micro grid report
TRANSCRIPT
-
7/28/2019 Micro Grid Report
1/13
Micro Grid
Page 1
1. Abstract
The legacy paradigm for electricity service in most of the electrified world today is based on
the centralized generation-transmission-distribution infrastructure that evolved under a
regulated environment. More recently, a quest for effective economic investments,
responsive markets, and sensitivity to the availability of resources, has led to various degrees
of deregulation and unbundling of services. In this context, a new paradigm is emerging
wherein electricity generation is intimately embedded with the load in micro grids.
Development and decay of the familiar macro grid is discussed. The salient features of micro
grids are examined to suggest that cohabitation of micro and macro grids is desirable, and
that overall energy efficiency can be increased, while power is delivered to loads at
appropriate levels of quality
-
7/28/2019 Micro Grid Report
2/13
Micro Grid
Page 2
2. Introduction:
Recent developments in the electric utility industry are encouraging the entry of power
generation and energy storage at the distribution level. Together, they are identified as
distributed generation units. Several new technologies are being developed and marketed for
distributed generation, with capacity ranges from a few kW to 100 MW. The distributed
generation includes micro turbines, fuel cells, photovoltaic systems, wind energy systems,
diesel engines
3. Definition of Micro grids
The Micro grid (MG) concept assumes a cluster of loads and micro sources operating as a
single controllable system that provides both power and heat to its local area. This concept
provides a new paradigm for defining the operation of distributed generation.
3.1 Micro grid Architecture:
The MG study architecture is shown in Figure 1.1. It consists of a group of radial feeders,
which could be part of a distribution system. There is a single point of connection to the
utility called point of common coupling (PCC). Feeders 1 and 2 have sensitive loads which
should be supplied during the events. The feeders also have the micro sources consisting of a
photovoltaic (PV), a wind turbine (WT), and fuel cell (FC), a micro turbine (MT), a diesel
generator (DG), and battery storage. The third feeder has only traditional loads.
The static switch (SD) is used to island feeders 1 and 2 from the utility when events happen.
The fuel input is needed only for the DG, FC, and MT as the fuel for the WT and PV comes
from nature. To serve the load demand, electrical power can be produced either directly by
PV, WT, DG, MT, or FC. The diesel oil is a fuel input to a DG, whereas natural gas is a fuel
input to fuel processor to produce hydrogen for the FC. The gas is also the input to the MT.
The use of DG, or FC or MT with other fuel types can be modeled by changing the system
parameters to reflect the change in the fuel consumption characteristics (e.g. fuel heating
values, and efficiency of the engines)
-
7/28/2019 Micro Grid Report
3/13
Micro Grid
Page 3
Each of the local generation unit has a local controller (LC). This is responsible for local
control that corresponds to a conventional controller (ex. automatic voltage regulator (AVR)
or Governor) having a network communication function to exchange information between
other LCs and the upper central controller to achieve an advanced control. The central
controller also plays an important role as a load dispatch control center in bulk power
systems, which is in charge of distributed generator operations installed in MG [5].
Furthermore, the central controller is the main interface between the upper grid and the Micro
grid. The central controller has the main responsibility for the optimization of the Micro grid
operation, or alternatively, it coordinates the actions of the local controllers to produce the
optimal outcome. MG technologies are playing an increasingly important role in the worlds
energy portfolio. They can be used to meet base load power, peaking power, backup power,
remote power, power quality, and cooling and heating needs.
3.2 Reasons for Micro grids
The conventional arrangement of a modern large power system offers a number of
advantages. Large generating units can be made efficient and operated with only a relatively
small number of personnel. The interconnected high voltage transmission network allows the
generator reserve requirement to be minimized, the most efficient generating plant to be
dispatched at any time, and bulk power to be transported large distances with limited
electrical losses. The distribution network can be designed for unidirectional flows of power
and sized to accommodate customer loads only. However, over the last few years a number
of influences have combined to lead to the increased interest in MG schemes [1] and [7]. The
policy drivers encouraging MGs are:
-
7/28/2019 Micro Grid Report
4/13
Micro Grid
Page 4
1. Reduction in gaseous emissions (mainly CO2).
2. Energy efficiency or rational use of energy.
3. Deregulation or competition policy.
4. Diversification of energy sources.
5. National and global power requirements.
Listed other reasons but with additional emphasis on commercial considerations such as:
Availability of modular generating plants. Ease of finding sites for smaller generators. Short construction times and lower capital costs of smaller plants.
4. Technologies
The key feature that makes the Micro Grid possible is the power electronics, control, and
communications capabilities that permit a Micro Grid to function as a semiautonomous
power system. The power electronics are the critical distinguishing feature of the Micro Grid,
and they are discussed in detail below. This section describes some of the other technologies
whose development will shape Micro Grids. While the more familiar reciprocating engines
will likely remain competitive in many applications for the foreseeable future, they lack
power electronics therefore minimizing their role in Micro Grids. Widespread use of fuel
cells, particularly high temperature ones most interesting for combined heat and power (CHP)
applications, remains a few years away. Among the renewable technologies, medium to largephotovoltaic systems, possibly building integrated, are a particularly promising technology,
while other renewable may also play a role. In addition to generating technologies, Micro
Grids also include storage, load control and heat recovery equipment.
4.1 Micro turbines:
Now currently in the 25-100 kW range, although larger ones are under development, may
ultimately be mass-produced at low cost. These are mechanically simple, single shaftdevices,
using high-speed (50,000-100,000 rpm) typically with airfoil bearings. They aredesigned to
combine the reliability of commercial aircraft auxiliary power units (APUs) with the lowcost of automotive turbochargers. Despite their mechanical simplicity, micro turbines rely on
power electronics to interface with loads. Example products include: Capstone's 30-kW and
60- kW systems, the former Honeywell 75-kW Parallon machine, and products from
European manufacturers Bowman and Turbec that feature CHP capabilities. Micro turbines
should also be acceptably clean running. Their primary fuel is natural gas, although they may
also burn propane or liquid fuels in some applications, which permits clean combustion,
notably with low particulates.
-
7/28/2019 Micro Grid Report
5/13
Micro Grid
Page 5
4.2 Fuel cells:
Fuel cells are also well suited for distributed generation applications. They offer high
efficiency and low emissions but are currently expensive. Phosphoric acid cells are
commercially available in the 200-kW range, and high temperature solid-oxide and molten-
carbonate cells have been demonstrated and are particularly promising for Micro Grid
application. A major development effort by automotive companies has focused on the
possibility of using on-board reforming of gasoline or other common fuels to hydrogen, to be
used in low temperature proton exchange membrane (PEM) fuel cells. Fuel cell engine
designs are attractive because they promise high efficiency without the significant polluting
emissions associated with internal combustion engines. Many other major companies are
investing in PEM fuel cells for mobile applications, and the recently announced Bush
administration Freedom CAR Initiative should accelerate development. This will accelerate
PEM development relative to other fuel cells, should lower costs, and will partially
compensate for the relatively unattractiveness of low-temperature PEMs for CHPapplications. Higher temperature PEMs are also under development.
4.3 Renewable generation:
Renewable generation could appear in Micro Grids, especially those interconnected
through power electronic devices, such PV systems or some wind turbines. Befouled micro
turbines arealso a possibility. Environmentally, fuel cells and most renewable sources are a
majorimprovement over conventional combustion engines.
5. Combined Heat and Power (CHP):
One important potential benefit of Micro Grids is an expanded opportunity to utilize the
waste heat from conversion of primary fuel to electricity. Because typically half to three-
quarters of the primary energy consumed in power generation is ultimately released
unutilized to the environment, the potential gains from using this heat productively are
significant. The gains of increased conversion efficiency are threefold. First, fuel costs will be
reduced both because individual fuel purchases will decrease and constrained overall demand
will drive down fuel prices. Second, carbon emissions will be reduced. And, third, the
environmental problem of disposing of large power plant waste heat into the environmentwill diminish. The emergence and deployment of technologies to facilitate efficient local use
of waste heat is, therefore, key for Micro Grids to emerge as a significant contributor to the
national electricity supply.
-
7/28/2019 Micro Grid Report
6/13
Micro Grid
Page 6
6. Micro Grid Structure
The Micro Grid structure assumes an aggregation of loads and micro sources operating as a
single system providing both power and heat. The majority of the micro sources must be
power electronic based to provide the required flexibility to insure controlled operation as a
single aggregated system. This control flexibility allows the Micro Grid to present itself to
the bulk power system as a single controlled unit, have plug-and-play simplicity for each
micro source, and meet the customers local needs. These needs include increased local
reliability and security.
Key issues that are part of the Micro Grid structure include the interface, control and
protection requirements for each micro source as well as Micro Grid voltage control, power
flow control, load sharing during islanding, protection, stability, and over all operation. The
ability of the Micro Grid to operate connected to the grid as well as smooth transition to and
from the island mode is another important function.
Figure illustrates the basic Micro Grid architecture. The electrical system is assumed to be
radial with three feeders A, B, and C and a collection of loads. The micro sources are
either micro turbines or fuel cells interfaced to the system through power electronics. The
Point of Common Coupling (PCC) is on the primary side of the transformer and defines the
-
7/28/2019 Micro Grid Report
7/13
Micro Grid
Page 7
separation between the grid and the Micro Grid. At this point the Micro Grid must meet the
prevailing interface requirements, such as defined in draft standard IEEE P1547.
The sources on Feeder A & B allow full exploration of situations where the micro sources are
placed away from the common feeder bus to reduce line losses, support voltage and/or use its
waste heat. Multiple micro sources on a radial feeder increase the problem of power flow
control and voltage support along the feeder when compared to all sources being placed at the
feeders common bus, but this placement is key to the plug-and-play concept. The feeders are
usually 480 volts or smaller. Each feeder has several circuit breakers and power and voltage
flow controllers. The power and voltage controller near each micro source provides the
control signals to the source, which regulates feeder power flow and bus voltage at levels
prescribed by the Energy Manager. As downstream loads change, the local micro sources
power is increased or decreased to hold the total power flow at the dispatched level
This eliminates nuisance trips of the traditional load when the Micro Grid islands to protect
critical loads. The Micro Grid assumes three critical functions that are unique to this
architecture:
Micro source Controller. The Power and Voltage Controller coupled with the micro
source provide fast response to disturbances and load changes without relying on
communications.
Energy Manager. Provides operational control through the dispatch of power and voltage
set points to each Micro source Controller. The time response of this function is measured in
minutes.
Protection. Protection of a Micro Grid in which the sources are interfaced using power
electronics requires unique solutions to provide the required functionality.
6.1 Micro source Controller:
The basic operation of the Micro Grid depends on the Micro source Controller to; regulate
power flow on a feeder as loads on that feeder change their operating points; regulate the
voltage at the interface of each micro source as loads on the system change; and insure that
each micro source rapidly picks up its share of the load when the system islands. In addition
to these control functions the ability of the system to island smoothly and to automaticallyreconnect to the bulk power system is another important operational function. Most of this set
of key functions does not exist on currently available micro sources.
Another important feature of each Micro source Controller is that it responds in milliseconds
and uses locally measured voltages and currents to control the micro source during all system
or grid events. Fast communication among micro sources is not necessary for Micro Grid
operation; each inverter is able to respond to load changes in a predetermined manner without
data from other sources or locations. This arrangement enables micro sources to plug and
play that is, micro sources can be added to the Micro Grid without changes to the control
and protection of units that are already part of the system. The basic inputs to the Micro
-
7/28/2019 Micro Grid Report
8/13
Micro Grid
Page 8
source Controller are steady-state set points for power, P, and local bus voltage, V. Section
5.0 discusses Micro source Controller in more detail.
6.2 Energy Manager
The Energy Manager provides for system operation of the Micro Grid through dispatch ofpower and voltage set points to each Micro source Controller. This function could be as
simple as having a technician enters these set points by hand at each controller to a state-of-
the-art communication system with artificial intelligence. The actual values of dispatch of P
and V depend on the operational needs of the Micro Grid. Some possible criteria are:
Insure that the necessary heat and electrical loads are met by the micro sources;
Insure that the Micro Grid satisfies operational contracts with the bulk power provider;
Minimize emissions and/or system losses;
Maximize the operational efficiency of the micro sources;
6.3 Protection
The protection coordinator must respond to both system and Micro Grid faults. For a fault on
the grid, the desired response may be to isolate the critical load portion of the Micro Grid
from the grid as rapidly as is necessary to protect these loads. This provides the same
function as an uninterruptible power supply at a potentially lower incremental cost. The speed
at which the Micro Grid isolates from the grid will depend on the specific customer loads on
the Micro Grid. In some cases, sag compensation can be used to protect critical loads without
separation from the distribution system. If a fault occurs within the islandable portion of the
Micro Grid, the desired protection is to isolates the smallest possible section of the radial
feeder to eliminate the fault.
6.4 Large Systems-Interconnected Micro Grids:
Because a Micro Grid exploits low voltage, use of waste heat, and the flexibility of power
electronics, its practical size may be limited to a few MVA (even though IEEE draft standard
P1547 specifies an upper limit of 10MVA). In a large complex, loads could be divided into
many controllable units e.g., among buildings or industrial sites. Each unit could be supplied
by one or more Micro Grids connected through a distribution system.
For example, consider a power park with a total load in excess of 50 MVA. This system
could be supplied from the transmission system through one or two substations using 13.8-kV
underground cables. Each load group (heat and/or electrical) would be a Micro Grid
connected to the 13.8-kV supply. In addition to these Micro Grids, the power park could
employ larger generation such as one- to ten-MVA gas turbines directly connected to the
13.8-kV feeder. Each Micro Grid would be a dispatch able load. The power park controlswould provide each Micro Grid with its load level (drawing power from the 13.8-kV feeder)
-
7/28/2019 Micro Grid Report
9/13
Micro Grid
Page 9
while the gas turbines Pand Q/V would be dispatched either locally or by the bulk power
producer. The advantages of this system are that the Micro Grid structure insures greater
stability and controllability, allows for a distributed command and control system, and
provides redundancy to insure greater power supply reliability for the power park.
7. Control Methods for Micro Grids:
Power electronics can provide the control and flexibility for the Micro Grid to meet its
customersas well as the grids needs. Micro Grid controls need to insure that: new micro
sources can be added to the system without modification of existing equipment, the Micro
Grid can connect to or isolate itself from the grid in a rapid and seamless fashion, reactive
and active power can be independently controlled, voltage sag and system imbalances can becorrected, and that the Micro Grid can meet the grids load dynamics requirements. Micro
source Controller techniques described below rely on the inverter interfaces found in fuel
cells, micro turbines, and storage technologies. A key element of the control design is that
communication among micro sources is unnecessary for basic Micro Grid operation. Each
Micro source Controller must be able to respond effectively to system changes without
requiring data from other sources or locations.
Micro source Control Functions
Operation of the Micro Grid assumes that the power electronic controls of current microsources are modified to provide a set of key functions, which currently do not exist. These
control functions include the ability to: regulate power flow on feeders; regulate the voltage
at the interface of each micro source; ensure that each micro source rapidly pickups up its
share of the load when the system islands. In addition to these control functions the ability of
the system to island smoothly and automatically reconnect to the bulk power system is
another important operational function.
-
7/28/2019 Micro Grid Report
10/13
Micro Grid
Page 10
Interface I nverter System
Basic Contr ol of Real and Reactive Power
There are two basic classes of micro sources: DC sources, such as fuel cells, photovoltaic
cells, and battery storage; and high-frequency AC sources such as micro turbines, which needto be rectified. In both cases, the DC voltage that is produced is converted using a voltage
source inverter. The general model for a micro source is shown in Figure 5.1. It contains
three basic elements: prime mover, DC interface, and voltage source inverter. The micro
source couples to the Micro Grid using an inductor. The voltage source inverter controls both
the magnitude and phase of its output voltage, V. The vector relationship between the inverter
voltage, V, and the local Micro Grid voltage, E, along with the inductors reactance, X,
determines the flow of real and reactive power (P &Q) from the micro source to the Micro
Grid. The P & Q magnitudes are coupled as shown in the equations below. For small
changes, P is predominantly dependent the power angle, p, and Q is dependent on the
magnitude of the inverters voltage, V. These relationships constitute a basic feedback loop
for the control of output power and bus voltage, E, through regulation of reactive power flow.
System Protection
A typical radial distribution system has been assumed in the discussions that follow; we also
assume that DER are integrated with this distribution system in accordance with IEEE draft
The changes that would be required in existing protection schemes are outlined below.
Transformer Protection:
Transformer Fault: Connecting the Micro Grid to a utility grid would not affect the abilityof the utility's differential protection scheme to detect and/or isolate a transformer fault. No
adjustments to this protection would be necessary.
Line Protection:
Ground Fault on the Feeder: DER that are connected to the faulted phase would contribute to
the fault and thus reduce the fault current seen by the AEPS. However, at the inception of the
fault, all but the lowest rated DER (on all phases) would detect the fault and separate from the
system per IEEE P1547. After the DER separate, the fault current contribution from the
AEPS would increase and feeder protection would enable, just as though DER had neverbeen connected to the feeder. The fault detection time might be prolonged because of the
-
7/28/2019 Micro Grid Report
11/13
Micro Grid
Page 11
presence of DER, but the protection scheme would not need to change. IEEE P1547 would
require DER to comply with local rules regarding reclosing coordination. A reasonable
approach for this coordination would be for the utility to require DER units that have tripped
off line to remain off line for a period of time that exceeds all disturbance and reclosing
events (e.g., five minutes). These requirements would have little impact on existing systemprotection.
Line-to-Line Fault on the Feeder: For DER connected to the faulted line, the voltage seen at
the DER terminals would, in most cases, be out of the allowable operating band specified in
P1547, so the DER would trip off line. DER operating on the unfaulted phase during a lineto-
line fault would, in most cases, also exhibit voltage outside of the allowable operating band
specified in P1547 and would thus trip off line. If the unfaulted phase voltage did not move
outside the allowable operating range, detection of the fault by the utility would not be
impeded by operation of DER. Thus all phases of the feeder would be tripped per the utilitys
normal protection scheme. At that point, all DER that remained connected would sense
voltage outside of the allowable operating range and would immediately disconnect.
Distri bution Area Monitoring and Control
Integrating DER so that they can provide the benefits outlined above will require overhauling
the conventional distribution system so that it functions similarly to the traditional
transmission system. The key ingredients of this overhaul would be as follows:
Frequency Supervision: When DER separate from the transmission grid, no frequency
leader exists for them to follow. Therefore, a real-time, global signal must be sent to DERto constantly set and synchronize the frequency at which they generate power.
Dispatch Control: In any closed power system, the power generated must equal the power
used. Controllers or governors can control the power generated up to a point beyond which
more available generation must be dispatched to meet demand. A control system is needed to
automatically dispatch generation when system load approaches available generation. Load-
Shedding Control: If demand exceeds all dispatched generation, loads must be reenergized or
the system will become unstable. A controller is needed to systematically reenergize loads
when sufficient generation is not available for dispatch. Voltage and Reactive Power Support:
DER must establish and support system voltage. Voltage support is needed to regulate
voltage throughout the distribution system. Reactive power control is also needed to ensure
system stability.
Synchronizing capability: An isolated distribution system must be able reattach to an
energized transmission system without an interruption in service. Likewise, isolated DER
must be able to reattach to an energized distribution system.
-
7/28/2019 Micro Grid Report
12/13
Micro Grid
Page 12
8. Conclusion
The Consortium for Electric Reliability Technology Solutions is pioneering the concept of
Micro Grids as an alternative approach to integrating small scale distributed energy resources
into electricity distribution networks, and more generally, into the current wider power
system. Traditional approaches focus on minimizing the consequences for safety and grid
performance of a relatively small number of individually interconnected micro generators,
implying, for example, that safety requires they instantaneously disconnect in the event of
system outage. By contrast, Micro Grids would be designed to operate independently, usually
operating connected to the grid but islanding from it, as cost effective or necessary to
maintain performance
-
7/28/2019 Micro Grid Report
13/13
Micro Grid
Page 13
9. Reference:
The Rise of Micro Grid Power Networkshttp://www.sustainablefacility.com/Articles/Feature_Article/58905d08bd629010Vgn
VCM100000f932a8c0
"Why the Micro Grid Could Be the Answer to Our Energy Crisis"http://www.fastcompany.com/magazine/137/beyond-the-grid.html
"How a Micro Grid Works http://science.howstuffworks.com/microgrid.htm M. Dicorato,G. Forte,M. TrovatoA procedure for evaluating Micro Grids technical
and economic feasibility issues , IEEE Bucharest Power Tech Conference, June 28th
- July 2nd,2009, Bucharest, Romania.
Chem Nayar, Markson Tang, and Wuthipong Suponthana Wind/PV/Diesel MicroGrid System implemented in Remote Islands in the Republic of Maldives,IEEE
transactions 2008.
http://science.howstuffworks.com/microgrid.htmhttp://science.howstuffworks.com/microgrid.htmhttp://science.howstuffworks.com/microgrid.htmhttp://science.howstuffworks.com/microgrid.htm