medium volatge distribution fluokit m 9 - schneider...

52
www.schneider-electric.com Installation - Commissioning Operation - Maintenance Medium Volatge Distribution FLUOKIT M 9

Upload: truongngoc

Post on 05-Feb-2018

233 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

www.schneider-electric.com

Installation - CommissioningOperation - Maintenance

Medium Volatge Distribution

FLUOKIT M 9

Page 2: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

2 AMTNoT058-02 02

Contents

■ Presentation ........................................................................................................ 6 □ Description .................................................................................................... 6 □ Presentation of the Functional Units IS and PF -PFA .................................... 6 □ Presentation of the Functional Units TM and PGC ........................................ 7 □ Presentation of the Functional Unit PGcoupling + current dividers + VBL circuit

breaker ............................................................................................................... 7

■ Packaging - Handling - Storage ........................................................................ 8 □ Transport -Delivery ......................................................................................... 8 □ Packaging for the Functional Units ................................................................ 8 □ The accessories pack .................................................................................... 8 □ Acceptance..................................................................................................... 9 □ Location of the technical data plates ............................................................. 9 □ Handling ......................................................................................................... 9 □ Storage ......................................................................................................... 10 □ Levels of intervention ................................................................................... 10 □ Special instructions for storage of less than 6 months ................................ 10 □ Special instructions for storage of between 6 and 12 months ..................... 10 □ Special instructions for storage of between 12 and 24 months .................. 10

■ Unpacking and installation of the equipment ................................................11 □ Type of Civil Engineering ..............................................................................11 □ Surface flatness characteristics ....................................................................11 □ Unpacking Functional Units ..........................................................................11 □ Handling the Functional Unit .........................................................................11 □ Installation on the ground ............................................................................. 12 □ Installation of a switchboard in its room ....................................................... 12 □ Revalorizing packaging waste...................................................................... 12

■ Installation ......................................................................................................... 13 □ Installing Functional Units ............................................................................ 13 □ Installation of each Functional Unit .............................................................. 13 □ Fixing the Functional Units ........................................................................... 14 □ Connection of the inter-Functional Units grounding circuit .......................... 14 □ Earthing the switchboard (possible on either the right or left) ..................... 15 □ Standard busbar connections ...................................................................... 15 □ Preparation of the HVA cable connections .................................................. 16 □ Connection of an IS Functional Unit ............................................................ 17 □ Connection of a PF-PFA or PGC Functional Unit ........................................ 18 □ Clamping the cables and connection of the screen braids .......................... 18 □ Fitting the fuses on to the PF-PFA Functional Units .................................... 19 □ Operations to be carried out and checks to be made before commissioning ...19

■ Commissioning ................................................................................................ 21 □ Switchgear operations .................................................................................. 21 □ Energising of the ”Incoming” cables............................................................. 21 □ Accessories for the control of voltage presence .............................................. 21 □ Voltage presence inspection and control. ...............................................................21 □ Checking the phase balance and voltage presence ............................................. 22 □ Energising the switchboard. ........................................................................ 22

■ Instructions for manoeuvres and operations ................................................ 23 □ Reminders .................................................................................................... 23 □ Testing the cables ........................................................................................ 24 □ Installing the earthing switch device ............................................................ 24 □ Opening the earthing switch (switch open; door panel in place) ............... 25 □ Closing the earthing switch (switch open) ................................................... 25 □ Closing the load break switch with the C310 control mechanism (earthing

switch open; door panel in place) ............................................................... 26

Page 3: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

3AMTNoT058-02 02

□ Opening the load break switch with the C310 control mechanism .............. 27 □ Arming the C40-1 control mechanism for closing the switch (earthing switch

open; door panel in place) ..............................................................................28 □ Closing the load break switch ...................................................................... 29 □ Opening the load break switch..................................................................... 29 □ Disarming the C40-1 mechanical control mechanism ................................. 30 □ Commissioning a PGC or PGcoupling Functional Unit................................ 32• Opening of the downstream earthing switch (only for PGC) ...................... 32• Opening the upstream earthing switch. ...................................................... 33• Closing the load break switch. .................................................................... 33 □ Circuit breaker closing and tripping operations ............................................ 34 □ De-energising a PGC or PGcoupling Functional Unit .................................. 34 □ Operating manoeuvres for the TM Functional Unit ...................................... 34

■ Locking-out and locking operations .............................................................. 35 □ Locking-out by padlock (not supplied) ......................................................... 35 □ Locking-out by keylocks ............................................................................... 36

■ Maintenance ...................................................................................................... 37 □ Maintenance levels ...................................................................................... 37 □ Frequency of intervention............................................................................. 37 □ Systematic maintenance .............................................................................. 37 □ Preventive maintenance of the Functional Units .............................................. 37 □ Preventive maintenance for the mechanical control mechanisms ............... 38 □ Corrective maintenance ............................................................................... 38 □ Lubrication and greasing points ................................................................... 39 □ Replacement of the three MV fuses ............................................................ 40 □ Replacement of a capacitive insulator in an IS Functional Unit .................. 41 □ Replacement of a capacitive insulator in a PF-PFA Functional Unit ........... 43 □ Replacement of the VDS (Voltage Detection System - LV capacitors ......... 45 □ Possible anomalies and remedies ............................................................... 46

■ Spare parts ........................................................................................................ 47 □ Identification of the equipment .................................................................... 47 □ Storage conditions ....................................................................................... 47 □ The spare parts ............................................................................................ 47 □ Additional spare parts .................................................................................. 47

■ At the end of the equipment’s operational life .............................................. 48 □ Dismantling the circuit breaker ..................................................................... 48 □ Specific recommendations for the ”SF6 gas” type circuit breaker and load

break switch ................................................................................................ 48 □ Specific recommendations for ”Vacuum” type circuit breakers .................... 48 □ Specific recommendations for the Functional Unit ...................................... 48 □ Example of the distribution of the weights on a Functional Unit .................. 48

■ Notes .................................................................................................................. 49

Contents (contd.)

Page 4: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

4 AMTNoT058-02 02

Overview

© - Schneider Electric - 2010. Schneider Electric, the Schneider Electric logo and their figurative forms are Schneider Electric registered trademarks. The other trademarks mentioned in this document, registered or not, belong to their respective holders.This user manual only applies to 12 and 17.5 kV Functional Units

ResponsibilitiesOur devices are quality controlled and tested at the factory in accordance with the standards and regulations currently in force.Apparatus efficiency and apparatus life depend on the compliance with the installation, commissioning and operation instructions described in this user manual. Non-compliance with these instructions is likely to affect your guarantee rights. The texts in this user manual make reference to international regulations.Local requirements especially about safety which are in accordance with the indications given in this document, must be observed.

Reminder concerning normal operating conditions In accordance with IEC 60694.

Permissible ambient temperature The ambient air temperature must remain within - 15° C and + 40° C. The average measured value for a 24 hour period must not exceed 35° C.

Installation altitude MV equipment can be operated up to an altitude of 1,000 m. If this altitude is exceeded, account must be taken of the decrease in the dielectric rigidity of the air, leading to a decrease in insulation. If such is the case, use substation switchgear of a higher voltage range.

Atmospheric pollution There must be no dust particles, fumes or smoke, corrosive or flammable gases, vapours or salts.

Permissible atmospheric humidity level The average value of atmospheric humidity in a 24 hour period must not exceed 95 %. The average water vapour pressure over a period of 24 hours must not exceed 22 mbar. The average atmospheric relative humidity value measured over a period of one month must not exceed 90 %. The average water vapour pressure over a period of one month must not exceed 18 mbar. Condensation may appear in case of any sharp variation in temperature, due to excessive ventilation, a high atmospheric humidity level or the presence of hot air. This condensation can be avoided by an appropriate lay-out of the room or of the building (suitably adapted ventilation, air driers, heating etc.). Whenever the humidity level is higher than 75%, we recommend that you take appropriate corrective measures for which Schneider Electric can offer you the necessary assistance. Do not hesitate to contact us.

Other technical instructions to be consulted ■ AMTNoT061–01 F3.020.015 C310–C310M Control

MechanismsOperation –Maintenance

■ AMTNoT062–01 F3.020.016 C40–1 Control Mechanism

Operation –Maintenance

■ AMTNoT066–01 F3.020.017 Fluokit M9 Installation instructions for standard interlocks by keylocks

■ F3.020.025 VB L (DPI L) G3 vacuum type circuit breaker

Operating instructions

■ F3.020.026 VB L (DPI L) G4 vacuum type circuit breaker

Operating instructions

Page 5: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

5AMTNoT058-02 02

Overview (contd.)

Tools and products (not supplied) required for the operations described in this user manual

■ Cutter

■ Crowbar

■ Flat blade screwdrivers size 70 i 73 i 76 i 78 & 79 mm

■ Ratchet handle + 750mm extension with socket sizes 70 i 73 i 76 & 78 mm

■ Torque wrench with sockets size 70 i 73 i 78 mm

■ Magnetic screwdriver + 3mm Allen key tip

■ Flat blade screwdriver

■ Allen key for sizes 4 i 5 i 6 i 8 mm

Product code ■ Clean dry cloth -

■ Solvent (dielectric withstand > 30kV)t excluding any chlorinated products

-

■ Mobilgrease 28 Red - synthetic grease from Mobil

■ Electrolube 2 GX - electrical contact grease from Comindus

Conventional symbols

Code of a product recommended and marketed by Schneider Electric

Value of the tightening torque Example: 7.6 daN.m

Mark corresponding to a legend

CAUTION ! Remain vigilant! Precautions to be taken in order to avoid any accident or injury.

FORBIDDEN! Do not do it! The compliance with this indication is compulsoryt non-compliance may damage the equipment.

INFORMATION - ADVICE Your attention is drawn to a specific point for installation or operation.

Page 6: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

6 AMTNoT058-02 02

Presentation

Description FLUOKIT M9 Functional Units are designed forindoor use.The range meets the definitions of switchgear ot the type ”under compartmentalised metal casing”, in compliance with the design and construction rules mentioned in chapter 5 of Standards NBN/EN 60298 and IEC 60466.Each Functional Unit is divided into four separate compartments, designed for indoor use. separated by metal partitions:

■ Telecontrol compartment ■ Busbar ■ Breaker or insulation switchgear with operating device ■ Cables.

Dimensions and approximate weight of the Functional Units

Functional Units IS PGrouping LRCT TM PF/PFA PGC

Width (mm) 375/500 750 375/500 375/500 375/500 750

Depth (mm) 1000 1000/1070* 1000 1000 1000 1000/1070*Height (mm) 1600 1600 1600 1600 1600 1600Approximate weight (kg) 120 470 180** 200 170 450

* Depth with circuit breaker** Function of the equipment (case of 2PT+ 2CT)

Presentation of the Functional Units IS and PF -PFALegend

1 Busbars connection plate2 ISR solating switch3 Roof panel4 Upstream earthing switch (in open position)5 Upper fuse support shell6 Cable connections shell7 MV Fuses8 Capacitive insulator9 Lower fuse holder shell10 Downstream earthing switch for PF/PFA fuses (in open position)11 Base plate in 4 elements12 LV casing13 Exhaust shaft14 Overpressure valves15 Switchgear earthing bar16 Busbars access panel17 Mechanical control mechanism for the switch18 Voltage presence luminous indicators or interface for Earthing Switch19 Inspection window for checking the earthing switch position20 Test pin for fitting the earthing block21 Access panel to the MV 1 cables compartment (IS - PF - PFA)22 Upper tightening straps support (IS)23 Earthing Switch (ES) location (LV capacitors)

IS (Isolating switch)

PF – PFA (Combined Fuse Protection)

Page 7: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

7AMTNoT058-02 02

Presentation (contd.)

Presentation of the Functional Units TM and PGCLegend

1 Busbars connection plate2 ISR solating switch3 Roof panel4 MV Fuses 5 Upper fuse support shell6 Insulating screen (under 24 kV).9 Lower fuse holder shell8 Voltage transformer9 Overpressure valves10 Switchgear earthing bar11 LV casing12 Busbars access panel13 Exhaust shaft14 Inspection window for checking MV fuses15 Access panel to the fuses compartment16 Earthing circuit for grounding the transformers.17 Mechanical control mechanism for the switch

18 Earthing switch19 VBL type vacuum circuit breaker20 Current dividers 21 Busbar insulator support -22 Capacitive insulato23 Upper tightening straps support 24 Base plate in 4 elements25 Voltage presence luminous indicators or interface for Earthing Switch26 Mechanical control mechanisms (load break switch and earthing switches)27 Test pin for fitting the earthing block28 Circuit breaker mechanical control mechanism 29 ES location (LV capacitors)

Presentation of the Functional Unit PGcoupling + current dividers + VBL circuit breakerLegend 1 Busbars connection plate 2 ISR <solating switch 3 Roof panel 4 Earthing switch 5 Current transformer 6 Current dividers 7 Insulator support 8 Voltage transformer 9 Overpressure valves 10 VBL type vacuum breaking circuit breaker 11 Load break switch closed.

TM (Isolating switch)

PGC + current dividers + VBL circuit breaker (General Cable Protection)

Page 8: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

8 AMTNoT058-02 02

Transport -DeliveryThe conditions and methods of transport are defined with the customer at the time of processing the contract.The packaging depends on the transport conditions, storage and the nature of the product transported.

The Functional Unit must be handled and transported vertically (position shown below).

Packaging for the Functional Units ■ Road and rail packaging for the Functional Unit:

□ fixed on to a wooden pallet or bound by hoops, □ covered by plastic sheeting, □ front cover protected with expanded polystyrene.

■ Air and sea packaging for the Functional Unit: □ under a heat-sealable cover with bags of dessicant, □ packed in wooden crates.

■ State of the equipment on delivery:1. Load break switch ”Open”2. Earthing switch ”Closed”.

The accessories packThis contains all of the elements required for installing and connecting the Functional Units, to busbar and cable connections.

Packaging - Handling - Storage

Page 9: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

9AMTNoT058-02 02

Packaging - Handling - Storage (contd.)

Acceptance ■ Ensure that the material delievered is all complete. ■ Carry out a visual inspection of the Functional Units and moving parts. ■ Check the presence of the accessories with the enclosed list. ■ Check the characteristics shown on the name and rating plates, in relation to the

initial order (See Location of the technical data plates).

In case of anomalies, make the necessery reserves with the carrier.

The Functional Unit must remain on its base, in its original factory packaging, during any storage period and until it arrives at the location of its installation.

Location of the technical data plates ■ 1 - Technical data plates. ■ 2 - Identification plate placed on the inside left-hand side of the LV casing.

Handling ■ Road and rail packaging (500 kg max.): using a forklift truck. ■ It is imperative that the forks of the truck are fully engaged throughout all of the

width of the Functional Unit.

■ Air and sea packaging: Depending on the weight indicated on the crate. ■ It is imperative that the forks of the truck are fully engaged throughout all of the

width of the crate.

■ Pass 2 slings, each one supporting 1,000 kg . ■ Remove the lifting parts after handling (4 screws, 13 mm spanner).

2

1

Page 10: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

10 AMTNoT058-02 02

Packaging - Handling - Storage (contd.)

StorageThe storage area must protect the equipment against any eventual degradation agents, such as :

■ Water ■ Water vapour ■ Salt-laden air ■ Pollution of all kinds ■ Micro-organisms

Contact Schneider Electric for any derogations to these criteria

Ensure that the material is suitably packaged for the requirements of the planned storage period.Avoid warehousing the equipment in premises that are subjected to large, sudden temperature differences.Ensure the total absence of aggressive vapours, sulphur dioxide (SO2) for instance.

Levels of interventionPreventive Maintenance Levels

Operations ensured by the Customer 1 1

Operations necessitating training to be carried out by an approved third party 2

Work to be carried out exclusively by Schneider Electric 3

Special instructions for storage of less than 6 monthsPackaging under plastic covers 1 2 3Inspect the packaging periodically ■ ■ ■

When unpacking : ■ check the mechanical operation by carrying out about ten operations - ■ ■

■ Test the min. threshold level (AC, 85% of Un ; DC, 70% of Un) for the electrical operations of the coils - ■ ■

Special instructions for storage of between 6 and 12 monthsPackaging under heat-sealable linen, with the presence of bags of dessicant

1 2 3

Inspect the packaging periodically (for absence of perforations amongst others) ■ ■ ■

When unpacking ■ lightly dilute the dried grease with a neutral vaseline oil - ■ ■

■ Check the mechanical operation by carrying out about ten operations - ■ ■

■ Test the min. threshold level (AC, 85% of Un ; DC, 70% of Un) for the electrical operations of the coils - ■ ■

Special instructions for storage of between 12 and 24 monthsPackaging under heat-sealable linen, with inspection hatch to change the bags of dessicant

1 2 3

Inspect the packaging periodically (for absence of perforations amongst others) ■ ■ ■

Periodically replace the bags of dessicant - ■ ■

When unpacking: ■ light maintenance work - - ■

■ Check the mechanical operation by carrying out about ten operations - - ■

■ Test the min. threshold level (AC, 85% of Un ; DC, 70% of Un) for the electrical operations of the coils - - ■

Page 11: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

11AMTNoT058-02 02

Type of Civil EngineeringThe installation of a switchboard requires sufficient flatness of the Civil Engineering structure. The dressing by a rule of a top coat of finishing cement should eliminate any surface irregularities of greater than 2 mm per metre. Seating on levelled metal supports is ideal as they will also serve as a guide for the dressing of the cement top coat.

SurfaceflatnesscharacteristicsOverall evenness: A 2 m rule, moved along the installation area, should not highlight any irregularity greater than 5 mm.Local evenness: A 20 cm rule, moved along the installation area, should not highlight any irregularity greater than 2 mm.

Unpacking Functional UnitsUnpacking of the Functional Units must only be carried out on their installation site.

Tools required: ■ Cutter for road and rail packaging ■ Crowbar for air and sea transport packaging

Use suitable protective gloves for any handling operations.

Handling the Functional Unit ■ Remove the protective plastic cover. ■ Open the front panel:

1. Lift up the panel 2. Pull the panel towards you.

■ Remove the 4 fixing screws (16 mm spanner) from the wooden base. ■ Free the Functional Unit.

■ Place the Functional Unit on the ground. ■ Replace the door panel.

Unpacking and installation of the equipment

Page 12: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

12 AMTNoT058-02 02

■ On PGcoupling and LRCT models, each door panel is fixed by 2 screws (5 mm Allen key).

■ Lift the Functional Unit using 4 slings each one capable of supporting 1,000 kg. ■ Respect the minimum carrying height as shown on the above diagram.

■ Slide the Functional Unit, using 3 cylindrical rollers of 30 mm min. diameter. ■ Move it in this way to its definitive location.

Installation on the groundThe limits of the civil engineering layout is dependent on the type and quantity of the equipment to be installed.Position the cubicles whilst respecting the minimum clearance distances in front of, behind and to each side of the switchboard (See Installation of a switchboard in its room).

Installation of a switchboard in its room ■ d1: > 20 mm ■ d2: > 125 mm ■ d3: > 125 mm ■ d4: > 800 mm ■ d5: > 125 mm

Revalorizing packaging wasteAfter unpacking, the materials used (cover, wooden floor panel, etc) should be sorted and sent to the appropriate recycling services.

Unpacking and installation of the equipment (contd.)

1 m min.

d2

d1

d4

M9switchboard(front face)

d4

d3d1

d5M9switchboard

(front face)

Transformer

Page 13: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

13AMTNoT058-02 02

Installing Functional UnitsFor a switchboard consisting of 1 to 8 Functional Units, it is recommended that the installation of the equipment start at the end of the room opposite the entrance.For switchboards using more than 8 units, start by installing the equipment in the middle of the switchboard.

Installation of each Functional UnitFor all installation operations, it is recommended that properly adapted work gloves be used for this work.Organise the incoming on the Functional Units in accordance with the single-line diagram.

■ On each far end Functional Unit, fix:1. The rear bracket,2. The side panel.

■ Position the first Functional Unit. ■ Check the perpendicularity in relation to the ground. ■ Mark out the 6 coupling points.

■ Juxtapose the second Functional Unit. ■ Align the front panels. ■ Continue to install the Functional Units whilst repeating the same checks each

time.

Installation

Page 14: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

14 AMTNoT058-02 02

Installation (contd.)

Fixing the Functional UnitsFix the Functional Units to the ground, by 2 points at the front and 2 points at the rear (H M12x30 screws) or 2 points at the centre (PGC and PGcoupling).Couple the Functional Units together by 6 fixing points (H M8x20 screws).

■ 4 fixing points (Fixings not supplied).

■ The Functional Units at each end mustbeanchoredtothefloorbytheir4fixingpoints.

■ With the exception of specific requirements (seismic resistance, vibrations), it is acceptable to install only one in two of the Functional Units using just the fixings at the rear.

Connection of the inter-Functional Units grounding circuit

■ Position and fix the grounding circuit bars, on the roof of the Functional Units (M8 washer + ES 8 washer + H M8 nut - 13 mm spanner).

■ Close-up of tightening.

Front face of the switchboard: 3 or X Functional Units

Page 15: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

15AMTNoT058-02 02

Installation (contd.)

Earthing the switchboard (possible on either the right or left)

■ Right-hand extremity connection.

■ Lateral down conductor on the right-hand extremity for connection of the earthing points to the room’s ground electrode.

■ Fixing by H M12x20 screws + flat washer + spring washer + H M 12 nut (Fixings not supplied).

Standard busbar connectionsNo preparation of the contact surfaces is necessary. A simple dusting down should be allowed for. If the storage time has been long, ensure that there has been no trace of any shocks or oxidation. In case of oxidation, lightly brush the parts with Vaseline, using a very fine metal brush.

■ Gain access to the busbars by removing the roof panel (fixing by 3 H M8 screws at the rear).

■ Standard assembly of the bars on to the supply terminals.

■ Connection of the busbars between two Functional Units.

Page 16: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

16 AMTNoT058-02 02

Installation (contd.)

Preparation of the HVA cable connections ■ State of the Functional Units after installation: all of the earthing switches

are closed.

■ Remove the cable access panels.

■ Remove the cable tightening straps (1) (H M8x20 screws) and the grommets (2).

■ Remove the lower front cross-bar (2 screws, 13 mm spanner).

■ 1 - Pull the first element towards you. ■ 2 - Lift up and extract this element. ■ Proceed in the same way for the following two elements.

Page 17: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

17AMTNoT058-02 02

Installation (contd.)

■ Remove the upper cable tightening straps (6 H M8x50 screws in a captive nut, 13 mm spanner).

■ Cut out the grommets to the dimension of the cables. ■ Fit these blanking pieces on to the cables.

■ Carry out the terminals and the crimping of the lug on each cable in accordance with the instructions in the manufacturer’s manual (lugs and cables not supplied).

Leave 40 mm of free clearance on the lug barrel for fitting the flat-face grounding clamp.

Ensure the correct orientation of the contact plate.

Never clamp the cable to its terminal. We advise you to use short cable terminations of the EUI-C type, with shells.

Never stick the phase markers to the cable terminals. The adhesive of the coloured marker is a conductor and decreases the dielectric strength of the

termination.

Connection of an IS Functional Unit ■ Lift off the deflector, the H M12 nut and the two washers for each point. ■ Connection is made by a round or rectangular lug.

Never leave a washer in incompatible material between the lug and the connecting plate.

Round lug connection ■ Fit the lug which must hold firm against the contact plate. ■ Replace the flat washer ■ Replace the Belleville washer ■ Screw in the nut (18 mm spanner). ■ Clip on the deflector simply by pressure.

Rectangular lug connection ■ Fit in place the spacer in copper. ■ Position the rectangular lug. ■ Replace the flat washer ■ Replace the Belleville washer ■ Screw in the nut (18 mm spanner). ■ Clip on the deflector simply by pressure.

Page 18: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

18 AMTNoT058-02 02

Installation (contd.)

Connection of a PF-PFA or PGC Functional Unit

■ Remove the H M8 nut and the two washers from each tip. ■ Connection is made by a round lug.

PF - PFA Connection ■ Proceed in the same way as for the IS unit (§ Connection of an IS Functional Unit). ■ There is no deflector.

■ Remove the H M8 nut and the two washers from each point. ■ Connection is made by a round lug.

Legend for § Connection of a PF-PFA or PGC Functional Unit & Clamping the cables and connection of the screen braids

■ 1 Round lug ■ 2 Deflector ■ 3 H M12 nut ■ 4 Belleville Washer ■ 5 Flat washer ■ 6 Rectangular lug ■ 7 Copper spacer delivered with the accessories pack. ■ 8 H M8 nut

Clamping the cables and connection of the screen braids

■ Connect up the cable at the back. ■ Position the grommet at floor level. ■ Fix the two tightening straps to the flooring metal plates. ■ Clamp the cable at floor level (2 M M8x70 screws) ■ Tighten but not excessively ■ Clamp the cable on the upper part for the ”Incoming” Functional Units. ■ Replace a floor element and connect up the following cable. ■ Examples of a connection.

The earthing braid for the cables must come out above the upper collar clamping.

Page 19: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

19AMTNoT058-02 02

Installation (contd.)

Fitting the fuses on to the PF-PFA Functional Units

■ For a striker fuse of the FN or FD type (DIN), remove the protective label. ■ For FNw and FDw fuses this label must remain on. ■ For other fuses, follow the manufacturer’s instructions. ■ In all cases, ensure that the striker is positioned towards the top.

■ Lift the lid of the upper supply terminal. ■ Hold the fuse by its upper part. ■ Fit the fuse into the lower shell.

■ Push the fuse home into the upper supply terminal. ■ Ensure the correct refitting of the lid and the position of the ■ label: it must be visible from the front face panel.

After any work in the cable compartment, replace the front face panel and lock it by turning the handle.

Ensure that all of the connections, couplings, cables, earthing circuits and low voltage circuits have been correctly carried out.

Ensure that the fuses have been correctly fitted in place, the presence of the roof panels and access to the interior of the Functional Units.

Operations to be carried out and checks to be made before commissioningBefore shipment, FLUOKIT M9 Functional Units will have been tested both mechanically and electrically.Nevertheless, before commissioning them, it is necessary to:

■ Clean all of the switchboard. ■ Vacuum clean all of the dust. ■ List and tidy away all assembly tools and unnecessary parts. ■ Tidy away, at their location in the switchgear unit, the operating accessories for the

Functional Units and circuit breakers. ■ Clearly display and hang up the Technical Instructions, inside the room.

Refer to the drawings and diagrams supplied with the equipment. They describe the functions carried out in order to put into effect the detail of the necessary operations.Record the numbers and identification marks for the equipment and sub-assemblies. Rigorously carry out with great care all locking-out operations and tests under site conditions.Respect the general instructions as well as those for the site in force.

■ Check the leaktightness of the room, the cable troughs, ventilation, etc. ■ If the equipment has remained in a wet place, we recommend that you heat the

room or possibly supply power to the heating elements for 24 hours, before commissioning.

You may use the table below for your final checks.

Page 20: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

20 AMTNoT058-02 02

Installation (contd.)

Check-List Details DateBegun

DateEnded

Remarks OK

Visual inspectionsEnsure the absence of any foreign body inside the switchboard, traces of knocks, scaling of paint (if necessary carry out touch-ups).

Check that the cable passage bottom plates are correctly blanked-off.

Mechanical checksCheck the functioning of the mechanical interlocks and the locking by keylocks for the access doors and mobile panels.

Manual setting of the command control, the closing and manual tripping of the switch.

Electrical checks

Check the correct execution of the connections

■ the cables. ■ the low voltage circuit ■ the earthing circuit right to the

unit’s ground electrode, the tightening of mechanical fixings, tightening of the fixing points on the power circuit and the earthing circuit, to the torque values indicated. Operation of all of the low voltageswitchgear.

Record the relay parameters afterhaving noted the proper functioningof the switchboard.

Check both the high voltage and lowvoltage dielectrics.

Page 21: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

21AMTNoT058-02 02

Commissioning

Operation and maintenance may only be carried out by personnel who have received suitable authorisation for the operations and mauvres they are

responsible for performing. If this is not the case, please contact our After-Sales Department.

All locking-out operations must be performed according to the particular rules for thenetwork concerned.

Switchgear operations ■ Consult the instruction manualspecific to each mechanical control mechanism. ■ Operate the breaking devices several times in order to check they

function correctly. After each operation, check the position on the mimic diagram.

Never try to operate a lever or a tie-rod inside the control mechanism, if the closing spring is primed

(tripping spring also primed), or if the low voltage power supply circuits (alternating or direct current) have not been cut off.

Energising of the ”Incoming” cablesBefore energising the ”Incoming” cables, ensure that all of the load break switches, and earthing switches are in the ”Open” position.

Accessories for the control of voltage presence

Voltage presence inspection and control.After having energised the cables,check the presence of voltage on the terminals L1 - L2 - L3 placed on the cover of the LV casing.This inspection can be carried out by a voltage presence detector or with luminous indicators.

Phase comparator.

Voltage presence detection device.

Page 22: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

22 AMTNoT058-02 02

Commissioning (contd.)

Checking the phase balance and voltage presence

■ The phase balance is carried out from terminals L1, L2 and L3 located on the LV casing for each ”Incoming” cubicle.

■ Remove the protective cover from each terminal.

■ Checking the phase comparator: plug in the two plugs of the device on to the 2phases of the same Functional Unit.The lamp should light up.

■ Check the phase balance with the aid of a phase comparator (optional). ■ Phase in balance (good): ---> Light off ■ Phase out of sequence (bad): ---> Light on ■ If the phases are out of sequence, check the cable connections.

■ Check the voltage presence on each phase with the voltage presence detection device.

Energising the switchboard.Close the breaking devices on the ”Incoming” functional units. Energise the ”Outgoing” functional units.Close the corresponding breaking devices.

Page 23: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

23AMTNoT058-02 02

Instructions for manoeuvres and operations

RemindersThe Functional Unit is delivered with the switch ”open”, earthing switch ”closed”.The manoeuvres for manual operation are made without anyspecial effort.If cubicle de-energised : the wearing of gloves is notcompulsory.If cubicle is energised : Respectand apply the operating and safetyinstructions in force on the site.

■ A single operating lever, for theload break switch and the earthing switch.

■ Place the lever in position:1. Lever pin in the main shaft for manoeuvring,2 . Secondary pin in the notch.

■ Specific disarming lever(optional) for the C40-1 mechanical control.

■ Key for access to the low voltage compartment.

Page 24: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

24 AMTNoT058-02 02

Instructions for manoeuvres and operations (contd.)

Testing the cables ■ This test is carried out before commissioning the Functional Unit. ■ Afterwards, it will also be regularly carried out by the Safety Organisations. ■ The load break switch must be open, the earthing switch closed.

The opening of the earthing switch, door panel removed, is forbidden, by the internal mechanical locks:

■ The closing of the switch, ■ The recovery of the key for locking the earthing switch ”open”.

■ Remove the door panel. ■ Using the right hand, turn the padlockable button and maintain it there. ■ With the left hand, insert theoperating lever.

■ With both hands, grasp the operating lever by its extremities. ■ Lower the lever towards the left. The earthing switch is now open. ■ After the tests, close the earthing switch again and replace the door panel in

position.

Installing the earthing switch device ■ With the earthing switch closed and the door panel removed :

□ Fix and tighten the earthing switch device’s clamp on to the test finger, □ Fix each clamp on the device on to the cables’ lug barrels (40 mm of space in

reserve).

After the tests, remove the earthing switch device, and replace the door panel in position.

Page 25: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

25AMTNoT058-02 02

Instructions for manoeuvres and operations (contd.)

Opening the earthing switch (switch open; door panel in place)

■ Using the left hand, turn the padlockable button and maintain it there. ■ Insert the lever.

■ With both hands, grasp the lever by its extremities.

■ Lower the lever towards the left. ■ The earthing switch is now open. ■ The door panel is now locked.

Closing the earthing switch (switch open) ■ Using the right hand, turn the padlockable button and maintain it there. ■ Insert the lever.

Page 26: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

26 AMTNoT058-02 02

■ With both hands, grasp the lever by its extremities.

■ Raise the lever towards the right. ■ The earthing switch is nowclosed.

Closing the load break switch with the C310 control mechanism (earthing switch open; door panel in place)

■ Using the left hand, turn the padlockable button and maintain it there. ■ Insert the lever.

■ With both hands, grasp the lever by its extremities.

Instructions for manoeuvres and operations (contd.)

Page 27: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

27AMTNoT058-02 02

■ Lower the lever towards the right. ■ The switch is now closed.

Opening the load break switch with the C310 control mechanism

■ Using the left hand, turn the padlockable button and maintain it there. ■ Insert the lever.

■ With both hands, grasp the lever by its extremities.

■ Raise the lever towards the left. ■ The switch is now open.

Instructions for manoeuvres and operations (contd.)

Page 28: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

28 AMTNoT058-02 02

Instructions for manoeuvres and operations (contd.)

Arming the C40-1 control mechanism for closing the switch (earthing switch open; door panel in place)

■ Using the left hand, turn the padlockable button and maintain it there. ■ Insert the lever.

■ With both hands, grasp the lever by its extremities.

■ Raise the lever towards the left: □ The control mechanism is armed, □ The switch is now open.

■ Remove the lever.

Page 29: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

29AMTNoT058-02 02

Closing the load break switch ■ The closing (1) and opening (2) of the switch is made with the aid of the levers

marked in the red box.

■ Lift up the left-hand lever.

■ The switch is now closed (1). ■ The spring is still primed (2), ready to open the switch.

Opening the load break switch ■ Conditions:

□ Switch is closed (1), □ Padlocking brackets for the

■ levers are now free (2).

Instructions for manoeuvres and operations (contd.)

Page 30: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

30 AMTNoT058-02 02

■ Lift up the right-hand lever (3).

■ The switch is now open (4). ■ The spring is released (5).

Disarming the C40-1 mechanical control mechanismCAUTION ! Respect the instructions and carry out the following operations, in the order as indicated.

This operation enables the springs to be disarmed without changing the status of the switch, the latter being in the ”open” position.

It is imperative to use the specific lever for disarming.

The operations described are carried out on de-energised equipment.

Respect the locking out procedures (wearing of protective gloves etc.) forenergised interventions.

■ Switch open (1), spring is primed (2). ■ Using the left hand, turn the padlockable button and maintain it there.

Instructions for manoeuvres and operations (contd.)

Page 31: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

31AMTNoT058-02 02

Instructions for manoeuvres and operations (contd.)

■ With the right hand, latch the tripping lever into the little upper notch. ■ Maintain the padlockable button in place to avoid the lever from being ejected.

■ Insert the specific disarming lever. ■ Release the padlockable button when the lever is in place.

■ Grasp the lever with both hands.a. Pull slightly towards the right.b. Immediately retain the lever because it is now bearing all of the effort of the spring tensioned and primed.

■ Slowly accompany the course of the lever towards the bottom, whilst holding it firmlyin both hands.

■ The switch is now open (1), the spring is disarmed (2).

Page 32: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

32 AMTNoT058-02 02

■ Remove the lever: the tripping lever falls back automatically into its initial position.

Commissioning a PGC or PGcoupling Functional UnitScrupulously respect the order for the following operations.

Opening of the downstream earthing switch (only for PGC).

■ Using the left hand, turn the padlockable button and maintain it there. ■ Insert the lever.

■ With both hands, grasp the lever by its extremities.

■ Lower the lever towards the left: the earthing switch is now open.For the PGC, the door panel is now locked.

Instructions for manoeuvres and operations (contd.)

Page 33: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

33AMTNoT058-02 02

Instructions for manoeuvres and operations (contd.)

Opening the upstream earthing switch.

■ Using the right hand, turn the padlockable button and maintain it there. ■ Insert the lever.

■ With both hands, grasp the lever by its extremities.

■ Lower the lever towards the left. ■ The earthing switch is now open.

Closing the load break switch

■ Using the left hand, turn the padlockable button and maintain it there. ■ Insert the lever.

Page 34: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

34 AMTNoT058-02 02

■ With both hands, grasp them lever by its extremities.

■ Lower the lever towards the right. ■ The switch is now closed.

Circuit breaker closing and tripping operationsRefer to the specific instruction manuals:

■ Vacuum type circuit breaker Type VB L (DPI L) G3 N° F3.020 025 ■ Vacuum type circuit breaker Type VB L (DPI L) G4 N° F3.020 026

De-energising a PGC or PGcoupling Functional UnitProceed with operations in the reverse order to those described in Commissioning a PGC or PGcoupling Functional Unit on page 32.

Operating manoeuvres for the TM Functional UnitThe manoeuvres are identical to those for the IS Functional Unit. Please refer page 25 to 27.

Instructions for manoeuvres and operations (contd.)

Page 35: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

35AMTNoT058-02 02

Locking-out by padlock (not supplied) ■ Padlocking of the switch on a C310 mechanical control mechanism in either the

open or closed position.

■ Padlocking of the earthing switch in either the open or closed position.

■ Other padlocking devices for the earthing switch or load break switch in the open or closed position, with a short shackle padlock.

Locking-out and locking operations

Page 36: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

36 AMTNoT058-02 02

Locking-out and locking operations (contd.)

■ Padlocking of the arming mechanism hub on the C40-1 mechanical controlmechanism: spring primed or disarmed.

■ Padlocking of the closing and tripping levers for the load break switch.

■ Padlocking the door panel. ■ All of the passage holes are designed for padlock shackles of Æ 6 to 8 mm. ■ The fitting of several padlocks at a single point requires the use of an accessory

that is not supplied.

Locking-out by keylocksFor all locking operations by keylocks, consult the instructions manual ”Instructions for the installation of standard locks by keylocks” (AMTNoT066 - 01 F5.020.017).

Page 37: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

37AMTNoT058-02 02

Maintenance

Maintenance levels

Definition LevelsOperations recommended in the instructions manual ”installation - operation - maintenance”, carried out by suitably qualified personnel having received training allowing them to intervene whilst respecting the safety rules.

1

Complex operations, requiring specific expertise and the implementation of support equipment in accordance with the manufacturer’s procedures. These are carried out by the manufacturer himself or by a specialised technician, regularly trained by Schneider Electric (DAFEP Training Centre) in the implementation of procedures, and who is equipped with specific equipment.

2

All preventive and corrective maintenance, all renovation and reconstruction work is carried out by the manufacturer. 3

Frequency of interventionOur recommendations apply to equipment installed under normal climatic conditions.Their frequency should be increased for more severe conditions (dust, humidity, pollution, etc.).This user manual takes the first three parameters into account that are the most easily identifiable.

Parameters Definitions Factors and means of monitoring

Time Gap between two interventions Documents - Labels

Number of operations Operating frequency of the equipment

Operations counter - Registerof the operations

Switchboard environment

Switchboard environment (humidity, dust, vibrations, aggressive gases)

■ Near the sea, etc.

Analysis of the elements (air, dust, etc.)

■ Visual estimation of the hazards involved or enquiry

Cumulated amperes (squared)

Current extracted and breaking load factor

Measurement indicators - Register - Calculation of the short circuit current

Type of current Self inductive, capacitive, non sinusoidal (harmonics)

Characteristics of the power consuming equipment - Measuring devices

Power network incidents Thunderstorms, overvoltages, short circuits, etc. Faults recorder

Systematic maintenanceChecks carried out systematically for all tightening points for High Voltage connections may be required.After every 3 operations, it is thus necessary to replace all of the fixings.

Preventive maintenance of the Functional UnitsFirst visit (end of warranty) Frequency Levels

Recommended operations 1 year after commissioning 1 2 3

Visual inspection of the equipment’s environment (cable troughs, ventilation, etc.) ■ - ■ ■

Verification of the lay-out of the Functional Units (alignment, couplings) ■ - ■ ■

Systematic inspection (torque wrench) of the tightening torque on the connections ■ - ■ ■

Verification of the conformity for the assemblies (MV and earthing connections,current dividers, etc.) ■ - ■ ■

Verification of the IP degree of protection in the compartments ■ - ■ ■

Possible cleaning of the internal elements (insulators, connections, supports, etc.) ■ - ■ ■

Visual inspection of the appearance and state of internal components ■ - ■ ■

Page 38: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

38 AMTNoT058-02 02

Preventive maintenance Frequency Levels

Recommended operations 1 year

3year

6year 1 2 3

Verification of the presence and state of the accessories (levers, fuses, etc.) ■ - - ■ ■ ■

Visual inspection of exterior appearance (cleanliness, absence of oxidation, etc.) ■ - - ■ ■ ■

Cleaning of external elements, with a clean, dry cloth. ■ - - ■ ■ ■

Verification of the mechanical operations by carrying out about ten operations - ■ - ■ ■ ■

Verification of the positioning of the status indicators (open and closed) - ■ - ■ ■ ■

Inspection of the mechanical locking by keylocks (state and proper functioning) - ■ - ■ ■ ■

Verification of the tightening torques (covers, wiring ducts, connections, etc) - ■ - - ■ ■

Dusting down of internal mechanical elements (without solvent) - ■ - - ■ ■

Cleaning of internal mechanical elements (with solvent) - - ■ - - ■

Lubrication and greasing of the mechanical elements (with recommended products) - - ■ - - ■

Inspection of the tightening torques and presence of internal stops (pins, circlips, etc.) - - ■ - - ■

Monitoring the general appearance of the mechanical components and connections - - ■ - - ■

Inspection of the “function” mechanical interlocks - - ■ - - ■

Preventive maintenance for the mechanical control mechanismsRefer to the instruction manuals:F5.020.015 AMTNoT061-01 C310-C310M control

mechanismsOperation - Maintenance

F5.020.016 AMTNoT062-01 C40-1 control mechanisms

Operation - Maintenance

F3.020.025 Vacuum type circuit breaker Type VB L (DPI L) G3

F3.020.026 Vacuum type circuit breaker Type VB L (DPI L) G4

Corrective maintenanceCorrective maintenance LevelsReplacementsormodifications 1 2 3Replacement of the three fuses - ■ ■

Replacement of the VDS (Voltage Detection System) - ■ ■

Replacement of a capacitive divider in an IS Functional Unit - - ■

Replacement of a capacitive divider in a PF-PFA Functional Unit - - ■

Maintenance (contd.)

Page 39: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

39AMTNoT058-02 02

Maintenance (contd.)

Lubrication and greasing points

Intervention Duration Busbars Cables Switch Earthing switch

Standard 50 min de-energised de-energised open closedPossible 50 min energised de-energised open closed

Apply the ”General Safety Instructions booklet for Electrical Applications” and the particular recommendations for the network concerned for locking-out operations.Greases: (See Overview)

■ Clean and apply a film ofgrease to the plugging-in studson the earthing switch

■ Clean and apply a film ofgrease to the lower cups on the PF-PFA, for contact with the earthing switch.

■ Clean and apply a film of grease to the contact plates on the lower earthing switch for a PGC.

Page 40: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

40 AMTNoT058-02 02

Maintenance (contd.)

Replacement of the three MV fuses

Intervention Duration Busbars Cables Switch Earthing switch

Standard 50 min de-energised de-energised open closedPossible 50 min energised de-energised open closed

Locking out of the Functional UnitAll locking-out operations must be performed according to the particular rules for the network concerned.Necessary tooling :

■ leather work glovesParts required :

■ 3 fuses with the same reference

The body of a fuse can become very hot following a short circuit.

Take standard precautions (wear work gloves).For an apparently single phase fault, it is imperative that all 3 fuses be replaced.

■ Open the load break switch or the line disconnector. ■ Ensure that there is an absence of voltage. ■ Close the earthing switch. ■ Remove the cable access panel.

■ Take hold of the fuse by the upper part. ■ Pull the fuse towards the front.

This causes the upper current supply terminal shell to open.The latter remains open.

■ Lift the fuse up to free it from the lower current supply terminal ■ Similarly remove all 3 fuses.

■ Fit in place the replacement fuses by reversing the order of the operations (See Fitting the fuses on to the PF-PFA Functional Units on page 19).

Page 41: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

41AMTNoT058-02 02

Maintenance (contd.)

Replacement of a capacitive insulator in an IS Functional Unit

Intervention Duration Busbars Cables Switch Earthing switch

Standard 50 min de-energised de-energised open closedPossible 50 min energised de-energised open closed

Locking out of the Functional UnitAll locking-out operations must be performed according to the particu lar rules for the network concerned.Necessary tooling :

■ 1 magnetic screwdriver + 3mm Allen key tipParts required :

■ 1 capacitive insulator

■ Open the switch. ■ Close the earthing switch. ■ Remove the cable access panel.

■ Pivot the capacitive insulator in the axis of the current supply terminal. ■ Free its base by pushing it upwards, then pull it down towards the bottom.

■ Remove the capacitive insulator from the stud of the current supply terminal. ■ Let the insulator drop downgently against the lateral metal plate.

Recover the spring from the contact placed in the upper part of the divider.

Page 42: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

42 AMTNoT058-02 02

Maintenance (contd.)

■ Unscrew the screw in the bottom of the capacitive divider to release the lug together with its conductor.

■ Connect up the wire to the screw at the bottom of the new capacitive insulator. ■ Position the contact spring in the upper dish.

■ For re-assembling, it is imperative to pass the conductor into the slot. ■ Ensure the presence of the contact spring located in the upper dish of the

capacitive insulator.

■ Fit the capacitive insulator into the axis of the current supply terminal. ■ Push its base into the cross-bar slot. ■ Slightly lower the capacitive insulator into its housing then turn it a quarter turn to

the right.

Page 43: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

43AMTNoT058-02 02

Maintenance (contd.)

Replacement of a capacitive insulator in a PF-PFA Functional Unit

Intervention Duration Busbars Cables Switch Earthing switch

Standard 2 h de-energised de-energised open closedPossible 2 h energised de-energised open closed

Locking out of the Functional UnitAll locking-out operations must be performed according to the particular rules for the network concerned.Necessary tooling :

■ 1 magnetic screwdriver + 3mm Allen key tipParts required :

■ 1 capacitive insulator

■ Open the switch. ■ Close the earthing switch. ■ Remove the front panel. ■ Remove the 3 fuses. ■ Remove the 3 cables and their screen braids. ■ Remove the 3 low voltage wiring ducts.

1. Disconnect the earthing braid from the earthing switch to the earth bar (13 mm spanner).2. Disconnect the linkage of the earthing switch downstreamfrom the fuses (13 mm spanner).

3. Draw a mark by pencil above the cross-bar. This will enable the cross-bar to berepositioned correctly.4. Unscrew the 7 nuts (13 mm spanner) maintaining the cross-bar on the partition.

■ Extract the cross-bar.

Page 44: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

44 AMTNoT058-02 02

Maintenance (contd.)

■ Dismantle the defective capacitive insulator (2 nuts, 13 mm spanner).

■ Disconnect the defective capacitive insulator and replace it.

■ Re-assembly: position the slots facing the crimped pins in theflange. ■ Realign the cross-bar according to the mark (4) previously drawn. ■ Screw in the 7 nuts.

■ Connect the link rod between the downstream and upstream earthing switches.

Page 45: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

45AMTNoT058-02 02

■ The 2 earthing switches being closed, maintain the retainer plate of the lower ES pressed hard against the shells.

■ Tighten the 2 fixing screws on the lower part. ■ Operate the earthing switch several times whilst checking its contact surface on

the lower current supply terminals. ■ If necessary, adjust the position of the cross-bar by unblocking the 7 nuts and by

sliding it into the slots. If needed, make a fine adjustment.

Replacement of the VDS (Voltage Detection System - LV capacitors

■ Check the characteristics of the VDS given on the voltage terminals rating plate (see Location of the technical data plates on page 9). They should correspond to the switchboard’s service voltage.

■ The VDS is located in the cross-bar which supports the capacitive insulators (See Presentation of the Functional Units IS and PF - PFA on page 6 and Presentation of the Functional Units TM and PGC on page 7).

■ For IS, extract the VDS via the front of the cross-bar, disconnect it and replace it.

HR SYSTEMIEC 1234-5

SDT 10-16 kV

Maintenance (contd.)

Page 46: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

46 AMTNoT058-02 02

Maintenance (contd.)

Possible anomalies and remedies

Symptom Component Probable cause RemedyStrange noises when energised, crackling noises or vibration Voltage presence box Plug badly connected to the

conductors Check the connection

Capacitive insulator Accidental destruction Replace the voltage divider

Insulators Insulating components polluted or damaged

Clean the insulating parts orcall our After-Sales Department: See address at thebeginning of this manual

Cable terminals Terminals damaged

Abnormal force required when operating a breakingdevice

Control mechanism forthe switch. Safety interlocks Check the position of the

breaking devices

Earthing switch Safety interlocks Check the position of thebreaking devices

Voltage presence detector extinguished (with switch board energised)

MV Fuses Fuse blown Replace the 3 fuses

Voltage indicator Deterioration of acomponent Replace the indicators

Abnormal overheating at the connection points Connections Badly tightened

■ Clean the connecting plates ■ Replace the damaged fasteners ■ Retighten to torque

Badly assembled

■ Clean the connecting plates ■ Eliminate any different type of material, placed in the current

passage point ■ Retighten to torque

Inappropriate tripping operations Cores Badly connected

■ Insulate the earthing braids from the cable screens ■ Pass these frames again into the core, in the reverse direction to

the cable,before connecting them toearth on the switchboard

Page 47: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

47AMTNoT058-02 02

Identificationoftheequipment (See Location of the technical data plates on page 9)

For all orders for spare parts, it is necessary to enclose the equipment characteristics form.

1. Technical data plate of the device (type, reference, order number, serial number, year of construction, etc.).2. Identification plate.These indications are indispensable in order to identify the parts, in relation to a highly varied range of products.

Storage conditionsThe parts must be stored, sheltered from dust, humidity and the sun. In order to facilitate the search, they must be marked by the Schneider Electric reference number. Certain parts are fragile, it is preferable to preserve them in their original factory mounted packaging.

The spare partsSchneider Electric offers 2 lists of spare parts:Consumables: parts or elements of first necessity liable to be replaced at defined intervals,

■ Components liable to wear: mechanical elements that can be replaced from time to time, depending on their state of degradation.

The replacement of these parts can only be carried out by a person who is suitablyqualified and trained for this operation.

ConsumablesMarked

(see presentation of the Functional Units IS and PF -PFA on page 6 )

Luminous voltage presence indicator 18

Earthing switch box 23

MV fuses (by 3) 7

Parts liable to wear MarkedNone, material requiring no maintenance

-

Additional spare partsThese are complete assemblies or sub-assemblies, useful for immediate replacement.The list of these components is proposed when making the contract. It is comprised of specific materials for the project.Examples : complete circuit breaker moving part, relays, CT, PT, etc.

Spare Parts Marked

C310 control mechanism17

(See Presentation of the Functional Units IS and PF -PFA on page 6 )

C40-1 control mechanism17

(See Presentation of the Functional Units IS and PF -PFA on page 6)

Operating lever (See Reminders on page 23)

Capacitive insulator8

(See Presentation of the Functional Units IS and PF -PFA on page 6))

Spare parts

Page 48: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

FLUOKIT M 9

48 AMTNoT058-02 02

At the end of the equipment’s operational life

Our Functional Units are composed of recyclable elements.Consult Schneider Electric or an approved company qualified for all decommissioning services.

Dismantling the circuit breaker ■ Remove the circuit breaker from the Functional Unit ■ Remove all of the electrical equipment (coils, motors, etc.). ■ When dismantling, the materials must be sorted and sent to the appropriate

recycling services.Do not dismantle the control mechanism’s springs without a releasing device

Specificrecommendationsforthe”SF6gas”type circuit breaker and load break switch

Recuperate the SF6 gas using a recuperation unit.

■ Dismantle the interrupting poles with the specific tools, compulsory protections, and all this in a specific room.

■ Clean the components before their elimination. ■ When dismantling, the materials must be sorted and sent to the appropriate

recycling services.

Specificrecommendationsfor”Vacuum”type circuit breakers

There is a risk of implosion at the contact chambers level in case of high mechanical stresses (shocks for instance).

Do not dismantle the poles without using the tooling required for dismantling the vacuum bottle and for releasing the compression springs.

SpecificrecommendationsfortheFunctional Unit

■ Remove all of the electrical equipment (coils, motors, etc.). ■ When dismantling, the materials must be sorted and sent to the appropriate

recycling services. ■ Do not dismantle the springs on the earthing switch without the releasing device.

Example of the distribution of the weights on a Functional Unit

Components/ Materials

Approximate weight

% of materials

Recycling stream

Steel 118 kg 66.30 % Valorization

Copper and copper alloys 4.70 kg 2.65 % Valorization

Thermosetting materials 51 kg 28.65 % Valorization

Thermoplastics materials 2.21 kg 1.24 % Valorization

Materials (Elastomers, paint) 0.17 kg 0.09 % Class 2 waste dump

SF6 gas 0.11 kg 0.06 % Regeneration

Other materials (sand, molecular sieve, etc.) 1.81 kg 1.01 % -

Copper

Sand

Resin

Steel

Resin + SF6

Copper

A PFA Functional Unit equipped with a C40-1 control mechanism

Page 49: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

49SDIOPM005-02 00

Appendices Notes

Page 50: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

Appendices

50 AMTNoT058-02 02

Notes

Page 51: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

Appendices

51AMTNoT058-02 02

Notes

Page 52: Medium Volatge Distribution FLUOKIT M 9 - Schneider …mt.schneider-electric.be/OP_MAIN/FLUOKIT/notices/amtnot058-02.pdf · Medium Volatge Distribution FLUOKIT M 9 . FLUOKIT M 9 2

AMTNoT058-02 02 10-2010

© 2

010

Sch

neid

er E

lect

ric -

All

right

s re

serv

ed

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Publishing: Schneider ElectricDesign: Schneider ElectricPrinting:

This document has been printed on ecological paper

Schneider Electric35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France

RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com