1
Megger Cable Fault Location
PFL40 series
2
Megger’s new PFL40-1500/2000 Power Fault Locator.
Restoration
Fault Identification
HV Pre-Location
Fault Conditioning
LV Pre-Location
PinpointFault Location
Fault Diagnosis
Fault Located Fault Located
Fault Located
PFL40 =
3
The PFL40-1500/2000 really is the “Complete Solution”
Megger’s new PFL40-1500/2000 Power Fault Locator.
4
What we “offer”• Ease of use• Cable and fault diagnosis• Fault conditioning• Fault prelocation• Pinpoint fault location• Easy to deploy • Rapid , accurate and safe• Tough, field proven equipment • Fully integrated system
Megger’s new PFL40-1500/2000 Power Fault Locator.
The PFL40-1500/2000 ticks all the boxes
5
What we “offer”
• Fully integrated system• Auto ranging, colour display TDR.• d.c. testing up to 40kV• Leakage current• 25mA constant test current • Proof/burn up to 34kV• 34kV arc reflection method• Impulse Current• Voltage Decay (optional)• 34kV 3-range surge generator (4kV option)• 1500joule (optional 2000j)• Safety ground monitor (optional)
Megger’s new PFL40-1500/2000 Power Fault Locator.
6
F. The PFL series are portable, stand-alone CFL & HV system. All CFL & HV testing features in one field proven case
B. No need to invest in expensive customized test vansA. No other manufacturer has the same feature set in
one enclosure/case
F. Analogue metering of the voltage and currentB Analogue metering is preferred as fault breakdown,
and ticking faults can be easily identifiedA. Analogue metering assists in identifying and
diagnosis the type of fault, essential when deciding which fault location method to use.
Megger’s new PFL40-1500/2000 Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
7
F. Easy to use PLC control., selects testing methodsB. Selection of HV operations is via this easy to use
PLC control.A. There has been a trend in recent years to combine all
controls with the TDR. This creates confusion and a difficult to use instrument
F. 40kV dc testing & 34kV dc proof / burn features.B. This combination allows d.c. testing (diagnosis) and
high voltage fault conditioning.A. No other manufacturer offer both these features in
the same unit, they normally offer one or the other. d.c. testing is used for diagnosis & the proof/burn mode is used to stabilise difficult to find faults.
Megger’s new PFL40-1500/2000 Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
8
F. 34kV Surge VoltageB. The 34kV Surge allows the prelocation and pinpoint
location of more difficult faults easier.A. This a unique feature that no other manufacturer has
in a mobile portable unit.
F. 1500 standard and 2000 joule Surge Energy on all ranges.
B. The high surge energy enables the creation of a flashover at the point of fault, in difficult situation.
A. No other manufacturer offers a 3-range 2000joule surge capability in a single portable unit.
Megger’s new PFL40-1500/2000 Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
9
F. Integrated large colour display TDR.B. The large colour display, makes fault analysis
easier, and encompasses pulse echo, arc reflection and impulse current methods of fault prelocation..
A.The large, uncluttered graphical display enables quick and accurate fault location. On-board memory for trace (with parameters) storage and recall, report generation assists with asset management.
Megger’s new PFL40-1500/2000 Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
10
F. Developed, manufactured by Megger.
B. Megger has over 100 years of experience of supplying test and measurement equipment worldwide. Several CFL patents are also held dating back sever decades.
A. The customer can be assured that he is supported by an International Company, with extensive experience and an experienced world-wide network of distributors and authorised repair agents.
Megger’s new PFL40-1500/2000 Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
11
Patents from the same stable.1957: Bechtel: Fault Location in Electrical Cables1974: Ironside: Multiple Null Bridges1992: Steiner: DART (Differential Arc Reflection Techniques
Megger’s new PFL40-1500/2000 Power Fault Locator.
No Spec’s but lets look at the FEATURES, BENEFITS and ADVANTAGES
We are Strong !
12
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
SFX 40-25
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
SFX 40-2540kV @ 15mA
NO12.5kV -25kV or
16kv – 32kV4kV or 8kV1000joules
2000j (2nd box)5 – 20 secs
ARMImpulse CurrentVoltage Decay20kV @ 100mA
Specificationd.c. TestingCurrent trips
Surge--
Optional EnergyOptional
Surge RateModes
----
Proof/Burn
SebaKMT: Trading company of Seba Dynatronic & Hagenuk KMT
13
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
SFX 3232kV @ 15mA
NO8-16-32kV
--1000joules
1750j3 - 10 secs
Arc ReflectionImpulse CurrentVoltage Decay32kV @ 160mA
Specificationd.c. TestingCurrent trips
SurgeOptional EnergyOptional
Surge RateModes
----
Proof/Burn
SFX32
SebaKMT: Trading company of Seba Dynatronic & Hagenuk KMT
14
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
SFX 2525kV @ 5mA
NO12.5 - 25kV
--1120joules
--3 - 9 secs
Arc Reflection------
Specificationd.c. TestingCurrent trips
SurgeOptional EnergyOptional
Surge RateModes
----
Proof/Burn
SFX 25
SebaKMT: Trading company of Seba Dynatronic & Hagenuk KMT
15
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
Syscompact 300032kV (850mA max?)
NO8 – 16 – 32kV
1100–1500–2100j
10 – 30secsSIM
DC SIM / MIMImpulse Current
32kV (850mA max?)
Specificationd.c. TestingCurrent trips
SurgeOptional Energy
Optional Surge Rate
Modes----
Proof/Burn
BAUR
Can be configured with
SSG1100/1500/2100
16
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
Syscompact 200016kV @
NO8 – 16kV
1024joules
10 – 20secsSIM
Impulse Current----
Specificationd.c. TestingCurrent trips
SurgeOptional EnergyOptional
Surge RateModes
----
Proof/Burn
BAUR
17
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
5100-FC15kVNO
7.5 or 15kV--
480joules--
6 secsARC Reflection
------
Specificationd.c. TestingCurrent trips
SurgeOptional Energy
Optional Surge Rate
Modes----
Proof/Burn
Hiptronics
18
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
CF 70 Series70kV NO
25kV--
3750joules7500joules
3 – 30secondsTDR only
----
70kV @ 100mA
Specificationd.c. TestingCurrent trips
SurgeOptional Energy
Optional Surge Rate
Modes----
Proof/Burn
Hipotronics
19
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
XF16-128016kVNO
8 – 16kV--
1280joules2560joules
15 secsArc Reflection
------
Specificationd.c. TestingCurrent trips
SurgeOptional Energy
Optional Surge Rate
Modes----
Proof/Burn
VON
20
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
XF25-156325kVNO
12-5 – 25kV--
1563joules3126 joules
15 secsArc Reflection
------
Specificationd.c. TestingCurrent trips
SurgeOptional Energy
Optional Surge Rate
Modes----
Proof/Burn
VON
21
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
XF28-196028kVNO
14 – 28kV--
1960joules3920joules
15 secsArc Reflection
--------
Specificationd.c. TestingCurrent trips
SurgeOptional Energy
Optional Surge Rate
Modes------
Proof/Burn
VON
22
Megger’s new PFL40-1500/2000 Power Fault Locator.
Competitor (Other Manufacturers!)
PFL40-1500/200040kV @ 25mA
Selectable8 – 16 – 34kV
4kV 1500joules
2000j (integrated)2 – 10sec
Arc ReflectionImpulse CurrentVoltage Decay14kV @ 120mA34kV @ 60mA
XF32-512032kVNO
8 – 16 – 32kV--
5120joules--
15 secsArc Reflection
--------
Specificationd.c. TestingCurrent trips
SurgeOptional Energy
Optional Surge Rate
Modes------
Proof/Burn
VON2-piece