SOPHISTICATED REMOTE TERMINAL UNIT FORSUBSTATION CONTROL, MONITORING, DISTRIBUTED IEDSDATA CONCENTRATION AND GATEWAY COMMUNICATIONWITH SCADAS.
The MiCOM C264-R combines the usual RTUs features withthe benefits of fast Ethernet communication. Its intrinsichigh-performance is further expanded through the modularI/Os acquisition racks. This up to date design helps theuser to simplify the engineering and installation, improvereliability and quality as well as increase efficiency throughspace and cost reductions in wiring, testing, maintenanceand management.
The MiCOM C264-R offers natively an on-board 100MbEthernet communication for SCADA communication, simplemaintenance access and the connection of many I/Osacquisition racks. This is in addition of the serial ports forevery application using multiple standard protocols. Eachport is able to communicate with a protocol includingIEC60870-5-103, IEC 60870-5-101, MODBUS, DNP3.0, orwith a SOE serial printer.
The MiCOM C264-R with high-performance, large capacity,expandable is well adapted for turnkey applications as wellas retrofit installations. MiCOM C264-R is also to beconsidered as a step on the way of Digital Control Systems.
FIELD OF APPLICATION
The MiCOM C264-R modular Remote Terminal Unit (RTU) provides a powerful solution for SCADAcommunication, Sequence of Event Recorder (SER), and can be integrated to digital substationcontrol systems. It is designed for a wide range of applications:
EElleeccttrriiccaall uuttiilliittyy>> Transmission and distribution substations
>> Power Plant substations
IInndduussttrryy
>> Process control, including manufacturing, transit, telecommunications, testing, etc...
>> Oil and gas, including pipelines
>> Water and wastewater
TTrraannssppoorrttaattiioonn eelleeccttrriiccaall ssuuppeerrvviissiioonn aanndd ccoonnttrrooll
>> Railways
>> Airport
AREVA T&D
C264-R ApplicationModular Remote Terminal Unit
SU BSTATION AUTOMATION
Customer Benefits• Modular RTU for
electrical substationsrequiring large capacities
• IEDs and Sub-RTUsconcentrator
• SCADA interfaces withserial and Ethernetprotocols
• A step for a smoothtransition to Digital ControlSystems
• LCD graphical display foruser-friendly local control,monitoring, and maintenance
• Expandable design with singleor multiple racks architectures
• High availability and reliabilitywith redundant communicationfacilities
APPLICATION PROFILE
>> Stand-alone RTU (Single or Multiple I/Os racks)
>> Sequence of Event Recorder (SER) – SOE printing
>> IEDs and remote sub-RTU’s data concentrator
>> Substation Gateway and protocol converter
>> Integrated into the AREVA-T&D DCS and SCADAsolutions
GENERAL FUNCTIONS
>> Data acquisition and processes for digital, analoguevalues inputs and outputs
>> Control and monitoring of switching devices
>> Configurable indications on local LCD screen,graphical Mimics and LEDs
>> Standardised and proprietary communicationprotocols
>> Sequence of Events (SOE) print in chronologicalorder
>> Local storage of events, counters and measurementvalues
>> Download of the configuration thru Ethernet or from SCADA (IEC101 serial communication)
>> Automation sequences (option)
>> Maintenance facilities over Ethernet (I/O valuesvisualisation, hardware status, software anddatabase download), with convivial software tool,on standard PC.
TECHNICAL DATA
HARDWARE
>> CCaassee
•• MiCOM C264CWxHxD 40T(206 mm) x 4U(177 mm) x 168 mmSlots 6 free assignment
•• MiCOM C264WxHxD 80T(405 mm) x 4U(177 mm) x 168 mmSlots 15 free assignment
>> CCoonnttrrooll ppaanneell
•• Large graphical LCD (optional) •• Display 72 x 72 mm (optional) •• Buttons (12): 7 for operations -
5 for control (optional)•• LEDs 17, 12 free configurable
>> PPoowweerr ssuuppppllyy bbooaarrdd
•• UN 24VDC, 48//60VDC, 110/125VDC,220 VDC, 230 VAC 50/60 Hz
•• Watchdog, Digital Input and Output relays forredundancy management
>> PPrroocceessssoorr bbooaarrdd
•• 32-bit Power PC-based processor
•• Internal Watchdog
•• Clock 80 Mhz
•• RAM 64 Mbytes
•• Flash 16 Mbytes
•• Ethernet-Based 10/100Base-FX or 10/100Base-TX
•• up to 4 serial interfaces RS232/485/optical fibreon each rack
•• IRIG-B interface, BNC plug, Amplitude modulated.Standard: NF- 5 85-500, May 1987.
>> DDiiggiittaall IInnppuutt BBooaarrdd ((1166 DDII))
•• 16 optically insulated inputs with one common for 2 DI.UN 24, 48/60, 110/125, 220 VDC
with DIU200 boardorUN 24 - 220 VDC
with multi-voltage DIU210 board
2>3
Serial Links to SCADA (IEC101,
Modbus, DNP3, HNZ)
Inputs / Outputs
Legacy serial buses (IEC103, IEC101,Modbus, DNP3)
Printer
Configuration andMaintenance Tools
EthernetExtension racks
Main
IEDs, relays, Sub-RTUs
Ethernet link to SCADA (IEC104)
SCADAs
MiCOM C264-R architecture
COMMUNICATIONS
• SSttaannddaarrdd EEtthheerrnneett SSCCAADDAA pprroottooccoollssIEC 60870-5-104 (multi-client), DNP3/IP (option)Ethernet 10/100Base-FX or 10/100Base-TX
• SSttaannddaarrdd sseerriiaall SSCCAADDAA pprroottooccoollssIEC 60870-5-101, MODBUS, HNZ, DNP3 (option)
• IInntteerrffaacceessOptical / RS232 / RS422 / RS485
• SSttaannddaarrdd IIEEDDss pprroottooccoollssIEC 60870-5-103, MODBUS, IEC 60870-5-101, DNP3 (option)
• SSyynncchhrroonniissaattiioonnExternal synchronisation using IRIG-B
RTU CAPACITY
>> Multiple acquisition racks over Ethernet
>> Up to 240 Digital Input signals per rack (15 slots)
>> Up to 4 serial links on a rack (RS232/RS485/optical)
>> Up to 2 SCADAs simultaneous connections
>> Double lines management over IEC60870-5-101SCADA connections
>> Up to 16 IEDs on the RS485 legacy buses
>> Global data management of up to 5012 digitaldatapoints, 1024 Analog values, 1024 Digitaloutputs, 100 Setpoints, 100 Tap Position Indicationon the C264-R
>> Redundancy of SCADA interface (option)
SOE RECORDS
>> 1ms time tagging
•• Chronological order•• 1 standard serial printer
>> 2000 events recorded in non volatile memory(Flash disk)
>> The 200 most recent events readable on optionalLCD screen
STANDARD COMPLIANCE
Superior construction: environment, EMC, isolations inaccordance with IEC Standards.
MiCOM C264: a compact, powerfull and innovative RTU for electrical applications
>> DDiiggiittaall OOuuttppuutt BBooaarrdd ((1100 DDOO))
•• 8 outputs NO + 2 outputs NO/NC UN 24- 250 VDC / 230 VAC
•• Continuous current: 2,5Ashort duration current:30A for 500ms, 100A for 30ms.
Breaking capacity:DC: 50W resistive
15 W inductive(L/R = 20ms)
>> MMiixxeedd bbooaarrdd ((88 DDII // 44DDOO))CCiirrccuuiitt bbrreeaakkeerr ccoonnttrrooll bbooaarrdd ((CCCCUU220000))
•• 8 optically insulated inputs with one common for 2 DI.UN 24, 48/60, 110/125, and 220 VDC
•• 4 power outputs relay (2 NO contacts) UN 24- 250 VDC / 230 VAC
Continuous current: 5Ashort duration current: 250A for 30ms
Breaking capacity:(double pole contacts wired in serial)DC: 100W resistive
30W inductive
>> AAnnaalloogguuee IInnppuutt BBooaarrdd ((44AAII //88AAII))
•• 4 isolated analogue inputs for measuring transducer connection (AIU201).Current: ± 1 / 2 / 5 / 10 / 20 mA / 4-20 mAVoltage: ± 1.25 / 2.5 / 5 / 10 V
•• 8 analogue inputs for measuring transducer connection (AIU21x).Current: ± 1 / 2 / 5 / 10 / 20 mA / 4-20 mA
>> AAnnaalloogguuee OOuuttppuutt BBooaarrdd ((44AAOO))
•• 4 analogue outputs with 4 read inhibit outputrelays (AOU200).Current: ± 5 / 10 / 20 mA / 4-20 mAExternal power supply (48V ±5%)Output maintained in case of C264 power supplyfailure
AAUU
TTOO
MMAA
TTIIOO
NN--LL
33--CC
226644RR
TTUU
--BBRR
--0055..
0077--11
228877bb
--GGBB
-- ©
- A
RE
VA
- 2
007.
AR
EV
A,
the
AR
EV
A lo
go a
nd a
ny a
ltern
ativ
e ve
rsio
n th
ereo
f ar
e tr
adem
arks
and
ser
vice
mar
ks o
f A
RE
VA
.M
iCO
M is
a r
egis
tere
d tr
adem
ark
of A
RE
VA
.All
trad
e na
mes
or
trad
emar
ks m
entio
ned
here
in w
heth
er r
egis
tere
d or
not
, ar
e th
e pr
oper
ty o
f th
eir
owne
rs.
- 38
9191
982
RC
S P
AR
IS -
Prin
ted
in F
ranc
e
AREVA T&D Worldwide Contact Centre:http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070
www.areva-td.comwww.areva-td.com/substationautomation
Our policy is one of continuous development. Accordingly thedesign of our products may change at any time. Whilst everyeffort is made to produce up to date literature, this brochureshould only be regarded as a guide and is intended forinformation purposes only. Its contents do not constitute an offerfor sale or advise on the application of any product referred to init. We cannot be held responsible for any reliance on anydecisions taken on its contents without specific advice.