model cws concealed sprinkler - johnson controls · 2020. 3. 9. · model cws concealed sprinkler...
TRANSCRIPT
-
Model CWS Concealed SprinklerSpecific Application Window Sprinkler
Features & Benefits
• Designed to provide a two-hour fire-resistance-rating to protect non-rated glazing
• UL and C-UL Listed as a specific application automatic window sprinkler
• Compliant with the International Building Code, fire-resistant rating evaluated in ICC ESR-2397
• Flat-plate design conceals the sprinkler above the ceiling
Protect glass and your design
At-A-GlanceThe TYCO® Model CWS Window Sprinkler is a specific application sprinkler that is a cost-effective alternative to fire-rated glass. The sprinkler discharges an even coat of water when activated, which cools the window to help prevent shattering in a fire event.
The flat-plate concealed design houses the sprinkler above the ceiling and the cover plate is available in a variety of colors and finishes, as well as in custom, factory-painted colors. This solution offers the cost-saving and aesthetic benefits of using non-fire-rated glass, while also providing an effective fire protection solution that blends into the ceiling.
This sprinkler is part of a full window sprinkler line that includes horizontal sidewall and pendent models. It also joins the TYCO® family of aesthetic fire sprinklers, including commercial flat-plate concealed models.
-
Always refer to the Technical Data Sheet (TFP621 for Model CWS and TFP620 for Model WS) for complete description of all Listing criteria, design parameters, installation instructions, care and maintenance guidelines.
Model WS TY3488 – Pendent Vertical Sidewall
Customer Service: Tel: 800.558.5236 • Fax: 800.877.1295Technical Service: Tel: 800.381.9312 • Fax: 800.791.5500
www.tyco-fire.com
© 2020 Johnson Controls. All rights reserved. FS2002001-Letter FEB 2020
Available models
Model CWS TY3498 – Concealed Pendent Vertical Sidewall
Model WS Pendent Vertical Sidewall Sprinkler – typical installation
Model CWS Concealed Pendent Vertical Sidewall Window Sprinkler – typical installation
Model WS TY3388 – Horizontal Sidewall
NO MAXIMUM
MODEL WS SPRINKLER
GLAZING FOR CLARITYSHOWN ON ONE SIDE OF
3" (76,2 mm)± 1" (25,4 mm)
4" (101,6 mm)HEIGHTTO 12" (304,8 mm)
EXPOSED
HEIGHTGLAZING
13'-0"
MAXIMUM(3,96 m)
NON-OPERABLEGLASS WINDOW
FLOW DIRECTION
DEFLECTOR
INDICATED ONSPRINKLER
MAXIMUMNO
FRAMEWINDOW
DISTANCE
STRUCTURECENTERLINE
OF SPRINKLERWATERWAY
BUILDING
FLUSHOR EXPOSED
WINDOWFRAME
6" to 12"(152 to
305 mm)
SPRAY
2"±2"(50,8 mm
±50,8 mm)
MODEL CWS SPRINKLER
GLAZING FOR CLARITYSHOWN ON ONE SIDE OF
HEIGHT
EXPOSED
HEIGHTGLAZING
13'-0"
MAXIMUM(3,96 m)
NON-OPERABLEGLASS WINDOW
MAXIMUMNO
STRUCTURECENTERLINE
OF SPRINKLERWATERWAY
BUILDING