model cws concealed sprinkler - johnson...

2
Model CWS Concealed Sprinkler Specific Application Window Sprinkler Features & Benefits Designed to provide a two-hour fire- resistance-rating to protect non-rated glazing UL and C-UL Listed as a specific application automatic window sprinkler Compliant with the International Building Code, fire-resistant rating evaluated in ICC ESR-2397 Flat-plate design conceals the sprinkler above the ceiling Protect glass and your design At-A-Glance The TYCO ® Model CWS Window Sprinkler is a specific application sprinkler that is a cost-effective alternative to fire-rated glass. The sprinkler discharges an even coat of water when activated, which cools the window to help prevent shattering in a fire event. The flat-plate concealed design houses the sprinkler above the ceiling and the cover plate is available in a variety of colors and finishes, as well as in custom, factory-painted colors. This solution offers the cost- saving and aesthetic benefits of using non-fire-rated glass, while also providing an effective fire protection solution that blends into the ceiling. This sprinkler is part of a full window sprinkler line that includes horizontal sidewall and pendent models. It also joins the TYCO ® family of aesthetic fire sprinklers, including commercial flat-plate concealed models.

Upload: others

Post on 31-May-2020

2 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Model CWS Concealed Sprinkler - Johnson Controlstycofpp.com/uploads/media/FS2002001_ConcealedWindow... · 2020-03-09 · TFP620 for Model WS) for complete description of all Listing

Model CWS Concealed SprinklerSpecific Application Window Sprinkler

Features & Benefits

• Designed to provide a two-hour fire-resistance-rating to protect non-rated glazing

• UL and C-UL Listed as a specific application automatic window sprinkler

• Compliant with the International Building Code, fire-resistant rating evaluated in ICC ESR-2397

• Flat-plate design conceals the sprinkler above the ceiling

Protect glass and your design

At-A-GlanceThe TYCO® Model CWS Window Sprinkler is a specific application sprinkler that is a cost-effective alternative to fire-rated glass. The sprinkler discharges an even coat of water when activated, which cools the window to help prevent shattering in a fire event.

The flat-plate concealed design houses the sprinkler above the ceiling and the cover plate is available in a variety of colors and finishes, as well as in custom, factory-painted colors. This solution offers the cost-saving and aesthetic benefits of using non-fire-rated glass, while also providing an effective fire protection solution that blends into the ceiling.

This sprinkler is part of a full window sprinkler line that includes horizontal sidewall and pendent models. It also joins the TYCO® family of aesthetic fire sprinklers, including commercial flat-plate concealed models.

Page 2: Model CWS Concealed Sprinkler - Johnson Controlstycofpp.com/uploads/media/FS2002001_ConcealedWindow... · 2020-03-09 · TFP620 for Model WS) for complete description of all Listing

Always refer to the Technical Data Sheet (TFP621 for Model CWS and TFP620 for Model WS) for complete description of all Listing criteria, design parameters, installation instructions, care and maintenance guidelines.

Model WS TY3488 – Pendent Vertical Sidewall

Customer Service: Tel: 800.558.5236 • Fax: 800.877.1295Technical Service: Tel: 800.381.9312 • Fax: 800.791.5500

www.tyco-fire.com

© 2020 Johnson Controls. All rights reserved. FS2002001-Letter FEB 2020

Available models

Model CWS TY3498 – Concealed Pendent Vertical Sidewall

Model WS Pendent Vertical Sidewall Sprinkler – typical installation

Model CWS Concealed Pendent Vertical Sidewall Window Sprinkler – typical installation

Model WS TY3388 – Horizontal Sidewall

NO MAXIMUM

MODEL WS SPRINKLER

GLAZING FOR CLARITYSHOWN ON ONE SIDE OF

3" (76,2 mm)± 1" (25,4 mm)

4" (101,6 mm)HEIGHTTO 12" (304,8 mm)

EXPOSED

HEIGHTGLAZING

13'-0"

MAXIMUM(3,96 m)

NON-OPERABLEGLASS WINDOW

FLOW DIRECTION

DEFLECTOR

INDICATED ONSPRINKLER

MAXIMUMNO

FRAMEWINDOW

DISTANCE

STRUCTURECENTERLINE

OF SPRINKLERWATERWAY

BUILDING

FLUSHOR EXPOSED

WINDOWFRAME

6" to 12"(152 to

305 mm)

SPRAY

2"±2"(50,8 mm

±50,8 mm)

MODEL CWS SPRINKLER

GLAZING FOR CLARITYSHOWN ON ONE SIDE OF

HEIGHT

EXPOSED

HEIGHTGLAZING

13'-0"

MAXIMUM(3,96 m)

NON-OPERABLEGLASS WINDOW

MAXIMUMNO

STRUCTURECENTERLINE

OF SPRINKLERWATERWAY

BUILDING