micronet bacnet™ unitary controller - storer servicesstorerservices.com/files/mnb-300 bacnet...
TRANSCRIPT
Printed in U.S.A. 2-05 © Copyright 2005 Invensys Building Systems, Inc. All rights reserved. F-27339
Invensys Building Systems, Inc.
1354 Clifford Avenue
P.O. Box 2940
Loves Park, IL 61132-2940
www.invensysibs.com
I/A Series™
MicroNet BACnet™ Unitary ControllerThe I/A Series MicroNet BACnet Unitary Controller is an interoperable controller with native BACnet, IP, and MS/TP communications support. The controller features Sensor Link (S-Link) support, LED status and output indication, screw terminal blocks, as well as a panel mount sub-base with removable electronics module.
ApplicationsWhen programmed using WorkPlace Tech Tool, the Unitary controller provides a wide range of control strategies for packaged rooftop, heat pump, fan coil, unit ventilator, and similar applications.
ConnectivityThe MicroNet BACnet Unitary Controller can function either in a standalone mode or as part of a BACnet building automation system (BAS) network.
Features—• The MicroNet BACnet Unitary Controller’s sequence
of operation and BACnet image are fully programmable using WorkPlace Tech Tool. The controllers can be applied to all common unitary HVAC applications.
• Capability to function in standalone mode or as part of an I/A Series building automation network.
• Extensive BACnet object and services support provides robust BAS integration and optimum use of network bandwidth.
• Integral MS/TP jack for direct connection of PC with WorkPlace Tech Tool.
• Removable electronics module mates with panel-mounted subbase.
• Optional plenum-rated enclosure.
• DIP switch addressable.
• Service pin button for BACnet “I am” message broadcast.
• Removable terminals for power and communications to facilitate commissioning.
• Isolated RS-485 transceiver for MS/TP communications.
• MS/TP baud rate selection from 9.6 up to 76.8 kbaud.
• LED indication of MS/TP communication activity, controller status, and UO and DO state.
• Firmware upgradeable over the network.
• Non-volatile storage of point history data and unconfirmed alarms.
MNB-300
2 © Copyright 2005 Invensys Building Systems, Inc. All rights reserved. F-27339
Hardware SpecificationsDimensions 3-15/16 in. H x 7 in. W x 2-3/16 in. D (100 mm x 178 mm x 56 mm).
Enclosure Conforms to NEMA-1. Meets UL 94-5V flammability ratings for plenum application use.
Mounting Panel mount.
Power Supply Input 20.4 to 30 Vac, 50/60 Hz.
Power Consumption 16 VA at 24 Vac.
Agency Listings
UL-916 File #E9429 Category PAZX.
Canadian UL Listed to Canadian Safety Standards (CAN/CSA 22.2).
FCC Part 15 Class A.
Australian Meets requirements to bear the C-Tick Mark.
European Community – EMC Directive 89/336/EECEN61326
Ambient Limits
TemperaturesOperating -40 to 140 °F (-40 to 60 °C).Shipping and Storage -40 to 160 °F (-40 to 71 °C).
Humidity 5 to 95% non-condensing.
Wiring Terminals (Figure-1)
I/O Points Fixed Screw terminals; up to two AWG #14 (2.08 mm2) or smaller wires.
Power and MS/TP Removable screw terminals; single AWG #14 (2.08 mm2) wire or up to two AWG #18 (0.823 mm2) or smaller wires.
Inputs from MN-Sx MicroNet™ Sensor
Space Temperature 32 to 122 °F (0 to 50 °C).
Space Humidity 5 to 95% RH, non-condensing.
Local Setpoint Adjustable within limits set by application programming tool.
Override Pushbutton For standalone occupancy control.
Fan Operation and Speed Mode On/off, speed (low/medium/high), or auto.
System Mode Heat, cool, off, or auto.
Emergency Heat Enable or disable.
Table-1 Model Chart.
ModelInputs and Outputs
UI UO DO (Triac)
MNB-300 6 3 6
EOL
TO1
C1
TO2
C2
TO3
C3
TO4
C4
TO5
C5
TO6
C6
UI1
COM
UI2
UI3
COM
UI4
UI5
COM
UI6
UO1
COM
UO2
UO3
COM
S-LK
RCVSTATUS
XMT
Physical
Address
Internal
Triac
Switches
(Isolated)
MNB-300
Unitary Controller
IAM
MS+
MS-
SLD
24H
24G (COM)
GND
MS/TP Jack
Figure-1 Unitary Controller Terminals.
F-27339 © Copyright 2005 Invensys Building Systems, Inc. All rights reserved. 3
Universal Inputs (6) Universal Input characteristics are software-configured to respond to one of the following input types:
10 kΩ Thermistor with 11 kΩ Shunt ResistorSensor operating range -40 to 250 °F (-40 to 121 °C), Invensys model TSMN-57011-850, TS-5700-850 series, or equivalent.
1 kΩ Balco -40 to 250 °F (-40 to 121 °C), Invensys model TSMN-81011, TS-8000 series, or equivalent.
1 kΩ Platinum -40 to 240 °F (-40 to 116 °C), Invensys model TSMN-58011, TS-5800 series, or equivalent.
1 kΩ Resistive 0 to 1500 Ω.
10 kΩ Resistive 0 to 10.5 kΩ.
Analog Voltage Range 0 to 5 Vdc.
Analog Current Range 0 to 20 mA; requires external 250 Ω shunt resistor (AD-8969-202).
Digital Dry switched contact; detection of closed switch requires less than 300 Ω resistance; detection of open switch requires more than 1.5 kΩ.
Standard Pulse Input (UI1-UI6)
Minimum Rate 1 pulse per 4 minutes.Maximum Rate 1 pulse per second.
Fast Pulse Input (UI1)
Minimum Rate 1 pulse per 4 minutes.Maximum Rate 10 pulses per second.
Digital Outputs – Triac (6) 12 VA at 24 Vac, 50/60 Hz, each output individually isolated.
Universal Outputs (3)
0 to 20 mA Output load from 80 to 550 Ω.
0 to 10 V With external 500 Ω, 1/2 W, 1% resistor.
Capable of Driving Functional Devices RIBUI1C Relay UO configured for 0 to 20 mAdc, no external resistor.
CommunicationsBACnet Networks The MicroNet BACnet Unitary Controller incorporates an isolated RS-485 transceiver for BACnet MS/TP communications at 9.6 up to 76.8 kbaud using standard MS/TP wiring methods. Up to 128 devices can be connected to an MS/TP sub-net without repeaters.
S-Link The Sensor Link (S-Link) communications wiring provides power and a communication interface for one MN-Sx I/A Series MicroNet sensor. The various MN-Sx sensors can provide room temperature, room humidity, setpoint adjustment, and occupancy override. This connection uses two-wire, unshielded cable and is not polarity sensitive. Maximum S-Link bus length is 200 ft (61 m).
BACnet ComplianceConformance Class BACnet Application Specific Device (B-ASD).
OptionsMNB-300-ENC: Wall-mount enclosure
S-Link Sensors: Temperature and humidity wall sensors with digital communication
TSMN Series: Temperature wall sensors
F-27339 Printed in U.S.A.
Invensys, I/A Series, and MicroNet are trademarks of Invensys plc and its subsidiaries and affiliates.BACnet is a trademark of the American Society of Heating, Ventilating, Refrigeration, and Air-conditioning Engineers (ASHRAE).All other trademarks are the property of their respective owners.
© Copyright 2005 Invensys. All rights reserved. No part of this document may be photocopied or reproduced by any means, or translated to another language without prior written consent of Invensys.
All specifications are nominal and may change as design improvements are introduced. Invensys shall not be liable for damages resulting from misapplication or misuse of its products.
BA
Cn
et
MS
/TP
Co
mm
un
ica
tio
ns B
us
BA
Cn
et
MS
/TP
Co
mm
un
ica
tio
ns B
us
PC Workstation with Enterprise
Server and WorkPlace Tech Tool
Software
PC Workstation
with WorkPlace
Tech Tool
Software
S-Link Sensor
S-Link Sensor
S-Link Sensor
S-Link Sensor
MicroNet BACnet
MNB-V1
Cooling Controller
MicroNet BACnet
MNB-V2
Deluxe ControllerS-Link Sensor
S-Link Sensor
MicroNet BACnet
MNB-V1
Cooling Controller
MicroNet BACnet
MNB-V2
Deluxe Controller
UNC-510-2
Universal Network
Controller
Ethernet
MicroNet BACnet
MNB-300
Unitary ControllerS-Link Sensor
MicroNet BACnet
MNB-300
Unitary Controller
MicroNet BACnet
MNB-1000
Plant Controller
MicroNet BACnet
MNB-1000
Plant Controller
Figure-2 I/A Series BACnet Topology.