micro grid report

Upload: santosh-kumar-buyya

Post on 03-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Micro Grid Report

    1/13

    Micro Grid

    Page 1

    1. Abstract

    The legacy paradigm for electricity service in most of the electrified world today is based on

    the centralized generation-transmission-distribution infrastructure that evolved under a

    regulated environment. More recently, a quest for effective economic investments,

    responsive markets, and sensitivity to the availability of resources, has led to various degrees

    of deregulation and unbundling of services. In this context, a new paradigm is emerging

    wherein electricity generation is intimately embedded with the load in micro grids.

    Development and decay of the familiar macro grid is discussed. The salient features of micro

    grids are examined to suggest that cohabitation of micro and macro grids is desirable, and

    that overall energy efficiency can be increased, while power is delivered to loads at

    appropriate levels of quality

  • 7/28/2019 Micro Grid Report

    2/13

    Micro Grid

    Page 2

    2. Introduction:

    Recent developments in the electric utility industry are encouraging the entry of power

    generation and energy storage at the distribution level. Together, they are identified as

    distributed generation units. Several new technologies are being developed and marketed for

    distributed generation, with capacity ranges from a few kW to 100 MW. The distributed

    generation includes micro turbines, fuel cells, photovoltaic systems, wind energy systems,

    diesel engines

    3. Definition of Micro grids

    The Micro grid (MG) concept assumes a cluster of loads and micro sources operating as a

    single controllable system that provides both power and heat to its local area. This concept

    provides a new paradigm for defining the operation of distributed generation.

    3.1 Micro grid Architecture:

    The MG study architecture is shown in Figure 1.1. It consists of a group of radial feeders,

    which could be part of a distribution system. There is a single point of connection to the

    utility called point of common coupling (PCC). Feeders 1 and 2 have sensitive loads which

    should be supplied during the events. The feeders also have the micro sources consisting of a

    photovoltaic (PV), a wind turbine (WT), and fuel cell (FC), a micro turbine (MT), a diesel

    generator (DG), and battery storage. The third feeder has only traditional loads.

    The static switch (SD) is used to island feeders 1 and 2 from the utility when events happen.

    The fuel input is needed only for the DG, FC, and MT as the fuel for the WT and PV comes

    from nature. To serve the load demand, electrical power can be produced either directly by

    PV, WT, DG, MT, or FC. The diesel oil is a fuel input to a DG, whereas natural gas is a fuel

    input to fuel processor to produce hydrogen for the FC. The gas is also the input to the MT.

    The use of DG, or FC or MT with other fuel types can be modeled by changing the system

    parameters to reflect the change in the fuel consumption characteristics (e.g. fuel heating

    values, and efficiency of the engines)

  • 7/28/2019 Micro Grid Report

    3/13

    Micro Grid

    Page 3

    Each of the local generation unit has a local controller (LC). This is responsible for local

    control that corresponds to a conventional controller (ex. automatic voltage regulator (AVR)

    or Governor) having a network communication function to exchange information between

    other LCs and the upper central controller to achieve an advanced control. The central

    controller also plays an important role as a load dispatch control center in bulk power

    systems, which is in charge of distributed generator operations installed in MG [5].

    Furthermore, the central controller is the main interface between the upper grid and the Micro

    grid. The central controller has the main responsibility for the optimization of the Micro grid

    operation, or alternatively, it coordinates the actions of the local controllers to produce the

    optimal outcome. MG technologies are playing an increasingly important role in the worlds

    energy portfolio. They can be used to meet base load power, peaking power, backup power,

    remote power, power quality, and cooling and heating needs.

    3.2 Reasons for Micro grids

    The conventional arrangement of a modern large power system offers a number of

    advantages. Large generating units can be made efficient and operated with only a relatively

    small number of personnel. The interconnected high voltage transmission network allows the

    generator reserve requirement to be minimized, the most efficient generating plant to be

    dispatched at any time, and bulk power to be transported large distances with limited

    electrical losses. The distribution network can be designed for unidirectional flows of power

    and sized to accommodate customer loads only. However, over the last few years a number

    of influences have combined to lead to the increased interest in MG schemes [1] and [7]. The

    policy drivers encouraging MGs are:

  • 7/28/2019 Micro Grid Report

    4/13

    Micro Grid

    Page 4

    1. Reduction in gaseous emissions (mainly CO2).

    2. Energy efficiency or rational use of energy.

    3. Deregulation or competition policy.

    4. Diversification of energy sources.

    5. National and global power requirements.

    Listed other reasons but with additional emphasis on commercial considerations such as:

    Availability of modular generating plants. Ease of finding sites for smaller generators. Short construction times and lower capital costs of smaller plants.

    4. Technologies

    The key feature that makes the Micro Grid possible is the power electronics, control, and

    communications capabilities that permit a Micro Grid to function as a semiautonomous

    power system. The power electronics are the critical distinguishing feature of the Micro Grid,

    and they are discussed in detail below. This section describes some of the other technologies

    whose development will shape Micro Grids. While the more familiar reciprocating engines

    will likely remain competitive in many applications for the foreseeable future, they lack

    power electronics therefore minimizing their role in Micro Grids. Widespread use of fuel

    cells, particularly high temperature ones most interesting for combined heat and power (CHP)

    applications, remains a few years away. Among the renewable technologies, medium to largephotovoltaic systems, possibly building integrated, are a particularly promising technology,

    while other renewable may also play a role. In addition to generating technologies, Micro

    Grids also include storage, load control and heat recovery equipment.

    4.1 Micro turbines:

    Now currently in the 25-100 kW range, although larger ones are under development, may

    ultimately be mass-produced at low cost. These are mechanically simple, single shaftdevices,

    using high-speed (50,000-100,000 rpm) typically with airfoil bearings. They aredesigned to

    combine the reliability of commercial aircraft auxiliary power units (APUs) with the lowcost of automotive turbochargers. Despite their mechanical simplicity, micro turbines rely on

    power electronics to interface with loads. Example products include: Capstone's 30-kW and

    60- kW systems, the former Honeywell 75-kW Parallon machine, and products from

    European manufacturers Bowman and Turbec that feature CHP capabilities. Micro turbines

    should also be acceptably clean running. Their primary fuel is natural gas, although they may

    also burn propane or liquid fuels in some applications, which permits clean combustion,

    notably with low particulates.

  • 7/28/2019 Micro Grid Report

    5/13

    Micro Grid

    Page 5

    4.2 Fuel cells:

    Fuel cells are also well suited for distributed generation applications. They offer high

    efficiency and low emissions but are currently expensive. Phosphoric acid cells are

    commercially available in the 200-kW range, and high temperature solid-oxide and molten-

    carbonate cells have been demonstrated and are particularly promising for Micro Grid

    application. A major development effort by automotive companies has focused on the

    possibility of using on-board reforming of gasoline or other common fuels to hydrogen, to be

    used in low temperature proton exchange membrane (PEM) fuel cells. Fuel cell engine

    designs are attractive because they promise high efficiency without the significant polluting

    emissions associated with internal combustion engines. Many other major companies are

    investing in PEM fuel cells for mobile applications, and the recently announced Bush

    administration Freedom CAR Initiative should accelerate development. This will accelerate

    PEM development relative to other fuel cells, should lower costs, and will partially

    compensate for the relatively unattractiveness of low-temperature PEMs for CHPapplications. Higher temperature PEMs are also under development.

    4.3 Renewable generation:

    Renewable generation could appear in Micro Grids, especially those interconnected

    through power electronic devices, such PV systems or some wind turbines. Befouled micro

    turbines arealso a possibility. Environmentally, fuel cells and most renewable sources are a

    majorimprovement over conventional combustion engines.

    5. Combined Heat and Power (CHP):

    One important potential benefit of Micro Grids is an expanded opportunity to utilize the

    waste heat from conversion of primary fuel to electricity. Because typically half to three-

    quarters of the primary energy consumed in power generation is ultimately released

    unutilized to the environment, the potential gains from using this heat productively are

    significant. The gains of increased conversion efficiency are threefold. First, fuel costs will be

    reduced both because individual fuel purchases will decrease and constrained overall demand

    will drive down fuel prices. Second, carbon emissions will be reduced. And, third, the

    environmental problem of disposing of large power plant waste heat into the environmentwill diminish. The emergence and deployment of technologies to facilitate efficient local use

    of waste heat is, therefore, key for Micro Grids to emerge as a significant contributor to the

    national electricity supply.

  • 7/28/2019 Micro Grid Report

    6/13

    Micro Grid

    Page 6

    6. Micro Grid Structure

    The Micro Grid structure assumes an aggregation of loads and micro sources operating as a

    single system providing both power and heat. The majority of the micro sources must be

    power electronic based to provide the required flexibility to insure controlled operation as a

    single aggregated system. This control flexibility allows the Micro Grid to present itself to

    the bulk power system as a single controlled unit, have plug-and-play simplicity for each

    micro source, and meet the customers local needs. These needs include increased local

    reliability and security.

    Key issues that are part of the Micro Grid structure include the interface, control and

    protection requirements for each micro source as well as Micro Grid voltage control, power

    flow control, load sharing during islanding, protection, stability, and over all operation. The

    ability of the Micro Grid to operate connected to the grid as well as smooth transition to and

    from the island mode is another important function.

    Figure illustrates the basic Micro Grid architecture. The electrical system is assumed to be

    radial with three feeders A, B, and C and a collection of loads. The micro sources are

    either micro turbines or fuel cells interfaced to the system through power electronics. The

    Point of Common Coupling (PCC) is on the primary side of the transformer and defines the

  • 7/28/2019 Micro Grid Report

    7/13

    Micro Grid

    Page 7

    separation between the grid and the Micro Grid. At this point the Micro Grid must meet the

    prevailing interface requirements, such as defined in draft standard IEEE P1547.

    The sources on Feeder A & B allow full exploration of situations where the micro sources are

    placed away from the common feeder bus to reduce line losses, support voltage and/or use its

    waste heat. Multiple micro sources on a radial feeder increase the problem of power flow

    control and voltage support along the feeder when compared to all sources being placed at the

    feeders common bus, but this placement is key to the plug-and-play concept. The feeders are

    usually 480 volts or smaller. Each feeder has several circuit breakers and power and voltage

    flow controllers. The power and voltage controller near each micro source provides the

    control signals to the source, which regulates feeder power flow and bus voltage at levels

    prescribed by the Energy Manager. As downstream loads change, the local micro sources

    power is increased or decreased to hold the total power flow at the dispatched level

    This eliminates nuisance trips of the traditional load when the Micro Grid islands to protect

    critical loads. The Micro Grid assumes three critical functions that are unique to this

    architecture:

    Micro source Controller. The Power and Voltage Controller coupled with the micro

    source provide fast response to disturbances and load changes without relying on

    communications.

    Energy Manager. Provides operational control through the dispatch of power and voltage

    set points to each Micro source Controller. The time response of this function is measured in

    minutes.

    Protection. Protection of a Micro Grid in which the sources are interfaced using power

    electronics requires unique solutions to provide the required functionality.

    6.1 Micro source Controller:

    The basic operation of the Micro Grid depends on the Micro source Controller to; regulate

    power flow on a feeder as loads on that feeder change their operating points; regulate the

    voltage at the interface of each micro source as loads on the system change; and insure that

    each micro source rapidly picks up its share of the load when the system islands. In addition

    to these control functions the ability of the system to island smoothly and to automaticallyreconnect to the bulk power system is another important operational function. Most of this set

    of key functions does not exist on currently available micro sources.

    Another important feature of each Micro source Controller is that it responds in milliseconds

    and uses locally measured voltages and currents to control the micro source during all system

    or grid events. Fast communication among micro sources is not necessary for Micro Grid

    operation; each inverter is able to respond to load changes in a predetermined manner without

    data from other sources or locations. This arrangement enables micro sources to plug and

    play that is, micro sources can be added to the Micro Grid without changes to the control

    and protection of units that are already part of the system. The basic inputs to the Micro

  • 7/28/2019 Micro Grid Report

    8/13

    Micro Grid

    Page 8

    source Controller are steady-state set points for power, P, and local bus voltage, V. Section

    5.0 discusses Micro source Controller in more detail.

    6.2 Energy Manager

    The Energy Manager provides for system operation of the Micro Grid through dispatch ofpower and voltage set points to each Micro source Controller. This function could be as

    simple as having a technician enters these set points by hand at each controller to a state-of-

    the-art communication system with artificial intelligence. The actual values of dispatch of P

    and V depend on the operational needs of the Micro Grid. Some possible criteria are:

    Insure that the necessary heat and electrical loads are met by the micro sources;

    Insure that the Micro Grid satisfies operational contracts with the bulk power provider;

    Minimize emissions and/or system losses;

    Maximize the operational efficiency of the micro sources;

    6.3 Protection

    The protection coordinator must respond to both system and Micro Grid faults. For a fault on

    the grid, the desired response may be to isolate the critical load portion of the Micro Grid

    from the grid as rapidly as is necessary to protect these loads. This provides the same

    function as an uninterruptible power supply at a potentially lower incremental cost. The speed

    at which the Micro Grid isolates from the grid will depend on the specific customer loads on

    the Micro Grid. In some cases, sag compensation can be used to protect critical loads without

    separation from the distribution system. If a fault occurs within the islandable portion of the

    Micro Grid, the desired protection is to isolates the smallest possible section of the radial

    feeder to eliminate the fault.

    6.4 Large Systems-Interconnected Micro Grids:

    Because a Micro Grid exploits low voltage, use of waste heat, and the flexibility of power

    electronics, its practical size may be limited to a few MVA (even though IEEE draft standard

    P1547 specifies an upper limit of 10MVA). In a large complex, loads could be divided into

    many controllable units e.g., among buildings or industrial sites. Each unit could be supplied

    by one or more Micro Grids connected through a distribution system.

    For example, consider a power park with a total load in excess of 50 MVA. This system

    could be supplied from the transmission system through one or two substations using 13.8-kV

    underground cables. Each load group (heat and/or electrical) would be a Micro Grid

    connected to the 13.8-kV supply. In addition to these Micro Grids, the power park could

    employ larger generation such as one- to ten-MVA gas turbines directly connected to the

    13.8-kV feeder. Each Micro Grid would be a dispatch able load. The power park controlswould provide each Micro Grid with its load level (drawing power from the 13.8-kV feeder)

  • 7/28/2019 Micro Grid Report

    9/13

    Micro Grid

    Page 9

    while the gas turbines Pand Q/V would be dispatched either locally or by the bulk power

    producer. The advantages of this system are that the Micro Grid structure insures greater

    stability and controllability, allows for a distributed command and control system, and

    provides redundancy to insure greater power supply reliability for the power park.

    7. Control Methods for Micro Grids:

    Power electronics can provide the control and flexibility for the Micro Grid to meet its

    customersas well as the grids needs. Micro Grid controls need to insure that: new micro

    sources can be added to the system without modification of existing equipment, the Micro

    Grid can connect to or isolate itself from the grid in a rapid and seamless fashion, reactive

    and active power can be independently controlled, voltage sag and system imbalances can becorrected, and that the Micro Grid can meet the grids load dynamics requirements. Micro

    source Controller techniques described below rely on the inverter interfaces found in fuel

    cells, micro turbines, and storage technologies. A key element of the control design is that

    communication among micro sources is unnecessary for basic Micro Grid operation. Each

    Micro source Controller must be able to respond effectively to system changes without

    requiring data from other sources or locations.

    Micro source Control Functions

    Operation of the Micro Grid assumes that the power electronic controls of current microsources are modified to provide a set of key functions, which currently do not exist. These

    control functions include the ability to: regulate power flow on feeders; regulate the voltage

    at the interface of each micro source; ensure that each micro source rapidly pickups up its

    share of the load when the system islands. In addition to these control functions the ability of

    the system to island smoothly and automatically reconnect to the bulk power system is

    another important operational function.

  • 7/28/2019 Micro Grid Report

    10/13

    Micro Grid

    Page 10

    Interface I nverter System

    Basic Contr ol of Real and Reactive Power

    There are two basic classes of micro sources: DC sources, such as fuel cells, photovoltaic

    cells, and battery storage; and high-frequency AC sources such as micro turbines, which needto be rectified. In both cases, the DC voltage that is produced is converted using a voltage

    source inverter. The general model for a micro source is shown in Figure 5.1. It contains

    three basic elements: prime mover, DC interface, and voltage source inverter. The micro

    source couples to the Micro Grid using an inductor. The voltage source inverter controls both

    the magnitude and phase of its output voltage, V. The vector relationship between the inverter

    voltage, V, and the local Micro Grid voltage, E, along with the inductors reactance, X,

    determines the flow of real and reactive power (P &Q) from the micro source to the Micro

    Grid. The P & Q magnitudes are coupled as shown in the equations below. For small

    changes, P is predominantly dependent the power angle, p, and Q is dependent on the

    magnitude of the inverters voltage, V. These relationships constitute a basic feedback loop

    for the control of output power and bus voltage, E, through regulation of reactive power flow.

    System Protection

    A typical radial distribution system has been assumed in the discussions that follow; we also

    assume that DER are integrated with this distribution system in accordance with IEEE draft

    The changes that would be required in existing protection schemes are outlined below.

    Transformer Protection:

    Transformer Fault: Connecting the Micro Grid to a utility grid would not affect the abilityof the utility's differential protection scheme to detect and/or isolate a transformer fault. No

    adjustments to this protection would be necessary.

    Line Protection:

    Ground Fault on the Feeder: DER that are connected to the faulted phase would contribute to

    the fault and thus reduce the fault current seen by the AEPS. However, at the inception of the

    fault, all but the lowest rated DER (on all phases) would detect the fault and separate from the

    system per IEEE P1547. After the DER separate, the fault current contribution from the

    AEPS would increase and feeder protection would enable, just as though DER had neverbeen connected to the feeder. The fault detection time might be prolonged because of the

  • 7/28/2019 Micro Grid Report

    11/13

    Micro Grid

    Page 11

    presence of DER, but the protection scheme would not need to change. IEEE P1547 would

    require DER to comply with local rules regarding reclosing coordination. A reasonable

    approach for this coordination would be for the utility to require DER units that have tripped

    off line to remain off line for a period of time that exceeds all disturbance and reclosing

    events (e.g., five minutes). These requirements would have little impact on existing systemprotection.

    Line-to-Line Fault on the Feeder: For DER connected to the faulted line, the voltage seen at

    the DER terminals would, in most cases, be out of the allowable operating band specified in

    P1547, so the DER would trip off line. DER operating on the unfaulted phase during a lineto-

    line fault would, in most cases, also exhibit voltage outside of the allowable operating band

    specified in P1547 and would thus trip off line. If the unfaulted phase voltage did not move

    outside the allowable operating range, detection of the fault by the utility would not be

    impeded by operation of DER. Thus all phases of the feeder would be tripped per the utilitys

    normal protection scheme. At that point, all DER that remained connected would sense

    voltage outside of the allowable operating range and would immediately disconnect.

    Distri bution Area Monitoring and Control

    Integrating DER so that they can provide the benefits outlined above will require overhauling

    the conventional distribution system so that it functions similarly to the traditional

    transmission system. The key ingredients of this overhaul would be as follows:

    Frequency Supervision: When DER separate from the transmission grid, no frequency

    leader exists for them to follow. Therefore, a real-time, global signal must be sent to DERto constantly set and synchronize the frequency at which they generate power.

    Dispatch Control: In any closed power system, the power generated must equal the power

    used. Controllers or governors can control the power generated up to a point beyond which

    more available generation must be dispatched to meet demand. A control system is needed to

    automatically dispatch generation when system load approaches available generation. Load-

    Shedding Control: If demand exceeds all dispatched generation, loads must be reenergized or

    the system will become unstable. A controller is needed to systematically reenergize loads

    when sufficient generation is not available for dispatch. Voltage and Reactive Power Support:

    DER must establish and support system voltage. Voltage support is needed to regulate

    voltage throughout the distribution system. Reactive power control is also needed to ensure

    system stability.

    Synchronizing capability: An isolated distribution system must be able reattach to an

    energized transmission system without an interruption in service. Likewise, isolated DER

    must be able to reattach to an energized distribution system.

  • 7/28/2019 Micro Grid Report

    12/13

    Micro Grid

    Page 12

    8. Conclusion

    The Consortium for Electric Reliability Technology Solutions is pioneering the concept of

    Micro Grids as an alternative approach to integrating small scale distributed energy resources

    into electricity distribution networks, and more generally, into the current wider power

    system. Traditional approaches focus on minimizing the consequences for safety and grid

    performance of a relatively small number of individually interconnected micro generators,

    implying, for example, that safety requires they instantaneously disconnect in the event of

    system outage. By contrast, Micro Grids would be designed to operate independently, usually

    operating connected to the grid but islanding from it, as cost effective or necessary to

    maintain performance

  • 7/28/2019 Micro Grid Report

    13/13

    Micro Grid

    Page 13

    9. Reference:

    The Rise of Micro Grid Power Networkshttp://www.sustainablefacility.com/Articles/Feature_Article/58905d08bd629010Vgn

    VCM100000f932a8c0

    "Why the Micro Grid Could Be the Answer to Our Energy Crisis"http://www.fastcompany.com/magazine/137/beyond-the-grid.html

    "How a Micro Grid Works http://science.howstuffworks.com/microgrid.htm M. Dicorato,G. Forte,M. TrovatoA procedure for evaluating Micro Grids technical

    and economic feasibility issues , IEEE Bucharest Power Tech Conference, June 28th

    - July 2nd,2009, Bucharest, Romania.

    Chem Nayar, Markson Tang, and Wuthipong Suponthana Wind/PV/Diesel MicroGrid System implemented in Remote Islands in the Republic of Maldives,IEEE

    transactions 2008.

    http://science.howstuffworks.com/microgrid.htmhttp://science.howstuffworks.com/microgrid.htmhttp://science.howstuffworks.com/microgrid.htmhttp://science.howstuffworks.com/microgrid.htm