mhw air handling unit (50/60hz) - acson international t.m/fcu/mhw(high_static... · mhw air...
TRANSCRIPT
MHW Air Handling Unit (50/60Hz)
Technical Manual
Engineered for flexibility and performance.TM
MHW - 2011 (50Hz/60Hz)
MHW015A MHW020AMHW025A MHW030AMHW035A MHW040AMHW050A
1
Contents
Nomenclature ...........................................................................................................................2
Features ...................................................................................................................................2
Electric Heater Power ...............................................................................................................3
Specifications ...........................................................................................................................4
Components data .....................................................................................................................5
Sound data ...............................................................................................................................6
Performance correction coefficient ...........................................................................................7
Outline and dimensions ............................................................................................................8
Electrical data .........................................................................................................................10
Wiring diagrams......................................................................................................................11
Installation ..............................................................................................................................13
Service and maintenance .......................................................................................................15
Trouble shooting .....................................................................................................................16
Exploded view and part list .....................................................................................................17
“McQuay” is a registered trademark of McQuay International. All rights reserved throughout the world.
© 2011 McQuay International
“Bulletin illustrations cover the general appearance of McQuay International products at the time of publicationand we reserve the right to make changes in design and construction at any time without notice.”
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning: Moving machinery and electrical power hazard. May cause severe personal injury or death. Disconnect and lock off power before servicing equipment.
Literature No.: TM-MHW-1101A Supersedes: TM-MHW-1001A Part No.: M08039110015
2
E:exportU:"Made in China" labelDesign seriesA:220-240V/1Ph/50HzK:208-230V/1Ph/60Hz
L-Left hand (Facing discharge)R-Right hand (Facing discharge)4-4 coil rows; 6-6 coil rowsA-Design Serial No.030-Nominal airflow is 3000 m3/hMHW-McQuay super thinhorizontal air handling unit
MHW 030 A- 4 L -A AA E
Nomenclature
FeaturesGeneral InformationMcQuay for years has been committed to provide high quality air handling systems of various models and types, and has made remarkable achievements in the industry. As a new generation of products, the MHW series slim ceiling air handling units are launched by McQuay to adapt to the increasingly cramped building layout.In addition to the outstanding performance of previous McQuay air handing units, the MHW series slim ceiling air handling units feature a slim size, only 420mm in height. The airflow is adjustable within the range of three levels to meet different air flow needs. Powered by a 50 or 60Hz single-phase power supply, this series eliminates the need for users to expand the power capacity. The MHW series can be mounted in a wide variety of places, especially those with limited space and high noise. Featuring easy installation and flexible use, the MHW series helps minimize the indoor space and maximize customers’ benefits.
StructureThe high-strength galvanized steel sheets, coated with electrostatic spraying, are highly corrosion-proof.Made of a new type of PE material, the heat insulator features ideal thermal insulation, sound absorption, and no moisture permeability. The insulator is also proof against cold bridge.
FansWith efficient tilted multi-blade centrifugal fans, this unit provides low noise but high reliability. The fan and the motor are coupled directly. The high-precision and quality ball bearing eliminate the need for lubricating.
Multi-level Speed ControlDriven by a single-phase capacitor-running asynchronous motor, the unit can be adjusted at three levels to provide different amounts of air flow.
FiltersThe air inlet is equipped with primary nylon filters.
Heat ExchangerMade on the OAK manufacturing facility the heat exchanger uses thin-walled copper tubes mechanically expanded into new-type fins, to ensure close contact between the cooper tubes and fins. This enables the coils to provide best heat exchange and the units to run reliably and efficiently.
PerformanceMHW series products feature high external total pressure (ETP) and large cooling capacity. Slim in size and simple in structure, this series makes it easy for installation and maintenance.
3
Electric Box Model Power Supply Capacity(kW)
MHW-EH-020BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 2
MHW-EH-030BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 3
MHW-EH-040BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 4
MHW-EH-050BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 5
MHW-EH-060BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 6
MHW-EH-075BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 7.5
Electric Heater Power
NOTES: EACH HEATER BOX CAN ONLY BE USED FOR ONE AIR DISCHARGE DUCT. 1) MHW015/20/025 - ONLY ONE HEATER BOX IS REQUIRED.2) MHW030/035/040/050 - NEED TO SELECT TWO BOX.
4
Specifications
MODEL MHW015A MHW020A MHW025A MHW030A MHW035A MHW040A MHW050A
NOMINAL AIR FLOW m3/h 1500 2000 2500 3000 3500 4000 5000
EXTERNAL TOTAL PRESSURE Pa 70 100 100 120 120 150 150
POWER SOURCE V/Ph/Hz 220-240V/1Ph/50Hz 208-230/1/60
N O M I N A L CAPACITY
COOLING
4 ROWS(RETURN AIR)
kW
6 10 12 16 18 23 29
4 ROWS(FRESH AIR) 19 27 31 40 47 57 70
6 ROWS(RETURN AIR) 10 15 17 22 26 31 37
6 ROWS(FRESH AIR) 25 34 39 49 61 70 84
HEATING
4 ROWS(RETURN AIR) 11 16 19 24 28 34 42
4 ROWS(FRESH AIR) 21 30 34 43 52 61 73
6 ROWS(RETURN AIR) 15 21 23 29 36 42 50
6 ROWS(FRESH AIR) 26 36 41 51 64 74 87
WATER FLOW
COOLING
4 ROWS(RETURN AIR)
m3/h
1.01 1.77 2.40 3.13 3.09 3.91 5.32
4 ROWS(FRESH AIR) 3.26 4.69 6.07 7.65 8.21 9.78 12.89
6 ROWS(RETURN AIR) 1.78 2.57 3.36 4.18 4.58 5.36 7.06
6 ROWS(FRESH AIR) 4.3 5.95 7.61 9.29 10.5 12.15 15.59
HEATING
4 ROWS(RETURN AIR) 0.96 1.38 1.80 2.27 2.42 2.91 3.83
4 ROWS(FRESH AIR) 1.85 2.57 3.26 4.07 4.47 5.28 6.83
6 ROWS(RETURN AIR) 1.27 1.78 2.28 2.79 3.14 3.64 4.69
6 ROWS(FRESH AIR) 2.30 3.14 3.98 4.84 5.52 6.36 8.10
WATER PRESSURE DROP
COOLING
4 ROWS(RETURN AIR)
kPa
5 14 24 14 13 25 40
4 ROWS(FRESH AIR) 39 40 46 32 36 46 74
6 ROWS(RETURN AIR) 14 27 54 21 44 45 75
6 ROWS(FRESH AIR) 77 89 96 76 79 103 113
HEATING
4 ROWS(RETURN AIR) 4 12 10 9 11 19 24
4 ROWS(FRESH AIR) 20 26 24 26 20 31 67
6 ROWS(RETURN AIR) 12 24 24 12 32 30 32
6 ROWS(FRESH AIR) 42 49 62 56 53 68 70
UNIT DIMENSION
LENGTH
mm
750 910 1070 1220 1370 1520 1850
WIDTH 750 750 750 750 750 750 750
HEIGHT 420 420 420 420 420 420 420
PACKING DIMENSION
LENGTH 950 1110 1270 1420 1570 1720 2050
WIDTH 1030 1030 1030 1030 1030 1030 1030
HEIGHT 580 580 580 580 580 580 580
WEIGHT4 ROWS
kg76 80 86 92 96 102 108
6 ROWS 79 84 90 96 101 107 113
General data
NOTES:1) ALLSPECIFICATIONSARESUBJECTEDTOCHANGEBYTHEMANUFACTURERWITHOUTPRIORNOTICE.2) THEABOVEPARAMETERSAREFORSTANDARDPRODUCTSONLY.3) STANDARDAIRRETURNCOOLINGCONDITIONS:27℃DB/19.5℃WB;STANDARDFRESHAIRCOOLINGCONDITIONS:34℃DB/28℃WB;
STANDARDCOOLINGWATERENTERING/LEAVINGCONDITIONS:7℃/12℃STANDARDAIRRETURNHEATINGCONDITION:21℃DB;STANDARDFRESHAIRHEATINGCONDITION:0℃DB;STANDARDHEATINGWATERENTERING/LEAVINGCONDITIONS:60℃/50℃
4) THEPARAMETERSINTHEABOVETABLEAREMEASUREDATTHEALTITUDEOF0MABOVESEALEVEL,ANDMAYVARYWITHTHEALTITUDE.
�
Components dataMODEL MHW015A MHW020A MHW025A MHW030A MHW035A MHW040A MHW050A
STRUCTURE TYPE Galvanized steel coated with elextrostatic spraying, internal glued with insulator PE
COIL
TYPE Corrugated aluminum fin mechanically bonded with copper tube
TUBE DIAMETER(mm) 9.�3
FPI 12
WORK PRESSURE(MPa) 1.6
INLET/OUTLET PIPE R1½’’
CONDENSING WATER PIPE R1’’
FAN
TYPE/MATERIAL Centrifugal forward curved blower and galvanized steel
FAN NO. 1 2
DRIVE TYPE Direct drive
AIR DISCHARGE Lower horizontal air discharge
MOTOR
TYPE Single phase capacitor running
QUANTITY 1 2
INDEX OF PROTECTION(IP) IP20
INSULATION CLASS B
FILTER
TYPE/MATERIAL Primary nylon
SIZE
THICKNESS
mm
21
HEIGHT 34�
LENGTH �36 696 8�6 1006 11�6 1306 1636
DRAIN PAN
TYPE/MATERIAL Cold-rolled steel plate
THICKNESS(mm) 1.0
INSULATION �mm PE
NOTES:ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
6
Sound data
Unit ESP Speed 1/1 Octave Sound pressure level (dB(A), ref 20μPa) Overall
dB(A)63 125 250 500 1k 2k 4k 8k
MHW015A 70Pa
High 24 36 34 40 38 34 27 19 44.1
Medium 21 33 30 37 34 30 21 15 40.7
Low 19 31 27 34 30 27 17 14 37.7
MHW020A 100Pa
High 28 43 43 43 46 41 33 27 50.6
Medium 27 41 41 41 42 38 30 23 48.0
Low 25 38 37 39 40 35 26 20 45.1
MHW025A 100Pa
High 37 49 49 50 48 46 37 27 55.7
Medium 34 46 46 46 44 42 33 23 52.2
Low 28 45 40 42 39 36 28 18 48.4
MHW030A 120Pa
High 29 45 46 46 46 40 33 25 52.5
Medium 27 43 46 44 43 37 29 21 50.5
Low 26 42 44 42 40 34 26 17 48.5
MHW035A 120Pa
High 37 46 45 47 46 45 43 36 53.5
Medium 35 45 43 46 45 44 41 35 52.1
Low 33 43 41 44 43 42 40 33 50.2
MHW040A 150Pa
High 30 45 44 48 49 44 35 27 53.6
Medium 29 43 42 46 47 41 32 24 51.5
Low 27 43 40 45 43 38 29 21 49.5
MHW050A 150Pa
High 35 49 49 50 52 48 40 33 57.0
Medium 34 49 48 49 51 47 39 32 56.0
Low 31 49 47 48 49 45 37 30 54.9
NOTE:SOUNDPRESSURELEVELSARETESTEDINBAFFLECHAMBER,WITHBACKGROUNDNOISELEVEL:11.5dB(A),MICROPHONEPOSITIONIS1METERINFRONTAND1METERBELOWTHEUNIT.
7
Performance correction coefficientCooling capacity performance curve
The above curve shows the cooling capacity variations at different entering water temperatures.Standard return air: 27ºC DB/19.5ºC WB;Temperature difference between entering and leaving water: 5ºCThe cooling capacity correction factors are based on the cooling capacity (using 1 as the coefficient) in standard cooling water entering/leaving conditions (7ºC for entering water/12ºC for leaving water).
The above curve shows the cooling capacity variations at different entering water temperatures.Standard return air: 34ºC DB/28ºC WB;Temperature difference between entering and leaving water: 5ºCThe cooling capacity correction factors are based on the cooling capacity (using 1 as the coefficient) in standard cooling water entering/leaving conditions (7ºC for entering water/12ºC for leaving water).
Heating capacity performance curve
The above curve shows the heating capacity variations at different entering water temperatures.Standard return air: 21ºC DB;Temperature difference between entering and leaving water: 10ºC. The heating capacity correction factors are based on the heating capacity (using 1 as the coefficient) in standard cooling water entering/ leaving conditions (60ºC for entering water/50ºC for leaving water).
The above curve shows the heating capacity variations at different entering water temperatures.Standard return air: 0ºC DB;Temperature difference between entering and leaving water: 10ºCThe heating capacity correction factors are based on the heating capacity (using 1 as the coefficient) in standard cooling water entering/ leaving conditions (60ºC for entering water/50ºC for leaving water).
NOTES:1) THEBLACKCURVESHOWSTHECAPACITYOFA4-ROW-COILUNITANDTHEGRAYCURVETHECAPACITYOFA6-ROW-COILUNIT.2) COMPARED WITH THE COEFFICIENT (SET TO 1) OF THE UNIT IN STANDARD OPERATING CONDITIONS (ENTERING WATER
AT60ºC,ANDLEAVINGWATERAT50ºC), THEVARIATIONCOEFFICIENTVARIESASFOLLOWSWHENTHEENTERINGWATERTEMPERATURERETAINSAT45ºCANDTHELEAVINGWATERTEMPERATUREAT40ºC:STANDARDAIRRETURNCONDITION:0.65FORA4-ROW-COILUNITAND0.64FORA6-ROW-COILUNIT;STANDARDFRESHAIRCONDITION:0.8FORA4-ROW-COILUNITAND0.78FORA6-ROW-COILUNIT.
8
Outlines and dimensions
DimensionsModel A B C D
MHW015A 750 540 238 667
MHW020A 910 700 318 827
MHW025A 1070 860 398 987
MHW030A, MHW035A, MHW040A, MHW050A
DimensionModel A B C D E
MHW030A 1220 1010 268 176 1137
MHW035A 1370 1160 323 216 1287
MHW040A 1520 1310 333 346 1437
MHW050A 1850 1640 398 546 1767
Unit: mm
Unit: mm
MHW015A, MHW020A, MHW025A
9
Flexile Pipe Connection
Electrical Heater
MHW Unit
Electric Box
Scheme of Electric Box Installation
10
Electrical dataMODEL MHW015A MHW020A MHW025A MHW030A MHW035A MHW040A MHW050A
POWER SOURCE 220V/1/50Hz
MOTOR
TYPE Asynchronous single phase
INSULATION CLASS B
PROTECTION CLASS IP20
RATED INPUT POWER
4 ROWSw
373 614 787 797 905 1248 1533
6 ROWS 397 653 823 845 1016 1362 1699
RATED INPUT CURRENT
4 ROWSA
1.72 2.96 3.61 3.62 4.22 5.68 6.98
6 ROWS 1.81 3.01 3.78 3.96 5.10 6.29 7.86
NOTES:1)ALLSPECIFICATIONSARESUBJECTEDTOCHANGEBYTHEMANUFACTURERWITHOUTPRIORNOTICE.2)ALLDATAAREBASEDONHIGHSPEED,STANDARDESP.
MODEL MHW015A MHW020A MHW025A MHW030A MHW035A MHW040A MHW050A
POWER SOURCE 220V/1/60Hz
MOTOR
TYPE Asynchronous single phase
INSULATION CLASS B
PROTECTION CLASS IP20
RATED INPUT POWER
4 ROWSw
279 387 945 619 733 1584 2063
6 ROWS 273 445 1137 681 1222 1607 2134
RATED INPUT CURRENT
4 ROWSA
1.28 1.79 4.35 2.83 3.41 7.59 9.55
6 ROWS 1.25 2.03 5.29 3.19 5.97 7.73 9.89
NOTES:1)ALLSPECIFICATIONSARESUBJECTEDTOCHANGEBYTHEMANUFACTURERWITHOUTPRIORNOTICE.2)ALLDATAAREBASEDONHIGHSPEED,STANDARDESP.
11
Wiring diagramsMHW015A, MHW020A, MHW025A
MHW030A, MHW035A, MHW040A, MHW050A
12
FACTORY WIRINGFIELD WIRING
TB1-2 TERMINAL BLOCKF FUSE FOR TEMP.
NOTE:
TH THERMAL OVERLOAD SWITCH DPS DIFFER. PRESS SWITCH
TB2 NL
TH
TB1 B
F
A
DPS
ELE-HEATER
RE
D
BLU
E
220Vac(Main Power)L N PECONTROL CIRCUIT
RE
D
RE
D
G/Y
PROTECTOR
WIRING OF ELE-HEATER
13
InstallationImportant NoticeInstallation and maintenance are to be performed only by technicians who are familiar with local rules and regulations, and experienced with this type of equipment.Make sure that the rated voltage of the power supply conforms to the voltage stated on the unit nameplate.Cut off all power supplies before mounting or maintaining the unit.Electric connections must conform to local laws and regulations.The voltage should fluctuate within the range of ± 10% of the rated voltage.The unit must be well earthed to prevent insulation failures.All the wires must be securely connected.The design of water pipes and ducts must conform to the specifications of heating, ventilation and air conditioning norms and regulations.
Mounting LocationMake sure it’s convenient to connect wires and pipes in the selected mounting location. The minimum space reserved around MHW units is shown in Figure 1.
Figure 1
14
Suspending InstallationDuring suspending installation, please handle the unit or packing case with care, to avoid damage to any part. Before leaving the factory, the unit or its packing case already has forklift handling holes or hoisting holes. During the hoisting, the lifting poles should be strong enough to bear the unit weight. Please handle the MHW unit as shown in Figure 2.
StorageWhen a unit is placed outdoors before it is installed in an equipment room, please protect it from dirt, rain, snow and even animals. Be sure not to damage the protective film on its surface.
Base SetupAdjust the base level.The base, if not on a level surface, may result in water leakage or break the dynamic balance of the fan due to poor drainage of condensing water, or cause the bearing malfunction or vibrate.The base height should match the U-shaped pipe bend. The drain pipe should be connected with the U-shaped water seal, as shown in Figure 3.
TRAP INSTALLATION
H is more than the negative pressure of unit + 20 mmO = 9.8 Pa1mm H2
H
NOT MORE THAN 1/2H
DRAIN PIPE
DRAIN PLUG
Figure 2
Figure 3
15
Service and maintenanceNoticesResponsibilities and ObligationsThis product comes to you with the McQuay service warranty. Only McQuay technicians or experienced technicians authorized by McQuay are allowed to install, test or maintain these products.
Use the UnitAfter installing the piping system, please first flush the pipes. To do so, be sure to shut off the valve connected to the unit, to prevent contamination in the pipes from entering the coils or blocking the loop.After the installation, please check there is anything sundries inside the fan. Turn the blades by hand. If no unusual noise is heard, turn on the fan, to see if it is running properly.Before turning on the water flow, please open the exhaust valve to let the air out of the pipe till water flows from the pipe.When the unit stops running, fill the coil with water or by other means to prevent pipe corrosion.When the environment temperature falls below 0°C in the winter, drain the pipe to prevent it from freezing.Clean the coils at regular intervals, to remove the dust from the coils. Clean the scale inside the coils every 2 or 3 years. If possible, please use soft water in the coils.Check the unit filter for dust regularly; if possible, please use a pressure difference gauge. Once the resistance reaches the limit, wash or replace the filter media in time.After the unit runs for a week, please readjust the V-belt. Afterwards, check the belt every three months.
Service and MaintenanceA good maintenance schedule helps reduce operational failures.A dirty filter may worsen the performance and air flow of the unit. Thus, replace or wash the filter in time. Be sure to check the filter every month to see if it is clean enough.Wash the coils with compressed air or water. Brush the coil surface gently with a soft brush or use a vacuum cleaner to clean the dust.Do the following on a regular basis:Clean up the fans every 6 months, to keep them in good balance.Check and clean the drain pan. Check the drain pipe in case dust or sundries block the pipes. Clean the dirt in the water coils at regular intervals.
16
Trouble shootingCommon failures Location Possible causes Solutions
Abnormal sound
1. Blower
Blower offset Contact the dealerLoose bearing due to big gap Contact the dealerBlower is loose Contact the dealerBlower is damaged Contact the dealerThe fastening fan screw is loose Fasten the screwThere are sundries inside fans Remove sundries
2. Drive The screw fixing the motor to the motor base is loose Fasten the screw
3. Fan housingThere are sundries inside housing Remove sundriesHousing is loose Contact the dealerAir intake housing is damaged Contact the dealer
4. Electric appliancesIncoming wire is loose Fasten the incoming wireMotor gives AC hum Contact the dealer
5. ShaftBent or distorted Replace shaftBalance weight is loose Fasten the balance weightShaft is loose Fasten shaft
6. Air speed is too high
Duct is too small Re-design the ductStatic pressure doesn't reach the designed ESP value Use the lower fan speed.
7. Periodical vibrationDuct is too small Re-design the ductSystem is unstable Adjust the systemDuct vibrates as the fan pulsates Adjust the fan speed
8. Noise caused by hi-speed wind passing the gap & holes
Duct leaks Seal it with glue
9. When blocked, the high-speed air rattles or howls
Duct bends abruptly Re-design ductDuct expands sharply Re-design ductDuct shrinks sharply Re-design ductAir speed is too high inside duct Re-design ductAnti-vibration joint is too high Re-adjust the damping connector
Fan operates normally but the
air flow is insufficient
1. Fan Blower is mounted incorrectly Contact the dealer.
2. Duct systemActual resistance exceeds the designed value. Re-design the systemDuct is poorly sealed Seal it with glueFireproof damper is shut off Turn on the fireproof damper
3. Filter Too dirty or blocked Clean or replace the filter4. Coil Too dirty or blocked Clean coils5. Air flow is short-circuited.
The air inlet and air outlet are not properly isolated. Thus, the air runs directly to the air inlet Add air separator
6. Fan inlet is blockedElbow at the air return area fan outlet are too close to the unit wallboard Move the fan
The fan outlet is blocked Remove the obstructions
7. No straight tube at the fan air outlet
A length of straight tube is mounted at the fan outlet during fan testing. Without straight tube, the fan performance might be worsened. Thus, the fan may run faster to overcome the resistance (check the fan speed)
Install straight tube
8. There are sundries inside fan system
The fan outlet is blocked Remove the obstructionsThere is an elbow tube at the fan outlet Re-design duct
The fan is functioning but the air supply is too large
1. System
Improper duct size Re-design The access door is open Close the access doorThe system is not well balanced and the actual resistance is lower than the set resistance Re-design the system
No air damper or air damper blade Install air damper or air damper blade.
Filter falls off or no filter installed Re-mount the filter2. Duct Return duct leaks Seal with glue
The air in the air-
conditioned room is
not fresh enough
1. Filter Filter is too dirty or blocked Clean or replace filter
2. Fresh air No enough fresh air Supply more fresh air
17
Exploded view and part listMHW015A, MHW020A, MHW025A
1.Top panel 2.Assy.,coil 3.Drainpan
4.Check panel 5.Inlet/outlet panel 6.Long wind guard
7.Filter 8.Short wind guard. 9.Base panel
10.Side panel 11.Blower 12.Motor
13.Front panel 14.Flange 15.Hanging angel
18
MHW030A, MHW035A, MHW040A, MHW050A
1.Top panel 2.Assy.,coil 3.Drainpan
4.Check panel 5.Inlet/outlet panel 6.Long wind guard
7.Filter 8.Short wind guard. 9.Base panel
10.Side panel 11.Blower 12.Motor
13.Front panel 14.Flange 15.Hanging angel
19
Main part number
Model Discription MHW030A MHW035A MHW040A MHW050A
Blower Left M03029001982 M03029001982 M03029001982 M03029001982
Blower Right M03029001983 M03029001983 M03029001983 M03029001983
Motor (4 Rows)
50HzClockwise M03039012176 M03039012178 M03039012180 M03039012184
Anti-clockwise M03039012177 M03039012179 M03039012181 M03039012185
60HzClockwise M03039001119 M03039001117 M03034350003 M03034350001
Anti-clockwise M03039001118 M03039001116 M03039000004 M03039000002
Motor (6 Rows)
50HzClockwise M03039012178 M03039012186 M03039012182 M03039012188
Anti-clockwise M03039012179 M03039012187 M03039012183 M03039012189
60HzClockwise M03039001117 M03039001115 M03034350003 M03034350014
Anti-clockwise M03039001116 M03039001114 M03039000004 M03039000015
Filter M03084352004 M03084352005 M03084352006 M03084352007
Drain Pan M50014351504 M50014351505 M50014351506 M50014351507
Terminal Block M04119003747 M04119003747 M04119003747 M04119003747
Model MHW015A MHW020A MHW025A
Blower M03029001982 M03029001982 M03029001982
Motor(4 Rows)
50HzClockwise M03039012174 M03039012186 M03039012184
Anti-clockwise M03039012175 M03039012187 M03039012185
60HzClockwise M03039001107 M03039001116 M03034350006
Anti-clockwise M03039001108 M03039001117 M03034350005
Motor(6 Rows)
50HzClockwise M03039012177 M03039012181 M03039012189
Anti-clockwise M03039012176 M03039012180 M03039012188
60HzClockwise M03039001109 M03039001111 M03034350006
Anti-clockwise M03039001110 M03039001112 M03034350005
Filter M03084352001 M03084352002 M03084352003
Drain Pan M50014351501 M50014351502 M50014351503
Terminal Block M04119003747 M04119003747 M04119003747
©2011 McQuay International +1 (800) 432-1342 www.mcquay.com
While utmost care is taken in ensuring that all details in the publication are correct at the time of going to press, we are constantly striving for improvement and therefore reserve the right to alter model specifications and equipment without notice.Details of specifications and equipment are also subject to change to suit local conditions and requirements and not all models are available in every market.
ISO 9001 Certificate No.: 9601019
BS-OHSAS 18001 Certificate No.: 7644
ISO 14001 Certificate No.: EMS 80362