modbus - tcp / jbus serial link - socomec€¦ · modbus - tcp / jbus serial link installation and...
TRANSCRIPT
green power 2.0 and Delphys BCM o d b u s - T C P / J b u s s e r i a l l i n k
Installation and operating manual GB
1. Foreword 4
2. SaFety requirement 4
2. 1. Using conditions 4
2. 2. dELPHYs grEEn PowEr oPErating rEfErEncE 4
3. environment 4
3. 1. rEcYcLing of ELEctricaL ProdUcts and EqUiPmEnt 4
4. introduction 5
4. 1. gEnEraL PUrPosE 5
4. 2. modbUs ProtocoL 5
4. 3. data dEcoding 5
5. inStallation inSide uPS 6
5. 1. ‘com-sLots’ LocaLisation 6
5. 2. modbUs sEriaL intErfacE PLUg in 6
5. 3. modbUs intErfacE in ParaLLEL sYstEm configUration 6
5. 4. connEctions and wiring 7
5. 5. modbUs sEriaL Link dEfaULt sEttings 8
5. 6. How to cHangE tHE sEriaL Link sEttings ? 8
6. conFiGuration oF the modBuS tcP ida connection 9
7. conventionS 9
7. 1. framE Errors managEmEnt 9
8. modBuS in SinGle uPS unit 10
8. 1. How to rEad data 10
8. 2. incoming data strUctUrE 10
8. 3. UPs idEntification: addrEss 0x1100, 32 words 11
8. 4. datE & HoUrs: addrEss 0x1360, 4 words 11
8. 5. UPs configUration: addrEss 0x1120, 16 words 11
8. 6. Unit statUs: addrEss 0x1143, 4 words 12
8. 7. Unit aLarms: addrEss 0x114a, 4 words 14
8. 8. Unit mEasUrEmEnts tabLEs: addrEss 0x1220, 80 words 16
8. 9. Unit EnabLEd controLs tabLE: addrEss 0x1150; 1 words 18
8. 10. controLs sEnd to UPs: addrEss 0x1190, writE 1 words 18
Index
2 Delphys green power - Ref.: IOMDGPJB0910-GB_07
9. modBuS in modular Parallel SyStem conFiGuration 19
9. 1. rEmindEr 19
9. 2. modbUs tabLE in modULar ParaLLEL sYstEm 20
9. 3. UPs idEntification: addrEss 0x0100, 32 words 20
9. 4. datE & HoUrs: addrEss 0x0360, 4 words 20
9. 5. UPs configUration: addrEss 0xm120, 16 words 20
9. 6. PrELiminarY rEmarks 20
9. 7. UPs statUs: addrEss 0x0140, 3 words 21
9. 8. UPs aLarms: addrEss 0x0148, 2 words 22
9. 9. UPs mEasUrEmEnts: addrEss 0x0200, 32 words 23
9. 10. UPs EnabLEd controLs tabLE: addrEss 0xm150, 2 words 24
9. 11. to sEnd controL to UPs: addrEss 0x15b0, writE 1 words 24
10. modBuS in Parallel SyStem with centraliSed ByPaSS 25
10. 1. rEmindEr 25
10. 2. modbUs tabLE in ParaLLEL sYstEm witH cEntraLisEd bYPass 26
10. 3. UPs idEntification: addrEss 0x0100, 32 words 26
10. 4. datE & HoUrs: addrEss 0x0360, 4 words 26
10. 5. UPs configUration: addrEss 0xm120, 16 words 26
10. 6. PrELiminarY rEmarks 26
10. 7. UPs statUs: addrEss 0x0140, 3 words 27
10. 8. UPs aLarms: addrEss 0x0148, 2 words 28
10. 9. UPs mEasUrEmEnts: addrEss 0x0200, 32 words 29
10. 10. UPs EnabLEd controLs tabLE: addrEss 0xm150, 2 words 30
10. 11. to sEnd controL to UPs: addrEss 0x15b0, writE 1 words 30
11. ByPaSS taBle 31
11. 1. bYPass statUs: addrEss 0xf143, 4 words 31
11. 2. bYPass aLarms: addrEss 0xf14a, 4 words 33
11. 3. bYPass mEasUrEmEnts tabLEs: addrEss 0xf220, 80 words 35
12. module taBle 37
12. 1. modULE statUs: addrEss 0xm143, 4 words 37
12. 2. modULE aLarms: addrEss 0xm14a, 4 words 39
12. 3. modULE mEasUrEmEnts tabLEs: addrEss 0xm220, 80 words 41
3Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
we thank you for the trust you have in our uninterruptible Power Systems.
This equipment is fitted with up to date technology. Rectifier and inverter subsets are provided with power semicon-
ductors (IGBT) including a digital micro-controller.
Our equipment complies with IEC EN 62040-2 standard.
CAUTION : “This is a product for restricted sales distribution to informed partners. Installation restrictions or addi-
tional measures may be needed to prevent disturbances”.
SOCOMEC UPS reserves the right to modify their specifications at any time as far as this contributes
to technical progress.
2. Safety RequIRement
2. 1. Using conditions
Do read carefully these operation instructions before using the JBUS/MODBUS interface.
Whatever the repairs, they must be made only by authorised staffs, which have been suitably trained.
For an optimal operation, it is recommended to maintain the ambient temperature and humidity of the DELPHYS
Green Power environment below the values specified by the manufacturer.
2. 2. dELPHYs grEEn PowEr oPErating rEfErEncE
Respect the safety requirements.
Do read carefully the operation instructions of DELPHYS Green Power.
This equipment meets the requirements of the European directives applied to this product. As a consequence it is
labelled as follows:
3. envIRonment
3. 1. rEcYcLing of ELEctricaL ProdUcts and EqUiPmEnt
Provision is made in European countries to break up and recycle materials making up the system. The various com-
ponents must be disposed of in accordance with the legal provisions in force in the country where the system is
installed.
1. foRewoRd
4 Delphys green power - Ref.: IOMDGPJB0910-GB_07
4. 1. gEnEraL PUrPosE
This document provides required information of the MODBUS protocol serial link or Ethernet network.
Before connecting a supervision equipment or BMS system (Building management system) to the UPS, it is neces-
sary to install and set up the serial interface or network configurations in the case of a network connection..
4. 2. modbUs ProtocoL
This document does not explain the MODBUS protocol management. Please refer on
www.modbus.org web site for more information.
the DELPHYS Green Power MODBUS uses the following functions :
– function 3 for reading Input Registers (16 bits),
– function 6 for writing single Registers (to control DELPHYS Green Power).
The data field is composed of 1 word, defined by a MSB (most significant byte) and a LSB (lowest significant byte),
and displayed in the following order on the serial link.
1 woRd data
b7 mSB b0 b7 LSB b0
b15 b0
4. 3. data dEcoding
Status and alarms Information
This information are coding in bit. This means that 1 word defines 16 information. If the related bit is set to 1, this
information is active or true.
Measurements and counters data
1 word defines a measurement or a counter. Some values are numeric decimal signed or unsigned (0 to 65535 or
from -32767 to 32767), or in hexadecimal (0x0000 to 0xFFFF).
4. IntRoductIon
5Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
5. 1. ‘com-sLots’ LocaLisation
The « Com-Slots » integrates all communication interfaces and it is located on the right side.
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot 2»
5. 2. modbUs sEriaL intErfacE PLUg in
The serial interface should be plugged in the slot 2, and fixed with 2 crews.
5. 3. modbUs intErfacE in ParaLLEL sYstEm configUration
There is only one MODBUS serial link interface for a parallel system configuration. One serial interface
is used for the whole installation. The access to the data of the UPS module or unit is managed by the
table addressing .
In a parallel installation with centralized bypass, it is recommended to install the serial card in slot 2
of the bypass.
1
2
5. InStaLLatIon InSIde uPS
6 Delphys green power - Ref.: IOMDGPJB0910-GB_07
5. 4. connEctions and wiring
NOTE : there is only one connection per interface (RS232 or RS422 or RS485)
5. 4.1. RS232 connection:
– Standard PC connection
– Sub-D 9 pins connector
– Pin 2 : Rx
– Pin 3 : Tx
– Pin 5 : Gnd
5. 4.2. Isolated RS485 connection
– 2 wires connection
– « dip-switch 1 » allows connecting the terminal resistor
– Isolation via “opto-coupler”
– 2 polarization resistors could be removed easily (if needed).
5. 4.3. Isolated RS422 connection
– 4 wires connection
– « dip-switch 1 and 2 » allows connecting the terminal
resistor
– Isolation via “opto-coupler”
– 4 polarization resistors could be removed easily (if needed).
RTX + RTX -
TX -
RX -
TX +
RX +
Before making any connection, please check the cabling. A wrong connection or cabling can damage
the serial link interface.
the shield should be earthing at one point.
the shield should be earthing at one point.
InstallatIon InsIde UPs
7Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
5. 5. modbUs sEriaL Link dEfaULt sEttings
Baud rate: 9600 bauds
Parity: none
data: 8 bits
Stop: 1 bit
Slave: 1
The serial link settings can be set from the control panel.
5. 6. How to cHangE tHE sEriaL Link sEttings ?
Available baud rate: 1200 - 2400 - 4800 - 9600 - 19200 bauds
Parity: even - odd - none
Slave number: 1 to 32
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot»
InstallatIon InsIde UPs
8 Delphys green power - Ref.: IOMDGPJB0910-GB_07
This protocol is available via Ethernet. RJ45 on the back of the mimic panel allows the connection to Ethernet net-
work. The IP settings and MODBUS TCP port selection is available on the mimic panel.
7. conventIonSThe table addresses are written in hexadecimal, beginning with ‘0x’.
Some PLC systems request a relative address starting from 400 (0x0190) or 40001 (0x9C41), on this address it’s
necessary to add the first address of the MODBUS table.
7. 1. framE Errors managEmEnt
In case of wrong data request, the DELPHYS Green Power answers with the following frame error :
error function code error code cause
80 + code function 1 Function error
80 + code function 2 Addresses error
80 + code function 3 Wrong data
80 + code function 6 busy
80 + code function 8 Write register error
6. confIguRatIon of the modBuS tcP Ida connectIon
9Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
8. modBuS In SIngLe uPS unIt
taBLe Start addresses table length in words modBuS functIon
UPS Identification 0x1100 32 3 read
Date and hours 0x1360 4 3 read
UPS Configurations 0x1200 16 3 read
UNIT Status (64 bits) 0x1143 4 3 read
UNIT Alarm (80 bits) 0x114A 5 3 read
unit measurements 0x1220 96 3 read
controls permission 0x1150 4 3 read
uPS controls 0x1190 4 6 write
8. 1. How to rEad data
The identification, status and alarms tables should be read completely (this means the number of word to read is
equal to the table length).
The measurements table should be read word by word or per group, without exceed the length of the table. (from
0x1220 to 0x127F).
8. 2. incoming data strUctUrE
Example of 6 words
1 2 3 4 5 6 7 8 9 10 11 12
mSB 0 lSB 0 mSB 1 lSB 1 mSB 2 lSB 2 mSB 3 lSB 3 mSB 4 lSB 4 mSB 5 lSB 5
word 0 word 1 word 2 word 3 word 4 word 5
b15 b0 b15 b0 b15 b0 b15 b0 b15 b0 b15 b0
S015 S000 S031 S016 S047 S032 S063 S048 S079 S064 S095 S080
a015 a000 a031 a016 a047 a032 a063 a048
m000 m001 m002 m003 m004 m005
10 Delphys green power - Ref.: IOMDGPJB0910-GB_07
8. 3. UPs idEntification: addrEss 0x1100, 32 words
code description number address type Remarks
i000 UPS identification 10 wordS 0x1100 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
i010 UPS Description 6 wordS 0x110A 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
i016 Location 6 wordS 0x1110 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
i022 Serial number 10 wordS 0x1116 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
8. 4. datE & HoUrs: addrEss 0x1360, 4 words
code description number address type Remarks
d00 Minutes / seconds 1 wordS 0x1360 Byte value MSB = minutes, LSB = seconds
d01 Hours / day 1 wordS 0x1361 Byte value MSB = day, LSB = hours
d02Month / day of
week1 wordS 0x1362 Byte value
MSB = month,
LSB = day of the week
1=Monday...7=Sunday
d03 year 1 wordS 0x1363 00 = 2000
8. 5. UPs configUration: addrEss 0x1120, 16 words
code measurements unit address Remarks
t000 Kind of equipment 0x11201= single unit, 3= parallel + centralised bypass 6 = modular parallel system
t001 uPS output power kva 0x1121
t002 unit output power kva 0x1122
t003 unit number 0x1123 1 - 8
t004 number of unit 0x1124 1 - 8
t005 UPS redundant 0x1125 0 - 1
t006 with battery 0x1126 0 - 1
t007 With flywheel 0x1127 0 - 1
t008 0x1128
t009 With genset 0x1129 0 - 1
t010 0x112A
t011 0x112B
t012 0x112C
t013 With rectifier input supply 0x112D 0 - 1
t014 Single 0x112E 0 = Tri, 1 = Single
t015 Measurements management 0x112F 0 = x 1, 1 = x 10
sIngle UnIt UPs modbUs tables
11Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
8. 6. Unit statUs: addrEss 0x1143, 4 words
code description Bit address Remarks
S048 Load on inverter 0 0x1143
S049 Load on auto. Bypass 1
S050 Load on maintenance Bypass 2
S051 Load not supplied 3
S052 unit is available 4
S053 Unit isolated from inst. 5
S054 Output switch Q2/3 closed 6
S055 Rectifier ON 7
S056 Battery charging 8
S057 Battery charged 9
S058 10
S059 inverter on 11
S060 Inverter switch/contactor closed 12
S061 Bypass switch activated 13
S062 14
S063 Servicing alert 15
S064 Rectifier input supply fault 0 0x1144
S065 Bypass input supply out of tolerance 1
S066 Bypass input supply failure V/F 2 2
S067 Bypass input supply is synchro ref 3
S068 Ext. synchro ref (ACS on) 4
S069 Synchro forced on ACS 5
S070 “UPS general power off” input active 6
S071 Generator set active 7
S072 Unit in normal mode 8
S073 Unit in eco-mode 9
S074 10
S075 Unit in stand-by mode 11
S076 12
S077 13
S078 14
S079 Unit in servicing mode 15
sIngle UnIt UPs modbUs tables
12 Delphys green power - Ref.: IOMDGPJB0910-GB_07
code description Bit address Remarks
S080 Unit Start procedure progress 0 0x1145
S081 Unit maintenance bypass procedure progress 1
S082 2
S083 Battery test interrupted 3
S084 Battery test in progress 4
S085 Battery test in stand-by 5
S086 6
S087 7
S088 8
S089 9
S090 Q1 closed 10
S091 Q4 closed 11
S092 Local maintenance bypass Q5 clos. 12
S093 Remote maintenance bypass closed 13 only on parallel
S094 Q21 switch closed 14 only on parallel
S095 Q22 switch closed 15 only on parallel
S096 Auxiliary input 1 active 0 0x1146
S097 Auxiliary input 2 active 1
S098 Auxiliary input 3 active 2
S099 Auxiliary input 4 active 3
S100 Auxiliary input 5 active 4
S101 Auxiliary input 6 active 5
S102 Auxiliary input 7 active 6
S103 Auxiliary input 8 active 7
S104 Auxiliary input 9 active 8
S105 Auxiliary input 10 active 9
S106 Auxiliary input 11 active 10
S107 Auxiliary input 12 active 11
S108 12
S109 13
S110 14
S111 Acknowledgement alarm request 15
sIngle UnIt UPs modbUs tables
13Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
8. 7. Unit aLarms: addrEss 0x114a, 4 words
code description Bit address Remarks
a032 unit imminent stop 0 0x114A
a033 Unit overload 1
a034 Transfer blocked 2
a035 transfer impossible 3
a036 Insufficient Resources 4 only on parallel
a037 5
a038 6
a039 Rectifier critical 7
a040 Inverter critical 8
a041 Bypass critical 9
a042 Common critical 10
a043 Fan alarm 11
a044 Back feed protection open 12
a045 ACS synchro source fault 13
a046 14
a047 15
a048 Operating on battery 0 0x114B
a049 Battery alarm 1
a050 Battery room 2
a051 Battery discharged 3
a052 End of autonomy time 4
a053 Battery test failure 5
a054 Earth leakage fault 6
a055 Battery circuit open 7
a056 on battery with mains oK 8
a057 DC voltage not OK 9
a058 Rectifier preventive 10
a059 inverter preventive 11
a060 Bypass preventive 12
a061 common preventive 13
a062 Mimic panel 14
a063 Ambient T° max 15
a064 BHC general alarm 0 0x114C
a065 1
a066 2
a067 3
a068 4
a069 5
a070 6
sIngle UnIt UPs modbUs tables
14 Delphys green power - Ref.: IOMDGPJB0910-GB_07
code description Bit address Remarks
a071 7
a072 8
a073 9
a074 10
a075 11
a076 12
a077 13
a078 14
a079 15
a080 Preventive maintenance 0 0x114D
a081 1
a082 Maintenance bypass alarm 2
a083 rotation phase fault 3
a084 Rectifier or Bypass Input supply not OK 4
a085 5
a086 6
a087 7
a088 8
a089 9
a090 10
a091 11
a092 12
a093 13
a094 Output since xx minutes on auto bypass 14
a095 unit General alarm 15
a096 Fly Wheel disconnected 0 0x114E
if seta097 Fly Wheel Critical 1
a098 Fly wheel preventive 2
a099 3
a100 4
a101 Aux. input alarm 5 if set
a102 6
a103 7
a104 8
a105 9
a106 10
a107 11
a108 12
a109 kW - kVA configuration Error 13
a110 Eco-mode configuration Error 14
a111 Option board alarm 15
sIngle UnIt UPs modbUs tables
15Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
8. 8. Unit mEasUrEmEnts tabLEs: addrEss 0x1220, 80 words
code description unit addressformat
t015=0
format
t015=1
m032 Output voltage U12 v 0x1220 ### ###m033 Output voltage U23 v 1 ### ###m034 Output voltage U31 v 2 ### ###m035 Output voltage L1 v 3 ### ###m036 Output voltage L2 v 4 ### ###m037 Output voltage L3 v 5 ### ###m038 Output current L1 a 6 # ### # ###.#m039 Output current L2 a 7 # ### # ###.#m040 Output current L3 a 8 # ### # ###.#m041 Output frequency x10 hz 9 ##.# ##.#m042 Output Power factor L1 a +/- #.## +/- #.##m043 Output Power factor L2 B +/- #.## +/- #.##m044 Output Power factor L3 c +/- #.## +/- #.##m045 Output Active Power L1 kw d # ### # ###.#m046 Output Active Power L2 kw e # ### # ###.#m047 Output Active Power L3 kw F # ### # ###.#m048 output apparent Power l1 kva 0x1230 # ### # ###.#m049 output apparent Power l2 kva 1 # ### # ###.#m050 output apparent Power l3 kva 2 # ### # ###.#m051 Output Crest Factor 3 #.# #.#m052 Output load rate L1 % 4 ### ###m053 Output load rate L2 % 5 ### ###m054 Output load rate L3 % 6 ### ###m055 Unit load rate % 7 ### ###m056 unit Power S output kva 8 # ### # ###.#m057 unit Power P output kw 9 # ### # ###.#m058 Rectifier input supply volt. U12 v a ### ###m059 Rectifier input supply volt. U23 v B ### ###m060 Rectifier input supply volt. U31 v c ### ###m061 Rectifier V1 v d ### ###m062 Rectifier V2 v e ### ###m063 Rectifier V3 v F ### ###m064 Rectifier input supply frequency x10 hz 0x1240 ##.# ##.#m065 Rectifier input supply current L1 a 1 ###.# ###.#m066 Rectifier input supply current L2 a 2 ###.# ###.#m067 Rectifier input supply current L3 a 3 ###.# ###.#m068 Inverter output voltage U12 v 4 ### ###m069 Inverter output voltage U23 v 5 ### ###m070 Inverter output voltage U31 v 6 ### ###
sIngle UnIt UPs modbUs tables
16 Delphys green power - Ref.: IOMDGPJB0910-GB_07
code description unit addressformatt015=0
formatt015=1
m071 Inverter frequency x10 hz 7 ##.# ##.#m072 Bypass input supply voltage U12 v 8 ### ###m073 Bypass input supply voltage U23 v 9 ### ###m074 Bypass input supply voltage U31 v a ### ###m075 Bypass input supply voltage V1 v B ### ###m076 Bypass input supply voltage V2 v c ### ###m077 Bypass input supply voltage V3 v d ### ###m078 Bypass input supply frequency x10 hz e ###.# ###.#m079 ambient t° °c F ##.# ##.#m080 Vdc + v 0x1250 ### ###m081m082 Battery voltage string + v 2 ### ###.#m083m084 Battery current + a 4 # ### # ###.#m085m086 6m087 7m088 8m089 9m090 am091 Battery t° °c B ##.# ##.#m092 Average battery T° °c c ##.# ##.#m093 Battery capacity ah d # ### # ###.#m094 Battery capacity % e ### ###m095 Remaining backup time mn F ### ###m096 0x1260m097 1m098 2m099 3m100 4m101 5m102 6m103 7m104 8m105 9m106 am107 Bm108 cm109 dm110 em111 F
sIngle UnIt UPs modbUs tables
17Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
8. 9. Unit EnabLEd controLs tabLE: addrEss 0x1150; 1 words
code description Bit address Remarksv007 Eco-mode 7 0x1150v008 Normal-mode 8v032 Unit Start procedure 0 0x1152v033 Reserved 1v034 make unit available 2v035 Switch load to inverter 3v036 Switch load to mains 4v037 Switch off unit output 5v038 6v039 7v040 Rectifier on 8v041 Rectifier off 9v042 inverter on 10v043 inverter off 11v044 12v045 Battery test 13
8. 10. controLs sEnd to UPs: addrEss 0x1190, writE 1 words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using ADICOM interface.The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed, the function will be ignored. Controls available by MODBUS connection:
code description Bit to write address Remarksc007 Eco-mode 7 0x1190c008 Normal-mode 8c032 Unit Start procedure 0 0x1192c033 Reserved 1c034 make unit available 2c035 Switch load to inverter 3c036 Switch load to mains 4c037 Switch off unit output 5 load oFF immediate!!c038 6c039 7c040 Rectifier on 8c041 Rectifier off 9c042 inverter on 10c043 inverter off 11c044 12c045 Battery test 13c046 14c047c048 reset alarm 0 0x1193
sIngle UnIt UPs modbUs tables
18 Delphys green power - Ref.: IOMDGPJB0910-GB_07
9. modBuS In moduLaR PaRaLLeL SyStem confIguRatIon
9. 1. rEmindEr
In UPS parallel system configuration, there is only one MODBUS interface. The addresses mapping gives the pos-
sibility to read data from each unit and system. There is no link between the MODBUS salve number and the unit
number.
The interface is plugged in the ‘com-slots’ in the UPS unit 1 “com slots” in case of modular system (see bellow).
MODBUS link setting
The setting of the link is made from the mimic panel unit where the board is plugged.
How to read data:
In the MODBUS table, one part is dedicated to UPS part; it means the data from the whole system.
This part is the same for each unit. Same data are present in the UPS fields addresses.
unit 1 unit 2 unt 3
uPS data = uPS data = uPS data
unit 1 data unit 2 data unit 3 data
1 2 3
19Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
9. 2. modbUs tabLE in modULar ParaLLEL sYstEm
table Start addresses table Length In words modbus function
UPS Identification 0x0100 32 3 read
Date and hours 0x0360 4 3 read
UPS Configurations 0x0200 16 3 read
UPS Status (48 bits) 0x0140 3 3 read
UNIT Status (64 bits) 0xm143 4 3 read
UPS Alarms (32 bits) 0x0148 2 3 read
UNIT Alarm (80 bits) 0xm14A 5 3 read
uPS measurements 0x0200 32 3 read
unit measurements 0xm220 80 3 read
controls permission 0xm150 4 3 read
uPS controls 0xm190 4 6 write
m = number of unit
Example: 0x3100 = ID of unit 3 0x3140 = UPS States 0x3143 = unit 3 states
9. 3. UPs idEntification: addrEss 0x0100, 32 words
See unit part
9. 4. datE & HoUrs: addrEss 0x0360, 4 words
See unit part
9. 5. UPs configUration: addrEss 0xm120, 16 words
See unit part
9. 6. PrELiminarY rEmarks
The UNIT data are the same as described for single unit.
Following tables describe only the UPS part (common for all units)
modbUs tables In modUlar Parallel system confIgUratIon
20 Delphys green power - Ref.: IOMDGPJB0910-GB_07
9. 7. UPs statUs: addrEss 0x0140, 3 words
code description Bit address Remarks
S000 Load supplied by inverter 0 0x0140
S001 Load on automatic bypass 1
S002 Load on maintenance. Bypass 2
S003 Load not supplied 3
S004 Eco-mode 4
S005 Energy Saver 5
S006 UPS in normal mode 6
S007 UPS Starting procedure in progress 7
S008 UPS on maintenance bypass proc. in progress 8
S009 9
S010 10
S011 11
S012 12
S013 13
S014 14
S015 Remote control enabled 15
S016 Unit 1 operating 0 0x0141
S017 Unit 2 operating 1
S018 Unit 3 operating 2
S019 Unit 4 operating 3
S020 Unit 5 operating 4
S021 Unit 6 operating 5
S022 Unit 7 operating 6
S023 Unit 8 operating 7
S024 8
S025 9
S026 10
S027 11
S028 12
S029 13
S030 14
S031 15
S032 unit 1 available 0 0x0142
S033 unit 2 available 1
S034 unit 3 available 2
S035 unit 4 available 3
S036 unit 5 available 4
S037 unit 6 available 5
S038 unit 7 available 6
S039 unit 8 available 7
modbUs tables In modUlar Parallel system confIgUratIon
21Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
9. 8. UPs aLarms: addrEss 0x0148, 2 words
code description Bit address Remarks
a000 uPS imminent stop 0 0x0148
a001 UPS overload 1
a002 UPS transfer blocked 2
a003 uPS transfer impossible 3
a004 UPS insufficient Resource 4
a005 UPS Redundancy loss 5
a006 Parallel fault 6
a007 7
a008 8
a009 9
a010 10
a011 11
a012 12
a013 13
a014 14
a015 15
a016 Unit 1 general 0 0x0149
a017 Unit 2 general 1
a018 Unit 3 general 2
a019 Unit 4 general 3
a020 Unit 5 general 4
a021 Unit 6 general 5
a022 Unit 7 general 6
a023 Unit 8 general 7
a024 8
a025 9
a026 10
a027 11
a028 12
a029 13
a030 14
a031 15
modbUs tables In modUlar Parallel system confIgUratIon
22 Delphys green power - Ref.: IOMDGPJB0910-GB_07
9. 9. UPs mEasUrEmEnts: addrEss 0x0200, 32 words
code description unit addressformatt015=0
formatt015=1
m000 Output voltage U12 v 0x0200 ### ###
m001 Output voltage U23 v 1 ### ###
m002 Output voltage U31 v 2 ### ###
m003 Output voltage L1 v 3 ### ###
m004 Output voltage L2 v 4 ### ###
m005 Output voltage L3 v 5 ### ###
m006 Output current L1 a 6 # ### # ###.#
m007 Output current L2 a 7 # ### # ###.#
m008 Output current L3 a 8 # ### # ###.#
m009 Output frequency x10 hz 9 ##.# ##.#
m010 Output Power factor L1 a +/- #.## +/- #.##
m011 Output Power factor L2 B +/- #.## +/- #.##
m012 Output Power factor L3 c +/- #.## +/- #.##
m013 Output Active Power L1 kw d # ### # ###.#
m014 Output Active Power L2 kw e # ### # ###.#
m015 Output Active Power L3 kw F # ### # ###.#
m016 output apparent P. l1 kva 0x210 # ### # ###.#
m017 output apparent P. l2 kva 1 # ### # ###.#
m018 output apparent P. l3 kva 2 # ### # ###.#
m019 Output Crest Factor 3 #.# #.#
m020 Output load rate L1 % 4 ### ###
m021 Output load rate L2 % 5 ### ###
m022 Output load rate L3 % 6 ### ###
m023 UPS load rate % 7 ### ###
m024 uPS output power kva 8 # ### # ###.#
m025 9
m026 a
m027 B
m028 c
m029 d
m030 e
m031 F
modbUs tables In modUlar Parallel system confIgUratIon
23Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
9. 10. UPs EnabLEd controLs tabLE: addrEss 0xm150, 2 words
code description Bit address Remarks
UPS Start procedure 0 0xm150
Reserved 1
Transfer load to inverter 2
Transfer load to mains 3
UPS load off 4
Energy Saver ON 5
Energy Saver OFF 6
Eco-mode 7
Normal mode 8
9
10
11
12
13
14
15
Remark: A bit set to 0 means that the control is disabled by the UPS. The control will be not executed.
9. 11. to sEnd controL to UPs: addrEss 0x15b0, writE 1 words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human Machine
Interface. Local controls are then locked.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored.
Controls available by MODBUS connection:
code control value to write address Remarks
UPS Start procedure 1 0xm190
Reserved 2
Transfer load to inverter 4
Transfer load to mains 8
UPS load off 16 immediate load oFF !!
Energy Saver ON 32
Energy Saver OFF 64
Eco-mode 128
Normal mode 256
512
modbUs tables In modUlar Parallel system confIgUratIon
24 Delphys green power - Ref.: IOMDGPJB0910-GB_07
10. modBuS In PaRaLLeL SyStem wIth centRaLISed ByPaSS
10. 1. rEmindEr
In UPS parallel system configuration, there is only one MODBUS interface. The addresses mapping gives the pos-
sibility to read data from each unit and system. There is no link between the MODBUS salve number and the unit
number.
The interface is plugged in the ‘com-slots’ in the UPS unit 1 “com slots” in case of modular system (see bellow).
MODBUS link setting
The setting of the link is made from the mimic panel unit where the board is plugged.
How to read data:
In the MODBUS table, one part is dedicated to UPS part; it means the data from the whole system.
This part is the same for each unit. Same data are present in the UPS fields addresses.
ByPaSS unit 1 unt 2
uPS data = uPS data = uPS data
UNIT BYPASS (15) unit 1 data unit 2 data
By-pass1
2
25Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
10. 2. modbUs tabLE in ParaLLEL sYstEm witH cEntraLisEd bYPass
table Start addresses table Length In words modbus function
UPS Identification 0x0100 32 3 read
Date and hours 0x0360 4 3 read
UPS Configurations 0x0200 16 3 read
UPS Status (48 bits) 0x0140 3 3 read
UNIT Status (64 bits) 0xm143 4 3 read
UPS Alarms (32 bits) 0x0148 2 3 read
UNIT Alarm (80 bits) 0xm14A 5 3 read
uPS measurements 0x0200 32 3 read
unit measurements 0xm220 80 3 read
controls permission 0xm150 4 3 read
uPS controls 0xm190 4 6 write
m = 1- - - - number of modulem = 8
m = 15 Bypass data
Example: 0x3100 = ID of unit 3 0x3140 = UPS States 0xF143 = Bypass 3 states
10. 3. UPs idEntification: addrEss 0x0100, 32 words
See unit part
10. 4. datE & HoUrs: addrEss 0x0360, 4 words
See unit part
10. 5. UPs configUration: addrEss 0xm120, 16 words
See unit part
10. 6. PrELiminarY rEmarks
Following tables describe only the UPS part (common for all units)
modbUs In Parallel system wIth centralIsed byPass
26 Delphys green power - Ref.: IOMDGPJB0910-GB_07
10. 7. UPs statUs: addrEss 0x0140, 3 words
code description Bit address RemarksS000 Load supplied by inverter 0 0x0140
S001 Load on automatic bypass 1
S002 Load on maintenance. Bypass 2
S003 Load not supplied 3
S004 Eco-mode 4
S005 Energy Saver 5
S006 UPS in normal mode 6
S007 UPS Starting procedure in progress 7
S008 UPS on maintenance bypass proc. in progress 8
S009 9
S010 10
S011 11
S012 12
S013 13
S014 14
S015 Remote control enabled 15
S016 Module 1 operating 0 0x0141
S017 Module 2 operating 1
S018 Module 3 operating 2
S019 Module 4 operating 3
S020 Module 5 operating 4
S021 Module 6 operating 5
S022 Module 7 operating 6
S023 Module 8 operating 7
S024 8
S025 9
S026 10
S027 11
S028 12
S029 13
S030 Bypass working 14
S031 15
S032 Module 1 available 0 0x0142
S033 Module 2 available 1
S034 Module 3 available 2
S035 Module 4 available 3
S036 Module 5 available 4
S037 Module 6 available 5
S038 Module 7 available 6
S039 Module 8 available 7
S046 Bypass available 14
modbUs In Parallel system wIth centralIsed byPass
27Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
10. 8. UPs aLarms: addrEss 0x0148, 2 words
code description Bit address Remarks
a000 uPS imminent stop 0 0x0148
a001 UPS overload 1
a002 UPS transfer blocked 2
a003 uPS transfer impossible 3
a004 UPS insufficient Resource 4
a005 UPS Redundancy loss 5
a006 Parallel fault 6
a007 7
a008 8
a009 9
a010 10
a011 11
a012 12
a013 13
a014 14
a015 15
a016 Module 1 general 0 0x0149
a017 Module 2 general 1
a018 Module 3 general 2
a019 Module 4 general 3
a020 Module 5 general 4
a021 Module 6 general 5
a022 Module 7 general 6
a023 Module 8 general 7
a024 8
a025 9
a026 10
a027 11
a028 12
a029 13
a030 Bypass alarm 14
a031 15
modbUs In Parallel system wIth centralIsed byPass
28 Delphys green power - Ref.: IOMDGPJB0910-GB_07
10. 9. UPs mEasUrEmEnts: addrEss 0x0200, 32 words
code description unit addressformatt015=0
formatt015=1
m000 Output voltage U12 v 0x0200 ### ###
m001 Output voltage U23 v 1 ### ###
m002 Output voltage U31 v 2 ### ###
m003 Output voltage L1 v 3 ### ###
m004 Output voltage L2 v 4 ### ###
m005 Output voltage L3 v 5 ### ###
m006 Output current L1 a 6 # ### # ###.#
m007 Output current L2 a 7 # ### # ###.#
m008 Output current L3 a 8 # ### # ###.#
m009 Output frequency x10 hz 9 ##.# ##.#
m010 Output Power factor L1 a +/- #.## +/- #.##
m011 Output Power factor L2 B +/- #.## +/- #.##
m012 Output Power factor L3 c +/- #.## +/- #.##
m013 Output Active Power L1 kw d # ### # ###.#
m014 Output Active Power L2 kw e # ### # ###.#
m015 Output Active Power L3 kw F # ### # ###.#
m016 output apparent P. l1 kva 0x0210 # ### # ###.#
m017 output apparent P. l2 kva 1 # ### # ###.#
m018 output apparent P. l3 kva 2 # ### # ###.#
m019 Output Crest Factor 3 #.# #.#
m020 Output load rate L1 % 4 ### ###
m021 Output load rate L2 % 5 ### ###
m022 Output load rate L3 % 6 ### ###
m023 UPS load rate % 7 ### ###
m024 uPS output power kva 8 # ### # ###.#
m025 9
m026 a
m027 B
m028 c
m029 d
m030 e
m031 F
modbUs In Parallel system wIth centralIsed byPass
29Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
10. 10. UPs EnabLEd controLs tabLE: addrEss 0xm150, 2 words
code description Bit address Remarks
UPS Start procedure 0 0xm150
Reserved 1
Transfer load to inverter 2
Transfer load to mains 3
UPS load off 4
Energy Saver ON 5
Energy Saver OFF 6
Eco-mode 7
Normal mode 8
9
10
11
12
13
14
15
Remark: A bit set to 0 means that the control is disabled by the UPS. The control will be not executed.
10. 11. to sEnd controL to UPs: addrEss 0x15b0, writE 1 words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human Machine
Interface. Local controls are then locked.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored.
Controls available by MODBUS connection:
code control value to write address Remarks
UPS Start procedure 1 0xm190
Reserved 2
Transfer load to inverter 4
Transfer load to mains 8
UPS load off 16 immediate load oFF !!
Energy Saver ON 32
Energy Saver OFF 64
Eco-mode 128
Normal mode 256
512
modbUs In Parallel system wIth centralIsed byPass
30 Delphys green power - Ref.: IOMDGPJB0910-GB_07
11. 1. bYPass statUs: addrEss 0xf143, 4 words
code description Bit address Remarks
S048 Load on inverter 0 0xF143
S049 Load on auto. Bypass 1
S050 Load on maintenance Bypass 2
S051 Load not supplied 3
S052 4
S053 5
S054 Output switch 3 closed 6
S055 7
S056 8
S057 9
S058 10
S059 1
S060 12
S061 Bypass switch activated 13
S062 14
S063 Servicing alert 15
S064 0 0xF144
S065 1
S066 2
S067 3
S068 4
S069 5
S070 6
S071 7
S072 Unit in normal mode 8
S073 9
S074 10
S075 1
S076 12
S077 13
S078 14
S079 Bypass in servicing mode 15
byPass tables
11. ByPaSS taBLe
31Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
code description Bit address Remarks
S080 Starting 0 0xF145
S081 Unit maintenance bypass procedure progress 1
S082 2
S083 3
S084 4
S085 5
S086 6
S087 7
S088 8
S089 9
S090 10
S091 Q4 closed 11
S092 Local maintenance bypass Q5 clos. 12
S093 Remote maintenance bypass closed 13
S094 14
S095 15
S096 Auxiliary input 1 active 0 0xF146
S097 Auxiliary input 2 active 1
S098 Auxiliary input 3 active 2
S099 Auxiliary input 4 active 3
S100 Auxiliary input 5 active 4
S101 Auxiliary input 6 active 5
S102 Auxiliary input 7 active 6
S103 Auxiliary input 8 active 7
S104 Auxiliary input 9 active 8
S105 Auxiliary input 10 active 9
S106 Auxiliary input 11 active 10
S107 Auxiliary input 12 active 11
S108 12
S109 13
S110 14
S111 Acknowledgement alarm request 15
byPass tables
32 Delphys green power - Ref.: IOMDGPJB0910-GB_07
11. 2. bYPass aLarms: addrEss 0xf14a, 4 words
code description Bit address Remarks
a032 unit imminent stop 0 0xF14A
a033 Unit overload 1
a034 Transfer blocked 2
a035 transfer impossible 3
a036 Insufficient Resources 4 only on parallel
a037 5
a038 6
a039 7
a040 8
a041 Bypass critical 9
a042 Common critical 10
a043 Fan alarm 11
a044 Back feed protection open 12
a045 ACS synchro source fault 13
a046 14
a047 15
a048 0 0xF14B
a049 1
a050 2
a051 3
a052 4
a053 5
a054 6
a055 7
a056 8
a057 9
a058 10
a059 11
a060 Bypass preventive 12
a061 13
a062 14
a063 15
a064 0 0xF14C
a065 1
a066 2
a067 3
a068 4
a069 5
a070 6
byPass tables
33Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
code description Bit address Remarks
a071 7
a072 8
a073 9
a074 10
a075 11
a076 12
a077 13
a078 14
a079 15
a080 Preventive maintenance 0 0xF14D
a081 1
a082 Maintenance bypass alarm 2
a083 3
a084 4
a085 5
a086 6
a087 7
a088 8
a089 9
a090 10
a091 11
a092 12
a093 13
a094 Output since xx minutes on auto bypass 14
a095 Bypass General alarm 15
a096 0 0xF14E
a097 1
a098 2
a099 3
a100 4
a101 Aux. input alarm 5 if set
a102 6
a103 7
a104 8
a105 9
a106 10
a107 11
a108 12
a109 13
a110 14
a111 Option board alarm 15
byPass tables
34 Delphys green power - Ref.: IOMDGPJB0910-GB_07
11. 3. bYPass mEasUrEmEnts tabLEs: addrEss 0xf220, 80 words
code description unit addressformat
t015=0
format
t015=1
m032 Output voltage U12 v 0xF220 ### ###m033 Output voltage U23 v 1 ### ###m034 Output voltage U31 v 2 ### ###m035 Output voltage L1 v 3 ### ###m036 Output voltage L2 v 4 ### ###m037 Output voltage L3 v 5 ### ###m038 Output current L1 a 6 # ### # ###.#m039 Output current L2 a 7 # ### # ###.#m040 Output current L3 a 8 # ### # ###.#m041 Output frequency x10 hz 9 ##.# ##.#m042 Output Power factor L1 a +/- #.## +/- #.##m043 Output Power factor L2 B +/- #.## +/- #.##m044 Output Power factor L3 c +/- #.## +/- #.##m045 Output Active Power L1 kw d # ### # ###.#m046 Output Active Power L2 kw e # ### # ###.#m047 Output Active Power L3 kw F # ### # ###.#m048 output apparent Power l1 kva 0xF230 # ### # ###.#m049 output apparent Power l2 kva 1 # ### # ###.#m050 output apparent Power l3 kva 2 # ### # ###.#m051 Output Crest Factor 3 #.# #.#m052 Output load rate L1 % 4 ### ###m053 Output load rate L2 % 5 ### ###m054 Output load rate L3 % 6 ### ###m055 Unit load rate % 7 ### ###m056 unit Power S output kva 8 # ### # ###.#m057 unit Power P output kw 9 # ### # ###.#m058 am059 Bm060 cm061 dm062 em063 Fm064 0xF240m065 1m066 2m067 3m068 4m069 5m070 6
byPass tables
35Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
code description unit addressformatt015=0
formatt015=1
m071 7m072 Bypass input supply voltage U12 v 8 ### ###m073 Bypass input supply voltage U23 v 9 ### ###m074 Bypass input supply voltage U31 v a ### ###m075 Bypass input supply voltage V1 v B ### ###m076 Bypass input supply voltage V2 v c ### ###m077 Bypass input supply voltage V3 v d ### ###m078 Bypass input supply frequency x10 hz e ###.# ###.#m079 ambient t° °c F ##.# ##.#m080 0xF250m081 1m082 2m083 3m084 4m085m086 6m087 7m088 8m089 9m090 am091 Bm092 cm093 dm094 em095 Fm096 0xF260m097 1m098 2m099 3m100 4m101 5m102 6m103 7m104 8m105 9m106 am107 Bm108 cm109 dm110 em111 F
byPass tables
36 Delphys green power - Ref.: IOMDGPJB0910-GB_07
12. 1. modULE statUs: addrEss 0xm143, 4 words
code description Bit address Remarks
S048 Load on inverter 0 0xm143
1
2
S051 Load not supplied 3
S052 Module is available 4
S053 Module isolated from inst. 5
S054 Output switch 2 closed 6
S055 Rectifier ON 7
S056 Battery charging 8
S057 Battery charged 9
S058 10
S059 inverter on 11
S060 Inverter switch/contactor closed 12
S061 13
S062 14
S063 Servicing alert 15
S064 Rectifier input supply fault 0 0xm144
S065 Bypass input supply out of tolerance 1
S066 2
S067 Bypass input supply is synchro ref 3
S068 4
S069 5
S070 “UPS general power off” input active 6
S071 Generator set active 7
S072 Module in normal mode 8
S073 Module in eco-mode 9
S074 10
S075 Module in stand-by mode 11
S076 12
S077 13
S078 14
S079 Module in servicing mode 15
12. moduLe taBLe
37Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
code description Bit address Remarks
S080 Module Start procedure progress 0 0xm145
S081 1
S082 2
S083 Battery test interrupted 3
S084 Battery test in progress 4
S085 Battery test in stand-by 5
S086 6
S087 7
S088 8
S089 9
S090 Q1 closed 10
S091 11
S092 12
S093 13
S094 Q21 switch closed 14
S095 Q22 switch closed 15
S096 Auxiliary input 1 active 0 0xm146
S097 Auxiliary input 2 active 1
S098 Auxiliary input 3 active 2
S099 Auxiliary input 4 active 3
S100 Auxiliary input 5 active 4
S101 Auxiliary input 6 active 5
S102 Auxiliary input 7 active 6
S103 Auxiliary input 8 active 7
S104 Auxiliary input 9 active 8
S105 Auxiliary input 10 active 9
S106 Auxiliary input 11 active 10
S107 Auxiliary input 12 active 11
S108 12
S109 13
S110 14
S111 Acknowledgement alarm request 15
modUle tables
38 Delphys green power - Ref.: IOMDGPJB0910-GB_07
12. 2. modULE aLarms: addrEss 0xm14a, 4 words
code description Bit address Remarks
a032 unit imminent stop 0 0xm14A
a033 Module overload 1
a034 2
a035 3
a036 4
a037 5
a038 6
a039 Rectifier critical 7
a040 Inverter critical 8
a041 9
a042 Common critical 10
a043 Fan alarm 11
a044 Back feed protection open 12
a045 13
a046 14
a047 15
a048 Operating on battery 0 0xm14B
a049 Battery alarm 1
a050 Battery room 2
a051 Battery discharged 3
a052 End of autonomy time 4
a053 Battery test failure 5
a054 Earth leakage fault 6
a055 Battery circuit open 7
a056 on battery with mains oK 8
a057 DC voltage not OK 9
a058 Rectifier preventive 10
a059 inverter preventive 11
a060 12
a061 common preventive 13
a062 Mimic panel 14
a063 Ambient T° max 15
a064 BHC general alarm 0 0xm14C
a065 1
a066 2
a067 3
a068 4
a069 5
a070 6
modUle tables
39Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
code description Bit address Remarks
a071 7
a072 8
a073 9
a074 10
a075 11
a076 12
a077 13
a078 14
a079 15
a080 Preventive maintenance 0 0xm14D
a081 1
a082 2
a083 rotation phase fault 3
a084 4
a085 5
a086 6
a087 7
a088 8
a089 9
a090 10
a091 11
a092 12
a093 13
a094 14
a095 unit General alarm 15
a096 Fly Wheel disconnected 0 0xm14E
if seta097 Fly Wheel Critical 1
a098 Fly wheel preventive 2
a099 3
a100 4
a101 Aux. input alarm 5 if set
a102 6
a103 7
a104 8
a105 9
a106 10
a107 11
a108 12
a109 kW - kVA configuration Error 13
a110 Eco-mode configuration Error 14
a111 Option board alarm 15
modUle tables
40 Delphys green power - Ref.: IOMDGPJB0910-GB_07
12. 3. modULE mEasUrEmEnts tabLEs: addrEss 0xm220, 80 words
code description unit addressformat
t015=0
format
t015=1
m032 Output voltage U12 v 0xm220 ### ###m033 Output voltage U23 v 1 ### ###m034 Output voltage U31 v 2 ### ###m035 Output voltage L1 v 3 ### ###m036 Output voltage L2 v 4 ### ###m037 Output voltage L3 v 5 ### ###m038 Output current L1 a 6 # ### # ###.#m039 Output current L2 a 7 # ### # ###.#m040 Output current L3 a 8 # ### # ###.#m041 Output frequency x10 hz 9 ##.# ##.#m042 Output Power factor L1 a +/- #.## +/- #.##m043 Output Power factor L2 B +/- #.## +/- #.##m044 Output Power factor L3 c +/- #.## +/- #.##m045 Output Active Power L1 kw d # ### # ###.#m046 Output Active Power L2 kw e # ### # ###.#m047 Output Active Power L3 kw F # ### # ###.#m048 output apparent Power l1 kva 0xm230 # ### # ###.#m049 output apparent Power l2 kva 1 # ### # ###.#m050 output apparent Power l3 kva 2 # ### # ###.#m051 Output Crest Factor 3 #.# #.#m052 Output load rate L1 % 4 ### ###m053 Output load rate L2 % 5 ### ###m054 Output load rate L3 % 6 ### ###m055 Unit load rate % 7 ### ###m056 unit Power S output kva 8 # ### # ###.#m057 unit Power P output kw 9 # ### # ###.#m058 Rectifier input supply volt. U12 v a ### ###m059 Rectifier input supply volt. U23 v B ### ###m060 Rectifier input supply volt. U31 v c ### ###m061 Rectifier V1 v d ### ###m062 Rectifier V2 v e ### ###m063 Rectifier V3 v F ### ###m064 Rectifier input supply frequency x10 hz 0xm240 ##.# ##.#m065 Rectifier input supply current L1 a 1 ###.# ###.#m066 Rectifier input supply current L2 a 2 ###.# ###.#m067 Rectifier input supply current L3 a 3 ###.# ###.#m068 Inverter output voltage U12 v 4 ### ###m069 Inverter output voltage U23 v 5 ### ###m070 Inverter output voltage U31 v 6 ### ###
modUle tables
41Delphys green power - Ref.: IOMDGPJB0910-GB_07
EN
GLI
SH
code description unit addressformatt015=0
formatt015=1
m071 Frequency inverter x10 hz 7 ##.# ##.#m072 v 8 ### ###m073 v 9 ### ###m074 v a ### ###m075 v B ### ###m076 v c ### ###m077 v d ### ###m078 hz e ###.# ###.#m079 ambient t° °c F ##.# ##.#m080 Vdc + v 0xm250 ### ###m081m082 Battery voltage string + v 2 ### ###.#m083m084 Battery current + a 4 # ### # ###.#m085m086 6m087 7m088 8m089 9m090 am091 Battery t° °c B ##.# ##.#m092 Average battery T° °c c ##.# ##.#m093 Battery capacity ah d # ### # ###.#m094 Battery capacity % e ### ###m095 Remaining backup time mn F ### ###m096 0xm260m097 1m098 2m099 3m100 4m101 5m102 6m103 7m104 8m105 9m106 am107 Bm108 cm109 dm110 em111 F
modUle tables
42 Delphys green power - Ref.: IOMDGPJB0910-GB_07
VALID FOR FRANCE VALID FOR ITALY
ISO 9001FM 28237
ISO14001EMS 553476
Non contractual document. © 2011, Socomec SA. All rights reserved.
www.socomec.com
VALID FOR FRANCE VALID FOR ITALY
ISO 9001FM 28237
ISO14001EMS 553476
YOUR DISTRIBUTOR
HEAD OFFICE
SOCOMEC GROUPS.A. SOCOMEC capital 11 149 200 € - R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC UPS Strasbourg11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 [email protected]
SOCOMEC UPS Isola VicentinaVia Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY Tel. +39 0444 598611 - Fax +39 0444 598622 [email protected]
SALES, MARKETING AND SERVICE MANAGEMENT
SOCOMEC UPS Paris95, rue Pierre Grange F-94132 Fontenay-sous-Bois Cedex - FRANCE Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12 [email protected]
Socomec UPS worldwideIN WESTERN EUROPE
BELGIUMSchaatsstraat, 30 rue du Patinage B - 1190 Bruxelles Tel. +32 (0)2 340 02 34 [email protected]
FRANCE95, rue Pierre Grange F - 94132 Fontenay-sous-Bois Cedex Tel. +33 (0)1 45 14 63 90 [email protected]
GERMANYHeppenheimer Straße 57 D - 68309 Mannheim Tel. +49 (0) 621 71 68 40 [email protected]
ITALYVia Leone Tolstoi, 73 - Zivido 20098 San Giuliano Milanese (MI) Tel. +39 02 98 242 942 [email protected]
PORTUGALNúcleo Empresarial de Mafra II Av. Dr. Francisco Sá Carneiro, Fracção N 2640-486 Mafra Tel. +351 261 812 599 [email protected]
SPAINC/Nord, 22 Pol. Ind. Buvisa E - 08329 Teià (Barcelona) Tel. +34 935 407 575 [email protected]
THE NETHERLANDSDuwboot 13 NL - 3991 CD Houten Tel. +31 (0)30 760 0911 [email protected]
UNITED KINGDOMUnits 7A-9A Lakeside Business Park Broadway Lane - South Cerney Cirencester - GL7 5XL Tel. +44 (0)1285 863300 [email protected]
OTHER COUNTRIESTel. +34 935 407 575 [email protected]
IN EASTERN EUROPE, MIDDLE EAST, AFRICA
POLANDul. Mickiewicza 63 01-625 Warszawa Tel. +48 22 825 73 60 [email protected]
ROMANIAHeliade Intre Vii Street no.8, 2 District 023383 Bucharest Tel. +40 21 319 36 88 ( 89, 81, 82) [email protected]
RUSSIA4th Street 8 Marta, 6A, 405 125167 - Moscow Tel. +7 495 775 19 85 [email protected]
SLOVENIASavlje 89 SI - 1000 Ljubljana Tel. +386 1 5807 860 [email protected]
TURKEYMasuklar Yokusu No:57/2 34357 Besiktas Istanbul Tel. +90 212 2580810 [email protected]
OTHER COUNTRIESTel. +39 0444 598 611 [email protected]
IN ASIA PACIFIC
AUSTRALIAUnit 3, 2 Eden Park Drive (Rydecorp) Macquarie Park NSW 2113 Tel. +61 2 9325 3900 [email protected]
CHINAUniversal Business Park B33, 3rd Fl, 10 Jiuxianqiao Rd., Chaoyang, Beijing 100016 P.R., China Tel. +86 10 59756108 [email protected]
INDIAB1, IInd Floor, Thiru-Vi-Ka-Industrial Estate Guindy Chennai – 600 032 Tel. +91 44 3921 5400 [email protected]
MALAYSIA31 Jalan SS 25/41- Mayang Industrial Park 47301 Petaling Jaya.- Selangor, Malaysia Tel. +603 7804 1153 [email protected]
SINGAPORE 31 Ubi Road 1, Aztech Building # 01-00 (Annex) - SG - Singapore 408694 Tel. +65 6745 7555 [email protected]
THAILANDNo.9 Soi Vibhavadirangsit 42 Vibhavadirangsit Rd, Ladyao Chatujak Bangkok 10900 Tel. +66 2 941-1644-7 [email protected]
VIETNAM539/23 Luy Ban Bich St., Phu Thanh Ward, Tan Phu Dist Ho Chi Minh City Tel. +84-839734.990 [email protected]
ASIA PACIFIC HEAD OFFICETel. +65 6507 [email protected]
IN AMERICA
LATIN AMERICAN COUNTRIESTel. +34 935 407 575 [email protected]