Maxilite Fire Damper Upgrade Systems Technical Manual tfire.com.au The Trafalgar fire stopping range includes: Sealant | Pillows | Mortar | FR Batts FR Collars | FR Access Panels | Pipe Wraps FyreWrap Duct Wrap | FR Downlight Covers Intumescent Dampers | Fire Door Hardware Fire Rated Board and Systems | Cable Coating FYREBOX for multiple and mixed services 27062018

Upload: others

Post on 17-Feb-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

  • Maxilite Fire Damper Upgrade Systems Technical Manual

    tfire.com.au

    The Trafalgar fire stopping range includes:

    Sealant | Pillows | Mortar | FR Batts

    FR Collars | FR Access Panels | Pipe Wraps

    FyreWrap Duct Wrap | FR Downlight Covers

    Intumescent Dampers | Fire Door Hardware

    Fire Rated Board and Systems | Cable Coating

    FYREBOX for multiple and mixed services

    27062018

  • tfire.com.au 1800 888 714

    Page 2 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Product Overview

    To maintain market leadership, Trafalgar stay up to date with the latest

    technologies and trends in passive fire protection and contemporary

    construction techniques. We are 70 years strong and still innovating!

    Maxilite is a lightweight, high performance fire rated board. It is a calcium silicate based

    product, bonded together with non-organic binders, that meets all requirements for

    asbestos, volatile organic compounds (VOC’s) and ozone depleting potential (ODP)

    Compounds. Maxilite boards are available in a number of discrete thicknesses for use in

    the fire protection of structural steel. Maxilite has been tested to various local and

    international test standards and is suitable for a large range of steel sizes and types.

    How does it work?

    Maxilite is an extremely effective insulating refractory board. The Maxilite board is stable

    under high temperature stress and remains strong and crack free, even when exposed to

    fully developed fires. The Maxilite board provides a thermal insulation as well as a heat

    sinking capacity for steel.

    Key Features • Lightweight

    • Low thermal conductivity

    • Up to 4 hours fire-rated protection

    • Fully Tested and Approved for the Australian market

    • Various methods of installation

    • No mess

  • tfire.com.au 1800 888 714

    Page 3 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    Technical Specifications

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    FRL Up to -/120/120 (Limited to that of the damper/fire barrier)

    Approved Wall Systems

    Concrete/Masonry Hollow Block Plasterboard Shaftwalls Hebel

    Approved Dampers

    Any fire damper which has been independently tested and validated for use in a wall for 120 minutes

    Maximum Size of Maxilite

    Maxilite limited to one sheet: 1500mm x 1000mm

    Figure 1: Oversized Wall Opening

    Figure 2: Installed Maxilite Fire Damper Upgrade System

    Fire Damper Upgrade Systems

    Often Brick or block work is finished short or left missing to allow for the installation of a fire damper. Maxilite Fire Damper Upgrade (MFDU) systems allow for the installation of a fire damper whilst simultaneously sealing the oversized penetration and maintaining the fire integrity of the wall as required by the Building Code of Australia.

  • tfire.com.au 1800 888 714

    Page 4 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Installation Guidelines

    Section A – Masonry Systems A.1 MFDU-01 This installation detail consists of 40mm Maxilite strips secured around the perimeter of the damper, the slab soffit and/or the perimeter of the wall opening. These strips are then faced with Maxilite board. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant.

    • All screw fixings are of a length equal to 1.5 X Maxilite thickness.

    • Fire damper is installed as per manufacturers specifications.

    Figure 3: MFDU-01 Maxilite Arrangement

  • tfire.com.au 1800 888 714

    Page 5 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Installation Guidelines

    Section A – Masonry Systems A.2 MFDU-02 This installation detail consists of a steel square hollow section (SHS) clad with minimum 30mm Maxilite. This clad steel section is then fixed to a Maxilite strip which has been secured around the perimeter of the slab soffit and/or wall opening. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant.

    • All screw fixings are of a length equal to 1.5 X Maxilite thickness.

    • Fire damper is installed as per manufacturers specifications.

    Figure 4: MFDU-02 Maxilite Arrangement

  • tfire.com.au 1800 888 714

    Page 6 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    Installation Guidelines

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Section A – Masonry Systems A.3 MFDU-03 This installation detail consists of laminated strips of Maxilite secured around the perimeter of the damper, the slab soffit and/or the perimeter of the wall opening. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant.

    • All screw fixings are of a length equal to 1.5 X Maxilite thickness.

    • Fire damper is installed as per manufacturers specifications.

    Figure 5: MFDU-03 Maxilite Arrangement

  • tfire.com.au 1800 888 714

    Page 7 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    Installation Guidelines

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Section A – Masonry Systems A.4 MFDU-04 This installation detail consists of a steel angle secured centrally around the perimeter of the slab soffit and/or the wall opening. Maxilite board is then laminated on each side of the angle, filling the opening around the damper. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant.

    • All screw fixings are of a length equal to 1.5 X Maxilite thickness.

    • Fire damper is installed as per manufacturers specifications. .

    Figure 6: MFDU-04 Maxilite Arrangement

  • tfire.com.au 1800 888 714

    Page 8 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    Installation Guidelines

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Section A – Masonry Systems A.5 MFDU-05 This installation detail consists of laminated strips of Maxilite secured around the perimeter of the damper, the slab soffit and/or the perimeter of the wall opening. A Maxilite board is then faced over these previously laminated Maxilite strips. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant.

    • All screw fixings are of a length equal to 1.5 X Maxilite thickness.

    • Fire damper is installed as per manufacturers specifications.

    Figure 7: MFDU-05 Maxilite Arrangement

  • tfire.com.au 1800 888 714

    Page 9 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    Installation Guidelines

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Section A – Masonry Systems A.6 MFDU-06 This installation detail consists of strips of Maxilite secured around the perimeter of the duct and the slab soffit (if required). Maxilite board is then fixed over the wall and the previously secured Maxilite strips. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant.

    • Maxilite board overlaps the wall opening by at least 100mm.

    • All screw fixings are of a length equal to 1.5 X Maxilite thickness.

    • Fire damper is installed as per manufacturers specifications.

    Figure 8: MFDU-06 Maxilite Arrangement

  • tfire.com.au 1800 888 714

    Page 10 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    Installation Guidelines

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    Section B – Plasterboard Systems B.1 MFDU-07 This installation detail involves trimming all four sides of the wall opening with Maxilite strips of equal width to the wall studs. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant.

    • All screw fixings are of a length equal to 2 X plasterboard thickness.

    • Fire damper is approved for use in plasterboard walls and installed as per manufacturers specifications

    Figure 9: MFDU-07 Maxilite Arrangement

  • tfire.com.au 1800 888 714

    Page 11 of 11 Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 27.06.2018

    Installation Guidelines

    MAXILITE F i r e D a m p e r U p g r a d e S y s t e m s

    This installation detail consists of a panel of Maxilite, with an intumescent damper, fixed to the face of the wall, over the wall opening. Please ensure:

    • All joins in Maxilite are sealed with Fyreflex Sealant

    • Maxilite board overlaps the wall opening by at least 100mm

    • The maximum damper size is 800x800mm

    • The Maximum Maxilite panel size is 1200x1200mm OR 1500x1000mm

    Section C – Masonry Systems C.1 MFDU-08

    Figure 10: MFDU-08 Maxilite Arrangement