www.lsis.biz

GL-A,B / GL-E,F

Low-Voltage Power Centers

Page 2: [Ls]Lv Swgr Power Center e 1304 1

We also provide Total Solutionsthat encompass customizeddesigns and more advancedtechnology, as well as efficientproduction and installation, andhighly accurate testing andanalysis of power equipment.

2

Page 3: [Ls]Lv Swgr Power Center e 1304 1

LS GL-type Power Center is designed for the low-voltage equipmentused in the power plant and LV distribution systems. It meets Low Voltage Switchgear Standards such as JEM-1265 andIEC60439, 60158 so as to be used in various industrial sectors.

In response to the high tech world, the new Power Center!

C O N T E N T S

Features 3GL-A, B type Power center 6GL-E, F-type Power center 9GL-type specifications/Ratings 12Ratings of Metasol Series Air Circuit Breakers 14Ratings of Susol Series Air Circuit Breakers 16GL-type configuration 18

LS Low Voltage Power Center 3

Page 4: [Ls]Lv Swgr Power Center e 1304 1

GL type Power Center Features

Basic type A : 3∅3W Space saving typeB : 3∅4W Space saving typeE : 3∅3W Univasal typeF : 3∅4W Univasal type

GL AType numbering

An innovative next-generation solutions through the state-of-the-art technology, New concept low-voltage load centers to improve the environment and loss

4

Page 5: [Ls]Lv Swgr Power Center e 1304 1

Options responing to power plants and power distribution systems areavailable. In addition the special housing to protect against dust andother contaminants such as insects and other external environment arealso available as an option. Various options are provided to conform tointernational standards (IEC, ANSI, BS standard).

ACB's front panel and internal protection cover increase the operator safety evenin opening the front door.

GL-A, B type GL-E, F type

Space Saving TypeCable Cable Cable Cable

Universal Type

Main cable is rear accessible and control cable is front accessible for theworkability of installation and checking.

Responding to the era of the electronics the digital device is used for integratedinstrumentation, monitoring and control. It functions the transducer features suchas current, voltage, power, energy, reactive power, reactive power, power factorand frequency which enable the interface with other facilities. (4-20mA)

Conventional Power Center

GL type Power Center

ACB

Providing compact size resulting in reduced floor space requirements

Safety feature

ACB with electronics technology

Electronic control circuit

Reduced floor space

Consideration for workability

Various options

A standard feature of the breaker, ACB is the digital trip unit that provides circuitprotection, instrumentation, display and monitoring functions which meet thesystem requirements with a high level of reliability. In addition, other types ofbreakers such as economic or premium series are also available.

GIMAC-IV

LS Low Voltage Power Center 5

Page 6: [Ls]Lv Swgr Power Center e 1304 1

■ACB up to 3200AF applicable■Bus Duct applicable■Can be aligned with 1000kVA dry type Transformer■Can be aligned in case of MCCB as feeder

GL-A, B Power Center

Customer satisfaction through quality and service.World-class products From LSIS.

6

Page 7: [Ls]Lv Swgr Power Center e 1304 1

Panel type Equipment Rating Standard enclosure, (W x H x D, mm)

Transformer Dry or Cast resin type 1,000kVA Max. 2,200max.×2,300×1,400

MCCB MCCB 50AF~600AF (600~1,000)×2,300×1,400

Condenser Condenser + Series Reactor 200kVA Max. 800max.×2,300×1,400

Note 1. Continuous current ratings of breakers must be derated for ambient temperatures above 40℃. Please contact us.2. Please contact us.if external withdraw cable length is over 325mm2×2 per phase

Circuit ACB type ACB Rated Number of Standard enclosure

System Metasol(N Type) Metasol(S Type) Susol Current(A) Stack (W x H x D, mm)

AN-06D AS-06D AH-06D/E 630

AN-10D AS-10D AH-10D/E 1,000700×2,300×1,200

AN-13D AS-13D AH-13D/E 1,2502

3∅∅3W AN-16D AS-16D AH-16D/E 1,600

AN-20E AS-20D/E AH-20D/E 2,000800×2,300×1,200

AN-25E AS-25E AH-25E 2,500

AN-32E AS-32E AH-32E 3,200 1 800×2,300×1,200

AN-06D AS-06D AH-06D/E 630

AN-10D AS-10D AH-10D/E 1,000700×2,300×1,400

AN-13D AS-13D AH-13D/E 1,250

3∅∅4W AN-16D AS-16D AH-16D/E 1,600 2

AN-20E AS-20D/E AH-20D/E 2,000800×2,300×1,400

AN-25E AS-25E AH-25E 2,500

AN-32E AS-32E AH-32E 3,200 1,000×2,300×1,400

Enclosure size

Panel size suitable for alignment with GL-A, B type Power Center

LS 3.6 / 7.2kV ~ 12kV Switchgear 7

Page 8: [Ls]Lv Swgr Power Center e 1304 1

GL-A, B Power Center

System application

Skeleton

Alignment

Structures

8

Page 9: [Ls]Lv Swgr Power Center e 1304 1

Structures■Lining up suitable for functions and statistics■Aligning with panels of TR, MCCB or even

medium voltage switchgears

GL-E, F Power Center

A stable power supply and maximize energy efficiencythrough a variety of industrial electrical technologies.

LS Low Voltage GL-E, F Power Center 9

Page 10: [Ls]Lv Swgr Power Center e 1304 1

Note 1. Continuous current ratings of breakers must be derated for ambient temperatures above 40℃. Please contact us.2. Enclosure Size may change for special structure specifications , so please contact us.3. Please contact us.if external withdraw cable length is over 325mm2×2 per phase .

Panel type Equipment Rating Standard enclosure, (W x H x D, mm)

Transformer Dry or Cast resin type1,500kVA Max. 2,400Max.×2,300×1,600

2,500kVA Max. 2,800Max.×2,500×1,800

MCCB MCCB 50AF~1200AF (600~1,000)×2,300×1,600

Condenser Condenser + Series Reactor 400kVA Max. 1,000Max.×2,300×1,600

Enclosure size

Panel size suitable for alignment with GL-E, F type Power Center

GL-E, F Power Center

10

Circuit ACB type ACB Rated Number of Standard enclosure

System Metasol(N Type) Metasol(S Type) Susol Current(A) Stack (W x H x D, mm)

AN-06D AS-06D AH-06D/E 630

AN-10D AS-10D AH-10D/E 1,000

AN-13D AS-13D AH-13D/E 1,250

AN-16D AS-16D AH-16D/E 1,600 700×2,300×1,600

3∅∅3WAN-20E AS-20D/E AH-20D/E 2,000

AN-25E AS-25E AH-25E 2,500

AN-32E AS-32E AH-32E 3,200

- AS-40E/F/G AH-40E/G 4,000 1,000×2,300×1,800~2,000

- AS-50F/G AH-50G 5,000 1,100×2,300×1,800~2,000

- AS-63G AH-63G 6,300 1,300×2,300×1,800~2,000

AN-06D AS-06D AH-06D/E 630

AN-10D AS-10D AH-10D/E 1,000700×2,300×1,600

AN-13D AS-13D AH-13D/E 1,250

AN-16D AS-16D AH-16D/E 1,600

3∅∅4WAN-20E AS-20D/E AH-20D/E 2,000

900×2,300×1,600AN-25E AS-25E AH-25E 2,500

AN-32E AS-32E AH-32E 3,200 1,000×2,300×1,600

- AS-40E/F/G AH-40E/G 4,000 1,200×2,300×1,800~2,000

- AS-50F/G AH-50G 5,0001,300×2,300×1,800~2,000

- AS-63G AH-63G 6,300

2

2

1

1

Page 11: [Ls]Lv Swgr Power Center e 1304 1

System application

Skeleton

Alignment

Structures

LS Low Voltage Power Center 11

Page 12: [Ls]Lv Swgr Power Center e 1304 1

Item Standard Specifications Special SpecificationsApplicable Standards JEM 1265 and IEC 60439

GeneralClass JEM 1265 Class 3 JEM 1265 Class F

SpecificationsInstallation Environment Altitude 1,000m Max. Temperature -5℃~40℃ indoor Rated operating voltage 690VRated insulation voltage 1,000V

Circuit System 3-phase 3-wire / 3-phase 4-wireRatings

Rated current 630 ~ 6300AFrequency 50 / 60 Hz

Control circuit voltage DC 100 / 110VDoor 2.3mm 3.2mm

Enclosure Thickness Side Plate 1.6mm 2.3mmTop & Bottom Plate 1.6mm 2.3mm

Panel Exterior 5Y 7/1Specified

by CustomerPainting Instruments and relays N 1.5

Material Acrylic Resin

Nameplate Color Character Black (inside carved) SpecifiedBackground color Milk white by Customer

Material CopperGrounding Bus bar Size 3t × 25mm

Installation location Lower

Material Horizontal busbar CopperVertical busbar Copper

Plating for main busbars connections Ag platingFrom the left R.S.T.N

AC From the top R.S.T.N.

Phase array From the front R.S.T.N.From the left N.P.

Bus bar DC From the top P.N.From the front P.N.

R-phase Red

AC S-phase White

Phase array T-phase BlueN-phase Black

DC P-phase RedN-phase Blue

Type Control KIV or IVMain KIV or IV Specified

Size Control 1.25mm2 by CustomerCable Main 3.5mm2 over

Control Gray SpecifiedColor Main Black by Customer

Ground Green

Specifications

GL type Specifications & Ratings

12

Page 13: [Ls]Lv Swgr Power Center e 1304 1

Floor plans, standard

LS Low Voltage Power Center 13

Page 14: [Ls]Lv Swgr Power Center e 1304 1

Ratings of Metasol Series Air Circuit Breakers

14

Type

Ampere frame (AF)

Rated current(A) (In max) at 40℃℃

Setting current (A) Control trip relay ( ... ×× In max)

Rated current of neutral pole (A)

Rated insulation voltage(V) (Ui)

Rated operating voltage(V) (Ue)

Rated impulse withstand voltage (kV) (Uimp)

Frequency (Hz)

Number of poles (P)

Rated breaking capacity (kA sym)IEC 60947-2

220V/230V/380V/415V

AC 50/60Hz (Icu)KS C 4620

460V/480V/500V

550V/600V/690V

Rated service breaking capacity (kA) (Ics) ... %××Icu

Rated making capacity (kA peak)IEC 60947-2

220V/230V/380V/415V

AC 50/60Hz (Icm) KS C 4620

460V/480V/500V

550V/600V/690V

Rated short-time 1 sec

withstand current (kA) (Icw) 2 sec

3 sec

Operating time (ms) Maximum total breaking time

Maximum closing time

Life cycle (time) Mechanical

Electrical

Connections Draw-out / Fixed Horizontal connection

Vertical connection

Front connection

Mixed connection

Weight (kg) Draw-out type Main body Motor charging type

(3P/4P) (With cradle) Manual charging type

Cradle only

Fixed type Motor charging type

Manual charging type

External dimensions (mm) Draw-out 3P

(H××W××D) type 4P

Fixed type 3P

4P

Trip relay

Certificate & Approval

Marine clasiflcation* Refer to trip relay specification. ** �: Standard, �: Option

※ Life time means not guarantee, but limitation.Quality guarantee: On/Off frequency on the basis of IEC60947-2 within the term of guarantee

H

WD

*

**

AN-06D AN-08D AN-10D AN-13D AN-16D AS-20D

630 800 1000 1250 1600 2000

200 400

400 630 1000 1250 1600 2000

630 800

(0.4 ~ 1.0) × In max

400400

630 1000 1250 1600 2000630

800

1000

690

12

50/60

3/4

65 70

65 70

50 65

100% 100%

143 154

143 154

105 143

50 65

42 55

36 50

40

80

20,000

5,000

� -

� �

� -

� -

63/74 70/85

61/72 68/83

29/32 33/40

34/44 38/47

32/42 36/45

430×334×375

430×419×375

300×300×295

300×385×295

N, A, P type

KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK

Page 15: [Ls]Lv Swgr Power Center e 1304 1

LS Low Voltage Power Center 15

AS-20E AS-25E AS-32E AS-40E AS-50F AS-40G AS-50G AS-63G

2000 2500 3200 4000 4000 5000 4000 5000 6300

630, 800

1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300

1600, 2000

(0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max

630, 800

1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300

1600, 2000

1,000 1000 1,000

690 690 690

12 12 12

50/60 50/60 50/60

3/4 3/4 3/4

85 100 120

85 100 120

85 85 100

100% 100% 100%

187 220 264

187 220 264

187 187 220

85 85 100

75 75 85

65 65 75

40 40 40

80 80 80

15,000 10,000 10,000

5,000 2,000 2,000

� � � �

� � � �

� - - -

� - - -

87/103 104/147 107/139 181/223 186/230

85/101 102/145 102/145 179/221 184/228

44/50 58/70 65/85 97/117 102/124

44/55 63/100 61/81 98/123 103/130

42/53 61/98 60/80 96/121 101/128

430×412×375 460×629×375 460×785×375

430×527×375 460×799×375 460×1015×375

300×378×295 300×597×295 300×751×295

300×493×295 300×767×295 300×981×295

N, A, P type N, A, P type N, A, P type

KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST

LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK

Page 16: [Ls]Lv Swgr Power Center e 1304 1

Ratings of Susol Series Air Circuit Breakers

16

Type

Ampere frame (AF)

Rated current(A) (In max) at 40℃℃

Setting current (A) Control trip relay ( ... ×× In max)

Rated current of neutral pole (A)

Rated insulation voltage(V) (Ui)

Rated operating voltage(V) (Ue)

Rated impulse withstand voltage (kV) (Uimp)

Frequency(Hz)

Number of poles (P)

Rated breaking capacity (kA sym)IEC 60947-2

220V/230V/380V/415V

AC 50/60Hz (Icu)KS C 4620

460V/480V/500V

550V/600V/690V

Rated service breaking capacity (kA) (Ics) ... %××Icu

Rated making capacity (kA peak)IEC 60947-2

220V/230V/380V/415V

AC 50/60Hz (Icm) KS C 4620

460V/480V/500V

550V/600V/690V

Rated short-time 1sec

withstand current (kA) (Icw) 2 sec

3 sec

Operating time (ms) Maximum total breaking time

Maximum closing time

Life cycle (time) Mechanical

Electrical

Connections Draw-out / Fixed Horizontal connection

Vertical connection

Front connection

Mixed connection

Weight (kg) Draw-out type Main body Motor charging type

(3P/4P) (With cradle) Manual charging type

Cradle only

Fixed type Motor charging type

Manual charging type

External dimensions (mm) Draw-out 3P

(H××W××D) type 4P

Fixed type 3P

4P

Trip relay

Certificate & Approval

Marine clasiflcation* Refer to trip relay specification. ** �: Standard, �: Option

※ Life time means not guarantee, but limitation.Quality guarantee: On/Off frequency on the basis of IEC60947-2 within the term of guarantee

AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D

630 800 1000 1250 1600 2000

200 400

400 630 1000 1250 1600 2000

630 800

(0.4 ~ 1.0) × In max

400400

630 1000 1250 1600 2000630

800

1000

690

12

50/60

3/4

85

85

65

100%

187

187

143

65

60

50

40

80

20,000

5,000

� -

� �

� -

� -

63/74 70/85

61/72 68/83

29/32 33/40

34/44 38/47

32/42 36/45

430×334×375

430×419×375

300×300×295

300×385×295

N, A, P, S type

KS / KEMA / KERI / GOST / CCC

LR, ABS, DNV, KR, BV, GL, RINA, NK

H

WD

*

**

Page 17: [Ls]Lv Swgr Power Center e 1304 1

LS Low Voltage Power Center 17

※Derating of the rated current is required according to the ambient temperature around the breaker in a panelif it is higher than the reference value. (See pages 109 to 112)

AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E

630 800 1000 1250 1600 2000 2500 3200 4000

630 800 1000 1250 1600 2000 2500 3200 4000

(0.4 ~ 1.0) × In max

630 800 1000 1250 1600 2000 2500 3200 4000

1,000

690

12

50/60

3/4

100

100

85

100%

220

220

187

85

75

65

40

80

15,000

5,000

� �

� �

� -

� -

87/103 107/139

85/101 102/145

44/55 65/85

44/55 61/81

42/53 60/80

430×412×375

430×527×375

300×378×295

300×493×295

N, A, P, S type

KS / KEMA / KERI / GOST / CCC

LR, ABS, DNV, KR, BV, GL, RINA, NK

AH-40G AH-50G AH-63G

4000 5000 6300

4000 5000 6300

(0.4 ~ 1.0) × In max

4000 5000 6300

1,000

690

12

50/60

3/4

150

150

100

100%

330

330

220

100

85

75

40

80

10,000

2,000

-

-

181/223 186/230

179/221 184/228

97/117 102/124

98/123 103/130

96/121 101/128

460×785×375

460×1015×375

300×751×295

300×981×295

N, A, P, S type

KS / KEMA / KERI / GOST / CCC

LR, ABS, DNV, KR, BV, GL, RINA, NK

Page 18: [Ls]Lv Swgr Power Center e 1304 1

Interlock minimize the risk of operational errors■Interlocks prevent racking of the breaker in or out when the breaker is closed■Closing and trip by electrical signals are available at the position of connection or test.

(Blocked at middle position)■Manual closing and trip are available at the position of connection or test.

(Blocked at middle position)

Main busbar and cable compartment is located at rear side. Branch bus and terminals to be connected from or to a breaker are arranged here. Bus Duct or Cable way is provided for external connection.

PT including primary and secondary fuses is mounted on drawable cradle. PT can be checked even in the service state at drawout position.

Breaker compartment

Main busbar and cable

Drawable PT, optional

GL type structure

GL Type Power Center provides front accessible breaker compartment and rear accessible main busbarand cable compartment. Control devices are installed at the door of the breaker compartment.

18

Page 19: [Ls]Lv Swgr Power Center e 1304 1

Follow the instructions shown in Figures for testing inthe compartment.Open the compartment door. Front panel of the breaker and internal coverprovide safe operation by isolating from the main circuit.

Push the trip button to make the breaker off state .

Open the racking slot cover and insert the racking tool and rotate itcounterclockwise. Connected - Test - Disconnected

Drawout sequence of the breaker, ACB

Remove the connector of control circuit at disconnected position and rotatethe racking tool counter-clockwise.

The extending rail locking is resolved automatically at Drawable position. The breaker can be drawout from the rail.

Use lifter or crane to remove the breaker out of the compartment

LS Low Voltage Power Center 19

Page 20: [Ls]Lv Swgr Power Center e 1304 1

�� For your safety, please read user's manual thoroughly before operating.

�� Contact the nearest authorized service facility for examination, repair, or adjustment.

�� Please contact a qualified service technician when you need maintenance.Do not disassemble or repair by yourself!

�� Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions

www.lsis.bizⓒ 2013.4 LSIS Co.,Ltd. All rights reserved.

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

�� HEAD OFFICEKorea Gyeonggi-do Anyang-si dongan-gu LS-ro 127 (Hogye-dong)TEL. (82-2)2034-4931/4943/4946FAX. (82-2)2034-4819

�� CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea

2013. 04 Low-Voltage Power Centers (E) 2013. 04/(01) 2013. 04 Printed in Korea STAFF

�LSIS (Middle East) FZE ��Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab EmiratesTel: 971-4-886 5360 Fax: 971-4-886-5361 �Dalian LSIS Co., Ltd. ��Dalian, China

Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 �LSIS (Wuxi) Co., Ltd. ��Wuxi, China

Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 �LSIS-VINA Co., Ltd. ��Hanoi, Vietnam

Address: Room 1311, 13th, M3-M4 Building 91 Nguyen Chi Thanh street, Hanoi, VietnamTel: 84-4-6275-8055 Fax: 84-4-6275-8056�LSIS-VINA Co., Ltd. ��Hochiminh , Vietnam

Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 �LSIS Shanghai Office ��Shanghai, China

Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, ChinaTel: 86-21-5237-9977 Fax: 89-21-5237-7189 �LSIS Beijing Office ��Beijing, China

Address: Room 2306, Building B Landgent Center, No.24 Middle Road, East 3rd Ring Road, Chaoyang District,Beijing, P.R. ChinaTel: 86-10-5761-3127 Fax: 86-10-5761-3128�LSIS Guangzhou Office ��Guangzhou, China

Address: Room 1403, 14th, New Poly Tower, 2 Zhongshan Liu Road, Guangzhou, P.R ChinaTel: 86-20-8326-6784 Fax: 86-20-8326-6287�LSIS Chengdu Office ��Chengdu, China

Address: Room 1701 17Floor, huamin hanjun international Building, No1 Fuxing Road Chengdu, 610016, P.R. ChinaTel: 86-28-8670-3201 Fax: 86-28-8670-3203 �LSIS Qingdao Office ��Qingdao, China

Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. ChinaTel: 86-532-8501-6058 Fax: 86-532-8501-6057 �LSIS NETHERLANDS Co.Ltd ��Schiphol-Rijk, Netherlands

Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The NetherlandsTel: 31-20-654-1420 Fax: 31-20-654-1429 �LSIS Gurgaon Office ��Gurgaon ,India

Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, IndiaTel: 91-1244-930-077 Fax: 91-1244-930-066

��Global Network