manual areva c264 en t c30 global

Upload: agusriyanto

Post on 11-Oct-2015

310 views

Category:

Documents


56 download

TRANSCRIPT

  • 5/20/2018 Manual Areva c264 en t c30 Global

    1/494

    MiCOM

    C264/C264CBay Computer

    Technical Guide

    C264 EN T C30

  • 5/20/2018 Manual Areva c264 en t c30 Global

    2/494

  • 5/20/2018 Manual Areva c264 en t c30 Global

    3/494

    Technical Guide C264/EN T/C30

    MiCOM C264/C264C Page 1/2

    MiCOM C264/C264C

    BAY COMPUTER

    CONTENT

    Safety & Handling C264/EN SA/C30

    Introduction C264/EN IT/C30

    Technical data C264/EN TD/C30

    Functional Description C264/EN FT/C30

    Hardware Description C264/EN HW/C30

    Connection C264/EN CO/C30

    Installation C264/EN IN/C30

    Settings C264/EN ST/C30

    Communications C264/EN CT/C30

    Commissioning C264/EN CM/C30

    Commissioning Record Sheet C264/EN RS/C30

    Maintenance C264/EN MF/C30

    Lexical C264/EN LX/C30

  • 5/20/2018 Manual Areva c264 en t c30 Global

    4/494

    C264/EN T/C30 Technical Guide

    Page 2/2 MiCOM C264/C264C

    BLANK PAGE

  • 5/20/2018 Manual Areva c264 en t c30 Global

    5/494

    Safety & Handling C264/EN SA/C30MiCOM C264/C264C

    SAFETY & HANDLING

  • 5/20/2018 Manual Areva c264 en t c30 Global

    6/494

  • 5/20/2018 Manual Areva c264 en t c30 Global

    7/494

    Safety & Handling C264/EN SA/C30

    MiCOM C264/C264C Page 1/12

    CONTENT

    1. INTRODUCTION 3

    2. HEALTH AND SAFETY 4

    2.1 Health and Safety 4

    2.2 Installing, Commissioning and Servicing 4

    3. DECOMMISSIONING AND DISPOSAL 6

    4. TECHNICAL SPECIFICATIONS FOR SAFETY 7

    5. HANDLING OF ELECTRONIC EQUIPMENTS 8

    6. PACKING AND UNPACKING 9

    7. GUARANTEES 10

    8.

    COPYRIGHTS & TRADEMARKS 11

    8.1 Copyrights 11

    8.2 Trademarks 11

    9.

    WARNINGS REGARDING USE OF AREVA T&D EAI PRODUCTS 12

  • 5/20/2018 Manual Areva c264 en t c30 Global

    8/494

    C264/EN SA/C30 Safety & Handling

    Page 2/12 MiCOM C264/C264C

    BLANK PAGE

  • 5/20/2018 Manual Areva c264 en t c30 Global

    9/494

    Safety & Handling C264/EN SA/C30

    MiCOM C264/C264C Page 3/12

    1. INTRODUCTION

    This document is a chapter of the MiCOM C264/C264C documentation binder. It describesthe safety, handling, packing and unpacking procedures applicable to MiCOM C264/C264Cmodular computer series and associated equipment's and software tools.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    10/494

    C264/EN SA/C30 Safety & Handling

    Page 4/12 MiCOM C264/C264C

    2. HEALTH AND SAFETY

    For all the safety purposes please refer to the AREVA T&D Safety Guide: SFTY/4L M/F11(or later issue) andto the following chapters.

    WARNING: THIS SAFETY SECTION SHOULD BE READ BEFORE COMMENCING

    ANY WORK ON THE EQUIPMENT.

    2.1 Health and Safety

    The information in the Safety Section of the product documentation is intended to ensurethat products are properly installed and handled in order to maintain them in a safe condition.It is assumed that everyone who will be associated with the equipment will be familiar withthe contents of the Safety Section.

    2.2 Installing, Commissioning and Servicing

    Equipment connections

    Personnel undertaking installation, commissioning or servicing work on this equipmentshould be aware of the correct working procedures to ensure safety. The productdocumentation should be consulted before installing, commissioning or servicing theequipment.

    Terminals exposed during installation, commissioning and maintenance may present ahazardous voltage unless the equipment is electrically isolated.

    If there is unlocked access to the rear of the equipment, care should be taken by allpersonnel to avoid electrical shock or energy hazards.

    Voltage and current connections should be made using insulated crimp terminations toensure that terminal block insulation requirements are maintained for safety. To ensure thatwires are correctly terminated the correct crimp terminal and tool for the wire size should be

    used.Before energising the equipment it must be earthed using the protective earth terminal, orthe appropriate termination of the supply plug in the case of plug connected equipment.

    Omitting or disconnecting the equipment earth may cause a safety hazard.

    The recommended minimum earth wire size is 2.5mm, unless otherwise stated in thetechnical data section of the product documentation.

    When the protective (earth) conductor terminal (PCT) is also used to terminate cablescreens, etc., it is essential that the integrity of the protective (earth) conductor is checkedafter the addition or removal of such functional earth connections.

    For M4 stud PCTs the integrity of the protective (earth) connection should be ensured by use

    of a locknut or similar."

    Before energising the equipment, the following should be checked:

    Voltage rating and polarity;

    CT circuit rating and integrity of connections;

    Integrity of earth connection (where applicable)

    Note: The term earth used throughout the product documentation is the direct equivalent ofthe North American term ground.

    Equipment operating conditions

    The equipment should be operated within the specified electrical and environmental limits.

    Current transformer circuits

    Do not open the secondary circuit of a live CT since the high level voltage produced may belethal to personnel and could damage insulation.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    11/494

    Safety & Handling C264/EN SA/C30

    MiCOM C264/C264C Page 5/12

    Insulation and dielectric strength testing

    Insulation testing may leave capacitors charged up to a hazardous voltage. At the end ofeach part of the test, the voltage should be gradually reduced to zero, to dischargecapacitors, before the test leads are disconnected.

    Insertion of modules and boards

    These must not be inserted into or withdrawn from equipment whist it is energised since thismay result in damage.

    Fibre optic communication

    Where fibre optic communication devices are fitted, these should not be viewed directly.Optical power meters should be used to determine the operation or signal level of the device.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    12/494

    C264/EN SA/C30 Safety & Handling

    Page 6/12 MiCOM C264/C264C

    3. DECOMMISSIONING AND DISPOSAL

    Decommissioning:

    The auxiliary supply circuit in the MiCOM computers may include capacitors across thesupply or to earth. To avoid electric shock or energy hazards, after completely isolating the

    supplies to the MiCOM computers (both poles of any dc supply), the capacitors should besafely discharged via the external terminals prior to decommissioning.

    Disposal:

    It is recommended that incineration and disposal to watercourses be avoided. The productshould be disposed of in a safe manner. Any products containing batteries should have themremoved before disposal, in order to avoid short circuits. Particular regulations within thecountry of operation may apply to the disposal of lithium batteries.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    13/494

    Safety & Handling C264/EN SA/C30

    MiCOM C264/C264C Page 7/12

    4. TECHNICAL SPECIFICATIONS FOR SAFETY

    The recommended maximum rating of the external protective fuse for this equipment is 16A,High rupture capacity (HRC) Red Spot type NIT or TIA, or equivalent unless otherwisestated in the technical data section of the product documentation. The protective fuse shouldbe located as close to the unit as possible.

    1. Fuse rating is dependent of auxiliary voltage and circuit loading.

    2. Differential protective switch on DC power supply is recommended.

    3. Differential protective switch on AC power supply is mandatory (printers, PACiSworkstation).

    Protective class: IEC 60255-27: 2005 Class I This equipment requiresa protective (safety)earth connection toensure user safety.

    Installation

    Category:

    IEC 60255-27:

    EN 60255-27:

    2005

    2006

    Installation Category III

    Distribution level, fixedinstallation.

    Equipment in thiscategory is qualificationtested at 5kV peak,

    1.2/50s, 500. 0.5J,between all supplycircuits and earth andalso betweenindependent circuits.

    Environment: IEC 60255-27:

    Pollution degree 2

    EN 60255-27:

    2005

    2006

    Compliance isdemonstrated byreference to safetystandards.

    Product Safety: 73/23/EEC Compliance with theEuropean CommissionLow Voltage Directive.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    14/494

    C264/EN SA/C30 Safety & Handling

    Page 8/12 MiCOM C264/C264C

    5. HANDLING OF ELECTRONIC EQUIPMENTS

    A persons normal movements can easily generate electrostatic potentials of severalthousand volts.

    Discharge of these voltages into semiconductor devices when handling circuits can cause

    serious damage, which often may not be immediately apparent but the reliability of the circuitwill have been reduced.

    The electronic circuits of AREVA T&D Energy Automation & Information products areimmune to the relevant levels of electrostatic discharge when housed in their cases. Do notexpose them to the risk of damage by withdrawing modules unnecessarily.

    Each module incorporates the highest practicable protection for its semiconductor devices.However, if it becomes necessary to withdraw a module, the following precautions should betaken in order to preserve the high reliability and long life for which the equipment has beendesigned and manufactured.

    1. Before removing a module, ensure that you are a same electrostatic potential as theequipment by touching the case.

    2. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoidtouching the electronic components, printed circuit track or connectors.

    3. Do not pass the module to any person without first ensuring that you are both at thesame electrostatic potential. Shaking hands achieves equipotential.

    4. Place the module on an antistatic surface, or on a conducting surface, which is at thesame potential as you.

    5. Store or transport the module in a conductive bag.

    More information on safe working procedures for all electronic equipment can be found inIEC 60147-0F and BS5783.

    If you are making measurements on the internal electronic circuitry of any equipment inservice, it is preferable that you are earthen to the case with a conductive wrist strap.

    Wrist straps should have a resistance to ground between 500k 10M Ohms. If a wrist strapis not available you should maintain regular contact with the case to prevent the build up ofstatic. Instrumentation which may be used for making measurements should be earthen tothe case whenever possible.

    AREVA T&D Energy Automation & Information strongly recommends that detailedinvestigations on the electronic circuitry, or modification work, should be carried out in aSpecial Handling Area such as described in IEC 60147-0F or BS5783.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    15/494

    Safety & Handling C264/EN SA/C30

    MiCOM C264/C264C Page 9/12

    6. PACKING AND UNPACKING

    All MiCOM C264/C264C computers are packaged separately in their own cartons andshipped inside outer packaging. Use special care when opening the cartons and unpackingthe device, and do not use force. In addition, make sure to remove from the inside carton thesupporting documents supplied with each individual device and the type identification label.

    The design revision level of each module included with the device in its as-deliveredcondition can be determined from the list of components. This list should be carefully saved.

    After unpacking the device, inspect it visually to make sure it is in proper mechanicalcondition.

    If the MiCOM C264/C264C computer needs to be shipped, both inner and outer packagingmust be used. If the original packaging is no longer available, make sure that packaging

    conforms to ISO 2248 specifications for a drop height 0.8m.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    16/494

    C264/EN SA/C30 Safety & Handling

    Page 10/12 MiCOM C264/C264C

    7. GUARANTEES

    The media on which you received AREVA T&D EAI software are guaranteed not to failexecuting programming instructions, due to defects in materials and workmanship, for aperiod of 90 days from date of shipment, as evidenced by receipts or other documentation.AREVA T&D EAI will, at its option, repair or replace software media that do not executeprogramming instructions if AREVA T&D EAI receive notice of such defects during theguaranty period. AREVA T&D EAI does not guaranty that the operation of the software shallbe uninterrupted or error free.

    A Return Material Authorisation (RMA) number must be obtained from the factory and clearlymarked on the package before any equipment acceptance for guaranty work. AREVA T&DEAI will pay the shipping costs of returning to the owner parts, which are covered bywarranty.

    AREVA T&D EAI believe that the information in this document is accurate. The documenthas been carefully reviewed for technical accuracy. In the event that technical ortypographical errors exist, AREVA T&D EAI reserves the right to make changes tosubsequent editions of this document without prior notice to holders of this edition. The

    reader should consult AREVA T&D EAI if errors are suspected. In no event shall AREVAT&D EAI be liable for any damages arising out of or related to this document or theinformation contained in it.

    Expect as specified herein, AREVA T&D EAI makes no guaranties, express or implied andspecifically disclaims and guaranties of merchantability or fitness for a particular purpose.Customer's rights to recover damages caused by fault or negligence on the part AREVAT&D EAI shall be limited to the amount therefore paid by the customer. AREVA T&D EAI willnot be liable for damages resulting from loss of data, profits, use of products or incidental orconsequential damages even if advised of the possibility thereof. This limitation of the liabilityof AREVA T&D EAI will apply regardless of the form of action, whether in contract or tort,including negligence. Any action against AREVA T&D EAI must be brought within one yearafter the cause of action accrues. AREVA T&D EAI shall not be liable for any delay in

    performance due to causes beyond its reasonable control. The warranty provided hereindoes not cover damages, defects, malfunctions, or service failures caused by owner's failureto follow the AREVA T&D EAI installation, operation, or maintenance instructions. Owner'smodification of the product; owner's abuse, misuse, or negligent acts; and power failure orsurges, fire, flood, accident, actions of third parties, or other events outside reasonablecontrol.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    17/494

    Safety & Handling C264/EN SA/C30

    MiCOM C264/C264C Page 11/12

    8. COPYRIGHTS & TRADEMARKS

    8.1 Copyrights

    Under the copyright laws, this publication may not be reproduced or transmitted in any form,electronic or mechanical, including photocopying, recording, storing in an information

    retrieval system, or translating, in whole or in part, without the prior written consent ofAREVA T&D EAI.

    8.2 Trademarks

    PACiS, PACiS SCE, PACiS ES, PACiS CMT, PACiS SMT, PACiS PS, PACiS SCE, AREVAT&D EAI, pacis.biz and pacis.com - are trademarks of AREVA T&D EAI. Product andcompany names mentioned herein are trademarks or trade names of their respectivecompanies.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    18/494

    C264/EN SA/C30 Safety & Handling

    Page 12/12 MiCOM C264/C264C

    9. WARNINGS REGARDING USE OF AREVA T&D EAI PRODUCTS

    AREVA T&D EAI products are not designed with components and testing for a level ofreliability suitable for use in connection with surgical implants or as critical components inany life support systems whose failure to perform can reasonably be expected to causesignificant injuries to a human.

    In any application, including the above reliability of operation of the software products can beimpaired by adverse factors, including - but not limited - to fluctuations in electrical powersupply, computer hardware malfunctions, computer operating system, software fitness,fitness of compilers and development software used to develop an application, installationerrors, software and hardware compatibility problems, malfunctions or failures of electronicmonitoring or control devices, transient failures of electronic systems (hardware and/orsoftware), unanticipated uses or misuses, or errors from the user or applications designer(adverse factors such as these are collectively termed "System failures").

    Any application where a system failure would create a risk of harm to property or persons(including the risk of bodily injuries and death) should not be reliant solely upon one form ofelectronic system due to the risk of system failure to avoid damage, injury or death, the user

    or application designer must take reasonably steps to protect against system failure,including - but not limited - to back-up or shut-down mechanisms, not because end-usersystem is customised and differs from AREVA T&D EAI testing platforms but also a user orapplication designer may use AREVA T&D EAI products in combination with other products.These actions cannot be evaluated or contemplated by AREVA T&D EAI; Thus, the user orapplication designer is ultimately responsible for verifying and validating the suitability ofAREVA T&D EAI products whenever they are incorporated in a system or application, evenwithout limitation of the appropriate design, process and safety levels of such system orapplication.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    19/494

    Introduction C264/EN IT/C30MiCOM C264/C264C

    INTRODUCTION

  • 5/20/2018 Manual Areva c264 en t c30 Global

    20/494

  • 5/20/2018 Manual Areva c264 en t c30 Global

    21/494

    Introduction C264/EN IT/C30

    MiCOM C264/C264C Page 1/8

    CONTENT

    1. INTRODUCTION TO MiCOM 3

    2. INTRODUCTION TO MiCOM GUIDES 4

    2.1 Chapters description 4

    2.1.1 Chapter Safety (SA) 4

    2.1.2 Chapter Introduction (IT) 4

    2.1.3 Chapter Technical Data (TD) 4

    2.1.4 Chapter Functional Description (FT) 4

    2.1.5 Chapter Hardware Description (HW) 4

    2.1.6

    Chapter Connection diagrams (CO) 4

    2.1.7 Chapter HMI, Local control and user interface (HI) 4

    2.1.8 Chapter Installation (IN) 4

    2.1.9 Chapter Settings (ST) 4

    2.1.10 Chapter Communications (CT) 5

    2.1.11 Chapter Commissioning (CM) 5

    2.1.12 Chapter Record Sheet (RS) 5

    2.1.13 Chapter Maintenance, Fault finding, Repairs (MF) 5

    2.1.14 Chapter Lexical (LX) 5

    2.1.15

    Chapter Applications (AP) 5

    2.2 Operation guide 5

    2.3 Technical guide 5

    3. INTRODUCTION TO MiCOM APPLICATIONS 6

    3.1 MiCOM Computers 6

    3.2 Applications and Scope 6

  • 5/20/2018 Manual Areva c264 en t c30 Global

    22/494

    C264/EN IT/C30 Introduction

    Page 2/8 MiCOM C264/C264C

    BLANK PAGE

  • 5/20/2018 Manual Areva c264 en t c30 Global

    23/494

    Introduction C264/EN IT/C30

    MiCOM C264/C264C Page 3/8

    1. INTRODUCTION TO MiCOM

    MiCOM is a comprehensive solution capable of meeting all electricity supply requirements. Itcomprises a range of components, systems and services from AREVA T&D EnergyAutomation & Information.

    Central to the MiCOM concept is flexibility.

    MiCOM provides the ability to define an application solution and, through extensivecommunication capabilities, to integrate it with your power supply control system.

    The components within MiCOM are:

    P range protection relays;

    C range control products;

    M range measurement products for accurate metering and monitoring;

    S range versatile PC support and substation control packages.

    MiCOM products include extensive facilities for recording information on the state andbehaviour of the power system using disturbance and fault records. They can also providemeasurements of the system at regular intervals to a control centre enabling remotemonitoring and control to take place.

    The MiCOM range will continue to be expanded. The general features of MiCOM will also beenhanced, as we are able to adopt new technology solutions.

    For up-to-date information on any MiCOM product, visit our website: www.areva-td.com

  • 5/20/2018 Manual Areva c264 en t c30 Global

    24/494

    C264/EN IT/C30 Introduction

    Page 4/8 MiCOM C264/C264C

    2. INTRODUCTION TO MiCOM GUIDES

    The guides provide a functional and technical description of the MiCOM C264/C264Ccomputers and a comprehensive set of instructions for the computers use and application.

    MiCOM guides is divided into two volumes, as follows:

    Operation Guide: includes information on the application of the computers and a technicaldescription of its features. It is mainly intended for protection & control engineers concernedwith the selection and application of the computers for the Control, Monitoring, Measurementand Automation of electrical power processes.

    Technical Guide: contains information on the installation and commissioning of thecomputer, and also a section on fault finding. This volume is intended for site engineers whoare responsible for the installation, commissioning and maintenance of the MiCOMC264/C264C computer.

    2.1 Chapters description

    2.1.1 Chapter Safety (SA)

    This chapter contains the safety instructions, handling and reception of electronic equipment,packing and unpacking parts, Copyrights and Trademarks.

    Chapters on product definition and characteristics

    2.1.2 Chapter Introduction (IT)

    This is this document containing the description of each chapter of the MiCOM computerguides. It is a brief introduction to MiCOM computer capabilities.

    2.1.3 Chapter Technical Data (TD)

    This chapter contains the technical data including, accuracy limits, recommended operatingconditions, ratings and performance data.

    It also describes environment specification, compliance with technical standards.

    2.1.4 Chapter Functional Description (FT)

    This chapter contains a description of the product. It describes functions of the MiCOMcomputer.

    2.1.5 Chapter Hardware Description (HW)

    This chapter contains the hardware product description (product identification, case,electronic boards, operator interface, etc.).

    2.1.6 Chapter Connection diagrams (CO)

    This chapter contains the external wiring connections to the C264/C264C computers.

    2.1.7 Chapter HMI, Local control and user interface (HI)

    This chapter contains the operator interface description, Menu tree organisation andnavigation, LEDs description, Setting/configuration software.

    Set of chapter upon Computer installation

    2.1.8 Chapter Installation (IN)

    This chapter contains the installation procedures.

    2.1.9 Chapter Settings (ST)

    This chapter contains the list of the setting with default values and range.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    25/494

    Introduction C264/EN IT/C30

    MiCOM C264/C264C Page 5/8

    2.1.10 Chapter Communications (CT)

    This chapter provides the companion standard of all supported protocols toward SCADA(Telecontrol BUS) and IED on LBUS. This is the list of protocol function that computer use inthis communication.

    User minimal actions

    2.1.11 Chapter Commissioning (CM)

    This chapter contains instructions on how to commission the computer, comprising checkson the settings and functionality of the computer.

    2.1.12 Chapter Record Sheet (RS)

    This chapter contains record sheet to follow the maintenance of the computer.

    2.1.13 Chapter Maintenance, Fault finding, Repairs (MF)

    This chapter advises on how to recognise failure modes, fault codes and describes therecommended actions to repair.

    2.1.14 Chapter Lexical (LX)

    This chapter contains lexical description of acronyms and definitions.

    2.1.15 Chapter Applications (AP)

    Comprehensive and detailed description of the features of the MiCOM C264/264C includingboth the computer elements and the other functions such as transducerless (CT/VT)measurements, events and disturbance recording, interlocking and programmable schemelogic. This chapter includes a description of common power system applications of theMiCOM C264/C264C computer, practical examples of how to do some basic functions,suitable settings, some typical worked examples and how to apply the settings to thecomputer.

    2.2 Operation guide

    This binder contains the following chapters:

    SA, IT, TD, FT, HW, CO, HI, AP, LX.

    2.3 Technical guide

    This binder contains the following chapters:

    SA, IT, TD, FT, HW, CO, IN, ST, CT, CM, RS, MF, LX.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    26/494

    C264/EN IT/C30 Introduction

    Page 6/8 MiCOM C264/C264C

    3. INTRODUCTION TO MiCOM APPLICATIONS

    AREVA philosophy is to provide a range of computers, gateways and IEDs products. Each ofthese products can be used independently, or can be integrated to form a PACiS system, aDigital Control System (DCS) or a SCADA system.

    3.1 MiCOM Computers

    Driven by the requirements around the world for advanced applications in SCADA, DigitalControl Systems, Automation, control and monitoring, AREVA has designed and developeda complete range of computer products, MiCOM C264 specifically for the power processenvironment and electric utility industry. It allows building a personalised solution for Control,Monitoring, Measurement and Automation of electrical processes.

    MiCOM C264/C264C computers range are designed to address the needs of a wide rangeof installations, from small to large and customer applications. Emphasis has been placed onstrong compliance to standards, scalability, modularity and openness architecture. Thesefacilitate use in a range of applications from the most basic to the most demanding. Theyalso ensure interoperability with existing components and, by providing building computers,

    PLC or IEDs approach, provide a comprehensive upgrade path, which allows PACiScapabilities to track customer requirements.

    Key features are that this computer family is based on a Ethernet client/server architecture,its a modular computer that offers a large variety of applications such as Bay Computer,Remote Terminal Unit and Programmable Logic Controller.

    Phase in time, dedicated computer available for each application will be purposed.

    3.2 Applications and Scope

    The MiCOM C264/C264C modular bay controller, RTU or PLC is used to control and monitorswitchbays. The information capacity of the MiCOM C264/C264C is designed for controllingoperated switchgear units equipped with electrical check-back signalling located in medium-

    voltage or high-voltage substations.External auxiliary devices are largely obviated by the integration of binary inputs and poweroutputs that are independent of auxiliary voltages, by the direct connection option for currentand voltage transformers, and by the comprehensive interlocking capability.

    This simplifies handling of bay protection and control technology from planning to stationcommissioning. During operation, the user-friendly interface makes it easy to set the unit andallows safe operation of the substation by preventing non-permissible switching operations.

    Continuous self-monitoring reduces maintenance costs for protection and control systems.

    A built-in liquid crystal display (optional front face with LCD) shows not only switchgearsettings but also measured data and monitoring signals or indications.

    The bay is controlled interactively by using the control keys and the display.

    Adjustment to the quantity of information required is made via the PACiS SystemConfigurator Editor (PACiS SCE).

    The MiCOM C264/C264C can be connected to a higher control level, local control level orlower levels by way of a built-in communications interface.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    27/494

    Introduction C264/EN IT/C30

    MiCOM C264/C264C Page 7/8

    C0001ENc

    Fast Ethernet

    IEC 61850

    Master clock(GPS)

    I/Os

    WEB access

    COMMON BAY

    MV FEEDER BAYS

    HV FEEDER BAY

    MV FEEDER BAYS

    C264CSCADA Interface

    DNP3 & IEC 60870-5-101& IEC 60870-5-104

    Cubicle/Switchboardintegration

    C264

    C264

    C264C

    OperatorInterface

    Main protection

    EHV FEEDER BAY

    I/Os

    TRANSFORMER BAY

    FIGURE 1 : TYPICAL USE OF A MiCOM C264 BAY CONTROLLER

    Remote

    HMI

    PSTN or

    dedicated

    line

    P3,BUS,0-5-103,

    I 870-5-101

    PLC

    M720

    Px20

    Px30

    BC

    C0002ENb

    Px30

    Px40

    I/Os

    I/Os

    SCADA Interface

    DNP3 & IEC 60870-5-101

    & IEC 60870-5-104

    FIGURE 2 : TYPICAL USE OF A MiCOM C264 RTU APPLICATION

    The figures show some typical cases that can be mixed to face specific constraint. Twoexamples can illustrate this case:

    The system application on figure 1 uses several C264 with several communicationlinks to SCADA (one per voltage level for example).

    RTU application can use several C264 linked together on SBUS Ethernet. One of theC264 RTUs is in charge of the concentration of data and of the communication withthe remote SCADA.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    28/494

    C264/EN IT/C30 Introduction

    Page 8/8 MiCOM C264/C264C

    BLANK PAGE

  • 5/20/2018 Manual Areva c264 en t c30 Global

    29/494

    Technical Data C264/EN TD/C30MiCOM C264/C264C

    TECHNICAL DATA

  • 5/20/2018 Manual Areva c264 en t c30 Global

    30/494

  • 5/20/2018 Manual Areva c264 en t c30 Global

    31/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 1/22

    CONTENT

    1. SCOPE OF THE DOCUMENT 3

    2. CONFORMITY 4

    3. GENERAL DATA 5

    3.1 Design 5

    3.2 Installation Position 5

    3.3 Degree of Protection 5

    3.4 Weight 5

    3.5 Dimensions and Connections 5

    3.6 Terminals 5

    3.7 Creepage Distances and Clearances 6

    4. RATINGS 7

    4.1 Auxiliary Voltage 7

    4.2 Digital inputs 7

    4.2.1 DIU200 7

    4.2.2 DIU210 8

    4.2.3

    CCU200 9

    4.3 Digital outputs 10

    4.3.1 DOU200 10

    4.3.2 CCU200 11

    4.3.3 BIU241 11

    4.4 Analogue inputs 12

    4.4.1 AIU201 12

    4.4.2 AIU210 13

    4.4.3 AIU211 13

    4.5

    CT/VT inputs 14

    4.5.1 TMU200/TMU220 - Currents 14

    4.5.2 TMU200/TMU220 Voltages 14

    4.5.3 TMU200/TMU220 - A/D converter 14

    5. BURDENS 15

    5.1 Auxiliary Voltage 15

    5.2 Power supply 15

    5.3

    CPU boards 15

    5.4 Digital inputs 15

    5.4.1 DIU200 15

    5.4.2 DIU210 15

    5.4.3 CCU200 16

  • 5/20/2018 Manual Areva c264 en t c30 Global

    32/494

    C264/EN TD/C30 Technical Data

    Page 2/22 MiCOM C264/C264C

    5.5 Digital outputs 16

    5.5.1 DOU200 16

    5.5.2 CCU200 16

    5.6 Analogue inputs 16

    5.7

    Ethernet Switches 16

    5.8 CT/VT inputs 17

    5.9 Front panels 17

    6. ACCURACY 18

    6.1 Reference Conditions 18

    6.2 Measurement Accuracy 18

    7.

    TYPE TESTS 19

    7.1

    Dielectric Withstand 19

    7.2 Mechanical Test 19

    7.3 Atmospheric Test 20

    7.4 DC Auxiliary Supply Test 20

    7.5 AC Auxiliary Supply Test 21

    7.6 EMC 21

  • 5/20/2018 Manual Areva c264 en t c30 Global

    33/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 3/22

    1. SCOPE OF THE DOCUMENT

    This document is a chapter of MiCOM C264 documentation binders, describing theTechnical data of this computer.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    34/494

    C264/EN TD/C30 Technical Data

    Page 4/22 MiCOM C264/C264C

    2. CONFORMITY

    (Per Article 10 of EC Directive 73/23/EEC).

    The product designated MiCOM C264/C264C computer has been designed andmanufactured in conformance with the standard IEC 60255-27:2005 and is compliant with

    the European Commission Low Voltage Directive 73/23/EEC.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    35/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 5/22

    3. GENERAL DATA

    3.1 Design

    Surface-mounted case suitable for wall installation or flush-mounted case for 19 cabinetsand for control panels.

    3.2 Installation Position

    Vertical 15

    3.3 Degree of Protection

    Per DIN VDE 0470 and EN 60255-27:2006 or IEC 60255-27:2005.

    IP52 for the front panel with LCD or Leds.

    IP10 for the blind front panel (GHU220,GHU221).

    IP50 for the body case of MiCOM C264C.

    IP20 for the rack of MiCOM C264.

    IP20 for rear panels of C264/C264C, except reduced to IP10 when the black MiDOS 28 wayterminal block is mounted (for TMU200 ,TMU210 and TMU220 boards).

    3.4 Weight

    Case 40 TE: approx. 4 kg

    Case 80 TE: approx. 8 kg

    3.5 Dimensions and Connections

    See dimensional drawings (Hardware description section C264_EN_HW) and terminalconnection diagrams (C264_EN_CO).

    3.6 Terminals

    PC Interface:

    DIN 41652 connector, type female D-Sub, 9-pin on the front panel.

    A direct wired cable is required.

    Ethernet LAN (in the rear panel through the CPU260 board):

    RJ-45 female connector, 8-pin for the 10/100Base-T self-negotiation.

    ST female connector for the 100Base-F.

    IRIG-B Input (optional, in the rear panel through the CPU260 board):

    BNC plug.

    Conventional communication links:

    M3 threaded terminal ends, self-centring with wire protection for conductor cross sectionsfrom 0.2 to 2.5 mm for BIU241 board.

    DIN 41652 connector; type D-Sub, 9-pin on the CPU260 board in the rear panel.

    Optical fibres trough ECU200 (external RS232/optical converter): optical plastic fibreconnection per IEC 874-2 or DIN 47258 or ST glass fibre optic connection (ST is aregistered trademark of AT&T Lightguide Cable Connectors).

    Inputs /Outputs or power supply modules:

    M3 threaded terminal ends, self-centring with wire protection for conductor cross sectionsfrom 0.2 to 2.5 mm for DIU200, DIU210, DIU220, DOU200, CCU200, AIU201, AIU210,AIU211 and BIU241 boards.

    The I/O boards and BIU241 are equipped with a 24-way 5.08 mm pitch male connector.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    36/494

    C264/EN TD/C30 Technical Data

    Page 6/22 MiCOM C264/C264C

    Current-measuring and Voltage-measuring inputs:

    M5 threaded terminal ends, self-centring with wire protection for conductor cross sectionsbetween 2.5 and 4 mm for TMU200 Transducerless (4CT+4VT) board.

    The TMU200 (4CT+4VT) board is equipped with a MiCOM: ASSEMBLY CONNECTEURBLOCKL GJ104 connector.

    3.7 Creepage Distances and Clearances

    Per IEC 60255-27:2005 and IEC 664-1:1992.

    Pollution degree 2, working voltage 250 V.

    Overvoltage category III, impulse test voltage 5 kV.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    37/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 7/22

    4. RATINGS

    4.1 Auxiliary Voltage

    MiCOM C264/C264C computers are available in four auxiliary voltage versions, specified inthe table below:

    Version Nominal ranges Operative DC range Operative AC range

    A01 24 VDC

    19.2 28.8 V -

    A02 48 to 60 VDC

    38.4 72 V -

    A03 110 to 125 VDC

    88 150 V -

    A04 220 VDC

    and 230 VAC

    176 264 V 176 264 V

    The nominal frequency (Fn) for the AC auxiliary voltage is dual rated at 50/60Hz, the operaterange is 45Hz to 65Hz.

    The main characteristics of the BIU241 board are: Power supply: 40 W

    Nominal output voltage: + 5V

    Supply monitoring

    Power loss withstands capacity: 50 ms

    Protection against polarity reversal

    Insulation resistance: >100 M( CM) at 500 VDC

    Dielectric withstand: 2 kV (CM) 50 Hz for 1minute

    4.2 Digital inputs

    4.2.1 DIU200

    The DIU200 board is available in four nominal voltage versions that characteristics arespecified in the table below.

    The DIU200 board has 16 digital inputs.

    Version Nominal voltage (+/-20%) Triggering threshold (VDC

    )

    A01 24 VDC

    if V >10.1 VDC

    Input status is setif V < 5 V

    DCInput status is reset

    A02 48 to 60 VDC if V >17.4 VDCInput status is setif V < 13.5 V

    DCInput status is reset

    A03 110 to 125 VDC

    if V > 50 VDC

    Input status is setif V< 34.4 V

    DCInput status is reset

    A04 220 VDC

    if V > 108 VDC

    Input status is setif V< 63 V

    DCInput status is reset

  • 5/20/2018 Manual Areva c264 en t c30 Global

    38/494

    C264/EN TD/C30 Technical Data

    Page 8/22 MiCOM C264/C264C

    The DIU200 board is designed to allow 2 inputs serially connected. This answers to thefollowing need:

    C0124ENa

    C264

    IN1 IN2

    0 VDC

    Un

    R

    If R is open then IN1 and IN2 are set.

    If R is closed then IN1 is set, IN2 is reset.

    With this scheme, when IN1 is reset, this means that there is a problem into the externalwiring.

    The input current at nominal voltage is detailed in chapter 5.4.

    There are at maximum 15 DIU boards (including DIU200 and DIU210) inside a C264 rack.

    4.2.2 DIU210

    The DIU210 board works for all voltages between 48 VDC and 220 VDC (+/- 20%).

    The DIU210 board has 16 digital inputs.

    Whichever voltage, the triggering threshold is 19VDC

    The maximum number of DIU210 board in one C264 rack depends on the rack type and onthe voltage level of inputs.

    Please refer to the following table:

    MaximumDIU210 boards in 40TE racks

    MaximumDIU210 boards in 80TE racks

    24V 2 8

    48V 6 15

    110-125V 3 10

    220V 1 5

  • 5/20/2018 Manual Areva c264 en t c30 Global

    39/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 9/22

    The DIU210 board is designed to allow 2 inputs serially connected. This answers to thefollowing need:

    C0124ENa

    C264

    IN1 IN2

    0 VDC

    Un

    R

    If R is open then IN1 and IN2 are set.

    If R is closed then IN1 is set, IN2 is reset.

    With this scheme, when IN1 is reset, this means that there is a problem into the externalwiring.

    The input current at nominal voltage is detailed in chapter 5.4.

    There are at maximum 15 DIU boards (including DIU200 and DIU210) inside a C264 rack.

    the voltage level of inputs.

    4.2.3 CCU200

    For versions A1 to A4 of the CCU200 board the characteristics of the eight inputs are thesame as the DIU200 board.

    For version A7 of the CCU board the characteristics of the eight inputs are:

    nominal voltage ( +/- 20%): 110-125 Vcc with

    triggering threshold: if Vinput> 86 VDC input status is set

    triggering threshold: if Vinput

    < 67 VDC

    input status is reset

    Maximum number of CCU200 boards to be installed in the C264 racks:

    15 in the C264 racks (80TE) not equiped with a TMUxxx board

    14 in the C264 racks(80TE) equiped with a TMUxxx board (CCU is not to be installedin Slot P)

    6 in the C264C racks (40TE) not equiped with a TMUxxx board

    3 in the C264C racks (40TE) equiped with a TMUxxx board (CCU is not to be installedin slot F)

  • 5/20/2018 Manual Areva c264 en t c30 Global

    40/494

    C264/EN TD/C30 Technical Data

    Page 10/22 MiCOM C264/C264C

    4.3 Digital outputs

    4.3.1 DOU200

    The characteristics of the Output Relay Contacts of the DOU200 board are specified in thetable below:

    Features Values

    Nominal operating voltage range 24V to 250 VDC

    / 230 VAC

    Make 2,5A

    Carry 2,5A continuous

    30 A for 500 ms or 100 A for 30 ms

    Break DC: 50 W resistive, 30 W inductive (L/R = 40 ms)

    AC: 1250 VA resistive, 1250 VA inductive (cos= 0,7)

    In these conditions, the contact resistance is still lower

    than 250 mfor 10000 operations

    Operating time Break < 7 ms

    8 simple pole contacts Normally open

    2 double pole contacts 1 Normally open +1 Normally close

    Isolation: 2 kV (CM) 50 Hz-for 1 min.

    The board is designed and monitored to avoid inadvertent controls.

    There are at maximum 15 DOU200 boards inside a C264 rack.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    41/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 11/22

    4.3.2 CCU200

    The characteristics of the 4 Output Relay Contacts of the CCU200 board are specified in thetable below:

    In the table bellow, the Break characteristic are indicated for two application cases:

    - each of the output contact is used separately

    - the two output contacts of each relay are wired in serial. The relays break characteristicsare optimal in these conditions.

    Features Values

    Operating voltage 24 to 250 VDC

    / 230 VAC

    Make 5A

    Carry 5A continuous

    30 A for 500 ms or 250 A for 30 ms

    Break (output contact usedseparately) DC: 50 W resistive, 30 W inductive (L/R = 40 ms)AC: 1250 VA resistive, 1250 VA inductive (cos= 0,7)

    In these conditions, the contact resistance is still lower

    than 250 mfor 10000 operations

    Break (Output contacts wired inserial)

    DC: 80 W resistive for current lower than 1A,100W resistive for current upper than 1A,30 W inductive (L/R = 40 ms)

    AC: 1250 VA resistive, 1250 VA inductive

    (cos= 0,7)

    In these conditions, the contact resistance is still lower

    than 250 mfor 10000 operations

    Operating time Break < 7 ms

    Isolation: 2 kV (CM) 50 Hz for 1 min.

    The board is designed and monitored to avoid inadvertent controls.

    There are at maximum 15 CCU200 boards inside a C264 rack.

    4.3.3 BIU241

    The characteristics of the Watchdog Relay Contacts of the BIU241 board are the same asthe contacts NO+NC contacts of the DOU200 board.

    The characteristics of the two output relays used for C264 redundancy are the same as thesingle pole one on the DOU200 board.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    42/494

    C264/EN TD/C30 Technical Data

    Page 12/22 MiCOM C264/C264C

    4.4 Analogue inputs

    4.4.1 AIU201

    The AIU201 board provides 4 independent analogue inputs. Each AI can be configured involtage or current range individually as specified in the table below:

    Type Ranges

    Current input range 1mA

    5 mA

    10 mA

    20 mA

    4-20 mA

    Voltage input range 1,25V

    2,5V

    5 V

    10V

    Sampling period 100 ms

    Accuracy 0,1% full scale at 25C

    AD conversion 16 bits (15bits+sign)

    Common mode rejection ratio (CMMR) > 100dB

    Serial mode rejection ratio (SMMR) > 40dB

    gains range (user-selectable) 1, 2, 4, 10

    Input impedance for voltage inputs 11 K

    Input impedance for current inputs 75

    Temperature derive: up to 30ppm/C.

    The ranges are defined during the configuration phase.

    The current/voltage selection is done by choosing the input number of the connector.

    There are at maximum 6 AIU boards (including AIU201 and AIU210) inside a C264 rack.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    43/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 13/22

    4.4.2 AIU210

    The AIU210 board provides 8 analogue inputs (1 common point for two inputs). Each AI canbe configured in the current range as specified in the table below:

    Type Ranges

    Current input range 1mA

    5 mA

    10 mA

    20 mA

    4-20 mA

    Sampling period 100 ms

    Accuracy 0,1% full scale at 25C

    AD conversion 16 bits (15 bits+sign)

    Common mode rejection ratio (CMMR) > 100dBSerial mode rejection ratio (SMMR) > 40dB

    gains range (user-selectable) 1, 2, 4, 10

    Input impedance for current inputs 75

    Temperature derive: up to 30ppm/C.

    The ranges are configured during the configuration phase.

    The current selection is done by choosing the input number of the connector.

    A maximum of 6 AIU boards (including AIU201, AIU210 and AIU211) can be installed insidea C264 rack.

    4.4.3 AIU211

    The AIU211 board provides 8 isolated analogue inputs. Each AI can be configured in thecurrent range as specified in the table below:

    Type Ranges

    Current input range 1mA

    5 mA

    10 mA

    20 mA

    Sampling period 100 ms

    Accuracy 0,1% full scale at 25C

    AD conversion 16 bits (15 bits+sign)

    Common mode rejection ratio (CMMR) > 100dB

    gains range (user-selectable) 1, 2, 4, 10

    Input impedance for current inputs 75

    Temperature derive: up to 30ppm/C.

    The ranges are configured during the configuration phase.

    The current selection is done by choosing the input number of the connector.

    A maximum of 6 AIU boards (including AIU201, AIU210 and AIU211) can be installed insidea C264 rack.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    44/494

    C264/EN TD/C30 Technical Data

    Page 14/22 MiCOM C264/C264C

    4.5 CT/VT inputs

    The TMU200 board provides 4 Current Transformer (CT) inputs and 4 Voltage Transformer(VT) Inputs.

    The TMU220 board provides 4 Current Transformer (CT) inputs and 5 Voltage Transformer(VT) Inputs.

    4.5.1 TMU200/TMU220 - Currents

    There are two available nominal currents with two different allocations on the terminal block.

    The four measurement Current Transformers (4 CT) inputs have the followingcharacteristics:

    Operating rangeFeatures

    1 A 5 A

    Nominal AC current (IN) 1 A

    eff 5 A

    eff

    Minimum measurable current with same

    accuracy

    0.2 Aeff 0.2 A

    eff

    Maximum measurable current 4 Aeff 20 A

    eff

    Frequency 50 or 60 Hz 10% 50 or 60 Hz 10%

    CT load rating:

    WithstandDuration

    1 A 5 A

    3 second (not measurable, without destruction) 6 Aeff 30 A

    eff

    1 second (not measurable, without destruction) 20 Aeff 100 A

    eff

    4.5.2 TMU200/TMU220 Voltages

    The measurement Voltage Transformers (VT) inputs have the following characteristics:

    Features Operating range

    Nominal AC voltage (VN) range 57.73 V

    effto 500 V

    eff.

    Minimum measurable voltage 7 Veff

    Maximum measurable voltage 577 Veff

    Frequency operating range 50 or 60 Hz 10%

    VT load rating:

    Duration Withstand

    10 second without destruction 880 Veff

    4.5.3 TMU200/TMU220 - A/D converter

    The A/D converter of the TMU200/TMU220 boards has the following characteristics:

    Features Values

    Width 16 bits

    Conversion period < 30 s

    Scanning period 64 samples/period

    Linearity error 2 LSB

    SINAD ratio up to 1kHz 0db

    Low passed filter at 1khz -40db/decade

  • 5/20/2018 Manual Areva c264 en t c30 Global

    45/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 15/22

    5. BURDENS

    5.1 Auxiliary Voltage

    The MiCOM C264/C264C computer burdens are specified in the table below:

    Version Nominal Maximum

    C264C 15W 22W

    C264 20W 40W

    5.2 Power supply

    The BIU241 board burden on the internal 5V bus is 1,25W. This takes into accountwatchdog, redundancy relays and communication ports.

    The efficiency of the power supply is 78%.

    5.3 CPU boards

    The CPU260 board ( also named CPU type 2 or CPU2) burden on the internal 5V and 12Vbus is 3,3W.

    The CPU270 board ( also named CPU type 3 or CPU3) burden on the internal 12V bus is2,7W.

    5.4 Digital inputs

    5.4.1 DIU200

    The DIU200 inputs burdens are specified in the table below:

    Version Nominal voltage Current at Un (mA)

    A01 24 VDC 3.5

    A02 48 to 60 VDC

    5 for 48 VDC

    6.8 for 60 V

    DC

    A03 110 to 125 VDC

    2.5 for 110 VDC

    3 for 125 V

    DC

    A04 220 VDC

    2

    The DIU200 board burden on the internal 5V bus is 75mW

    5.4.2 DIU210

    The DIU210 inputs burdens are specified in the table below:

    Nominal voltage Current at Un (mA)

    24 VDC

    >25

    48 to 60 VDC

    3.8

    110 to 125 VDC

    4

    220 VDC

    4.1

    The DIU210 board burden on the internal 5V bus is 75mW.

    Power consumption per input:

    Un = 24VDC to 110V DC: 0,5W 30% per inputUn > 110VDC: 5mA 30%

    From 48Vdc to 220Vdc voltage, a high current consumption is created on binary inputsduring a short period and circulates through external binary contacts to clean them. See thepeak current response curve.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    46/494

    C264/EN TD/C30 Technical Data

    Page 16/22 MiCOM C264/C264C

    WARNING: FOR THE 24V VOLTAGE, THERE IS NO SHORT PEAK CURRENT

    BECAUSE OF THE PERMANENT HIGH CONSUMPTION ON INPUTS>25mA.

    The current peak response curve.

    C0159ENaTension (V)

    Current(mA)

    35

    30

    25

    20

    15

    10

    5

    0

    0 50 100 150 200 250 300

    5.4.3 CCU200

    The CCU200 inputs consumption is specified in the table below:

    Version Nominal voltage Current at Un (mA)

    A01 24 VDC

    3.5

    A02 48 to 60 VDC

    5 for 48 VDC

    6.8 for 60 V

    DC

    A03 110 to 125 VDC

    2.5 for 110 VDC

    3 for 125 V

    DC

    A04 220 VDC

    2

    A07 110 to 125 VDC

    3.4 for 110VDC

    5.4 for 132VDC

    5.5 Digital outputs

    5.5.1 DOU200

    The DOU200 board burden on the internal 5V bus is 250mW plus 200mW per activatedrelay.

    5.5.2 CCU200

    The CCU200 board burden on the internal 5V bus is 400mW plus 200mW per activatedrelay.

    5.6 Analogue inputs

    The AIU201 and the AIU210 boards burden on the internal 5V bus is 1 W.

    5.7 Ethernet Switches

    The SWU20x board burden on the internal 5V bus is 3,85W with 2 optical ports.

    The SWR20x board burden on the internal 5V bus is 4 W.The SWD202/SWD204 board burden on the internal 5V bus is 4W.

  • 5/20/2018 Manual Areva c264 en t c30 Global

    47/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 17/22

    5.8 CT/VT inputs

    The TMU200/TMU220 burdens on the internal transformers are specified in the table below:

    Nominal consumption (VA)CT burden (at nominal current IN)

    TMU200 TMU220

    1A < 0.1 < 0.02

    5A < 0.5 < 0.2

    VT burden (at nominal voltage VN) Nominal consumption (VA)

    TMU200 TMU220

    Vn = 130 Veff

  • 5/20/2018 Manual Areva c264 en t c30 Global

    48/494

    C264/EN TD/C30 Technical Data

    Page 18/22 MiCOM C264/C264C

    6. ACCURACY

    For all specified accuracy, the repeatability is 2.5% unless otherwise specified.

    If no range is specified for the validity of the accuracy, then the specified accuracy shall bevalid over the full setting range.

    6.1 Reference Conditions

    Quantity Reference conditions Test tolerance

    General

    Ambient temperature 20 C 2 C

    Atmospheric pressure 86kPa to 106kPa -

    Relative humidity 45 to 75 % -

    Input energising quantity

    Current IN

    5%

    Voltage VN 5%

    Frequency 50 or 60Hz 0.5%

    Auxiliary supply 24VDC, 48VDC-60VDC,110VDC-125VDC,220VDC230VAC

    5%

    6.2 Measurement Accuracy

    The TMU200 board has the following characteristics:

    Quantity Accuracy

    Current 0.2% full scale

    Voltage 0.2% full scale

    Frequency 0.01 Hz

    Amplitude < 1%

    Phase 1

    Overall temperature coefficient 10 ppm/C

    Harmonics 15H

  • 5/20/2018 Manual Areva c264 en t c30 Global

    49/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 19/22

    7. TYPE TESTS

    7.1 Dielectric Withstand

    Type Test Name Type Test Standard Conditions

    Insulation Resistance IEC 60255-5 (2000) 100 Mat 500 Vdc (CM & DM)

    Dielectric Withstand IEC60255-5 (2000)IEEE C37.90 (1989)

    50 Hz for 1mn, 2kV (CM), 1kV (DM)

    High Voltage ImpulseTest

    IEC 60255-5 (2000) 5 kV CM & 3 kV DM

    7.2 Mechanical Test

    Type Test Name Type Test Standard Conditions

    2 falls of 5 cm (Computer not powered)Free Fall Test

    Free Fall Packaging

    Test

    IEC 60068-2-31 (1969)+ A1 (1982)

    IEC 60068-2-32 (1975)+A1 (1982) + A2(1990)

    25 falls of 50 cm (Packaging computer)

    Vibration Response Powered On

    IEC 60255-21-1 (1988) Class 2:

    Acceleration: 1g from 10 to 150Hz

    Vibration Response Not Powered On

    IEC 60255-21-1 (1988) Class 2:

    Acceleration: 2g from 10 to 500Hz

    Vibration Endurance Not Powered On

    IEC 60068-2-6 (1995) Class 2:

    Acceleration: 1g from 10 to 500Hz

    Shocks Not PoweredOn

    IEC 60255-21-2 (1988) Class 1:

    15g, 11 ms

    Shocks Powered On IEC 60255-21-2 (1988) Class 2:

    10g, 11 ms

    Bump Test NotPowered On

    IEC 60255-21-2 (1988) Class 1:

    10g, 16ms, 2000/axis

    Seismic Test PoweredOn

    IEC 60255-21-3 (1993) Class 2:

    Acceleration: 2g

    Displacement: 7.5mm upon axe H

    Acceleration: 1g

    Displacement: 3.5mm upon axe V

  • 5/20/2018 Manual Areva c264 en t c30 Global

    50/494

    C264/EN TD/C30 Technical Data

    Page 20/22 MiCOM C264/C264C

    7.3 Atmospheric Test

    Type Test Name Type Test Standard Conditions

    Damp Heat Test Operating

    IEC 60068-2-3 (1969) Test Ca:

    +40C / 10 days / 93% RH

    Cold Test - Operating IEC 60068-2-1 (1990) Test Ab: - 25c / 96 H

    Cold Test - Storage IEC60068-2-1 (1990) Test Ad:

    -40C / 96h

    Powered On at 25C (for information)

    Dry Heat Test Operating

    IEC 60068-2-2 (1974) 70c / 24 H

    Dry Heat Long Test

    Operating

    DICOT HN 46-R01-06

    (1993)

    55c / 10 days

    Dry Heat Test Storage IEC 60068-2-1 (1990) Test Bd:

    +70C / 96h

    Powered On at +70C

    Enclosure Protection IEC 60529 (1989) + A1(1999)

    Front: IP=52

    7.4 DC Auxiliary Supply Test

    Type Test Name Type Test Standard Conditions

    Inrush current (start-up) DICOT HN 46-R01-4(1993)

    T < 1.5 ms / I < 20 A

    1.5ms < T < 150 ms / I < 10 A

    T > 500 ms / I < 1.2 In

    Supply variation IEC 60255-6 (1988) Vn 20%

    Vn+30% & Vn-25% for information

    Overvoltage (peakwithstand)

    IEC 60255-6 (1988) 1.32 Vn max

    2 Vn during 10 ms (for information)

    Ramp down to zero N/A From Vn down to 0 within 1 minute

    From Vn down to 0 within 100 minutesRamp up from zero N/A From 0 up to Vn within 1 minute

    From 0 up to Vn within 100 minutes

    Supply interruption IEC 60255-11 (1979) From 2.5 ms to 1 s at 0.8 Vn

    50 ms at Vn, no malfunction

    Reverse polarity N/A Polarity for the lower potential of thesupply

    Polarity + for the lower potential of thesupply

    Ripple (frequencyfluctuations) IEC 60255-11 (1979) 12% Vn at f=100Hz or 120Hz12% Vn at f=200Hz for information

  • 5/20/2018 Manual Areva c264 en t c30 Global

    51/494

    Technical Data C264/EN TD/C30

    MiCOM C264/C264C Page 21/22

    7.5 AC Auxiliary Supply Test

    Type Test Name Type Test Standard Conditions

    Supply variations IEC 60255-6 (1988) Vn 20%

    AC Voltage dips & short

    interruptions

    EN 61000-4-11 (1994) 2ms to 20ms & 50ms to 1s

    50 ms at Vn, no malfunction

    Frequency fluctuations IEC 60255-6 (1988) 50 Hz: from 47 to 54 Hz

    60 Hz: from 57 to 63 Hz

    Voltage withstand N/A 2 Vn during 10 ms (for information)

    7.6 EMC

    Type Test Name Type Test Standard Conditions

    High FrequencyDisturbance

    IEC 60255-22-1 (1988)

    IEC 61000-4-12 (1995)

    IEEE C37.90.1 (1989)

    Class 3: 2.5kV (CM) / 1kV (DM)

    Electrostatic discharge IEC 60255-22-2 (1996)

    IEC 61000-4-2 (1995) +A1 (1998) + A2 (2001)

    Class 4:

    8kV contact / 15 kV air

    Class 3:

    10 V/m 80 to 1000 MHz

    & spot tests

    Radiated Immunity IEC 60255-22-3 (2000)

    IEC 61000-4-3 (2002) +A1 (2002)

    IEEE C37.90.2 (1987)

    35 V/m 25 to 1000 MHz

    Fast Transient Burst IEC 60255-22-4 (2002)

    IEC 61000-4-4 (1995) +A1 (2001)

    IEEE C37.90.1 (1989)

    Class 4: 4kV 2.5kHz (CM)

    Class 4: 2.5kV 2.5kHz (DM) on DI/DO

    Surge immunity IEC 61000-4-5 (1995) +A1 (2001)

    Class 4:

    4kV (CM) 2kV (DM)

    High frequencyconducted immunity

    IEC 61000-4-6 (2003) Class 3:

    10 V, 0.15 80 MHz

    Harmonics Immunity IEC 61000-4-7 (2002) 5% & 10% de H2 H17

    Power FrequencyMagnetic Field Immunity

    IEC 61000-4-8 (1993) Class 5:

    100A/m for 1mn

    1000A/m for 3s

    Pulse magnetic fieldimmunity

    IEC 61000-4-9 (1993) Class 5:

    6.4 / 16 s

    1000A/m for 3s

    Damped oscillatorymagnetic field immunity

    IEC 61000-4-10 (1993)+ A1 (2001)

    Class 5:

    100 kHz & 1 MHz 100A/m

    Power Frequency IEC 61000-4-16 (1998) CM 500 V / DM 250 V via 0.1 F

  • 5/20/2018 Manual Areva c264 en t c30 Global

    52/494

    C264/EN TD/C30 Technical Data

    Page 22/22 MiCOM C264/C264C

    Type Test Name Type Test Standard Conditions

    Conducted emission EN 55022 (1998) + A1(2000) + A2 (2003)

    Gr. I, class A: from 0.15 to 30 MHz

    Radiated emission EN 55022(1998) + A1(2000) + A2 (2003)

    Gr. I, class A: from 30 to 1000 MHz

  • 5/20/2018 Manual Areva c264 en t c30 Global

    53/494

    Functional Description C264/EN FT/C30MiCOM C264/C264C

    FUNCTIONAL DESCRIPTION

  • 5/20/2018 Manual Areva c264 en t c30 Global

    54/494

  • 5/20/2018 Manual Areva c264 en t c30 Global

    55/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 1/132

    TABLE OF CONTENTS

    1. SCOPE OF THE DOCUMENT 5

    1.1 Software features 5

    2. MiCOM C264/C264C MANAGEMENT 7

    2.1 Operating mode management 7

    2.1.1 Definitions 7

    2.1.2 Initialisation mode 7

    2.1.3 Operational mode 8

    2.1.4 Maintenance mode 9

    2.1.5 Test mode 9

    2.1.6 Faulty mode 10

    2.1.7 Halt mode 10

    2.2 Database management 11

    2.3 Time management 13

    2.3.1 External clock 14

    2.3.2 Clock message from a SCADA gateway 15

    2.3.3 System master clock 15

    2.3.4 Time set by an operator 15

    2.3.5 Local clock update 16

    2.4 Redundancy Management 18

    3. COMMUNICATIONS 20

    3.1 Telecontrol bus 20

    3.2 Legacy bus 21

    3.3 Station bus 21

    3.3.1 Exchanges 22

    3.3.2 Supported Common Data Classes 22

    3.3.3 Controls 22

    4. DIRECT PROCESS ACCESS 23

    4.1 Input check 23

    4.2 Output check 23

    4.3 Time tagging 23

    4.4 Digital input acquisition (DI) 23

    4.4.1 Acquisition 23

    4.4.2 Debouncing and filtering 244.4.3 Toggling 24

    4.5 Counters acquisition (CT) 25

    4.5.1 Single counter (SCT) 25

  • 5/20/2018 Manual Areva c264 en t c30 Global

    56/494

    C264/EN FT/C30 Functional Description

    Page 2/132 MiCOM C264/C264C

    4.5.2 Double counter (DCT) 25

    4.6 Digital measurement (DM) 26

    4.6.1 Acquisition without Read Inhibit signal 26

    4.6.2 Acquisition with Read Inhibit signal 27

    4.6.3 Encoding 28

    4.7 Analogue input acquisition (AI) 29

    4.7.1 Input ranges 29

    4.7.2 Acquisition cycle 29

    4.8 Digital outputs (DO) 29

    4.9 Digital Setpoints 30

    4.9.1 Encoding 30

    4.9.2 Read Inhibit 30

    5. DATA PROCESSING 31

    5.1 Binary Input processing 31

    5.1.1 Binary Input definition 31

    5.1.2 Processing of Single Point Status 32

    5.1.3 Processing of Double Point Status 34

    5.1.4 Processing of Multiple Point Status 38

    5.1.5 System Inputs 39

    5.1.6 IED inputs 40

    5.1.7 Group processing 405.1.8 SBMC Mode Processing 41

    5.1.9 BI sent to automatism features 41

    5.2 Measurement Input Processing 42

    5.2.1 Open circuit management 42

    5.2.2 Scaling 42

    5.2.3 Zero value suppression 43

    5.2.4 Thresholds detection 43

    5.2.5 Manual suppression 44

    5.2.6 Substitution 44

    5.2.7 Forcing an invalid measurement 44

    5.2.8 Measurement resulting states 44

    5.2.9 Transmission 45

    5.2.10 CT/VT additional processing 46

    5.2.11 Digital Measurement Processing 50

    5.3 Tap Position Indication processing 51

    5.3.1 Acquisition from Digital Inputs 51

    5.3.2 Acquisition from Analogue Inputs 51

    5.3.3 Manual suppression 51

    5.3.4 Substitution 51

    5.3.5 Forcing an invalid TPI 51

  • 5/20/2018 Manual Areva c264 en t c30 Global

    57/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 3/132

    5.3.6 TPI resulting states 52

    5.3.7 Transmission 52

    5.4 Accumulator Input Processing 52

    5.5 Energy counting 53

    6. CONTROL SEQUENCES 54

    6.1 Generic description 54

    6.1.1 Generalities 54

    6.1.2 Control sequence phase management 55

    6.1.3 Direct Execution mode 58

    6.1.4 SBO once mode 59

    6.1.5 SBO many mode 62

    6.1.6 Generic selection checks 64

    6.1.7 Selection behaviour 68

    6.1.8 Generic execution checks 69

    6.1.9 Execution behaviour 69

    6.1.10 Controls time sequencing 70

    6.2 Control of non synchronised breakers 73

    6.2.1 Non synchronised circuit breakers features 73

    6.2.2 Control sequence of non-synchronised circuit breakers 73

    6.3 Control of synchronised breakers 74

    6.3.1 Circuit breakers features 746.3.2 Circuit breakers with external synchrocheck 75

    6.3.3 Circuit breakers with internal synchrocheck 80

    6.4 Control of disconnectors 84

    6.4.1 Disconnectors features 84

    6.4.2 Control sequence of disconnectors 84

    6.5 Control of transformers 85

    6.5.1 Transformers features 85

    6.5.2 Control sequence of transformers 85

    6.6 Control of ancillary devices 88

    6.7 Control of Intelligent Electrical Devices (IED) 89

    6.7.1 Control to IEDs 89

    6.7.2 IED controls 89

    6.7.3 Digital setting point (SP) 89

    6.8 System controls 89

    6.9 Kind of control sequence 90

    6.10 Control sequences checks 90

    6.10.1 Mode Management 90

    6.10.2 IED connected 90

    6.10.3 Control mode 90

    6.10.4 Uniqueness of control 91

  • 5/20/2018 Manual Areva c264 en t c30 Global

    58/494

    C264/EN FT/C30 Functional Description

    Page 4/132 MiCOM C264/C264C

    6.10.5 Inter-control delay 91

    6.10.6 Status of the device 91

    6.10.7 Lock device 91

    6.10.8 Running Automation 91

    6.10.9 Interlocking 916.11 HV Control Sequences 91

    6.11.1 Circuit breaker 91

    6.11.2 Disconnector 91

    6.11.3 Transformer 91

    7. AUTOMATIONS 92

    7.1 Built-in Automation functions 92

    7.1.1 Synchrocheck 92

    7.1.2 Auto-Recloser (AR) 94

    7.1.3 Trip Circuit Supervision 100

    7.1.4 Automatic Voltage Regulation (AVR) 102

    7.2 Interlocking: logical equations 116

    7.2.1 Inputs 116

    7.2.2 Outputs 116

    7.2.3 Control 116

    7.2.4 Behaviour 117

    7.2.5 Limits and performance 1197.3 Slow automation: Programmable Logic Control (PLC) 120

    7.3.1 Inputs 121

    7.3.2 Outputs 121

    7.3.3 Control 121

    7.3.4 Behaviour 122

    7.3.5 Limits and performances 122

    7.4 Fast automation: Programmable Scheme Logic (PSL) 123

    8. USER INTERFACE 124

    9. RECORDS 125

    9.1 Permanent records storage 125

    9.1.1 Data storage 125

    9.1.2 Waveform Recording 125

    9.1.3 Events 127

    9.2 Non-permanent data storage 127

    9.2.1 Alarms 127

  • 5/20/2018 Manual Areva c264 en t c30 Global

    59/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 5/132

    1. SCOPE OF THE DOCUMENT

    This document is a chapter of MiCOM C264/C264C documentation binders. It is thefunctional description of this computer. The hardware description is defined in HW chapterand all connection diagrams in CO chapter. The technical data of the computer (capabilities,performances, environmental limits) are grouped in TD chapter.

    1.1 Software features

    The MiCOM C264/C264C computer belongs to the new range of modular product athardware, software and functional levels. All functionalities are fully configurable followingcustomer needs and requirements. MiCOM C264/C264C computers assume:

    Direct process interface through Digital Inputs (DI), Digital Outputs (DO), AnalogueInputs (AI), and CT/VT boards.

    Direct operator interface

    Embedded parameterised control of all common plant or device

    High communication abilities to IED, Ethernet, and RTU

    User configurable automation modules

    Events, alarms, measurement display, printing and archiving

    Enhanced inner management with databases handling, self-test controls andsynchronisation means

    Computer Kernel

    Embedded Automation(basic+AR, Synchrocheck+AVR)Configurable Automation(Fast PSL / Sequential PLC)

    TelecontrolInterface IEC 61850

    T-BUS S-BUS

    RTU, SCADA PACiS system, IEC 61850 IEDs

    HumanInterface

    (LCD)

    RTC

    Printing

    C0003ENb

    SynchronsationTime tagging

    I/O boardsLegacy Gateway

    L-Bus

    IED

    DI DO AI CT/VT

    ArchivesCT, Disturb

    SOEAlarms

    FIGURE 1: SOFTWARE FEATURES

  • 5/20/2018 Manual Areva c264 en t c30 Global

    60/494

    C264/EN FT/C30 Functional Description

    Page 6/132 MiCOM C264/C264C

    The components of the software management are:

    Inputs/Outputs board (DI, DO, AI)

    Analogue Inputs (AI, from CT/VT board - optional)

    Automatic functions (Built-in, PLC, PSL)

    Communications with Telecontrol Bus, Station Bus and Legacy Bus (see chapterCommunication)

    RTC (Real Time Clock), time management; synchronisation, time tagging (see Timemanagement chapter)

    Communication with peripherals such as:

    Local Operator Interface (LCD, front panel)

    Local Printer (local sequence of events - SOE)

  • 5/20/2018 Manual Areva c264 en t c30 Global

    61/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 7/132

    2. MiCOM C264/C264C MANAGEMENT

    2.1 Operating mode management

    2.1.1 Definitions

    The terms defined below are used in this whole section 2.

    Anomaly: an anomaly is a fault causing a downgraded behaviour of the computer.There are hardware and/or software anomalies:

    Board failure

    Loss of synchronisation

    Loss of communication

    Software fault: A software fault results of a major software error. In this case thecomputers enters the Faultymode.

    Vital harware fault: a vital hardware fault is a fault causing a software halt. This kindof fault causes the computer to stop the application software.

    CPU fault

    Power supply fault

    Bus fault

    Permanent Interruption fault

    2.1.2 Initialisation mode

    After power on or manual reset the computer enters the initialisation mode and performs

    different types of checks:

    Vital hardware tests

    Non-volatile memory test: in case of a problem the computer tries to repair this non-volatilememory. If a vital hardware test fails, the initialisation is stopped and the computer enters theHaltmode.

    Non vital hardware tests

    Non-vital hardware tests are only performed on present boards:

    Inputs and outputs boards:

    To determinate the number and the type of the present input and outputboards

    To check the presence of the previously input and output boards and to beinformed if a board is absent

    To check the good working order of the present input and output boards andto be informed if a board is out of order

    Communication boards: this test is performed within the communication protocol.

    Display (LCD, LEDs): the single test that can be done is the presence of the HMIboard.

    Peripheral devices (printer, external clock ..). Check of the presence of the devicesby use of timeouts.

    If any of these non-vital hardware tests fails the computer enters theoperational/downgradedmode depending on the type of the fault.

    Software tests (database coherency tests)

  • 5/20/2018 Manual Areva c264 en t c30 Global

    62/494

    C264/EN FT/C30 Functional Description

    Page 8/132 MiCOM C264/C264C

    These tests are performed at each restart of the computer. The checks of the databaseguarantees that the database is compatible with the hardware and the software of thecomputer and that it does not contain incoherent data of configuration. The following checksare performed:

    Check of the presence of a database

    Check of the DB/ software compatibility

    This control makes it possible to check that the software and the database arecoherent. The computer contains in its static data a version and a revision numberindicating which structure of database it is able to interpret. The database must havethe same version to be accepted.

    Check of the DB/ equipment compatibility

    This control makes it possible to check that the database is intended for theequipment on which it was downloaded. To check it, the type and the number ofequipment contained in the heading of the database are compared with the type andthe number of equipment contained in the static data of the software.

    Check of the validity of the data of the database

    This control checks that the configured inputs and outputs are present and that thenumber of objects (bays, digital inputs ) remains within acceptable limits.

    If any of these checks fails, the computer enters the Maintenancemode.

    The initialisation of the computer does not exceed one minute.

    2.1.3 Operational mode

    This mode can be divided into two sub-modes: Normal mode and Downgradedmode.

    2.1.3.1 Normal mode

    This is the nominal operating mode of the active computer. In this mode the watchdog relayis activated and all the functionalities of the computer are available. Nevertheless, detectionof an error can lead to the Downgradedmode, to the Faultymode or to the Halt mode,depending on the nature and the gravity of the failure.

    From this mode a transition to the Maintenancemode can be requested by an operator fromlocal HMI or upper level (maintenance request).

    From this mode a transition to the Testmode can be requested by an operator from localHMI or upper level (simulation request).

    In this mode, the operations that can be done on databases are the following:

    Download a standby database Swap the databases: then the computer automatically restarts

    Modify a database

    Display database information

    This mode is transmitted to local HMI and upper level (RCP).

  • 5/20/2018 Manual Areva c264 en t c30 Global

    63/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 9/132

    2.1.3.2 Downgraded mode

    This mode is entered in case of an anomaly. In this mode the general working of thecomputer is not very disturbed because it involves the degradation of only few functions. Thewatchdog relay is activated.

    The downgraded mode depends on the hardware configuration of the computer. But we can

    define the different kinds of downgraded modes that can happen:

    Operation without DO on a board

    Operation without DI on a board

    Operation without AI on a board

    Operation without communication with some relays

    Operation without communication with some station devices

    A combination of two, or more, of these previous items

    When the cause(s) of the transition into Downgraded mode disappear(s), the computerreturns to the Normalmode.

    2.1.4 Maintenance mode

    In Maintenancemode, communication on the station bus is operational in order to managethe database. This mode is displayed on local HMI (led and LCD) and on upper level.

    The watchdog relay is de-activated.

    In this mode the operator can manage the database:

    Download a database

    Swap the databases

    Modify a database

    Display database information

    From this mode a transition to the operationalmode can be requested by an operator fromlocal HMI or upper level (active request).

    2.1.5 Test mode

    In Testmode, the computer works normally but output relays are not activated. This mode isentered on operator request in order to simulate the functioning of distributed automatismssuch as interlocking. Instead of activating the output relays, the computer sends a test OKmessage to the SCP if the command is valid otherwise a test NOK message.

    NOTE: to realise the tests, the operator has to manually create the testingconditions by forcing BI or Measurements on different computers.Once the conditions are realised, he can generate a command andsee at the SCP level (HMI) if the result corresponds to the expectedone.

    This mode is displayed on local HMI (led and LCD) and on upper level.

    From this mode a transition to the operationalmode can be requested by an operator fromlocal HMI or upper level (end of simulation).

  • 5/20/2018 Manual Areva c264 en t c30 Global

    64/494

    C264/EN FT/C30 Functional Description

    Page 10/132 MiCOM C264/C264C

    2.1.6 Faulty mode

    The Faultymode is entered when a fault, that prevents the exploitation, happens. This modecan be entered from any mode described above.

    This mode is also entered when a failure is detected on DO boards and if the configuration

    allows this mode on DO faults.The only way to leave this mode is an automatic reset or a transition to the Haltmode. Eachtime the computer enters this mode, an internal counter is incremented. As long as the valueof this counter is lower than Max_Fault (parameter defined during the configuration step) theInitialisation mode is entered. The value of this counter is automatically reset when thelasted time since the last incrementation of the counter reaches the valueFault_Detection_Lasting (parameter defined during the configuration step). When the valueof this counter reaches Max_Fault the computer enters the Haltmode.

    2.1.7 Halt mode

    In this mode the computer doesnt operate anymore. The watchdog relay and all the outputsrelays are deactivated. The only way to get out of this mode is to operate a manual reset.

    The following figure summarises the different operating modes of the computer and thetransitions.

    FAULTY

    automatic reset manual reset

    HALT

    TEST

    simulation request

    end of simulation

    major hardware faultor software fault

    OPERATIONAL MAINTENANCE

    INITIALISATION

    Init OK

    hardware test OKand coherency not OK

    maintenance request

    active request

    boot

    software fault ormajor hardwraefault

    no DB

    vital hardwarefaultvital hardware fault

    major hardware fault

    Counter of faults = Max_Fault

    vital hardware fault

    C0307ENa

    vitalhardwarefault

    DB/software compatibility not OKorDB/equipment compatibility not OKordata of database not valid

    swapping of the databases

    FIGURE 2: OPERATING MODES OF THE COMPUTER

  • 5/20/2018 Manual Areva c264 en t c30 Global

    65/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 11/132

    2.2 Database management

    The MiCOM C264/C264C uses structured databases for data management. A database(DB) is a file which contains the description of the whole of the electric process, as of thewhole of the equipment which the computer is likely to dialogue with (IED, HMI ,etc.). Itcontains also some parameter settings of the software and of the transmission. Databases

    are generated and versioned by an independent equipment: the System Configuration Editor(SCE). Each database file has an associated Vdbs(System Baseline Version) A database isdownloaded into the non-volatile memory of the computer via the IEC61850 station bus withthe System Management Tool (SMT) or directly over Ethernet with the ComputerMaintenance Tool (CMT).

    The computer stores at any moment up to two DBs in its non-volatile memory. The two DBs(and these associated V

    dbs) are called thereafter DB1 and DB2 (and these associated V

    dbs1

    and Vdbs2).

    Each database (DB1 and DB2) of the computer can take one of the following states:

    Missing: the DB is not present in non-volatile memory of the computer;

    Standby: the DB was downloaded in non volatile memory of the computer; however,this version is not taken into account by the software;

    Current: the downloaded DB is taken into account by the software;

    Current Modified: the DB, currently taken into account by the software, underwent aparameter setting;

    Standby Modified: the DB underwent a parameter setting, but it is not taken anymore into account by the software.

    The following diagram represents the life cycle of the databases in the computer:

    C0308ENa

    Standby CurrentSwitching

    Standby

    Modified

    Parameter setting

    Current

    Modified

    Switching

    Downloading

    Absent

    Parameter setting

    FIGURE 3: THE DIFFERENT STATUS OF A DATABASE

    At any moment, there is only one Currentor Current Modifieddatabase. In the same way,there is only one Standbyor Standby Modifieddatabase.

    A file descriptor (DB context) stored in non-volatile memory contains the configuration of theDB present on the equipment. This file, containing the state of each of the two databases

    (DB1 and DB2) and the Vdbs (Vdbs1 and Vdbs2) of each one, makes it possible to know theconfiguration of the databases at the moment of the boot, and to start again with the currentdatabase (if it exists). DB Context is updated by the sub-functions "Download a database","Switch the databases", "Check a database", "Modify a Database".

  • 5/20/2018 Manual Areva c264 en t c30 Global

    66/494

    C264/EN FT/C30 Functional Description

    Page 12/132 MiCOM C264/C264C

    To download a database ( via Ethernet)

    The downloading of a database is usually performed with SMT tool via the station bus.

    The first downloading of a database (and its associated Vdbs) can be performed onlywhen the computer is in maintenance mode.

    The downloading of a standby database (and its associated Vdbs) can be performedwhen the computer, running with the current database, is either in operational mode orin maintenance mode.

    The sequencing is:

    To work out and transmit to the calling equipment a response to the request: therequest can be refused if another request on database is already in progress;

    To carry out the transfer of the DB file (and associated Vdbs) and to check itsintegrity (calculation of checksum and control of the database);

    In case of fault, to announce to the calling equipment the failure of the transfer;

    In case of successful transfer, to control the database compatibility;

    In case of invalid DB, to announce to the calling equipment the failure of theinstallation;

    In case of valid DB, to assign to the downloaded database (and associated Vdbs)the state standby by removing a possible standby database (and associatedVdbs) present in the computer; to signal to the calling equipment the success ofthe installation;

    To update the file descriptor (Context database) in non-volatile memory.

    To switch the databases

    This function answers to a request of DB switching coming from the station bus. Thisrequest specifies the Version of the standby DB (Vdbs) to become current. Aftera DB switch the computer automatically reboots and goes into active Mode if the DB iscoherent with the software.

    C0309ENa

    Vdbs n.m

    DB1

    Vdbs x.y

    DB2

    CURRENT STANDBY

    Vdbs x.y

    DB2

    Vdbs n.m

    DB1

    CURRENT STANDBY

    SWITCH

    MAINTENANCEMAINTENANCE

    T0 T0 + T1

    Vdbs x.y

    DB2

    Vdbs n.m

    DB1

    CURRENT STAND-BY

    OPERATIONAL

    T0 + T1

    T0 + T1

    FIGURE 4: DATABASES SWITCHING

    To check the database

    This function is carried out at each reboot. (refer to 3.2.1 Initialisation mode)

  • 5/20/2018 Manual Areva c264 en t c30 Global

    67/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 13/132

    To modify the database

    The parameter setting of database consists in modifying some values of configurationpresent in the database. A parameter setting can be carried out only on the currentdatabase (Currentor Current Modified). Following a parameter setting, file database ismodified: the new value taken by the data is memorised there. The index of parameter

    setting of the database is incremented, and the checksum of the file is recomputed.The database then takes the Current Modified state. Only certain data are settable.This is performed from the local HMI.

    To carry out a parameter setting of data

    This function treats the requests of parameter setting:

    To check the coherence of the request: known object (the object is reallypresent in the database), settable data, value of parameter setting compatiblewith the type of data conveyed (value belonging to the range of acceptablevariation),

    If the request is incoherent, to emit a negative report to the emitter of the

    request,

    To write in database file the current value of the data,

    To write in database file the date of modification of the data,

    To compute the checksum and to write it in data base file,

    To assign the state Current Modifiedto it,

    To emit a positive report with the emitting equipment of the request,

    To update the file descriptor (Context database) in non-volatile memory.

    To consult a settable data

    This function treats the requests of consultation of parameter issued from the OperatorStation:

    To check the coherence of the request: known object (the object is quite present inthe database), settable data and currentDB

    If the request is incoherent, to emit a negative response to the transmitter of therequest

    To work out the response to the transmitter of the request by giving the currentvalue of the data

    2.3 Time managementThe main purposes of the time management are:

    Synchronisation of the computer by:

    The external clock

    Station/legacy bus

    Operator

    Updating of the internal clock

    Synchronisation of other equipments via station bus

    Time synchronisation of a computer can be done by four means:

    External clock (IRIG-B signal

    Clock message from a SCADA gateway (T-Bus)

    Clock message from the system master clock (S-Bus)

    Time set by an operator

  • 5/20/2018 Manual Areva c264 en t c30 Global

    68/494

    C264/EN FT/C30 Functional Description

    Page 14/132 MiCOM C264/C264C

    Concerning these four external time references, there is a priority rule: if the external clock isoperating, modifications on the computer clock are not possible by other ways (for examplefrom SCADA gateway, system master clock or operator). In case of external clock isdisconnected or not operating, there is a priority order: clock message from a SCADAgateway or from the system master clock takes priority over operator.

    When the computer is master of legacy bus, it synchronises the IED according to thesynchronisation procedure of the protocol. The synchronisation is done just after thecomputer has been synchronised by external clock or station bus or RCP. If the computer isnot synchronised, it synchronises periodically the IED all the same.

    When the computer is synchronised all events and measurements have a time tag withsynchronised attribute. If synchronisation is lost, or has never been received attributesindicates that time tag is not synchronised.

    The time management organisation is based on the following scheme:

    C0004ENc

    External clock

    Whichsynchronises

    IECequipment

    Which synchronisesthrough station bus

    IEDs

    Which synchronisesthrough legacy bus

    Synchronisation signal

    SCADA

    Which synchronisesthrough SCADA bus

    SystemMasterClock

    Operatortime setting

    FIGURE 5: TIME MANAGEMENT

    2.3.1 External clock

    A computer gets functionality of system master clock: it is the architecture equipment whichreceives periodically, from an external IRIG-B clock reference, messages containing the dateand the hour.

    The external clock device receives the synchronisation signal through several possibleprotocols (GPS, DCF77, etc) and then sends it periodically to the dedicated IRIG-B inputof the MiCOM C264/C264C.

    The external clock transmits to the computer the hour and date that itself receives.

    In case of loss of the radio signal by the external clock two cases have to be considered:

    1. Some external clocks can synchronise the computer for 8 hours after loss of radiosignal because they have an oscillator with a very good accuracy. The external clockindicates via the protocol two informations: no radio received and loss radiosignal since more 8 hours. The computer remains synchronised until the indicator"loss radio signal since more 8 hours"is activated. Then the status of internal clock

    becomes not-synchronised.

    2. Some external clocks haven't internal accuracy circuit to back up the radio signal. Inthis case, the status of internal clock of computer becomes not-synchronisedafterconfirmation of loss radio signal(few minutes).

  • 5/20/2018 Manual Areva c264 en t c30 Global

    69/494

    Functional Description C264/EN FT/C30

    MiCOM C264/C264C Page 15/132

    If the computer is master clock for the other equipment of the substation then it sends thesynchronisation message to the other equipment even if it is not synchronised. In this same,it stays synchronised even if it loses the external clock communication. A dedicated binaryinput is associated to the external clock status.

    2.3.2 Clock message from a SCADA gateway

    SCADA clock acquisition is a SCADA gateway specification. The purpose of this part is todetail acquisition of clock message from SCADA gateway.

    SCADA clock synchronisation depends on the protocol. The synchronisation message isdirectly acquired by the MiCOM C264/C264C through the SCADA link.

    The clock message from SCADA gateway is in UTC time.

    The SCADA clock to local clock update function. This clock is transmitted after acquiredframe from the SCADA gateway has been checked and its control fields removed.

    When the acquisition of clock message from SCADA gateway is operating (depending on thepriority), the computer receives a clock synchronisation message from the SCADA. Aninterruption is related to the frame arrival and clock message from SCADA gateway can be

    acquired. The delay transmission from SCADA gateway is compensated.Whatever the protocol, clock message from SCADA gateway must contain:

    Day / month / year / hour / minutes / seconds / milliseconds

    The update of computer internal clock upon the clock message from SCADA gateway ismanaged as specified in local clock update function.

    2.3.3 System master clock

    On an IEC61850 network, time synchronisation is based on SNTP ( Simple Network TimeProtocol). In a PACiS system up to two computers can be defined as System Master Clockand so are SNTP servers. All others IEC61850 equipment are SNTP clients. In case offailure