micom c264 rtu brochure en

4
SOPHISTICATED REMOTE TERMINAL UNIT FOR SUBSTATION CONTROL, MONITORING, DISTRIBUTED IEDS DATA CONCENTRATION AND GATEWAY COMMUNICATION WITH SCADAS. The MiCOM C264-R combines the usual RTUs features with the benefits of fast Ethernet communication. Its intrinsic high-performance is further expanded through the modular I/Os acquisition racks. This up to date design helps the user to simplify the engineering and installation, improve reliability and quality as well as increase efficiency through space and cost reductions in wiring, testing, maintenance and management. The MiCOM C264-R offers natively an on-board 100Mb Ethernet communication for SCADA communication, simple maintenance access and the connection of many I/Os acquisition racks. This is in addition of the serial ports for every application using multiple standard protocols. Each port is able to communicate with a protocol including IEC60870-5-103, IEC 60870-5-101, MODBUS, DNP3.0, or with a SOE serial printer. The MiCOM C264-R with high-performance, large capacity, expandable is well adapted for turnkey applications as well as retrofit installations. MiCOM C264-R is also to be considered as a step on the way of Digital Control Systems. FIELD OF APPLICATION The MiCOM C264-R modular Remote Terminal Unit (RTU) provides a powerful solution for SCADA communication, Sequence of Event Recorder (SER), and can be integrated to digital substation control systems. It is designed for a wide range of applications: Electrical utility > Transmission and distribution substations > Power Plant substations Industry > Process control, including manufacturing, transit, telecommunications, testing, etc... > Oil and gas, including pipelines > Water and wastewater Transportation electrical supervision and control > Railways > Airport AREVA T&D C264-R Application Modular Remote Terminal Unit SUBSTATION AUTOMATION Customer Benefits • Modular RTU for electrical substations requiring large capacities • IEDs and Sub-RTUs concentrator • SCADA interfaces with serial and Ethernet protocols • A step for a smooth transition to Digital Control Systems • LCD graphical display for user-friendly local control, monitoring, and maintenance • Expandable design with single or multiple racks architectures • High availability and reliability with redundant communication facilities

Upload: ganeshd2k6

Post on 08-Apr-2015

1.225 views

Category:

Documents


21 download

TRANSCRIPT

Page 1: Micom c264 Rtu Brochure En

SOPHISTICATED REMOTE TERMINAL UNIT FORSUBSTATION CONTROL, MONITORING, DISTRIBUTED IEDSDATA CONCENTRATION AND GATEWAY COMMUNICATIONWITH SCADAS.

The MiCOM C264-R combines the usual RTUs features withthe benefits of fast Ethernet communication. Its intrinsichigh-performance is further expanded through the modularI/Os acquisition racks. This up to date design helps theuser to simplify the engineering and installation, improvereliability and quality as well as increase efficiency throughspace and cost reductions in wiring, testing, maintenanceand management.

The MiCOM C264-R offers natively an on-board 100MbEthernet communication for SCADA communication, simplemaintenance access and the connection of many I/Osacquisition racks. This is in addition of the serial ports forevery application using multiple standard protocols. Eachport is able to communicate with a protocol includingIEC60870-5-103, IEC 60870-5-101, MODBUS, DNP3.0, orwith a SOE serial printer.

The MiCOM C264-R with high-performance, large capacity,expandable is well adapted for turnkey applications as wellas retrofit installations. MiCOM C264-R is also to beconsidered as a step on the way of Digital Control Systems.

FIELD OF APPLICATION

The MiCOM C264-R modular Remote Terminal Unit (RTU) provides a powerful solution for SCADAcommunication, Sequence of Event Recorder (SER), and can be integrated to digital substationcontrol systems. It is designed for a wide range of applications:

EElleeccttrriiccaall uuttiilliittyy>> Transmission and distribution substations

>> Power Plant substations

IInndduussttrryy

>> Process control, including manufacturing, transit, telecommunications, testing, etc...

>> Oil and gas, including pipelines

>> Water and wastewater

TTrraannssppoorrttaattiioonn eelleeccttrriiccaall ssuuppeerrvviissiioonn aanndd ccoonnttrrooll

>> Railways

>> Airport

AREVA T&D

C264-R ApplicationModular Remote Terminal Unit

SU BSTATION AUTOMATION

Customer Benefits• Modular RTU for

electrical substationsrequiring large capacities

• IEDs and Sub-RTUsconcentrator

• SCADA interfaces withserial and Ethernetprotocols

• A step for a smoothtransition to Digital ControlSystems

• LCD graphical display foruser-friendly local control,monitoring, and maintenance

• Expandable design with singleor multiple racks architectures

• High availability and reliabilitywith redundant communicationfacilities

Page 2: Micom c264 Rtu Brochure En

APPLICATION PROFILE

>> Stand-alone RTU (Single or Multiple I/Os racks)

>> Sequence of Event Recorder (SER) – SOE printing

>> IEDs and remote sub-RTU’s data concentrator

>> Substation Gateway and protocol converter

>> Integrated into the AREVA-T&D DCS and SCADAsolutions

GENERAL FUNCTIONS

>> Data acquisition and processes for digital, analoguevalues inputs and outputs

>> Control and monitoring of switching devices

>> Configurable indications on local LCD screen,graphical Mimics and LEDs

>> Standardised and proprietary communicationprotocols

>> Sequence of Events (SOE) print in chronologicalorder

>> Local storage of events, counters and measurementvalues

>> Download of the configuration thru Ethernet or from SCADA (IEC101 serial communication)

>> Automation sequences (option)

>> Maintenance facilities over Ethernet (I/O valuesvisualisation, hardware status, software anddatabase download), with convivial software tool,on standard PC.

TECHNICAL DATA

HARDWARE

>> CCaassee

•• MiCOM C264CWxHxD 40T(206 mm) x 4U(177 mm) x 168 mmSlots 6 free assignment

•• MiCOM C264WxHxD 80T(405 mm) x 4U(177 mm) x 168 mmSlots 15 free assignment

>> CCoonnttrrooll ppaanneell

•• Large graphical LCD (optional) •• Display 72 x 72 mm (optional) •• Buttons (12): 7 for operations -

5 for control (optional)•• LEDs 17, 12 free configurable

>> PPoowweerr ssuuppppllyy bbooaarrdd

•• UN 24VDC, 48//60VDC, 110/125VDC,220 VDC, 230 VAC 50/60 Hz

•• Watchdog, Digital Input and Output relays forredundancy management

>> PPrroocceessssoorr bbooaarrdd

•• 32-bit Power PC-based processor

•• Internal Watchdog

•• Clock 80 Mhz

•• RAM 64 Mbytes

•• Flash 16 Mbytes

•• Ethernet-Based 10/100Base-FX or 10/100Base-TX

•• up to 4 serial interfaces RS232/485/optical fibreon each rack

•• IRIG-B interface, BNC plug, Amplitude modulated.Standard: NF- 5 85-500, May 1987.

>> DDiiggiittaall IInnppuutt BBooaarrdd ((1166 DDII))

•• 16 optically insulated inputs with one common for 2 DI.UN 24, 48/60, 110/125, 220 VDC

with DIU200 boardorUN 24 - 220 VDC

with multi-voltage DIU210 board

2>3

Serial Links to SCADA (IEC101,

Modbus, DNP3, HNZ)

Inputs / Outputs

Legacy serial buses (IEC103, IEC101,Modbus, DNP3)

Printer

Configuration andMaintenance Tools

EthernetExtension racks

Main

IEDs, relays, Sub-RTUs

Ethernet link to SCADA (IEC104)

SCADAs

MiCOM C264-R architecture

Page 3: Micom c264 Rtu Brochure En

COMMUNICATIONS

• SSttaannddaarrdd EEtthheerrnneett SSCCAADDAA pprroottooccoollssIEC 60870-5-104 (multi-client), DNP3/IP (option)Ethernet 10/100Base-FX or 10/100Base-TX

• SSttaannddaarrdd sseerriiaall SSCCAADDAA pprroottooccoollssIEC 60870-5-101, MODBUS, HNZ, DNP3 (option)

• IInntteerrffaacceessOptical / RS232 / RS422 / RS485

• SSttaannddaarrdd IIEEDDss pprroottooccoollssIEC 60870-5-103, MODBUS, IEC 60870-5-101, DNP3 (option)

• SSyynncchhrroonniissaattiioonnExternal synchronisation using IRIG-B

RTU CAPACITY

>> Multiple acquisition racks over Ethernet

>> Up to 240 Digital Input signals per rack (15 slots)

>> Up to 4 serial links on a rack (RS232/RS485/optical)

>> Up to 2 SCADAs simultaneous connections

>> Double lines management over IEC60870-5-101SCADA connections

>> Up to 16 IEDs on the RS485 legacy buses

>> Global data management of up to 5012 digitaldatapoints, 1024 Analog values, 1024 Digitaloutputs, 100 Setpoints, 100 Tap Position Indicationon the C264-R

>> Redundancy of SCADA interface (option)

SOE RECORDS

>> 1ms time tagging

•• Chronological order•• 1 standard serial printer

>> 2000 events recorded in non volatile memory(Flash disk)

>> The 200 most recent events readable on optionalLCD screen

STANDARD COMPLIANCE

Superior construction: environment, EMC, isolations inaccordance with IEC Standards.

MiCOM C264: a compact, powerfull and innovative RTU for electrical applications

>> DDiiggiittaall OOuuttppuutt BBooaarrdd ((1100 DDOO))

•• 8 outputs NO + 2 outputs NO/NC UN 24- 250 VDC / 230 VAC

•• Continuous current: 2,5Ashort duration current:30A for 500ms, 100A for 30ms.

Breaking capacity:DC: 50W resistive

15 W inductive(L/R = 20ms)

>> MMiixxeedd bbooaarrdd ((88 DDII // 44DDOO))CCiirrccuuiitt bbrreeaakkeerr ccoonnttrrooll bbooaarrdd ((CCCCUU220000))

•• 8 optically insulated inputs with one common for 2 DI.UN 24, 48/60, 110/125, and 220 VDC

•• 4 power outputs relay (2 NO contacts) UN 24- 250 VDC / 230 VAC

Continuous current: 5Ashort duration current: 250A for 30ms

Breaking capacity:(double pole contacts wired in serial)DC: 100W resistive

30W inductive

>> AAnnaalloogguuee IInnppuutt BBooaarrdd ((44AAII //88AAII))

•• 4 isolated analogue inputs for measuring transducer connection (AIU201).Current: ± 1 / 2 / 5 / 10 / 20 mA / 4-20 mAVoltage: ± 1.25 / 2.5 / 5 / 10 V

•• 8 analogue inputs for measuring transducer connection (AIU21x).Current: ± 1 / 2 / 5 / 10 / 20 mA / 4-20 mA

>> AAnnaalloogguuee OOuuttppuutt BBooaarrdd ((44AAOO))

•• 4 analogue outputs with 4 read inhibit outputrelays (AOU200).Current: ± 5 / 10 / 20 mA / 4-20 mAExternal power supply (48V ±5%)Output maintained in case of C264 power supplyfailure

Page 4: Micom c264 Rtu Brochure En

AAUU

TTOO

MMAA

TTIIOO

NN--LL

33--CC

226644RR

TTUU

--BBRR

--0055..

0077--11

228877bb

--GGBB

-- ©

- A

RE

VA

- 2

007.

AR

EV

A,

the

AR

EV

A lo

go a

nd a

ny a

ltern

ativ

e ve

rsio

n th

ereo

f ar

e tr

adem

arks

and

ser

vice

mar

ks o

f A

RE

VA

.M

iCO

M is

a r

egis

tere

d tr

adem

ark

of A

RE

VA

.All

trad

e na

mes

or

trad

emar

ks m

entio

ned

here

in w

heth

er r

egis

tere

d or

not

, ar

e th

e pr

oper

ty o

f th

eir

owne

rs.

- 38

9191

982

RC

S P

AR

IS -

Prin

ted

in F

ranc

e

AREVA T&D Worldwide Contact Centre:http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070

www.areva-td.comwww.areva-td.com/substationautomation

Our policy is one of continuous development. Accordingly thedesign of our products may change at any time. Whilst everyeffort is made to produce up to date literature, this brochureshould only be regarded as a guide and is intended forinformation purposes only. Its contents do not constitute an offerfor sale or advise on the application of any product referred to init. We cannot be held responsible for any reliance on anydecisions taken on its contents without specific advice.