8/13/2019 Model of Generator Saturation for Use in Power System Studies http://slidepdf.com/reader/full/model-of-generator-saturation-for-use-in-power-system-studies 1/5 Model of generator saturation for use in power  - system studies G Shackshaft, B.Eng., Ph.D., Mem. I.E.E.E., C.Eng., F.I.E.E., and P.B. Henser, M.Sc, Ph.D., D.I.C., A.C.G.I., C.Eng.. M.I.E.E. Indexing terms: Electric  generators,  Electric  reactance, Magnetisation,  Power  systems Abstract The representation of magnetic saturation of generators in power system studies is re-examined in the light of new test data obtained on  5 MW  and 660  MW  units. A new saturation model, of adequate simplicity for use in multi- machine studies, is formulated and checked for accuracy. The parameters for use in the model are obtained firstly from no-load measurements but later in the paper it is shown that the parameters can be obtained from on-load measurements. The primary incentive for the work was to devise a method for the accurate calculation of generator rotor angle when operating at leading power factors. In the event, the model is shown to produce accurate calculation of both rotor angle and excitation requirements over the whole of the normal operating range. List of symbols Xdo,Xqo  = unsaturated synchronous reactances (i.e. airgap-line values) Xd,Xq  = saturated synchronous reactances Xado, X a qo  =  unsaturated mutual reactances Xad  Xaq   saturated mutual reactances X a  = armature leakage reactance Xsai  —  X d0  ~X qo  = saliency reactance Xi  = saturated mutual reactance of intermediate axis 0 = angle between airgap voltage and direct axis (degrees) 5 = rotor angle, degrees V ag  —  airgap-line voltage Id .  Iq  =  stator currents Suffixes  d  and  q  indicate direct- and quadrature-axis parameters, respectively. Unless otherwise stated, all parameters are in per-unit. 1 Introduction Accurate calculation of iron-saturation effects in synchronous machines has been the objective of many workers during the last decade. The methods employed have been based on the use of digital computers and have been categorised as finite-difference, 1  finite- element 2  and discrete-reluctance 3  methods. All have examined the problem from the machine designer's point of view, and have been primarily concerned with the accuracy of calculation of excitation requirements, and, hence, very complex models have been solved; in general, computation time has been of secondary importance. In the same period, power-system analysts have come to under- stand the importance of machine saturation in large-scale system studies and have been seeking suitable analytical methods. Here, the main concern is to devise a simple model which is very efficient in computing time, bearing in mind that a power system involving many machines is likely to be studied, and yet to have a model which is sufficiently accurate for the purposes for which it is being used. The main problem has recently been identified as that of calculating or measuring the saturation characteristic of the quadrature axis to enable an accurate calculation of generator rotor-angle to be made. The importance of quadrature-axis saturation was generally recognised as a result of an international exercise organised by CIGRE 4 which was based on system fault tests carried out by the CEGB on an underexcited 120  MW  generator at Northfleet Power Station. 5  The exercise was primarily concerned with comparing the accuracy of calculation of mechanical and electromagnetic transients, but an important byproduct was that it revealed errors in the calculation of the starting rotor-angle of the test generator. This led to a further CIGRfi investigation 6  which sought to collect test evidence on the saturation characteristics of generators, particularly of the quadrature axis, and on the models used to represent it in computer programs. On the basis of the test evidence submitted, it was concluded that, for large modern machines, the saturation characteristics of the direct and quadrature axes are quite different, and that the errors in the calcu-  per  8368P first received 1st December 1978 and in revised form 17th April 1979 Dr. Shackshaft and Dr. Henser are with the System Technical Branch Planning Department Central Electricity Generating Board 15 Newgate Street London EC1A  7A U England PROC.  IEE, Vol. 126, No. 8, AUGUST  1979 lation of the initial rotor-angle in the Northfleet exercise were due to inadequate representation of saturation in the quadrature axis. It was also concluded that none of the saturation models in use could adequately represent all the observed effects, and that further test evidence, involving both no-load and on-load results on a generator, was required. The CEGB has since carried out a number of such measurements on large generators (two 500 MW  and one 660  MW  units), and these have enabled a new saturation model to be formulated and validated; the purpose of this paper is to report this work. 2 The representation of saturation 2.1 Mathematical model The saturation characteristics of the direct and quadrature axes are represented by the following two equations (Fig.  1  refers): 0)  2) =  l+ m d (V*W)  = l+m Q Hence, given the airgap voltage in the axis under consideration, the mutual reactances in the direct and quadrature axes are given by X ad s  = X aqs  =  3)  4) excitation current, p.u Fig 1 Normalised saturation characteristics a Airgap line b Direct axis c  Quadrature axis 759 0020-3270/79/080759  05 $01-50/0

Upload: yourou1000

Post on 04-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Model of Generator Saturation for Use in Power System Studies

8/13/2019 Model of Generator Saturation for Use in Power System Studies

http://slidepdf.com/reader/full/model-of-generator-saturation-for-use-in-power-system-studies 1/5

Model of generator saturation for use in power -system studiesG Shackshaft, B.Eng., Ph.D., Mem. I.E.E.E., C.Eng., F.I.E.E., and P.B. Henser, M.Sc, Ph.D., D.I.C., A.C.G.I., C.Eng.. M.I.E.E.

Indexing terms:  Electric generators, Electric  reactance, Magnetisation, Power systems

Abstract

The representation of magnetic saturation of generators in power system studies is re-examined in the light of newtest data obtained on  5 MW  and 660 MW  units. A new saturation m odel, of adequate simplicity for use in multi-machine studies, is formulated and checked for accuracy. The parameters for use in the model are obtained firstlyfrom no-load measurements but later in the paper it is shown that the parameters can be obtained from on-loadmeasurements. The primary incentive for the work was to devise a method for the accurate calculation of generatorrotor angle when operating at leading power factors. In the event, the model is shown to produce accuratecalculation of both rotor angle and excitation requirements over the whole of the normal operating range.

List of symbols

Xdo,Xqo  = unsaturated synchronous reactances (i.e. airgap-linevalues)

Xd,Xq  = saturated synchronous reactancesXado, Xaqo  =  unsaturated mutual reactancesXad  Xaq  — saturated mutual reactances

Xa  = armature leakage reactance

Xsai  —  Xd0  ~Xqo  = saliency reactanceXi   = saturated mutual reactance of intermediate axis

0 = angle between airgap voltage and direct axis (degrees)5 = rotor angle, degrees

Vag  — airgap-line voltageId .  Iq

  =  stator currents

Suffixes  d  and  q  indicate direct- and quadrature-axis parameters,respectively. Unless otherwise stated, all parameters are in per-un it.

1 Introduction

Accurate calculation of iron-saturation effects in synchrono usmachines has been the objective of many workers during the lastdecade. The methods employed have been based on the use of digitalcompu ters and have been categorised as finite-diff erence ,

1  finite-

element2  and discrete-reluctance3  meth ods. All have examined theproblem from the machine designer's point of view, and have beenprimarily concerned with the accuracy of calculation of excitationrequirements, and, hence, very complex models have been solved; ingeneral, computation time has been of secondary importance.

In the same period, power-system analysts have come to under-stand the importance of machine saturation in large-scale systemstudies and have been seeking suitable analytical methods. Here, themain concern is to devise a simple model which is very efficient incomputing time, bearing in mind that a power system involving manymachines is likely to be studied, and yet to have a model which issufficiently accurate for th e purposes for which it is being used. Themain problem has recently been identified as that of calculating ormeasuring the saturation characteristic of the quadrature axis toenable an accurate calculation of generator rotor-angle to be made.

The importance of quadrature-axis saturation was generallyrecognised as a result of an international exercise organised by CIGRE4

which was based on system fault tests carried out by the CEGB on anunderexcited 120 MW  generator at Northfleet Power Station .

5  The

exercise was primarily concerned with comparing the accuracy ofcalculation of mechanical and electromagnetic transients, but animportant byproduct was that it revealed errors in the calculation ofthe starting rotor-angle of the test generator. This led to a furtherCIGRfi investigation

6  which sought to collect test evidence on the

saturation characteristics of generators, particularly of the quadratureaxis, and on the models used to represent it in computer programs. Onthe basis of the test evidence submitted, it was concluded that, forlarge modern machines, the saturation characteristics of the direct andquadrature axes are quite different, and that the errors in the calcu-

  per  8368P first received 1st December 1978 and in revised form 17th April1979

Dr. Shackshaft and Dr. Henser are with the System Technical Branch PlanningDepartment Central Electricity Generating Board 15 Newgate Street LondonEC1A   7A U England

PROC.  IEE, Vol. 126, No. 8, AUGUST  1979

lation of the initial rotor-angle in the Northfleet exercise were due toinadequate representation of saturation in the quadrature axis. It wasalso concluded that none of the saturation models in use couldadequately represent all the observed effects, and that further testevidence, involving both no-load and on-load results on a generator,was required.

The CEGB has since carried out a number of such measurementson large generators (two 500 MW  and one 660 MW  units), and thesehave enabled a new saturation model to be formulated and validated;the purpose of this paper is to report this work.

2 The representation of saturation

2.1 Mathematical model

The saturation characteristics of the direct and quadratureaxes are represented by the following two equations (Fig.  1 refers):

0)

 2 )

=  l+ md

(V*W)  = l+mQ

Hence, given the airgap voltage in the axis under consideration, themutual reactances in the direct and quadrature axes are given by

Xads  =

Xaqs  =

 3 )

 4 )

excitation current, p.u

Fig 1

Normalised saturation characteristics

a  Airgap lineb  Direct axisc  Quadrature axis

759

0020-3270/79/080759   05 $01-50/0

Page 2: Model of Generator Saturation for Use in Power System Studies

8/13/2019 Model of Generator Saturation for Use in Power System Studies

http://slidepdf.com/reader/full/model-of-generator-saturation-for-use-in-power-system-studies 2/5

The above representation  of saturation characteristics is not new. It isbeing used in many computer programs for power-system analysis, but

this particular representation  is not an  important aspect of the modeldescribed herein.

The first assumption used in the model, which is based  on experi-mental observation, is that there is a sinusiodal variation of permeancein  the  airgap between  the  direct  and  quadrature axes. Hence, the

mutual reactance  in any  intermediate axis  Xt),  for a  given airgapvoltage is defined by

Xi   =  Xads  cos 0 + Xaqs  sin  6  5)

The second assumptipn used  in the  model, which  is  also based on

experimental observation, is

 that the

  difference between the

 saturatedvalues of the direct- and quadrature-axis mutual reactances is constant(X sa{),   and that these reactances are sinusiodally distributed about the

intermediate mutual reactance  Xt)  according  to the  following  two

equations:

Jinrl  — i  • ^sril  Si n  0

XaQ  =  .

• +  Xggi sin  6 p)

+ Xulco s26  7)

The saturated values of the corresponding synchronous reactances are

given by

y  - y  + X 9)Aq  —

 Aaq

  Aa   ̂

The mutual reactance variations associated with the above assumptions

are portrayed in Fig. 2.

30 60 90

9,degrees

Fig. 2

Diagrammatic portrayal of assumed variations of mutual reactances

2.2 Reasons fo r choice of  model

The test information, which  led to the  choice  of the modeldescribed above, was  obtained somewhat  by  accident, since it camefrom tests which were  not intended  to  explore saturation character-istics. The tests, w hich are known as  either stator-decrement  or  flux-decay tests and are used  to  obtain transient parameters, were carriedout with  the  initial airgap voltage  in  various positions between  the

direct  and quadrature axes; each test was carried out from rated statorvoltage (hence approximately constant airgap voltage) with  the  fieldwinding  on  open circuit, and it is the  initial conditions for the testthat provide the key information. Such tests were carried out on onlyone (generator C) of the three generators to be discussed herein.

From  the  measured initial values  of  active  and  reactive powers,stator voltage  and  current  and  rotor angle, and  using  the equationsgiven in Appendix 9, values were calculated  for the mutual reactanceof  the  axis  in  which  the airgap was positioned  Xt) and also for the

mutual reactances  in the  direct  Xad)  and  quadrature  Xaq)  axes.These calculated values are shown  in  Fig. 3, and whereas  the curves,drawn using  the  assumption stated above, do not  give a perfect  fit,

the agreement is sufficient to justify investigation of the assumptions.

Two points need  be made at  this stage regarding  the assumptionsand the fitted test points shown in Fig. 3:

(i) The sinusoidal variation of the reactance  Xt) is entirely consist-ent with Park's original formulation  of the  2-axis model.

7  Park

ignored saturation in postulating sinusoidal variations, but the p roposedmodel includes saturation  and  postulates sinusoidal variations  for

constant airgap voltage.

(ii) The assumption that there  is a  constant difference betweendirect-  and quadrature-axis synchronous reactances (i.e. regardless of

load, saturation,  etc.) has no  sound theoretical basis, and it  must be

judged on the overall effectiveness  of the model.

2.3 Data for the model

The essential data  are the  saturation characteristics  of  bothdirect and quadrature axes.The characteristic of the direct axis presents no problem  as this is

always measured in the works prior  to dispatch to the site. H owever,owing to  repairs, many generator stators are not now associated withthe rotors with which they were works-tested,  and so new  open-circuit characteristics were measured  on  site  for  each  of the threegenerators discussed herein. Additionally, measurements were made of

the saturation characteristic using  the  alternative method,  in  whichthe generator  is  excited from  the  power system with  its rotor angleheld  at zero and with  no field excitation; the stator voltage is variedusing  the  generator transformer taps. Good agreement  was obtained

30 60 90

6.degrees

Fig. 3

Measured mutual reactances and fitted curves

x Interdediate axiso Direct axis0 Quadrature axis

760 PROC. IEE, Vol. 126, No. 8, AUGUST 1979

Page 3: Model of Generator Saturation for Use in Power System Studies

8/13/2019 Model of Generator Saturation for Use in Power System Studies

http://slidepdf.com/reader/full/model-of-generator-saturation-for-use-in-power-system-studies 3/5

Table 1PARAMETERS FOR SATURATION MODEL

Parameter

Rated MWPower factor

md

 

Data source

DesignDesignTestCalculationCalculationTestTestTestTest

GeneratorA

66 00-852-0551-810-18500857 00-428 0

GeneratorB

50 00-852-772-470-170 1 67-00-378 0

GeneratorC

50 00-852-712-500-2000957 00-398-0

Table 2

MEAN ERRORS IN

LATIONS

Number of testsMean rotor-angleerror, degreesMean field-currenterror,

ROTOR ANGLE

Generator

A

450-22

1-26

AND F IELD C UR R ENT C ALC U-

Generator

B

351 1 9

1 1 2

Generator

C

490-26

- 1 0 9

1-0r

09

 a.d, 08o>o

0-5 -

0-2 03 0 4 0-5

quad rature-a xis current, p.u

0-6

Fig. 4Measured points on saturation characteristic of quadrature axis andfitted curve

n f l0 5

b

-10 -5 15

_n-10 10 15

-5 -10 -5

active iopower,p

-0-5

lead

0 5 10

reac tive power, p.u. lag

Fig.  5Performance chart of generator show ing typical range of test points(Generator A)

• Normal operating boundaryTest point

between the results obtained from the two methods for all threegenerators , and, thus, some test justification w as obtained for the

calculated values of the armature leakage reactance   (Xa).

The saturation characteristic of the quadrature axis presents rather

more of a problem. It has to be measured on site with the generator

excited from the power system , as described above for the direct axis,

PROC. 1EE, Vol. 126, No. 8, AUGUST 1979

Fig. 6Histograms of rotor-angle and field-current errors

a, b  an d  c Rotor-angle er rors for gen erators A, B and C, respectively

d, e  and / Field-current errors for g enerators A , B and C, respectively

but with the rotor angle held at 90°. The problem lies in extrapolating

the m easured results, the range of which is limited by the gene ratortransformer taps, to cover the full range of operating flux levels. The

points in Fig. 4 show a typical range of test results, and it can be seen

that the voltage can neither be reduced sufficiently to allow a check

to be ma de o n th e calculated po sition of the airgap-line, nor be raised

sufficiently to cover the full operating range of flux levels  (Vag  equal

to abo ut 1-1 p.u . is required for th is, and up to 1-0 p.u . if the

imp orta nt leading power-factor range is to be adequa tely covered ).

This problem is discussed further in Section 5.

3 Testing the mode l

The procedure used to check the validity of the model was to

construct it , as described above, using the results of open-circuit and

no-load tests to obtain parameters, and then to use the model tocalculate conditions with the generator on load and compare these

with test results.

The model parameters for the three generators discussed herein are

given in Table 1. It is to be noted that only two of the parameters are

obtained from design calculations.

76 1

Page 4: Model of Generator Saturation for Use in Power System Studies

8/13/2019 Model of Generator Saturation for Use in Power System Studies

http://slidepdf.com/reader/full/model-of-generator-saturation-for-use-in-power-system-studies 4/5

The range of a typical set of on-load tests is shown in Fig. 5.Generally speaking, the measurem ents ranged from 25 —100 of therated load, with the reactive power loading ranging between the ratedreactive load and that corresponding to a measured rotor angle of 90°.For each test point, the model was supplied with the measured valuesof terminal voltage and active and reactive powers, and it used theseto calculate values for rotor angle and field current. These calculatedvalues were then compared with the measured values and the errorsused to assess the accuracy of the model. The errors are defined bythe following equations:

Rotor-angle error (degrees) = calculated value — measured value

(calculated value —

 measured value) x 100Field-current error ( ) =measured value

The errors are plotted in histogram form in Fig. 6, and the meanerrors are given in Table 2. The histograms show the number of resultsobtained in a given error band (1° for ro tor angle and 1 for fieldcurrent); each small square on the histograms represents a test result.

It can be seen that in all cases the errors are reasonably distributedabout near zero mean error and thus the scatter of the points can beattributed to test measurement errors.

As stated earlier, the primary concern is to provide a model whichgives a good calculation of rotor angle, particularly at leading powerfactors, having regard to the fact that in existing models the errortends to increase as operation is changed from lag to lead. To checkon this, the errors were plotted against reactive power and an exampleis shown in Fig. 7. There is a slight, but not really significant, change

in th e mean ro tor angle between lagging and leading oper ation; similarresults were obtained for the other two generators.

4 Comparison with other models

To demonstrate the improved accuracy of the proposedmodel, the rotor-angle errors for various models are shown in histo-gram form in Fig. 8. The results used in this comparison are from allthe on-load leading-power-factor tests conducted on Generator A.

rotor -ang leerror,

degrees

-4L.

15field -current

error.

• °1 0

  5

• i • • i • •

-5

-

• • •

* *

- 0 6  -0 4 -0-2 0 02 0 4 06lead reactive power, p u  lag

Fig. 7Rotor-angle and field-current errors as affected by reactive powerloading Generator A)

762

Table 3

PARAMETERS AND MEAN ROTOR-ANGLE AND FIELD-CURRENTERRORS OBTAINED USING ON-LOAD METHOD (RESULTS FROM NO-LOAD METHOD A RE GIVEN IN BRACKETS)

^ q 0

mq

  Q

Mean rotor-angle error, degrees

(All tests)Mean rotor-angle error, degrees

(Leading p.f. tests)Mean field-current error,

(All tests)Mean field-current error,

(Lagging p.f. tests)

GeneratorA

1-8

(1-81)0-46

(0-42)9-5

( 8 0 )0 1 5

0-220-25

(0-24)1-50

(1-26)0-18

 -016

GeneratorB

2-41(2-47)0-38

(0-37)9-4

( 8 0 )0-46

1 1 90-56

(1-38)0-81

(112)-0 -45

  -0-39)

GeneratorC

2-55(2-50)0-49

(0-39)6-7

(8-0)0 0 1

0-260 1 5

(0-74)0 1 3

  -109)

- 1 1 3  -1-70)

Fig. 8a shows the errors using the proposed mode l, with a meanrotor-angle error of  —0-7°.  Fig. 8b  shows the errors for the model,frequently used by the CEGB and by o thers , in which the direct-axissaturation characteristic is used to saturate both direct and quadratureaxes in an equal manner;

8  the mean error is +5-1°. Fig. 8c is for the

model in which the direct-axis saturation characteristic is used tosaturate the direct axis alone; the mean error is +7-4°. Fig.  8d is for

the model used in Fig. 86, except that the measured quadrature axissaturation characteristic is used to saturate both axes; the mean erroris —2-3°. An infrequently used mode l, which is not shown in Fig. 8, inwhich both saturation and synchronous saliency are ignored  (XQ =Xd  = constant), gives a mean error of +1 3-9 °.

5 An alternative approach

Having reached this stage in the work, at which it wasconsidered that the model had been satisfactorily validated, we canpose the question as to what could be done if neither no-load testinformation nor calculated parameters are available on the quadrature-axis saturation characteristic: alternatively stated, can a model of thequadrature axis be constructed using on-load test information alone?The lack of no-load information can arise from one of two reasons:

(i) Some supply authorities are reluctant or unable to carry out theno-load tests because of problems of turbine heating caused byno-load running.

(ii) Some autho rities d o n ot fit tap changers to generator trans-formers and thus an adequate range of test results cannot be obtained.

The following routine has been devised in an attempt to answer theabove question using the proposed model. It is assumed that thesaturation characteristic of the direct axis is known.

(i) For each on-load test, calculate  Vag and 8 from measured data.(ii) For each test, calculate values for  Xd  and  XQ  using the

equations given in Appendix 9 (excluding those points near to 0° and90° rotor angle because of inaccuracy in the calculation) and thencalculate the mean value of the difference between   Xd  and  Xq  toobtain  Xsat.

-10 -5 10 -5 10 15 20

H n ,-5 10 15 -10 - 5

Fig. 8Histograms of  rotor-angle errors  for  various saturation models (Gen-erator A)

a Model presented hereinb Direct-axis characteristic saturating both direct and quadrature axesc Direct-axis characteristic saturating direct axis aloned  Quadrature-axis characteristic saturating both direct and quadrature axes

PROC.  IEE, Vol,  126, No. 8, AUGU ST 1979

Page 5: Model of Generator Saturation for Use in Power System Studies

8/13/2019 Model of Generator Saturation for Use in Power System Studies

http://slidepdf.com/reader/full/model-of-generator-saturation-for-use-in-power-system-studies 5/5

(iii) For each test, calculate Xad  = Xd — Xa)  and Xaq  = Xq — Xa)

and, using eqns. 6 and 7, calculate a value for Xt.

(iv) For  each test, calculate a value for Xads  (using the direct-axissaturation characteristic) and use this in eqn. 5 to calculate  Xaqs.

(v) Using the  above calculate values for Vag and Xaqs  for each test,together with Xaq0  = -^ado ~ Xsai),  carry out a least-square-error fitonto eqn. 4 to obtain values for mQ and  nq.

The above routine could have been applied to all the  on-load testpoints for each generator  to obtain a best fit for all points. How ever,it  was decided  to use  only those points at nominal full load and thusto simulate  the way in  which model parameters might  be  obtainedin  the  future. (There are 9, 8 and 12  test points at  nominal full load

for Generators A,B and C, respectively). The model data thus o btainedwere checked  by using it, as described in Section 3, to calculate rotorangle  and field current for all the on-load tests. The results obtainedusing  the  above routine  the  on-load method)  are  summarised  in

Table 3,  which also contains,  in brackets,  the  corresponding resultsobtained using the no-load method.

The first three items in Table 3 define the quadrature-axis saturationcharacteristic and the last four items indicate the accuracy w ith whichrotor angles  and  field currents  are  calculated. Comparison  of the

no-load  and  on-load methods reveals differences between  the satu-ration characteristics but no  significant differences between the meanerrors in  rotor angle and field current; the standard deviations of theerrors  for the two methods  are  very similar.  The conclusion  to be

drawn from this would appear  to be  that  a  highly accurate deter-mination  of the  quadrature-axis saturation characteristic  is not

essential using the proposed model.Overall, it has  been demonstrated that  a satisfactory model can be

obtained from on-load measu rements. The measurements can be madeat  the  normal operating load of the unit  and  should cover as large arange of reactive power loading as possible. •

6 Conclusions

The model proposed herein  is superior in all respects to any

other known model of comparable simplicity, and it is recommendedfor use in power-system s tudies.

The examples used  to  demonstrate  its  effectiveness have beenbased  on  measured data. However, to  enable  the model to be used instudies of  new machine designs, calculated data will be required. Thisraises  the  question as to whether or not the saturation curve for the

quadrature axis can be predicted accurately at the design stage. Binns9

has shown that modern methods can do this for the direct axis, andthere  is  reason  to  assume that  the  same could  be  done  for the

quadrature axis.Both no-load  and on-load m ethods have been used herein to obtain

the saturation characteristic  of the  quadrature axis. Both methodshave produced good results and neither  has been demonstrated  to be

superior to the  other. However, the on-load method  is recommendedfor the following reasons:

(i) It  involves minimum disruption  to the  normal operation  of a

generator when measurements are made.(ii) The range  of  airgap voltage over which measurements can be

made  are  those prevailing during normal operation.  0-9 to  1-1 p.u.

for on-load method compared with 0-75 to 0-95 for no-load metho d).(iii) All  the  quadrature-axis parameters  are  obtained,  and, in

particular,  a  design calculation  of the  unsaturated synchronous

reactance is not needed.

The model  has  been applied  to  turbogenerators alone because no

adequate test results are available for hydrogenerators. However, thereis evidence

6  that  the direct- and quadrature-axis saturation character-

istics of hydrogenerators are quite different, and thus the model couldalso find application for such machines.

7 Acknowledgments

The test results used  in  this paper  are  mainly  due to the

efforts  of  M.D. Barber and A.T. Poray, who organised  the generatortests on which this w ork is based.

The authors  are  grateful  to the  Central Electricity GeneratingBoard for permission to publish this paper.

8 References

1 FUCHS, E.F., and ERDELYI, E.A.: 'Non-linear theory of turbo-alternators.,IEEE Trans.,  1972, PAS-91 pp. 583-599

2 CHAR1, M.V.K., and SILVESTER, P.: 'Analysis of  turbo-alternator magneticfields by  finite elements', ibid.,  1977, PAS-90, pp. 454-464

3 BINNS, K.J., and SMITH, J.R.:  'Prediction  of  load characteristics of turbo-generators', Proc. IEE, 1978,125,  (3), pp. 197-202

4 CHORLTON,  A., and  SHACKSHAFT,  G.:  'Comparison  of  accuracy  ofmethods  for  studying stability. Northfleet exercise',  Electra  1972 23 ,pp . 9-49

5 SHACKSHAFT,  G., and  NEILSON,  R.:  'Results  of  stability tests on an

underexcited 120 MW generator', Proc. IEE,  1972, 119, (2), pp. 1 75-1886 SHACKSHAFT,  G.:  'Generator parameters  for  stability studies', CIGRE,1967, Paper 32-15

7 PARK,  R.H.:  'Two-reaction theory  of  synchronous machines; generalisedmethod of analysis — Part V,AIEE  Trans.,  1929,48, pp. 716-730

8 SHACKSHAFT,  G.:  'General-purpose turbo-alternator model',  Proc IEE1963,110, (4), pp. 703 -713

9 BINNS, K.J.: 'Prediction of the no-load magnetisation characteristics of largeturbogenerators', ibid.,  1965,112, (4), pp. 720-730

9 Appendix

Calculation o 2 axis reactances

The following per-unit equations  are  used  to  calculate  thesynchronous reactances  in the direct  and  quadrature axes from  themeasured test quantities:

Xd  = iVq + IqRa  IfdXa)l Ifd-Id)Xq  = Vd+IdRa)/Jq

In which

Vd  =  Vt sin 5

Vq  = Vt cos 5

Id  = / , sin  5 + 0)

Iq  = It  COS 5 + 0)

0  =  tan1  Qt/P t)

(10)

(11)

(12)

(13)

(14)

05

(16)

Vt, It, Pt  and  Qt  are the  measured stator voltage, stator current,stator active  and  reactive powers, respectively; Ifd  is the  measured

field current and 5 is the measured rotor angle.

PROC.  IEE,  Vol.  126, No. 8, AUGUST 1979 763