manual general bomba vrs- 021

Upload: rafael-padilla-yauricasa

Post on 02-Jun-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Manual General Bomba VRS- 021

    1/40

    Model VRS

    Installation, Operation and Maintenance Instructions

  • 8/10/2019 Manual General Bomba VRS- 021

    2/402 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    3/40VRS IOM - 5/08 3

    FORWORDThis manual provides instructions on the Installation, Operation, and Maintenance of the Goulds Model VRS Rubber LinedVertical Cantilever Pump. This manual covers the standard product plus common options that are available. For specialoptions, supplemental instructions are supplied. You must read and understand this manual before installing the VRS.

    The design, materials, and workmanship incorporated in the construction of Goulds pumps makes them capable of givinglong, trouble-free service. The life and satisfactory service of any mechanical unit, however, is enhanced and extended bycorrect application, proper installation, periodic inspection, condition monitoring, and careful maintenance. This instructionmanual was prepared to assist operators in understanding the construction and the correct methods of installing, operating,and maintaining these pumps.

    Goulds will not accept responsibility for damage or delays caused by failure to observe the instructions forInstallation, Operation, and Maintenance contained in this manual.

    Warranty is valid only when genuine Goulds parts are used.

    Use of the equipment on a service other than stated in the order may nullify the warranty, unless written approval is obtainedin advance from Goulds Pumps, Inc.

    To assure proper installation, supervision from an authorized manufacturers representative is recommended.

    Additional manuals can be obtained by contacting your local Goulds representative.

    THIS MANUAL EXPLAINS Proper Installation

    Start-up Procedures

    Operating Procedures Routine Maintenance

    Pump Overhaul

    Trouble Shooting

    Ordering Spares or Repair Parts

  • 8/10/2019 Manual General Bomba VRS- 021

    4/404 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    5/40VRS IOM - 5/08 5

    TABLE OF CONTENTSPAGE SECTION

    7 SAFETY

    9 GENERAL INFORMATION

    11 INSTALLATION

    17 OPERATION

    19 PREVENTIVE MAINTENANCE

    23 DISSASEMBLY AND REASSEMBLY

    27 SPARE AND REPAIR PARTS

    1

    2

    3

    4

    5

    6

    7

  • 8/10/2019 Manual General Bomba VRS- 021

    6/406 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    7/40

    S-1

    IMPORTANT SAFETY NOTICE

    To: Our Valued Customers

    User safety is a major focus in the design of our products. Following the precautions outlined in thismanual will minimize your risk of injury.

    ITT Goulds pumps will provide safe, trouble-free service when properly installed, maintained, andoperated.

    Safe installation, operation, and maintenance of ITT Goulds Pumps equipment are an essential end userresponsibility. This Pump Safety Manual identifies specific safety risks that must be considered at alltimes during product life. Understanding and adhering to these safety warnings is mandatory to ensure

    personnel, property, and/or the environment will not be harmed. Adherence to these warnings alone,however, is not sufficient it is anticipated that the end user will also comply with industry and corporatesafety standards. Identifying and eliminating unsafe installation, operating and maintenance practices isthe responsibility of all individuals involved in the installation, operation, and maintenance of industrialequipment.

    Please take the time to review and understand the safe installation, operation, and maintenance guidelinesoutlined in this Pump Safety Manual and the Instruction, Operation, and Maintenance (IOM) manual.Current manuals are available at www.gouldspumps.com/literature_ioms.html or by contacting your nearest Goulds Pumps sales representative.

    These manuals must be read and understood before installation and start-up.

    For additional information, contact your nearest Goulds Pumps sales representative or visit our Web site atwww.gouldspumps.com .

  • 8/10/2019 Manual General Bomba VRS- 021

    8/40

    S-2

    SAFETY WARNINGS

    Specific to pumping equipment, significant risks bear reinforcement above and beyond normal safety precautions.

    WARNING

    A pump is a pressure vessel with rotating parts that can be hazardous. Any pressure vessel can explode,rupture, or discharge its contents if sufficiently over pressurized causing death, personal injury, propertydamage, and/or damage to the environment. All necessary measures must be taken to ensure over

    pressurization does not occur.

    WARNING

    Operation of any pumping system with a blocked suction and discharge must be avoided in all cases.Operation, even for a brief period under these conditions, can cause superheating of enclosed pumpage andresult in a violent explosion. All necessary measures must be taken by the end user to ensure this condition isavoided.

    WARNINGThe pump may handle hazardous and/or toxic fluids. Care must be taken to identify the contents of the pumpand eliminate the possibility of exposure, particularly if hazardous and/or toxic. Potential hazards include, butare not limited to, high temperature, flammable, acidic, caustic, explosive, and other risks.

    WARNING

    Pumping equipment Instruction, Operation, and Maintenance manuals clearly identify accepted methods fordisassembling pumping units. These methods must be adhered to. Specifically, applying heat to impellersand/or impeller retaining devices to aid in their removal is strictly forbidden. Trapped liquid can rapidlyexpand and result in a violent explosion and injury.

    ITT Goulds Pumps will not accept responsibility for physical injury, damage, or delays caused by a failure toobserve the instructions for installation, operation, and maintenance contained in this Pump Safety Manual or thecurrent IOM available at www.gouldspumps.com/literature.

  • 8/10/2019 Manual General Bomba VRS- 021

    9/40

    S-3

    SAFETY

    DEFINITIONSThroughout this manual the words WARNING , CAUTION , ELECTRICAL, and ATEX are used to indicate

    where special operator attention is required.

    Observe all Cautions and Warnings highlighted in this Pump Safety Manual and the IOM provided withyour equipment.

    WARNINGIndicates a hazardous situation which, if not avoided, could result in death or serious injury.

    Example: Pump shall never be operated without coupling guard installed correctly.

    CAUTION

    Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.Example : Throttling flow from the suction side may cause cavitation and pump damage.

    ELECTRICAL HAZARD Indicates the possibility of electrical risks if directions are not followed.

    Example: Lock out driver power to prevent electric shock, accidental start-up, and physical injury.

    When installed in potentially explosive atmospheres, the instructions that follow the Ex symbol must befollowed. Personal injury and/or equipment damage may occur if these instructions are not followed. If thereis any question regarding these requirements or if the equipment is to be modified, please contact an ITT

    Goulds Pumps representative before proceeding.Example: Improper impeller adjustment could cause contact between the rotating and stationary

    parts, resulting in a spark and heat generation.

  • 8/10/2019 Manual General Bomba VRS- 021

    10/40

    S-4

    GENERAL PRECAUTIONS

    WARNING

    A pump is a pressure vessel with rotating parts that can be hazardous. Hazardous fluids may be contained by the pump including high temperature, flammable, acidic, caustic, explosive, and other risks. Operators andmaintenance personnel must realize this and follow safety measures. Personal injuries will result if proceduresoutlined in this manual are not followed. ITT Goulds Pumps will not accept responsibility for physical injury,damage or delays caused by a failure to observe the instructions in this manual and the IOM provided with yourequipment.

    General Precautions

    WARNING NEVER APPLY HEAT TO REMOVE IMPELLER. It may explode due totrapped liquid.

    WARNING NEVER use heat to disassemble pump due to risk of explosion from tapped liquid.

    WARNING NEVER operate pump without coupling guard correctly installed.

    WARNING NEVER run pump below recommended minimum flow when dry, or without prime.WARNING ALWAYS lock out power to the driver before performing pump maintenance.WARNING NEVER operate pump without safety devices installed.

    WARNING NEVER operate pump with discharge valve closed.

    WARNING NEVER operate pump with suction valve closed.

    WARNING DO NOT change service application without approval of an authorized ITTGoulds Pumps representative.

    WARNING

    Safety Apparel: Insulated work gloves when handling hot bearings or using bearing heater Heavy work gloves when handling parts with sharp edges, especiallyimpellers

    Safety glasses (with side shields) for eye protection Steel-toed shoes for foot protection when handling parts, heavy tools, etc. Other personal protective equipment to protect against hazardous/toxic fluids

    WARNING

    Receiving:Assembled pumping units and their components are heavy. Failure to properly liftand support equipment can result in serious physical injury and/or equipmentdamage. Lift equipment only at specifically identified lifting points or asinstructed in the current IOM. Current manuals are available at

    www.gouldspumps.com/literature_ioms.html or from your local ITT GouldsPumps sales representative. Note: Lifting devices (eyebolts, slings, spreaders, etc.)must be rated, selected, and used for the entire load being lifted.

    WARNING

    Alignment:Shaft alignment procedures must be followed to prevent catastrophic failure ofdrive components or unintended contact of rotating parts. Follow couplingmanufacturers coupling installation and operation procedures.

  • 8/10/2019 Manual General Bomba VRS- 021

    11/40

    S-5

    General Precautions

    WARNING Before beginning any alignment procedure, make sure driver power is locked out.Failure to lock out driver power will result in serious physical injury.

    CAUTION

    Piping:

    Never draw piping into place by forcing at the flanged connections of the pump.This may impose dangerous strains on the unit and cause misalignment between pump and driver. Pipe strain will adversely effect the operation of the pumpresulting in physical injury and damage to the equipment.

    WARNING Flanged Connections:Use only fasteners of the proper size and material.

    WARNING Replace all corroded fasteners.

    WARNING Ensure all fasteners are properly tightened and there are no missing fasteners.

    WARNING

    Startup and Operation:

    When installing in a potentially explosive environment, please ensure that themotor is properly certified.

    WARNING Operating pump in reverse rotation may result in contact of metal parts, heatgeneration, and breach of containment.

    WARNING Lock out driver power to prevent accidental start-up and physical injury.

    WARNING The impeller clearance setting procedure must be followed. Improperly settingthe clearance or not following any of the proper procedures can result in sparks,unexpected heat generation and equipment damage.

    WARNING If using a cartridge mechanical seal, the centering clips must be installed and setscrews loosened prior to setting impeller clearance. Failure to do so could resultin sparks, heat generation, and mechanical seal damage.

    WARNING The coupling used in an ATEX classified environment must be properly certifiedand must be constructed from a non-sparking material.

    WARNING Never operate a pump without coupling guard properly installed. Personal injurywill occur if pump is run without coupling guard.

    WARNING Make sure to properly lubricate the bearings. Failure to do so may result in excessheat generation, sparks, and / or premature failure.

    CAUTION The mechanical seal used in an ATEX classified environment must be properlycertified. Prior to start up, ensure all points of potential leakage of process fluid tothe work environment are closed.

    CAUTION Never operate the pump without liquid supplied to mechanical seal. Running amechanical seal dry, even for a few seconds, can cause seal damage and must beavoided. Physical injury can occur if mechanical seal fails.

    WARNING Never attempt to replace packing until the driver is properly locked out and thecoupling spacer is removed.

    WARNING Dynamic seals are not allowed in an ATEX classified environment.

    WARNING DO NOT operate pump below minimum rated flows or with suction and/ordischarge valve closed. These conditions may create an explosive hazard due tovaporization of pumpage and can quickly lead to pump failure and physical injury.

  • 8/10/2019 Manual General Bomba VRS- 021

    12/40

    S-6

    General Precautions

    WARNING Ensure pump is isolated from system and pressure is relieved beforedisassembling pump, removing plugs, opening vent or drain valves, ordisconnecting piping.

    WARNING

    Shutdown, Disassembly, and Reassembly:Pump components can be heavy. Proper methods of lifting must be employed toavoid physical injury and/or equipment damage. Steel toed shoes must be worn atall times.

    WARNING

    The pump may handle hazardous and/or toxic fluids. Observe properdecontamination procedures. Proper personal protective equipment should beworn. Precautions must be taken to prevent physical injury. Pumpage must behandled and disposed of in conformance with applicable environmentalregulations.

    WARNING Operator must be aware of pumpage and safety precautions to prevent physicalinjury.

    WARNING Lock out driver power to prevent accidental startup and physical injury.CAUTION Allow all system and pump components to cool before handling them to prevent physical injury.

    CAUTION

    If pump is a Model NM3171, NM3196, 3198, 3298, V3298, SP3298, 4150, 4550,or 3107, there may be a risk of static electric discharge from plastic parts that arenot properly grounded. If pumped fluid is non-conductive, pump should bedrained and flushed with a conductive fluid under conditions that will not allowfor a spark to be released to the atmosphere.

    WARNING Never apply heat to remove an impeller. The use of heat may cause an explosiondue to trapped fluid, resulting in severe physical injury and property damage.

    CAUTION Wear heavy work gloves when handling impellers as sharp edges may cause

    physical injury.

    CAUTION Wear insulated gloves when using a bearing heater. Bearings will get hot and cancause physical injury.

  • 8/10/2019 Manual General Bomba VRS- 021

    13/40

    S-7

    ATEX CONSIDERATIONS and INTENDED USESpecial care must be taken in potentially explosive environments to ensure that the equipment is properlymaintained. This includes but is not limited to:

    1. Monitoring the pump frame and liquid end temperature.

    2. Maintaining proper bearing lubrication.3. Ensuring that the pump is operated in the intended hydraulic range.

    The ATEX conformance is only applicable when the pump unit is operated within its intended use. Operating,installing or maintaining the pump unit in any way that is not covered in the Instruction, Operation, andMaintenance manual (IOM) can cause serious personal injury or damage to the equipment. This includes anymodification to the equipment or use of parts not provided by ITT Goulds Pumps. If there is any questionregarding the intended use of the equipment, please contact an ITT Goulds representative before proceeding.Current IOMs are available at www.gouldspumps.com/literature_ioms.html or from your local ITT GouldsPumps Sales representative.

    All pumping unit (pump, seal, coupling, motor and pump accessories) certified for use in an ATEX classified

    environment, are identified by an ATEX tag secured to the pump or the baseplate on which it is mounted. Atypical tag would look like this:

    The CE and the Ex designate the ATEX compliance. The code directly below these symbols reads as follows:

    II = Group 22 = Category 2G/D = Gas and Dust presentT4 = Temperature class, can be T1 to T6 (see Table 1)

    Table 1

    Code

    Max permissiblesurface temperature

    oF ( oC)

    Max permissibleliquid temperature

    oF ( oC)T1 842 (450) 700 (372)

    T2 572 (300) 530 (277)

    T3 392 (200) 350 (177)

    T4 275 (135) 235 (113)

    T5 212 (100) Option not available

    T6 185 (85) Option not available

    The code classification marked on the equipment must be in accordance with the specified area where theequipment will be installed. If it is not, do not operate the equipment and contact your ITT Goulds Pumps salesrepresentative before proceeding.

  • 8/10/2019 Manual General Bomba VRS- 021

    14/40

    S-8

    PARTS

    The use of genuine Goulds parts will provide the safest andmost reliable operation of your pump. ITT Goulds Pumps ISOcertification and quality control procedures ensure the parts aremanufactured to the highest quality and safety levels.

    Please contact your local Goulds representative for details ongenuine Goulds parts.

  • 8/10/2019 Manual General Bomba VRS- 021

    15/40

    GENERAL INFORMATIONGENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9PUMP DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9NAMEPLATE INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10RECEIVING THE PUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Storage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    GENERAL

    Keep this instruction manual handy for reference. Further information can be obtained by contacting Goulds Pumps,Ashland Operations, 500 East Centre St., Ashland, PA17921 or your local representative.

    Goulds Pumps will not be liable for any damages or delaycaused by failure to comply with the provisions of thisinstruction manual. This pump is not to be operated at

    speeds, working pressures, discharge pressures, or temperatures, nor used on liquids other than stated in theoriginal order acknowledgment without written permissionof Goulds Pumps.

    PUMP DESCRIPTIONThe Model VRS pump is a rubber lined vertical cantilever centrifugal pump. The wet end of the pump contains thesame casing halves, liners, and impeller as a similar sizeModel SRL pump.

    The impeller is threaded onto the shaft. It is axiallyadjustable by means of jacking bolts in the thrust housingto renew and maintain proper leakage path clearances.

    The heavy duty bearing frame is made of cast iron andcontains a deep groove ball bearing on the inboard side andan angular contact ball bearing on the outboard side. All bearings are grease lubricated through fittings on the

    bearing frame. The direction of rotation is clockwise whenviewed from the power end to the wet end.

    VRS IOM - 5/08 9

  • 8/10/2019 Manual General Bomba VRS- 021

    16/40

    NAMEPLATE INFORMATION

    Every pump has a nameplate that provides information about the pump. The nameplate is located on the bearing frame and provides information about the pumps hydraulic characteristics.

    RECEIVING THE PUMPInspect the pump as soon as it arrives. Carefully check thateverything is in good order. Make notes of damaged or missing items on the receipt and freight bill. File any claimswith the transportation company as soon as possible.

    STORAGE REQUIREMENTSShort Term : (Less than 6 months) Goulds normal packaging procedure is designed to protect the pumpduring shipping in covered trucks and during coveredstorage. Upon receipt, store in covered and dry location.

    Long Term : (More than 6 months) Requires special precautions. Preservative treatment is applied to bearingsand machined surfaces. Rotate shaft several times every 30days. Contact driver, coupling and mechanical sealmanufacturers for long term storage procedures.

    HANDLINGUse care when moving pump. Lifting equipment must beable to adequately support the entire assembly.

    10 VRS IOM - 5/08

    Figure 1Goulds Pumps Nameplate

  • 8/10/2019 Manual General Bomba VRS- 021

    17/40

    INSTALLATIONSI TE / FO U N DATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11SUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11LEVEL THE PUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12ALIGNMENT PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Alignment Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12V-Belt Drive Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Direct Connect Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Alignment Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Set Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Measurement Techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Angular Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Method 1 - Dial Indicator Method . . . . . . . . . . . . . . . . . . . . . . 14Method 2 - Feeler Gauge Method . . . . . . . . . . . . . . . . . . . . . . 14

    Parallel Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Method 1 - Dial Indicator Method . . . . . . . . . . . . . . . . . . . . . . 14Method 2 - Straight Edge Method . . . . . . . . . . . . . . . . . . . . . . 14

    Factors That May Disturb Alignment . . . . . . . . . . . . . . . . . . . . . . 14PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Final Piping Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    SITE/FOUNDATIONA pump should be located near the supply of liquid in aclean dry area free from flooding. The area should provideadequate space for operation, maintenance, and inspection,considering complete disassembly and handling of equipment.

    The pump support must be sufficiently substantial and levelto give rigid support to the pump and absorb vibration.

    The location and size of the mounting holes are shown onthe outline assembly drawing supplied with the pumporder. The bolts which secure the pump to the foundationshould be 1/8 less in diameter than the hole size.

    SUMPThe sump must be screened to prevent any foreign objectsfrom falling into the sump and damaging the pump. Theopenings in the screening should be smaller than theopenings in the pump impeller. Guidelines for sump designcan be found in the Hydraulic Institute Standards for sumpdesign.

    VRS IOM - 5/08 11

  • 8/10/2019 Manual General Bomba VRS- 021

    18/40

    LEVEL THE PUMPLeveling the pump is best performed without the drive andmotor installed. Loosen the (4) bearing frame hold down bolts. Level the bearing housing to within 0.010 in.(0.25 mm). Place shims between bearing housing andsupport so that a gap of no more than 0.002 in (0.05 mm)

    exists at any of the (4) anchor bolts when the bolts are

    loose. Tighten the anchor bolts. If a floorplate is used, shimeach anchor bolt location so that a gap of no more than0.002 in (0.05mm) exists at any of the anchor bolt locationswhen the bolts are loose.

    ALIGNMENT PROCEDURE

    ! WARNING Before beginning any alignment procedur, make suredriver power is locked out.

    Check the alignment twice:

    Initial Alignment is done prior to operation when the pump and driver are at ambient temperature.

    Final Alignment is done just after operation when the pump and driver are at operating temperature.

    NOTE: Proper alignment is the responsibility of theinstaller and user of the unit.

    Accurate alignment of the equipment must be attained.Trouble free operation can be accomplished by followingthese procedures.

    ALIGNMENT CHECKS

    Initial Alignment (Cold Alignment)

    Before Connecting Piping - To be sure alignment can beobtained.

    After Connecting Piping - To ensure pipe strains havenot altered alignment. If changes have occurred, alter piping to remove pipe strains on pump flanges.

    Final Alignment (Hot Alignment)

    After First Run - To obtain correct alignment when both pump and driver are at operating temperature. Thereafter,alignment should be checked periodically in accordancewith plant operating procedures.

    V-BELT DRIVE PUMPS

    ! WARNING Before beginning any alignment procedure, make suredriver power is locked out.

    1. Place a straight edge across the top of the motor and pump sheaves to measure the angular and parallelmisalignment (see Figure 2). Measure the gap betweenthe straight edge and the sheaves with feeler gauges. If the gap exceeds 0.010 in (0.25 mm), adjust the sheavesalong the shafts to correct parallel misalignment andshim the motor to correct angular misalignment.

    2. A dial indicator can be used to check runout on the

    periphery and face of each sheave.

    12 VRS IOM - 5/08

    Angular Misalignment Parallel Misalignment Perfect Alignment

    Figure 2V-Belt Drive Alignment

  • 8/10/2019 Manual General Bomba VRS- 021

    19/40

    DIRECT CONNECT PUMPS

    ALIGNMENT CRITERIADisconnect coupling halves before proceeding with thealignment. Check for parallel and angular alignment witheither the Dial Indicator Method or the Straight EdgeMethod outlined below.

    The faces and outside diameters of the coupling halvesmust be square and concentric with the bores. Goodalignment is achieved when the dial indicator readings for both parallel and angular misalignment are 0.003 in(0.076 mm) total indicator reading (TIR) or less when the pump and driver are at operating temperature (see FinalAlignment). Figure 3 provides a representation of what tolook for.

    SET UP

    ! WARNING Before beginning any alignment procedure, make suredriver power is locked out.

    1. Mount two dial indicators on one of the couplinghalves (X) so that they contact the other coupling half (Y) as shown in Figure 4.

    2. Check setting of indicators by rotating coupling half Xto ensure indicators stay in contact with coupling half Y but do not bottom out. Adjust indicatorsaccordingly.

    MEASUREMENT TECHNIQUES1. To ensure accuracy of indicator readings, always rotate

    both coupling halves together so indicators contact thesame point on coupling half Y. This will eliminate anymeasurement problems due to runout on coupling half Y.

    2. Take indicator measurements with driver hold down bolts tightened. Loosen hold down bolts prior to

    making alignment corrections.3. Take care not to damage indicators when moving

    driver during alignment corrections.

    ANGULAR ALIGNMENTA unit is in angular alignment when indicator A (Angular Indicator), Figure 3, does not vary by more than 0.003 in(0.076 mm) as measured at four points on the coupling periphery 90 degrees apart at operating temperature. Thereare two methods outlined below which are acceptable toachieve alignment.

    VRS IOM - 5/08 13

    Figure 3Direct Connect Alignment

    Angular Misalignment

    ParallelMisalignment

    PerfectAlignment

    Figure 4Dial Indicator Setup

    Figure 5Directions of viewing coupling

    from top of pump

  • 8/10/2019 Manual General Bomba VRS- 021

    20/40

    METHOD 1 - DIAL INDICATOR METHOD

    For the following steps, refer to Figure 5.

    1. Zero indicator A at position 1 of coupling half Y. Mark this position on both flanges.

    2. Rotate both flanges 180 degrees to position 3. Observeneedle and record reading.

    3. Negative Reading - The coupling halves are further apart at position 3 than position 1.

    Positive Reading - The coupling halves are closer at position 3 than position 1.

    4. The angular alignment should not be a problem. If,however, 0.003 in (0.076 mm) TIR or less is notattainable, check the motor and motor mount for perpendicularity to their respective centerlines.

    5. Repeat steps 1 through 4 substituting position 2 for position 1 and position 4 for position 3. Use the samemarks made on the coupling from position 1 and besure to turn the coupling halves together.

    METHOD 2 - FEELER GAUGE METHOD

    For the following steps refer to Figure 5.

    1. Insert a feeler gauge at position 1 at the periphery of the couplings. Mark this position on both flanges.

    2. Record the largest gauge size which fits snugly between the two flanges.

    3. Rotate both flanges 180 degrees to position 3.

    4. Insert a feeler gauge at position 3 at the periphery of the couplings.

    5. Record the largest gauge size which fits snugly between the two flanges.

    6. Calculate the difference between the readings at positions 1 and 3. The difference should not be greater than 0.003 in (0.076 mm). If, however, 0.003 in (0.076mm) TIR or less is not attainable, check the motor andmotor mount for perpendicularity to their respectivecenterlines.

    7. Repeat steps 1 through 6 substituting position 2 for position 1 and position 4 for position 3. Use the samemarks made on the coupling from position 1 and besure to turn the coupling halves together.

    PARALLEL ALIGNMENT

    The unit is in parallel alignment when indicator P (ParallelIndicator, see Figure 4) does not vary by more than 0.003in (0.076 mm) as measured at four points on the coupling periphery 90 degrees apart at operating temperature. Thereare two methods outlined below which are acceptable toachieve alignment.

    METHOD 1 - DIAL INDICATOR METHOD

    For the following steps, refer to Figure 5.

    1. Zero indicator P at position 1 of coupling half Y. Mark this position on both flanges.

    2. Rotate both flanges 180 degrees to position 3. Observethe needle and record the reading.

    3. Negative Reading - The coupling half Y is shiftedtoward position 1. If the value is greater than 0.003 in(0.076 mm), shift the motor accordingly.

    Positive Reading - The coupling half Y is shifted toward position 3. If the value is greater than 0.003 in (0.076 mm),shift the motor accordingly.

    4. Repeat steps 1 through 3 until indicator P reads 0.003in (0.076 mm) or less.

    5. Once ideal alignment is reached, repeat steps 1 through4 substituting position 2 for position 1 and position 4for position 3.

    METHOD 2 - STRAIGHT EDGE METHOD

    For the following steps, refer to Figure 5.

    1. Place a straight edge across the two coupling flanges at position 1 and mark this position on both flanges.

    2. Adjust the motor so that the straight edge rests evenlyon both flanges within 0.003 in (0.076 mm).

    3. Rotate both flanges to position 2 and repeat steps 1 and2.

    4. The unit will be in parallel alignment when the straightedge rests evenly within 0.003 in (0.076 mm) on the

    coupling periphery at both positions along the periphery.

    NOTE: Care must be taken to have the straight edge parallel to the axis of the shafts.

    TIP: Since the coupling halves are disconnected, this would be a good time to check the direction of motor rotation.

    FACTORS THAT MAY AFFECTALIGNMENT

    CAUTIONThe unit should be checked periodically for alignment.

    If the unit does not stay aligned after being properlyinstalled, it may be due to any of the following causes:

    1. Non-rigid foundation

    2. Foundation settling

    3. Bearing wear

    14 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    21/40

    4. Distortion due to piping loads/strain

    5. Distortion of support due to an adjacent heat source

    6. Structural changes due to variable loading or other causes

    7. Loose nuts/bolts on the pump and/or drive assembly

    PIPINGGENERALReview the guidelines for piping in the Hydraulic InstituteStandards prior to pump installation.

    1. All piping must be supported independently of, andline up naturally with, the pump flanges.

    CAUTION Never draw piping into place by forcing the flanged connections of the pump. This may impose dangerous strains on the unit and cause misalignment between pump and driver. Pipe strain will adversely affect thereliability of the pump.

    2. Piping runs should be as short as possible to minimizefriction losses.

    3. Arrangements should be made to keep the pump from back spinning severely during shutdown. In situationswhere this occurs, a non-slam check valve should beinstalled.

    CAUTION Do not start the pump while the impeller is in reverserotation.

    FINAL PIPINGCHECK After Connecting the Piping to Pump:

    1. Turn the shaft several times by hand to confirm freerotation.

    2. Check alignment per the procedure outlined earlier. If pipe strain is affecting alignment, it must be corrected prior to startup.

    VRS IOM - 5/08 15

  • 8/10/2019 Manual General Bomba VRS- 021

    22/4016 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    23/40

    OPERATIONPREPARATION FOR START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Pump Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Shaft Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Correct Driver Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Priming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    START THE PUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18RUNNING PUMP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Operating At Reduced Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Final Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    PREPARATION FOR START-UPPUMPSUPPORTBefore starting a newly installed pump, check the pumpsupports and piping to be certain that they conform to thespecifications in the Installation section of this manual.

    BEARING LUBRICATIONThe bearings must have adequate lubrication. The bearingswere properly filled with grease prior to shipment.Regrease bearings if pump was disassembled. Refer to theMaintenance of Bearings section.

    SHAFT ROTATIONThe pump shaft must turn without any binding or rubbing -only the uniform frictional drag of the bearings should befelt. If the pump does not turn freely by hand, check todetermine the cause of the binding.

    CORRECT DRIVER ROTATION

    CAUTION Incorrect rotation could result in considerable damageto the pump. Check the motor rotation when motor isnot connected to the pump shaft.

    The direction of rotation of the driver must be checked before it can be coupled to the pump. The correct directionof rotation of the pump is indicated on the bearing frame.Since the impeller is threaded on, reverse rotation couldcause the impeller to unscrew from the shaft.

    ! WARNING Lock out driver power to prevent accidental start-upwhen working on drive.

    1. Lock out power to driver.

    2. Disconnect coupling from the driver or the belts fromthe drive. Make sure no parts are loose.

    3. Unlock driver power.

    4. Make sure everyone is clear of driver. Jog the driver just long enough to determine the direction of rotation.Rotation must correspond to the arrow on the pump.

    5. Lockout power to driver and reinstall coupling or belts.

    6. Reinstall coupling or belt drive guard.

    PRIMINGThe liquid level must be above that shown on thedimensional drawing supplied with the order.

    VRS IOM - 5/08 17

  • 8/10/2019 Manual General Bomba VRS- 021

    24/40

    START THE PUMP

    ! WARNINGThis unit must never be used without proper installation of the safety guards for rotating parts.

    1. Make sure the liquid level is at or above the minimum.

    2. Slightly open the discharge valve.

    3. Start driver.

    CAUTION Immediately observe the discharge gauge after starting pump. If discharge pressure is not quickly obtained,

    stop the driver, check the liquid level and dischargevalve, and attempt to restart.

    4. Slowly open the discharge valve.

    RUNNING PUMP

    GENERALCONSIDERATIONSDriver may overload if the pumpage specific gravity(density) is greater than originally assumed or the ratedflow rate is exceeded.

    Always operate the pump at or near the rated conditions to prevent damage resulting from cavitation or recirculation.

    New bearing housing seals may generate some heat until broken in. Oil should be applied to them if heat becomesexcessive.

    OPERATING AT REDUCEDCAPACITY

    ! WARNING Do NOT operate pump below minimum rated flows or with the discharge valve closed. These conditions canquickly lead to pump failure and a possible explosion.

    Damage caused by reduced flow operations includes:

    1. Increased Vibration Levels - Affects bearings.

    2. Increased Radial Thrust - Stresses on shaft and bearings.

    3. Heat Build Up - Vaporization causing rotating parts toscore or seize or possible explosion.

    FINALALIGNMENT1. Run the pump under actual conditions for a sufficient

    length of time to bring the pump and driver up tooperating temperature.

    2. Check the alignment per alignment procedure outlinedearlier.

    18 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    25/40

    PREVENTIVE MAINTENANCEGENERAL COMMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19MAINTENANCE SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Routine Inspections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Quarterly Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Yearly Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    MAINTENANCE OF BEARINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20MAINTENANCE OF SEALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20MAINTENANCE OF DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20IMPELLER CLEARANCE SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . 21PUMP WASHDOWN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21TROUBLESHOOTING GUIDE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    GENERAL COMMENTSA routine maintenance program can extend the life of your pump. Well maintained equipment will last longer andrequire fewer repairs. A maintenance record will helpidentify the potential causes of problems.

    MAINTENANCE SCHEDULERoutine Maintenance

    Bearing Lubrication Vibration Analysis

    Routine Inspections

    Check for unusual noise, vibration and bearingtemperature

    Inspect pump and piping for leaks Check temperature of bearings Observe discharge pressure

    Quarterly Inspections

    Check hold down bolts for tightness

    Yearly Inspections

    Check pump capacity, pressure, and power. If the pump performance does not satisfy your processrequirements, the pump should be disassembled andinspected. Worn parts should be replaced.

    VRS IOM - 5/08 19

  • 8/10/2019 Manual General Bomba VRS- 021

    26/40

    MAINTENANCE OF BEARINGSThe bearings have been adequately greased prior toshipment. Under normal operating conditions, add greasemonthly or after 500 operating hours, whichever occursfirst. Add approximately (4) pumps to the inboard fittingand outboard fitting. Use a lithium based NLGI 2 grease to

    match the type used when the pump was initially built.

    CAUTION Never mix greases of different consistency (NLGI 1 or 3 with NLGI 2) or different thickener soaps (sodium or calcium with lithium). The consistency usuallybecomes softer and will not provide adequatelubrication to the bearings.

    NOTE: When regreasing there is a possibility of impurities entering the bearing housing. The greasecontainer, the greasing device, and the fittings must beclean.

    Acceptable Greases:Shell Alvania No. 2Mobil Mobilux EP No. 2Texaco Multifak No. 2Sun Oil Co. Prestige No. 42American Oil Co. Amolith Grease No. 2

    MAINTENANCE OF SEALSWhen it becomes necessary to replace the bearing housingseals, the housing and the bearings should be flushed cleanwith a solvent and repacked with new grease. Overpackingresults in excessive bearing temperature.

    MAINTENANCE OF DRIVE

    Well designed and properly installed V-belt drives arecapable of running for years without maintenance. Thereare a few points that should be checked periodically.

    Sheave Alignment - Alignment must be maintainedfor full power transmission, minimum vibration, andlong drive life.

    Belt Installation - When installing new belts, shortenthe center distance between sheaves so that the beltscan be placed on the sheave without the use of force. Never roll or pry the belts into place, as this coulddamage the belt cords.

    Check Belt Fit - Regardless of the belt section used,the belt should never be allowed to bottom in thegroove. This will cause the belts to lose their wedgingaction and allow slippage. Replace such sheaves or belts.

    Maintain Proper Belt Tension - Tension is essentialfor long belt life. Improper tension could cause beltfatigue and/or hot bearings. Methods of determining proper belt tension can be obtained from the drivemanufacturer.

    Use Belt Guards - Belt guards protect personnel fromdanger and the drive from contamination. Inspect

    periodically to assure that belts do not rub againstguard. Keep Belts Clean - Dirt and grease reduce belt life.

    Belt dressing affects performance only temporarilyand is never recommended. Maintaining a clean driveis a better idea.

    If any questions arise pertaining to the drive limitations,consult the manufacturer.

    20 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    27/40

    IMPELLER CLEARANCE SETTINGA change in pump performance may be noted over time bya drop in head or flow or an increase in power required.Performance can usually be restored by adjusting theimpeller clearance. Each application is different and henceit is necessary to monitor the amount of wear over a certain

    period of time in order to set up an adjustment schedule.Other factors which may indicate that impeller adjustmentis required are:

    High thrust bearing temperatures resulting fromuneven adjustment of impeller adjusting bolts

    Noise and vibration resulting from the impeller rubbing the suction liner

    Adjust the impeller clearance with the pump in the vertical position.

    ! WARNING Lockout driver power to prevent accidental start-up.

    1. Lockout power to driver.

    2. Remove the coupling guard (direct drive) or belt guard(belt drive).

    3. Break the coupling (direct drive) or remove tensionfrom belts (belt drive).

    NOTE: Lubricate the adjusting bolts and nuts for easyturning.

    4. Loosen the thrust housing adjusting bolt nuts (415A)and locking capscrews (356B).

    5. Turn thrust housing adjusting bolts (9956)counterclockwise to lower the thrust housing (134A)

    until the impeller (101) touches the suction liner (600R).

    6. Turn the thrust housing adjusting bolts (9956)clockwise to raise the thrust housing (134A) 0.030 in(0.76 mm), which is the recommended operatingclearance. This adjustment is best measured with a dialindicator. Adjust each bolt slightly each time around sothat the thrust housing rises evenly and is not cockedin the bearing frame (228). Make sure the rotatingassembly turns freely throughout the entire rotation.

    7. Tighten the thrust housing adjusting bolt nuts (415A)and locking capscrews (356B), carefully noting that

    the dial indicator does not change during finaltightening.

    8. Make sure the rotating assembly turns freelythroughout the entire rotation.

    9. Align the coupling (direct drive) or sheaves (beltdrive) as outlined in the installation section.

    10. Replace the coupling guard (direct drive) or belt guard(belt drive).

    PUMP WASHDOWNThe pump is designed to prevent liquid from entering the bearing frame. Care should be taken, however, to avoidspraying a high pressure stream directly at the bearingframe seals.

    TROUBLESHOOTING GUIDE

    INSUFFICIENT CAPACITY Pump not primed, check the sump liquid level Speed too low Total head higher than pump rating Insufficient NPSH Impeller passages partially blocked. Wrong direction of rotation Mechanical defects: impeller worn or damaged,

    defective gasket causing leakage

    INSUFFICIENT PRESSURE Speed too low Air in liquid Wrong direction of rotation Mechanical defects: impeller worn or damaged,

    defective gasket causing leakage

    VRS IOM - 5/08 21

  • 8/10/2019 Manual General Bomba VRS- 021

    28/40

    MOTOR OVERLOAD Speed too high Total head lower than pump rating resulting in

    increased flow Liquid being pumped has higher specific gravity than

    that for which it is rated

    Mechanical defects: bent shaft, worn bearings, wornimpeller or other wet end parts Solids locked in and around impeller Rubbing or binding of rotating elements

    PUMP VIBRATION Foundation not sufficiently rigid Impeller partially blocked causing imbalance Misalignment of thrust housing - housing cocked Mechanical defects: bent shaft, worn bearings, worn

    impeller

    WATER HAMMER Water hammer is a high pressure surge within a closed pipesystem, created by a rapid change in the flowrate. The mostcommon is the sudden opening or closing of a valve or other flow control device. Rapid changes in flowrate canalso occur when there is a sudden change in pump speed.Extensive damage to the pump and pipeline can result fromwater hammer.

    22 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    29/40

    DISASSEMBLY AND REASSEMBLYPUMP DISASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Disassembly of Wet End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Disassembly of Power End. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    INSPECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Impeller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Suction/Gland Liners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Casing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Shaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Column Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Seals, O-Rings, Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    REASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Reassembly of Power End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Reassembly of Wet End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Reassembly of Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    REFER TO FIGURES AT END OF MANUAL FOR DISASSEMBLY AND REASSEMBLY.

    PUMP DISASSEMBLY

    DISASSEMBLY OF WET END

    ! WARNING Lockout driver power to prevent accidental startup.

    1. Lockout power supply to motor.

    2. Close discharge valve. Drain the pump.

    ! WARNINGThe pump may handle hazardous and/or toxic fluids. Hazardous fluids may be under pressure and may erupt when pump is opened, particularly if pump is hot. Allow pump to cool and open cautiously. Skin and eye protection may be required. Precautions must be takento prevent injury or environmental damage. Alwaysknow the contents of the pump prior to opening it.Failure to do so can result in death, personal injury or property or environmental damage.

    3. Remove piping from pump.

    4. Remove coupling guard (direct connect) or belt guardand belts (belt drive). Remove motor.

    5. Remove pump from sump and lay on horizontalsurface.

    6. Wash down pump and inside column pipe and casingwith appropriate cleaner.

    7. Remove motor mount and coupling (direct drive) or sheave (belt drive) from the pump.

    8. Remove strainer, and/or tailpipe from suction half casing (100A), if supplied.

    9. Remove the discharge pipe assembly (195) from bearing frame (228) and casing (100A/D), if applicable.

    ! WARNING Suction casing (100A) must be supported beforeremoving tiebolts.

    10. Remove the suction half casing (100A). The suctionliner (600R) will be attached to the casing.

    11. Remove the suction liner (600R) from the suction half casing (100A).

    ! WARNING Do NOT apply heat to the hub or nose of the impeller due to the danger of explosion.

    12. Unscrew the impeller (101) from the shaft (122) byclamping the shaft and turning the impeller in thedirection for a normal right hand thread (counter-clockwise when viewing eye of impeller). After removing impeller, wrap tape around shaft threads to

    VRS IOM - 5/08 23

  • 8/10/2019 Manual General Bomba VRS- 021

    30/40

    avoid damage. Remove impeller washer (199).

    13. Mark the orientation of the gland half casing (100D) tothe column pipe (192). Disassemble the gland half casingfrom the column pipe by removing capscrews (371W).The gland liner (600T) will be attached to the casing.

    14. Remove the gland liner (600T) from the gland half casing (100D).

    15. Mark orientation of column pipe (192) to bearingframe (228). Disassemble column pipe from bearingframe by removing capscrews (371M).

    DISASSEMBLY OF POWER END1. Remove the inboard bearing deflector (123A) by

    sliding it down the shaft.

    2. Remove the inboard seal plate (119B) with O-ring(412) and seal (333) from the bearing housing (228).

    3. Remove thrust housing locking capscrews (356B).

    4. Draw thrust housing (134A) and shaft (122) from bearing frame (228).

    5. Check inboard bearing (168C) to see if it is worn,loose, or rough and noisy when rotated. Press theinboard bearing (168C) off the shaft (122) if replacement is required. It is recommended that a new bearing be installed after pressing off old bearing,regardless of condition. The thrust bearing must beremoved from the shaft to replace the inboard bearing(see step 7).

    6. Remove the outboard deflector (123) by sliding up theshaft.

    7. Remove the thrust bearing locking clip (361) from thethrust housing (134A).

    8. Slide thrust housing (134A) up the shaft to removefrom the thrust bearing (112C).

    7. Check outboard thrust bearing (112C) to see if they areworn, loose, or rough and noisy when rotated. Removethe outboard bearing locknut (136) and lockwasher (382). Press the outboard bearing (112C) off the shaftif replacement is required. It is recommended that anew bearing be installed after pressing off old bearing,regardless of condition.

    8. Check the condition of the inboard seal (333). Removethe inboard seal from the inboard seal plate (119B) if replacement is required. It is recommended that a newseal be installed after pressing out old seal, regardlessof condition.

    9. Check the condition of the outboard seal (332). Pressthe outboard seal from the thrust housing (134A) if replacement is required. It is recommended that a newseal be installed after pressing out old seal, regardlessof condition.

    INSPECTIONS

    IMPELLER Replace if excessive erosion, extreme wear, or vane breakage is evident. Reduction in hydraulic performancemay be caused by excessive wear, especially along thesuction wear ring surface.

    SUCTION/GLAND LINERSReplace if excessive erosion or extreme wear is evident.

    CASINGReplace if excessive erosion, corrosion, or extreme wear is

    evident.

    SHAFTCheck for runout [0.006 in (.015 mm) maximum] to ensurethat the shaft is not bent. Bearing seats and seal areas must be smooth and free of scratches and grooves. Shaft threadsmust be in good condition. Replace if necessary.

    COLUMN PIPEReplace if worn or excessively corroded.

    BEARINGSReplace if worn, loose, or rough and noisy when rotated.

    SEALS, O-RINGS, GASKETSReplace during reassembly.

    24 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    31/40

    REASSEMBLY

    REASSEMBLY OF POWER END1. Clean shaft (122) thoroughly, checking for nicks or

    worn areas.

    2. Press the outboard seal (332) into the thrust housing(134A), positioning the seal so that the lip pointsupward when installed in the pump. Press the inboardseal (333) into the inboard seal plate (119B), positioning the seal so that the lip points downwardwhen installed in the pump. Lubricate both seals with athin coat of grease.

    3. Heat the inboard bearing (168C) evenly using an oven, bearing heater, or hot clean oil bath. The use of a torchis not recommended. Heat the bearing to 230 degrees Fto 250 degrees F (110 degrees C to 121 degrees C).Slide the bearing onto the shaft from the drive enduntil the bearing shoulder is firmly against the shaft

    shoulder. Hold in place until bearing cools and gripsthe shaft.

    4. Heat the outboard bearing (112C) evenly using anoven, bearing heater, or hot clean oil bath. The use of atorch is not recommended. Heat the bearing to 230degrees F to 250 degrees F (110 degrees C to 121degrees C). Slide the bearing onto the shaft until the bearing shoulder is firmly against the shaft shoulder.Hold in place until bearing cools and grips the shaft.

    5. Position bearing lockwasher (382) and locknut (136)against the bearing shoulder and tighten firmly. Bendtang of lockwasher into locknut slot after the locknut

    has been tightened.6. Hand pack the inboard (168C) and outboard bearings

    (112C) with recommended grease (see Maintenancesection). Mound a small amount of grease above the bearing to ensure sufficient lubrication.

    7. Insert thrust housing (134A) over the outboard bearing(112C).

    8. Insert bearing locking clip (361) in thrust housing(134A).

    9. Install O-ring (496A) on thrust housing (134A) andlubricate.

    10. Install outboard deflector (123) by sliding it down theshaft until it is approximately 0.06 in (1.5 mm) fromthe thrust housing (134A).

    11. Insert thrust housing and shaft assembly into bearingframe (228). Install thrust housing locking capscrews(356B), thrust housing adjusting capscrews (9956) andnuts (415A). Adjust all hardware so that the thrusthousing (134A) bottoms out in bearing frame (228).

    12. Install O-ring (412) on inboard seal plate (119B). Slideinboard seal plate and seal up shaft and mount to

    bearing housing (228).

    13. Install inboard deflector (123A) by sliding it up theshaft until it is approximately 0.06 in (1.5 mm) fromthe inboard seal plate (119B).

    REASSEMBLY OF WET END1. Slide column pipe (192) up shaft (122) and attach to

    bearing frame (228) with capscrews (371M) using theorientation marks made during disassembly.

    2. Attach gland liner (600T) into gland half casing(100D).

    3. Attach gland half casing (100D) to column pipe (192)using the orientation marks made during disassembly.

    4. Remove protective tape from shaft (122) threads.Install impeller washer (199) on shaft (122). Threadthe impeller (101) onto the shaft until it is snug againstthe shaft washer (199). Hold the drive end of the shaftand firmly tighten the impeller.

    5. Move the impeller (101) by means of the thrusthousing adjusting capscrews (9956) toward the driveend as far as possible.

    6. Install the suction liner (600R) into the suction half casing (100A).

    7. Attach the suction half casing (100A) and liner to thegland half casing (100D).

    8. Adjust the impeller using the thrust housing adjustingscrews (9956) so that the impeller turns freely.

    9. Assemble the discharge pipe assembly (195) to thecasing discharge (100A/D) and bearing frame, if supplied.

    10. Install strainer and/or tailpipe onto suction half casing(100A), if supplied.

    11. Install unit into sump, being careful not to damage thestrainer, if supplied.

    12. Connect piping to pump following procedures in theInstallation section.

    13. Use the impeller clearance setting procedure on page18 to set proper impeller clearance.

    REASSEMBLY OF DRIVE1. Mount drive onto pump.

    2. Align the coupling (direct drive) or sheaves (beltdrive) as outlined previously.

    3. Replace the coupling guard (direct drive) or belt guard(belt drive).

    VRS IOM - 5/08 25

  • 8/10/2019 Manual General Bomba VRS- 021

    32/4026 VRS IOM - 5/08

  • 8/10/2019 Manual General Bomba VRS- 021

    33/40

    SPARE AND REPAIR PARTSREPLACEMENT PARTS PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . 27RECOMMENDED SPARE PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    REPLACEMENT PARTS PROCEDURETo ensure against possible long and costly down time periods, especially on critical services, it is advisable tohave spare parts on hand.

    Repair orders will be handled with a minimum of delay if the following directions are followed:

    1. Give model number, size of pump, and serial number.These can be obtained from the nameplate on the pump.

    2. Write plainly the name and part number of each partrequired. These names and numbers should agree withthose on the bill of material.

    3. Give the number of parts required.

    4. Give complete shipping instructions.

    RECOMMENDED SPARE PARTSLight Duty - Random mildly abrasive particles

    (1) Seal/Gasket Set

    Medium Duty - Light slurries up to 1.2 SG withmoderately abrasive materials

    (1) Impeller (1) Gland Liner (1) Suction Liner (1) Seal/Gasket Set(1) Set Bearings

    Heavy Duty - Slurries over 1.2 SG with highly abrasivematerials

    (1) Impeller (1) Gland Liner (1) Suction Liner (1) Shaft/Bearing Assembly(3) Seal/Gasket Set

    Severe Duty - Key process equipment and/or heavyslurries over 1.2 SG with high heads and highly abrasive particles

    (2) Impeller (2) Gland Liner (2) Suction Liner (3) Seal/Gasket Set(1) Spare Pump

    VRS IOM - 5/08 27

  • 8/10/2019 Manual General Bomba VRS- 021

    34/4028 VRS IOM - 5/08

    Figure 6VRS Sectional

  • 8/10/2019 Manual General Bomba VRS- 021

    35/40VRS IOM - 5/08 29

    Figure 7VRS Wet End Assembly

  • 8/10/2019 Manual General Bomba VRS- 021

    36/4030 VRS IOM - 5/08

    Figure 8

    VRS Power End Assembly

  • 8/10/2019 Manual General Bomba VRS- 021

    37/40

    NOTES

    VRS IOM - 5/08 31

  • 8/10/2019 Manual General Bomba VRS- 021

    38/40

  • 8/10/2019 Manual General Bomba VRS- 021

    39/40

  • 8/10/2019 Manual General Bomba VRS- 021

    40/40

    HOW TO ORDER PARTS

    When ordering parts call1-800-446-8537

    or your local ITT Goulds Representative

    EMERGENCY SERVICE

    Emergency parts service is available24 hours a day, 365 days/year

    Call 1-800-446-8537

    Visit our website at www.gouldspumps.com