M. Yoda, S. I. Abdel-Khalik, D. L. Sadowski and M. D. Hageman
Woodruff School of Mechanical Engineering
Update on Thermal Performance of the Gas-
Cooled Plate-Type Divertor
ARIES-Pathways (8/09) 2
Objective / MotivationObjective• Experimentally evaluate and validate thermal performance of
gas-cooled divertor designs in support of the ARIES team
Motivation• Leading divertor designs rely on jet impingement cooling to
achieve desired performance• Accommodate heat fluxes up to 10 MW/m2 • Performance is “robust” with respect to manufacturing
tolerances and variations in flow distribution• Extremely high heat transfer coefficients (~50 kW/(m2K))
predicted by commercial CFD codes used for the design• Experimentally validate such numerical predictions
ARIES-Pathways (8/09) 3
Approach• Design and instrument test modules that closely
match divertor geometries• Conduct experiments at conditions matching and
spanning expected non-dimensional parameters for prototypical operating conditions– Reynolds number Re– Use air instead of He
• Measure temperature distributions and pressure drop• Compare experimental data with predictions from
CFD software for test geometry and conditions– Nu(Re), P*(Re)
ARIES-Pathways (8/09) 4
Investigated leading gas-cooled divertor designs• FZK Helium-Cooled Multi-Jet (HEMJ) “Finger”
[Norajitra et al. 2005]
– Ihli et al. 2007; Crosatti et al. 2009• ARIES-CS T-Tube [Ihli et al. 2007; Raffray et al. 2008]
– Crosatti et al. 2007; Abdel-Khalik et al. 2008; Crosatti et al. 2009
• ARIES-Pathways Plate-Type Design[Malang; Wang et al. 2009]
– Variant with metal open-cell foam: Gayton et al. 2009
[Sharafat et al. 2007]
– Variant with pin-fin array: In progress
Some History
ARIES-Pathways (8/09) 5
Outcomes• Enhanced confidence in predicted performance by
commercial CFD codes at prototypical and off-normal operating conditions– FLUENT®
• Use validated CFD codes to optimize/modify divertor designs
• Predict sensitivity to changes in geometry and operating conditions to define and establish manufacturing tolerances
ARIES-Pathways (8/09) 6
Plate-Type Divertor Design• Covers large area (2000 cm2 = 0.2 m2): divertor area
O(100 m2)
100 cmCastellated
W armor0.5 cm thick
20– HEMJ, T-tube
cool 2.5, 13 cm2
– Accommodates
up to 10 MW/m2
without exceeding
Tmax 1300 °C, max 400 MPa
– 9 individual manifold units with ~3 mm thick W-alloy side walls brazed together
ARIES-Pathways (8/09) 7
GT Test ModuleArmor
In
Out
• Jet issues from 0.5 mm slot, then impinges on and cools underside of W-alloy pressure boundary– Coolant flows along 2 mm gap,
exits via outlet manifold– Original design
[Malang 2007]
– Use air as coolant– Reynolds number Re = 1.1104–
6.8104 (vs. 3.3104 at nominal operating conditions)
– Nominal heat flux qnom = 0.2– 0.75 MW/m2
In
Out
Heated brass shell
Al inner cartridge
ARIES-Pathways (8/09) 9
Al Inner Cartridge
InOut
• Inlet, outlet manifolds embedded inside Al cartridge– Manifolds 19 mm 15 mm 76.2 mm – 2 mm 76.2 mm slot– Coolant enters outlet
manifold via holes – Side wall bolted on
ARIES-Pathways (8/09) 10
Brass Outer Shell• Models pressure boundary
– 5 TC in shell to measure cooled surface temperature distribution: 2 in center; (1,5) and (3,4) at same depth 0.5 mm from surface
– Brass shell heated by heater block
– k for brass similar to that of W-alloy
ARIES-Pathways (8/09) 11
Pin-Fin Array• Can thermal performance of leading divertor
designs be further improved?– Mo open-cell foam in 2 mm gap increased HTC by
40–50%, but also increased P* by similar fraction[Gayton et al. 2009]
– In HEMP, a variant of HEMJ, coolant impinges on pin-fin array [Diegele et al. 2003]
• Combine plate with pin-fin array– 808 1.0 mm 2.0 mm pin fins (nearly) contacting
Al cartridge on 1.2 mm pitch
– 2 mm “clear” area for impinging jet
– Pin fins EDM’ed into inside of brass shell
ARIES-Pathways (8/09) 12
Heated Test Section
Copper heater block
Graphite shim
Brass outer shell
Aluminum cartridge
Gasket
ARIES-Pathways (8/09) 13
GT Air Flow Loop
Inlet P, T measurement
Outlet P, T measurement
Cu heater block• 3 cartridge heaters• 6 TC in neck measure q• 2 TC at top monitor max.
Cu temperature
ARIES-Pathways (8/09) 14
• Nu from TC data – Nearly uniform T along
slot– Nu based on gap width, k
at 300K and effective HTC (for pin fins)
• qnom = 0.2–0.75 MW/m2
Effect of Pin Fins
Re (/104)
Pin finsBare surface
TC 1 TC 4 TC 2 TC 5 TC 3
Nominal operating condition
Nu
ARIES-Pathways (8/09) 15
• Ratio of Nu and P for cooled surface with, without pin-fins
• Pin-fins with ~260% more surface area improve cooling performance by ~150%–200% while increasing pressure drop by ~40–70%
Comparison: Pins vs. Bare
Re (/104)
Nu
p /
Nu
Mass flow rate [g/s]
P
p* /
P *
Nominal operating condition
ARIES-Pathways (8/09) 16
Summary• Designed and studied experimental test modules
modeling leading He-cooled divertor designs– T-tube, HEMJ “finger,” plate– Conducted dynamically similar thermal-hydraulics
experiments matching and spanning expected prototypical operating conditions
• Used commercial CFD software to predict performance of experimental test modules– Good agreement between experimental data and model
predictions (including those from other groups)– Use validated codes to predict performance of gas-cooled
components with complex geometries
ARIES-Pathways (8/09) 17
Conclusions• Plate-type divertor + pin-fin array promising design
– Smaller number of divertor modules required reduced cost, complexity
– Two- to three-fold enhancement by pin fins can accommodate heat fluxes much higher than 10 MW/m2
• Initial results for un-optimized configuration: use CFD to suggest improvements to current experimental design– Effect of pin pitch, diameter– Effect of slot width
ARIES-Pathways (8/09) 18
Next Steps
To complete ARIES-Pathways study:• Validate CFD codes (e.g. FLUENT) and plate models
with experimental data– Model pin-fin array
• Use validated CFD codes to optimize/modify pin-fin layout – Predict maximum heat flux that can be accommodated by
optimized pin-fin/plate-type divertor– Predict pressure drop across optimized pin-fin array