stechyshyn Architect
Inc o/a i4architecture.
This electronic document may not be forwarded to others, transmitted,
downloaded or reproduced in any format, whether print or electronic, without the
express, written permission of the copyright owner.
Scale
Drawn by
Project No.
12 St Paul St.Thunder Bay, ON, CAP7A 4S5
807.346.2277 (office)8555.558.1459 (fax)i4a.ca
Sheet Number
Professional Seal
DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION UNLESS ARCHITECTS SEAL IS AFFIXED, SIGNED AND DATED.
Project Name
Project Address
Sheet Name
As indicated
A0.1
2017-68
TNG
Room FinishSchedule, Door &Frame Schedule,Door & Frame TypeLegend, FireSeperation Legend,Fire SeperationPlan & Furniture /Finish Plan
Lakehead UniversityAboriginalInitiatives - InteriorRenovation
955 Oliver Road,Thunder Bay, ON,P7B 5E1
Room Finish Schedule
ROOM NO. ROOM NAME
FLOOR WALLS CEILING
COMMENTSMAT'L BASENORTH EAST SOUTH WEST
MAT'L FINISH HEIGHTMAT'L FINISH MAT'L FINISH MAT'L FINISH MAT'L FINISH100 WAITING AREA SV RUB GYP PT GYP / EX CONC BLOCK PT GYP PT GYP PT ACT - 8'-0"101 RECEPTION SV RUB - - GYP PT GYP PT GYP PT GYP PT 7'-6"102 JAN / ELEC RM EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST103 MANAGER OFFICE SV RUB EX CONC BLOCK PT EX CONC BLOCK PT EX CONC BLOCK PT EX CONC BLOCK PT ACT - 8'-0"104 FILE RM SV RUB EX CONC BLOCK PT EX CONC BLOCK PT EX CONC BLOCK PT EX CONC BLOCK PT ACT - 8'-0"105 LOUNGE AREA SV RUB EX CONC BLOCK / GYP PT GYP PT GYP PT EX CONC BLOCK PT ACT / WD-L - 8'-0" / 7'-9" +/-106 COUNSELOR'S OFFICE SV RUB GYP PT EX CONC BLOCK PT GYP PT GYP PT ACT - 8'-0"107 ELDER'S ROOM SV RUB GYP PT EX CONC BLOCK PT GYP PT GYP PT ACT - 8'-0"108 COMMUNITY PARTNER PROGRAM ROOM SV RUB GYP PT EX CONC BLOCK PT GYP PT GYP PT ACT - 8'-0"109 STORAGE SV RUB GYP PT EX CONC BLOCK PT EX BRICK PT GYP PT ACT - 8'-0"110 SEATING AREA SV RUB GYP PT GYP PT - - GYP PT ACT - 8'-0"111 MULTI PURPOSE AREA SV RUB - - GYP PT EX BRICK PT GYP PT ACT - 8'-0"
Door and Frame Schedule
DOOR NO. ROOM NAME
DOOR FRAME FIRERATING(MIN.) COMMENTS HARDWARE
NO.LEAFS WIDTH HEIGHT TYPE MAT'L FINISH
FRAMEPROFILE TYPE MAT'L FINISH
D100 WAITING AREA 2 6' - 4" 7' - 0" D4 HM PT WRAP F1 HM PT 1 HR W/ SIDELITE & TRANSOM - ALL GLAZING TO BE FIRE-RATED 1, 2D101 RECEPTION 1 3' - 0" 7' - 0" D1 WD CLEAR - - - - - BARN STYLE DOOR 3D102 JAN / ELEC RM 1 3' - 0" 7' - 0" D1 HM PT BUTT F2 HM PT 1 HR - 1, 2D103 MANAGER OFFICE 1 3' - 0" 7' - 0" D3 WD CLEAR BUTT F2 HM PT - FIELD VERIFY EXISTING OPENING 1, 4, 6 ,7D105 LOUNGE AREA 1 3' - 2" 7' - 0" D1 HM PT WRAP F4 HM PT - W/ SIDELITE & TRANSOM 1, 2, 5
D106A COUNSELOR'S OFFICE 1 3' - 2" 7' - 0" D1 WD CLEAR WRAP F2 HM PT - - 1, 6, 7D106B COUNSELOR'S OFFICE 1 3' - 2" 7' - 0" D1 WD CLEAR WRAP F3 HM PT - W/ SIDELITE 1, 6, 7D107 ELDER'S ROOM 1 3' - 2" 7' - 0" D1 WD CLEAR WRAP F3 HM PT - W/ SIDELITE 1, 6, 7D108 COMMUNITY PARTNER PROGRAM ROOM 1 3' - 2" 7' - 0" D1 WD CLEAR WRAP F3 HM PT - W/ SIDELITE 1, 6, 7D109 STORAGE 1 3' - 2" 7' - 0" D1 WD CLEAR WRAP F2 HM PT - - 1, 6
Scale = 3/16" = 1'-0"A0.11 Furniture / Finish Plan
Rev. No. Description DateA ISSUED FOR 95% REVIEW 12-SEP-2018B ISSUED FOR 100% REVIEW 19-SEP-2018C ISSUED FOR PERMIT &
CONSTRUCTION20-SEP-2018
MECH CHASE
Scale = 3/16" = 1'-0"A0.12 Fire Separation Plan
20-SEP-2018
EXIST'G DRINKING FOUNTAIN
MECH CHASE
EXIST'G MOP SINK
EXPOSED CONC BLOCK EXPOSED BRICK
EXPOSED CONC BLOCK
6'-1 1/2" 10'-0 1/2"
9'-11
"
34'-4
1/8"
59'-7"
EXPOSED CONCRETE
BLOCK
FHC
EXISTING SPACE HAS BEEN DEMOLISHED & IS READY FOR NEW CONSTRUCTION
15'-9
"
EXPOSED CONCRETE
BLOCK
4'-0"
MANAGER OFFICE103
RECEPTION101
COMMUNITY PARTNERPROGRAM ROOM
108
STORAGE109
LOUNGE AREA105
FHC
SEATING AREA110
MULTI PURPOSE AREA111
COUNSELOR'S OFFICE106
ELDER'S ROOM107
9'-0 1/2"
9'-11
"
4'-7 1
/2"
6'-1 1/2"
RELOCATED BULLETIN BD CABINET
D106
B
D107
D108
D109
D106A
D101
D100
12'-0
1/2"
O/F STUD
12'-1 1/4" 3 5/8"
O/F STUD
12'-1 1/4" 3 5/8"
O/F STUD
9'-0 5/8" 3 5/8"
O/F STUD
7'-1 3/4"
15'-10 1/8"
P3HS
P3HS
P3H
P24H
P24H
P24H
A5.0
2
1
A5.0 4
22'-0
"
P3HS
P3HS
P3HS
4'-4 7
/8"
4'-0"
3'-9"
6'-8"
2'-5"
EXIST'G DRINKING FOUNTAINS
EXIST'G MOP SINK
MECH CHASE
P3HS
P3HS
CLEA
R
3'-0"
CN-01
CN-02
2'-1 1/2"
16'-3
3/4"
2'-1 1/2" 18'-1 3/8" 3'-0" 3'-0" 13'-0 1/4"
7A2.0 A5.0
SV CPT
3'-6"
12'-2
3/8"
P3H
59'-7" (FIELD VERIFY)
FILE RM104
JAN / ELEC RM102
WAITING AREA100
A5.06
3'-8"
CLEA
R
6'-0"
D105
D102
D103
5'-6"
CN-01
P3HS
P40DH
P40DH
CN-01
CN-02 CN-02 CN-02
DISHWASHER
FRIDGE
2'-61
/4"6'-
81/4"
GROMMETS
2'-6"
2'-11
/2"
2'-8" 1'-0" 1'-6" 4'-11" 2'-1"
7'-75
/8"
3'-6"2'-10" CLEAR
4'-0"
3'-75
/8"
3
8"
P40DH4
A2.0A2.0
4'-17
/8"
GYP 8' - 0"
GYP 7' - 6"
ACT-1 8' - 0"ACT-1 8' - 0"
ACT-1 8' - 0" ACT-1 8' - 0"
ACT-1 8' - 0" ACT-1 8' - 0"
ACT-1 8' - 0"
LOUNGE AREA105
SEATING AREA110
MULTI PURPOSE AREA111
RECEPTION101
COUNSELOR'S OFFICE106
ELDER'S ROOM107
COMMUNITY PARTNERPROGRAM ROOM
108
STORAGE109
MANAGER OFFICE103
ACT-1 8' - 0"
4'-71
/2"6"
4'-7"
1'-2"
4'-11
1/8"
47/8"
10'-5
"0"
12'-4
5/8"
6'-25
/8"
45'-2
5/8"
2'-0" 15'-9 1/2" 4 7/8" 41'-4 5/8"
59'-7"
11'-1
17/8"
47/8"
21'-1
13/8"
34'-4
1/8"
19'-1 1/8" 4 7/8" 12'-0" 4 7/8" 12'-0" 4 7/8" 8'-11 3/8" 4 7/8" 7'-1 1/8"
9'-5"
60'-9 1/8"
3'-8 1/2" 6" 6'-1 1/2" 1'-0" 9'-0 1/2"
20'-4 1/2"
3'-4 1/8" 6'-4 7/8" 9'-6"
VALANCE UNDER CABINET LIGHITNG
VALANCE UNDER CABINET LIGHITNG
EXIST TO REMAIN
FILE RM104
MECH CHASE
JAN / ELEC RM102
WAITING AREA100
WD-L 7'-9" +/-
GYP BLKHD
CEILING PLAN SYMBOL LEGEND
CALLA - 24"x24" - TEGULARACT-1
SUPPLY AIR DIFFUSER
GYPSUM BOARDGYP
WOODWORKS LINEAR VENEERED PANELS - TAPEREDWD-L
EXPOSED STRUCTURE PAINTEDEXP PT
SUPPLY AIR DIFFUSER - LINEAR
WALL SCONCE
RECESSED FIXTURE - 24"x24"
RETURN AIR GRILLE
CIRCULAR RECESSED DOWNLIGHT
RETURN AIR GRILLE - WALL MTD
11" +/-
FHC
8"+/-
P40DH
WAITING AREA100
FIRE DAMPER -SEE MECH
RETURN GRILLE -SEE MECH
DEMOLISH EXIST'G CONC BLOCK + BRICKAS REQ'D FOR INSTALLATION OF RETURN AIR DUCT
P40DH
P40DH
COPYRIGHT NOTICE:
Copyright of this electronic document belongs to Cory R. Stechyshyn Architect
Inc o/a i4architecture.
This electronic document may not be forwarded to others, transmitted,
downloaded or reproduced in any format, whether print or electronic, without the
express, written permission of the copyright owner.
Scale
Drawn by
Project No.
12 St Paul St.Thunder Bay, ON, CAP7A 4S5
807.346.2277 (office)8555.558.1459 (fax)i4a.ca
Sheet Number
Professional Seal
DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION UNLESS ARCHITECTS SEAL IS AFFIXED, SIGNED AND DATED.
Project Name
Project Address
Sheet Name
As indicated
A2.0
2017-68
EMC + TNG
Renovated FloorPlan & ReflectedCeiling Plan,Construction Notes& Existing Plan &3D View
Lakehead UniversityAboriginalInitiatives - InteriorRenovation
955 Oliver Road,Thunder Bay, ON,P7B 5E1
Scale = 3/16" = 1'-0"A2.01 Existing Main Floor Plan
Scale = 3/16" = 1'-0"A2.03 Renovation Plan
Scale = 3/16" = 1'-0"A2.05 Renovation Reflected Ceiling Plan
Construction NotesMark Description
CN-01 PATCH & MAKE GOOD EXISTING CONCRETE BLOCKCN-02 RUN GYPSUM IN FRONT OF BRICK PLASTER
Scale =A2.02 3D View
Rev. No. Description DateA ISSUED FOR 75% REVIEW 23-JUL-2018B ISSUED FOR 95% REVIEW 12-SEP-2018C ISSUED FOR 100% REVIEW 19-SEP-2018D ISSUED FOR PERMIT &
CONSTRUCTION20-SEP-2018
Scale = 3/4" = 1'-0"A2.0A2.04 Plan Detail @ Shaft Wall
20-SEP-2018
VALENCE PANELS ABOVE CABINETS TO U/S T-BAR CLG
3'-0"
UPPE
RS1'-
71/2"
2'-71
/2"UP
PERS
9"PA
NEL
8'-0"
FIEL
DVE
RIFY
3'-0" CORNER 2'-3" 2'-3" 1'-3" 2'-7"
6'-0"
1'-3"
9"PA
NEL
11'-4" FIELD VERIFY
11/2"
TILE BACKSPLASH
4"TO
EKIC
K
EE
1'-0" 1'-0" 2'-3" 7'-1"
FRIDGE SUPPLIED BY
OWNER
MICROWAVESUPPLIED BY
OWNER
VALENCE LIGHTING -SEE ELEC
3/4" MILLWORK GABLE END PANELTO U/S OF VALANCE
VALENCE PANELS ABOVE CABINETS TO U/S T-BAR CLG
3/4" MILLWORK GABLE END PANELTO U/S OF VALANCE
3/4" MILLWORK GABLE END PANELTO U/S OF VALANCE
2'-0"1'-0"1'-0"2'-0"3'-0"1'-6"
3'-0"
1'-71
/2"3'-
41/2"
10'-6 3/4"
3'-0" 3'-0" 3/4" 3'-2 1/2" 3'-2 1/2" 3'-2 1/2" 3/4"
RAKKS 18" x 24" COUNTERSUPPORT BRAKCET (TYP)4" MAX SPACING
4" PULL OUT DRAWERS
LOCKABLE
3/4" 1'-0" 2'-6" 2'-6" 2'-6" 2'-0"
5'-6"
2'-6"
CLEAT - TYP
4" TILE BACKSPLASH S
8'-0"
FIEL
DVE
RIFY
4"
VALENCE LIGHTING -SEE ELEC
DISHWASHER SUPPLIED BY
OWNER
E E ETILE
BACKSPLASH
ED
4'-10 1/8" 3'-5" 3'-5" 3'-5" 3/4"
GROMMETS - TYP
15'-1" 6'-1 1/2" 9'-7 3/8"
E
ED ED ED
EE
3"2'-
6"11
/2"1'-
71/2"
3'-0"
7'-6"
FILLER 2'-0" 2'-0" 2'-0" 1'-3" FILLER
7'-7 5/8" FIELD VERIFY
FILLER
2'-0" 5'-4 3/4"
OPEN BEYOND
E DE DE DE D
VALENCE LIGHTING- SEE ELEC
6"
6" VALENCE
4"TO
EKIC
K
RAKKS SUPPORT BRACKET
LOCKABLE - TYP ALL CABINETS & DRAWERS IN RECEPTION AREA
BFHE
IGHT
2'-91
/8"
7A2.0 A5.0
3'-7 3/4" B/F WIDTH 4'-0" COUNTER WIDTH
3'-6"
B/F
HEIG
HT
2'-91
/8"
4"3'-
01/2"
11/2"
6"7'-
6"
7'-7 5/8" FIELD VERIFY
GYPSUM BULKHEAD
LOCKABLE
ADJUSTABLE SHELF
WATERFALL EDGE
PLAM W/ PVC EDGING WALL RAIL SUPPORT
2 - 6mm LAMINATED GLASS DOORS ON SLIDING TRACK
3'-2"
4"TO
EKIC
K3'-
6"
1'-0"
1'-0" 1'-6"2'-6"
VALENCE LIGHTING -SEE ELEC
3/4" GABLE END PANEL
RAKKS SUPPORT BRACKET
WATERFALL EDGE
87/8"
BFHE
IGHT
2'-91
/8"
ADJUSTABLE SHELVING
11/2"
2'-6"
5'-0"
4"
2'-6"
7'-6"
FIEL
DVE
RIFY
ADJUSTABLE SHELVES
1'-3" 1'-3"
ED
2'-1 1/2"
3'-0"
WHITEBOARD / SCREEN (NIC) - SEE ELEC
3'-0" CLEAR 18'-5 1/4"
PRINTER (NIC)
RAKKS SUPPORT BRACKETS -4'-0" MAX SPACING
GROMMETS - TYP
ED ED ED ED ED
2" 1'-5 1/4"
73/8"
2"
15/8"
6"
3'-0"
4"
2'-1"
PLAM COUNTERTOP W/ PVC D-WRAP NOSE
PLAM DRAWER W/ PVC EDGING ON METAL GLIDES C/W SOFT CLOSE FUNCTION
ADJUSTABLE MELAMINE SHELF W/ PVC EDGING
PLAM DOOR W/ PVC EDGING W/ D-PULL C/W SOFT CLOSE FUNCTION ON HINGES
RUBBER BASE BY FLOORING INSTALLER
2'-0"
33/4"
15/8"
6"57
/8"57
/8"1'-
03/4"
4"
3'-0"
2'-1"
PLAM COUNTERTOP & BACKSPLASH W/ PVC D-WRAP NOSE
PLAM & PVC EDGE BACKSPLASH & SIDESPLASH(SEALANT AT WALL)
PLAM DRAWER W/ PVC EDGEING ON METAL GLIDES C/W SOFT CLOSE FUNCTION
RUBBER BASE BYFLOORING INSTALLER
2'-0"
MICROWAVE
1'-2"
1'-35
/8"1'-
33/4"
3/4"
3"
(SEE
ELEV
)(S
EEEL
EV)
2'-8"
11 3/4"
PLAM & PVC EDGE VALANCE AND UNDER COUNTER LIGHT WHERE SHOWN IN ELEVATIONS - SEEELEC
PLAM ALL EXPOSEDSURFACES W/ PVC EDGING
2" 1'-5 1/4"
73/8"
2"
13/4"
57/8"
3'-0"
4"
2'-1"PLAM COUNTERTOP & BACKSPLASH W/ D-WRAP NOSE
ADJUSTABLE MELAMINE SHELF W/ PVC EDGING
PLAM DOOR W/ PVC EDGING W/ D-PULL C/W SOFT CLOSE FUNCTION ON HINGES
RUBBER BASE BY FLOORING INSTALLER
2'-0"
SINK - REF. MECH.
1'-2"
(SEE
ELEV
)(S
EEEL
EV)
2'-8"
11 3/4"
PLAM & PVC EDGE VALANCE AND UNDER COUNTER LIGHT
9 1/4"1"
11/2"
PLAM DOOR W/ PVC EDGING & WIRE PULL C/W SOFT CLOSE FUNCTION ON HINGES
ADJUSTABLE MELAMINE SHELF W/ PVC EDGING
2"57
/8"
BASE CABINET BASE CABINET
WHERE APPLICABLE
FIXED PLAM FASCIA W/ PVC EDGING
BASE CABINET
4" SHELF EXTENTION
UPPER CABINET UPPER CABINET
PLAM VALANCE TO U/S CEILING
PLAM VALANCE TO U/S CEILING
2'-0"
7'-6"
PLAM DOOR FRONTS W/ PVC EDGING
ADJUSTABLE PLAM SHELVES W/ PVC EDGES
TALL PANTRY
WHITE MELAMINE INTERIOR SURFACES
RUBBER BASE BY FLOORING INSTALLER
ACCESSIBLE COUNTER
2'-1"
BFHE
IGHT
2'-91
/8"
PLAM BOTH SIDES OF DOUBLE PARTICLE CORE W/ PVC EDGING
PLAM W/ PVC EDGING WALL RAIL SUPPORT
Typical Millwork Section Details
PULL OUT DRAWERS
COPYRIGHT NOTICE:
Copyright of this electronic document belongs to Cory R. Stechyshyn Architect
Inc o/a i4architecture.
This electronic document may not be forwarded to others, transmitted,
downloaded or reproduced in any format, whether print or electronic, without the
express, written permission of the copyright owner.
Scale
Drawn by
Project No.
12 St Paul St.Thunder Bay, ON, CAP7A 4S5
807.346.2277 (office)8555.558.1459 (fax)i4a.ca
Sheet Number
Professional Seal
DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION UNLESS ARCHITECTS SEAL IS AFFIXED, SIGNED AND DATED.
Project Name
Project Address
Sheet Name
As indicated
A5.0
2017-68
TNG
Interior Elevations& Typical MillworkSection Details
Lakehead UniversityAboriginalInitiatives - InteriorRenovation
955 Oliver Road,Thunder Bay, ON,P7B 5E1
Scale = 1/2" = 1'-0"A5.0A2.01 Interior Elevation - Kitchen Area
Scale = 1/2" = 1'-0"A5.0A2.02 Interior Elevation - Kitchen Area & Storage Cabinets
Scale = 1/2" = 1'-0"A5.0A2.04 Interior Elevation - Reception Cabinetry
Scale = 1/2" = 1'-0"A5.0DD.015 Interior Elevation - Reception Millwork
Scale = 1/2" = 1'-0"A5.0A2.07 Section Detail - Reception Millwork
Scale = 1/2" = 1'-0"A5.0A2.06 Interior Elevation - Medicine Cabinet
Rev. No. Description DateA ISSUED FOR 95% REVIEW 12-SEP-2018B ISSUED FOR 100% REVIEW 19-SEP-2018C ISSUED FOR PERMIT &
CONSTRUCTION20-SEP-2018
Scale = 1/2" = 1'-0"A5.0A2.03 Interior Elevation - Computer Stations
20-SEP-2018
MAIN FLOOR PLAN-NEW PLUMBING:
PLUMBING FIXTURES:
PLUMBING ISOMETRIC:
MANAGER OFFICE103
RECEPTION101
COMMUNITY PARTNERPROGRAM ROOM
108
STORAGE109
LOUNGE AREA105
SEATING AREA110
MULTI PURPOSE AREA111
COUNSELOR'S OFFICE106
ELDER'S ROOM107
MECHCHASE
FILE RM104
JAN / ELEC RM102
WAITING AREA100
MAIN FLOOR PLAN-NEW VENTILATION:
GRILLES & DIFFUSERS:
TRANSFER DUCT DETAIL:
EQUIPMENT LIST:
BYPASS BOX SEQUENCE OF OPERATION-HEAT/COOL CHANGEOVER:
MANAGER OFFICE103
RECEPTION101
COMMUNITY PARTNERPROGRAM ROOM
108STORAGE
109
LOUNGE AREA105
SEATING AREA110 MULTI PURPOSE AREA
111
COUNSELOR'S OFFICE106
ELDER'S ROOM107
MECHCHASE
FILE RM104
JAN / ELEC RM102
WAITING AREA100