models: m5msy20br m5msy25br m5msy30br - romstal · 2020. 2. 18. · catalog m5msy - 2010 inverter-y...
TRANSCRIPT
Catalog M5MSY - 2010
Inverter-Y Multi SplitModels: M5MSY20BR M5MSY25BR M5MSY30BR
Table of Contents M5MSY-2010
“McQuay” is a registered trademark of McQuay International. All rights reserved.© 2010 McQuay International. All rights reserved throughout the world.
Bulletin illustrations cover the general appearance of McQuay International products at the time of publication. We reserve the right to change design and construction specifi cations at any time without notice.
ContentsNomenclature......................................................................................................................1
Indoor Unit .....................................................................................................................1
Outdoor Unit ..................................................................................................................3
Product Line-Up .............................................................................................................4
Features.............................................................................................................................10Application Information ................................................................................................... 11
Operating Range ......................................................................................................... 11
Refrigerant Circuit Diagram .........................................................................................12
Controller ....................................................................................................................14
Installation Guideline ...................................................................................................17
Engineering & Physical Data ...........................................................................................42General Data - Heat pump ..........................................................................................42
Components Data - Heat pump ...................................................................................48
Performance Data .............................................................................................................54Outline and Dimension ....................................................................................................57Electrical Data ...................................................................................................................61Wiring Diagram .................................................................................................................63Service and Maintenance.................................................................................................70Troubleshooting ...............................................................................................................72Exploded View and Part List ...........................................................................................82
Nomenclature M5MSY-2010
1
NomenclatureIndoor Unit
M 5 WM Y 10 J R
BrandM : McQuay
Refrigerant5 : R410A
Model NameWM : Wall Mounted
Inverter System TypeY : Y series
Capacity Index10152025
: 10,000 Btu/h: 15,000 Btu/h: 20,000 Btu/h: 25,000 Btu/h
ChassisJ : J Series
Model Type“ “R
: Omitted if cooling only: Heatpump
M5MSY-2010 Nomenclature
2
Indoor Unit
M 5 CK Y 10 C R
BrandM : McQuay
Refrigerant5 : R410A
Model NameCKCCCM
: Ceiling Cassette: Ceiling Concealed: Ceiling Mounted
Inverter System TypeY : Y series
Capacity Index10152025
: 10,000 Btu/h: 15,000 Btu/h: 20,000 Btu/h: 25,000 Btu/h
ChassisCE
: C Series: E Series
Model Type“ “R
: Omitted if cooling only: Heatpump
Nomenclature M5MSY-2010
3
Outdoor Unit
M 5 MS Y 20 B R
BrandM : McQuay
Refrigerant5 : R410A
Model NameMS : Multi Split Condensing Unit
Inverter System TypeY : Y series
Capacity Index202530
: 20,000 Btu/h: 25,000 Btu/h: 30,000 Btu/h
ChassisB : B Series
Model Type“ “R
: Omitted if cooling only: Heatpump
4
M5MSY-2010 Product Line-Up
Product Line-UpIndoor UnitM5WMY-J Series
M5WMY
Nom
encl
atur
e
Classifi cation
Han
dset
PC
B
Air
Pur
ifi ca
tion
Mar
king
Oth
ers
GS
01
W_2
_03A
Sar
anet
Filt
er
Neg
ativ
e Io
nize
r
Nan
o Te
chno
logy
Air
Filtr
atio
n
CE
Aut
o R
esta
rt
HE
ATP
UM
P 10JR ACLTC X X X X X
15JR ACLTC X X X X X
20JR ACLTA X X X X X
25JR ACLTA X X X X X
5
Product Line-Up M5MSY-2010
Indoor UnitM5CKY-C Series
M5CKY
Nom
encl
atur
e
Classifi cation
Han
dset
PC
B
Air
Pur
ifi ca
tion
Mar
king
Oth
ers
GS
01
C_2
_01A
_M
Sar
anet
Filt
er
Neg
ativ
e Io
nize
r
Nan
o Te
chno
logy
Air
Filtr
atio
n
CE
Aut
o R
esta
rt
HE
ATP
UM
P
10CR ACOA X X X
15CR ACOA X X X
20CR ACOA X X X
PLCKYCR NGS01 X X X
6
M5MSY-2010 Product Line-Up
Indoor UnitM5CKY-E Series
M5CKY
Nom
encl
atur
e
Classifi cation
Han
dset
PC
B
Air
Pur
ifi ca
tion
Mar
king
Oth
ers
GS
01
C_2
_01A
_M
Sar
anet
Filt
er
Neg
ativ
e Io
nize
r
Nan
o Te
chno
logy
Air
Filtr
atio
n
CE
Aut
o R
esta
rt
HE
ATP
UM
P
20ER ACOA X X X
25ER ACOA X X X
PLCKYER NGS01 X X X
7
Product Line-Up M5MSY-2010
Indoor UnitM5CCY-C Series
M5CCY
Nom
encl
atur
e
Classifi cation
Han
dset
PC
B
Air
Pur
ifi ca
tion
Mar
king
Oth
ers
Net
war
e 3C
C_2
_01A
_M
Sar
anet
Filt
er
Neg
ativ
e Io
nize
r
Nan
o Te
chno
logy
Air
Filtr
atio
n
CE
Aut
o R
esta
rt
HE
ATP
UM
P 10CR ACPA X X X X X
15CR ACPA X X X X X
20CR ACPA X X X X X
25CR ACPA X X X X X
8
M5MSY-2010 Product Line-Up
Indoor UnitM5CMY-E Series
M5CMY
Nom
encl
atur
e
Classifi cation
Han
dset
PC
B
Air
Pur
ifi ca
tion
Mar
king
Oth
ers
GS
01
C_2
_01A
_M
Sar
anet
Filt
er
Neg
ativ
e Io
nize
r
Nan
o Te
chno
logy
Air
Filtr
atio
n
CE
Aut
o R
esta
rt
HE
ATP
UM
P
15ER ACAA X X X X X
20ER ACAA X X X X X
25ER ACAA X X X X X
9
Product Line-Up M5MSY-2010
Outdoor UnitM5MSY-BR
M5MSY
Nom
encl
atur
e
Classifi cation
Ref
riger
ant
Con
trol
Fin
Saf
ety
Dev
ices
Com
pres
sor
Mar
king
Oth
ers
Cap
Tub
e
EX
V
Gol
d co
ated
Blu
e co
ated
Bar
e
Con
tact
or
HP
LP DC
Inve
rter S
win
g
CE
Dra
in E
lbow
HE
ATP
UM
P
20BR ACDOA X X X X X25BR ACDOA X X X X X30BR ACDOA X X X X X
10
M5MSY-2010 Features
FeaturesSelf Diagnosis
The microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs in thesystem. The error will be refl ected by the blinking of the LED lights.
Advance Technology
Incorporating fuzzy logic control enables greater fl exibility in system control handling to achievePowerful, effi cient and economical operation.Even room temperature control.Constant and quiet compressor operation.Enhanced system reliability and reduced maintenance costs.
On / Off Button on Indoor Unit
On/Off button is provided on the front panel of the unit. It can be used when the remote controller is missing or if its battery has run out. (Note: This button can also be used for forced operation mode)
Wireless Remote Controller
The compact LCD transmitter is able to operate the air conditioner unit within the distance of 8 meters.Fan speed can be set at high / medium / low / super low or automatic.Sleep mode auto control will gradually increase or decrease the setting temperature to provide a comfortable surrounding for sleeping.Air fl ow direction can be controlled automatically.Room temperature is controlled by electronic thermostat.The real time timer allows the air conditioner to be switched On and Off automatically based on usersettings.Turbo mode function is available to enables the required set temperature to be achieved in a short time.Personalized Setting allows user to preset and store 2 groups of personal settings (including timer setting)in the handset.
Higher Energy Savings
The inverter compressor is programmed to run at the optimum speed. This is controlled by input frequency that varies according to the indoor load requirements.Once the indoor set temperature is achieved, the input frequency supply to the compressor will be reduced. Hence, less power is required to maintain the unit operation and this will consume less energy.
Improved Compressor Life Span
For this multi-split inverter system, once the unit is started, the compressor rotation speed is steadily ramp up or down based on load requirement throughout the operation. This control method gives the compressor motor a smooth operation. It helps to reduce the wear and tear of the compressor motor. In the long run, the life span of compressor is increased.
Overheating Protection (for heat pump unit only)
In case the internal and/or the external temperature are too high, or the fi lter is dirty and clogged up, therefrigerant may be overheated. The compressor will reduce its running speed in order to lower the temperature of heat exchanger. If the temperature is still very high, the compressor will stop.
••••
•••
•••
••
11
Application Information M5MSY-2010
Application InformationOperating Range
Ensure the operating temperature is in allowable range.
Heatpump
Heating
Out
door
tem
p. (°
CW
B)
Indoor temp. (°CDB)
Cooling
Out
door
tem
p. (°
CD
B)
Indoor temp. (°CWB)
-16
15 20 27
18
Standardpoint
Caution :
The use of your air conditioneroutside the range of workingtemperature and humidity can resultin serious failure.
0
4643
12 2319
10
12
M5MSY-2010 Application Information
Refrigerant Circuit Diagram
Model: M5MSY20BR
13
Application Information M5MSY-2010
Refrigerant Circuit Diagram
Model: M5MSY25BR M5MSY30BR
14
M5MSY-2010 Application Information
Controller
GS01
TURBO QUIET
SLEEP
ON OFF
MODE
TIMER
CANCEL CANCELCLOCK
7
4
12
11
10
8
5639
13
2
1
15
Application Information M5MSY-2010
1 Transmission sourceThe source where the signal will be transmitted.•
2 Signal transmission indicationBlink to confi rm that the last setting has been transmitted to the unit.
•
3 “ON/OFF” ButtonPress once to start the air conditioner unit.Press again to stop the unit.
••
4 Fan Speed SelectionPress the button continuously will toggle the fan speed in the following order:Low p Med p High p AutoStop pressing when the desired fan speed appears on the display screen.
•
•
5 Operation modePress the MODE button to select the type of operating mode.For cooling only unit, the available modes are: COOL ( ), DRY ( ) and FAN ( ).For heat pump unit, the available modes are: AUTO ( ), COOL ( ), DRY ( ), FAN ( ) and HEAT ( ).The AUTO ( ) mode is unavailable for chilled water system.
•
•
•
•
6 Automatic air swingPress the SWING button to activate the automatic air swing function.To distribute the air to a specifi c direction, press the SWING button and wait until the louver move to the desired direction and press the button once again.
Swing mode selection method (for CK-E model)Press SWING ( ) button for 4 seconds to enter fi eld setting mode. While in fi eld setting mode, it will only show SWING MODE ( ).Press temperature and button to select SWING MODE ( ) rotation from Swing Mode 1 to Swing Mode 3.There are 3 different SWING MODE, which are:
Swing mode 1 Swing mode 2 Swing mode 3
SWING MODE will not activate unless SWING is activated.Swing is indicated by the logo:If no mode changes within 4 seconds, unit will operate according to the selected SWING MODE ( ).
•
•
•
•
•
•••
7 Turbo function (model dependent)Press for fast cooling or heating operation.Fan speed turn to maximum speed.Press again to deactivate the function.Available under HEAT, COOL and DRY modes only.Any change of fan speed will deactivate this function.The Turbo function ( ) is unavailable for chilled water system and remote control with SWING MODE ( ) function.
••••••
8 OFF timer settingPress the TIMER OFF button will activate the off timer function.Set the desired off time by pressing the TIMER OFF button continuously.Press the CANCEL button to cancel the off timer setting.
•
•
•
9 Quiet function (model dependant)Press for quiet operation.Fan speed turn to minimum speed.Press again to deactivate the function.Any change of fan speed will deactivate this function.The Silent function ( ) is unavailable for chiller water system.
•••••
10 Clock time settingPress and hold button to set the clock time.•
11 ON timer settingPress the TIMER ON button will activate the on timer function.Set the desired on time by pressing the TIMER ON button continuously. If the timer is set to 7.30am, the air conditioner will turn on at 7.30am sharp.Press the CANCEL button to cancel the on timer setting.
•
•
•
12 Sleep mode settingPress the button will activate the sleep mode function.This is an energy saving option. When the unit is operating under cooling mode, the set temperature is increased by 0.5°C after the fi rst half an hour, another 0.5°C after the second half an hour and 1°C after the following 1 hour.When the unit is operating under heating mode, the set temperature is decreased by 1°C after the fi rst half an hour, another 1°C after the second half an hour and 1°C after the following 1 hour.This function is available under COOL, HEAT and AUTO mode.
••
•
•
13 Temperature settingTo set the desired room temperature, press the * or * button to increase or decrease the set temperature.The temperature setting range is from 16°C to 30°C (Optional setting 20°C to 30°C).Press both buttons and simultaneously to toggle from °C to °F setting.
•
•
•
+2 C
+1 C
- 1 C
- 2 C
0 0.5 1 1.5 2
- 3 C
Operation Guide
16
M5MSY-2010 Application Information
Controller
Netware 3C
1 ON/OFF ButtonStarting Operation:When the unit is turned off, press the ON/OFF button.The operation LED lights and the unit is turned on.Stopping Operation:When the unit is turned on, press the ON/OFF button. The operation LED is extinguished and control are turned off.
•
•
2 SLEEP ButtonPress SLEEP button to activate the sleep mode or energy saving mode.
•
3 FAN ButtonPress FAN button to select AUTO, HIGH, MEDIUM or LOW fan speed.
•
4 MODE ButtonPress the MODE button to switch operation from COOL, HEAT, DRY, FAN.Check the display to see in which mode the control is set.
•
•
5,6 ‘▲’ or ‘▼’ Set Temperature ButtonPress the temperature button and set the temperature of your choice. By pressing the ‘▲’ or ‘▼’ button once, temperature changes by 1°C [or 1°F].Temperature can be set within the range 16°C~30°C (61°F~86°F)During fan mode, temperature cannot be set.If pressing ‘▲’ and ‘▼’ together, the unit of temperature will change from °C to °F and vice-versa.
•
•
••
7 SWING buttonPress SWING button to activate the air sweep function.•
8 ON TIMER ButtonEnable/disable the Event 1, 2 and 3 ON TIMER setting mode
•
9 OFF TIMER ButtonEnable/disable the Event 1, 2 and 3 OFF TIMER setting mode
•
10 Timer Active ButtonThese timers will not triggered if the timer is not active. To activate the timers, press the TIMER ACTIVE key unit “TIMER ACTIVE” appears on LCD. This symbol is to indicate Event 1, Event 2 and/or Event 3 timers are active. Pressing the same steps will deactivate the timers and “TIMER ACTIVE” symbol will disappear.Another method to cancel the timers setting is changed all the hour setting of the timers to null one by one. When the setting is null, the LCD display --:--, then this respective timer will be disable.
•
•
11 CLOCK ButtonEnable/disable the Real Time Clock (RTC) setting mode•
12 DAY Buttona) Select the day for RTC or timer settingb) Enable/disable FAN Key lock
13 HOUR Buttona) Select the hour for RTC or timer settingsb) Set Override function for 1, 2 or 4 hours
14 MINUTE Buttona) Select the minute for RTC or timer settingsb) Enable/disable key lock
17
Application Information M5MSY-2010
Installation Guideline
Safety Precautions
WARNING CAUTIONInstallation and maintenance should be performed by qualifi ed persons who are familiar with local code and regulation, and experienced with this type of appliance.All fi eld wiring must be installed in accordance with the national wiring regulation.Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.The unit must be GROUNDED to prevent possible hazard due to insulation failure.All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.Confi rm that the unit has been switched OFF before installing or servicing the unit.Disconnect from the main power supply before servicing the air conditioner unit.DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fi re hazards.Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}.
•
•
•
•
•
•
•
•
•
Please take note of the following important points when installing.
Do not install the unit where leakage of ammable gas may occur.
If gas leaks and accumulates around the unit, it may cause reignition.Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.
Do not overcharge the unit. This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
Ensure that the unit’s panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places.Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat.Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.IMPORTANT : DO NOT INSTALL OR USE THEAIR CONDITIONER UNIT IN A LAUNDRY ROOM.Do not use joined and twisted wires for incoming power supply.
•
•
•
•
•
•
•
•
•••
NOTICEDisposal requirementsYour air conditioning product is marked with this symbol. This means that electrical and electronic productsshall not be mixed with unsorted household waste.Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment ofthe refrigerant, of oil and of other parts must be done by a qualied installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.
18
M5MSY-2010 Application Information
Installation Diagram
Air filterM4 x 12L
Front panel
30mm or more from ceiling
50mm or more from walls (on both sides)
Caulk pipehole gap with putty.
Cut thermal insulation pipe to an appropriatelength and wrap it withtape, making sure that no gap is left in the insulation pipe’s cut line.
Wrap the insulation pipe with the finishing tape from bottom to top.
Service lid ••••• Opening service lid
Service lid is opening/closing type.
••••• Opening method1) Remove the service lid
screws.2) Pull out the service lid
diagonally down in the direction of the arrow.
3) Pull down.
llawmorfmm052
CautionBefore installing the unit, ensure that the power supply matches the power requirement of the air conditioner.•
Service SpaceInstall the indoor unit at a location with the following requirements
Location is suitable for wiring, piping and drainage.No obstruction of air fl ow into and out of unit where cooler air can be evenly distributed.Ensure that air discharge is not short circuited with air intake.Ensure that wall is suffi ciently strong, rigid, fl at, perpendicular and vibration free.Where air fi lter cassette can be slided in or out easily.Where there is no danger of fl ammable gases.Where there is no direct sunlight on unit.
min. 50
(Space formaintenance)
Air flow(Indoor)
min. 50
(Space formaintenance)
03.nim
rofecapS(
)ecn amrofrep
Required space
•••••••
Wall Mounted
19
Application Information M5MSY-2010
Routing of PipingThe refrigerant piping can be routed to the unit in a number of ways (left or right from the back of the unit), by using the cut-out holes on the casing of the unit . Bend the pipes carefully to the required position in order to align it with the holes. For the side and bottom out, hold the bottom of the piping and then position it to the required direction. The condensation drain hose can be taped to the pipes.
Right-side, right-back or right-bottom piping
Right-back piping
Bind coolant pipeand drain hosetogether withinsulating tape.
Right-bottompiping
Remove pipe port coverhere for right-bottom piping
Right-sidepiping
Remove pipe port coverhere for right-side piping
Remove pipe port cover here forleft-bottom piping
Remove pipe portcover here forleft-side piping
Left-backpiping
Left-sidepiping
Left-bottom piping
Left-side, left-back or left-bottom piping
Mounting Installation PlatePaste the installation plan provided on the desired location on the wall and marks the holes location accordingly.Ensure the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars.Ensure the levelness of the installation plate, and fi x with 5 suitable screws.
Mounting plate
Mounting platefixing screw
•
•
•
•
20
M5MSY-2010 Application Information
Fix the installation plate fi rmly to the wall, without tilting to left or right. Use a plumb line, if available.
Throughthe wallholeØ 65mm
Drainhoseposition
Recommended mounting plateretention spots (5 spots in all)
Use tape measure as shown.Position the end of a tape measureat
Gas pipe endLiquid pipe end
166 184
181.7 55554.5 153.8263 51.9
800
45.9
42.2
288
42.2
45.9
42.2
All dimensions are in mm
In case of rear piping drawings out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall.
Inside
Caulking
OutsideWall embedded pipe(Field supply)
Wall hole cover(Field supply) Wall embedded pipe
(Field supply)
Ø 65
Hole with cone drill
Mounting Unit onto the Installation PlateHook the indoor unit onto the upper portion of the installation plate (engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate). Ensure the hooks are properly seated onto the installation plate by moving it to the left and right.To attach the indoor unit, hook the claws of the bottom frame to the mounting plate. If the claws are diffi cult to hook, remove the front grille. To remove the indoor unit, push the marked area (at the lower part of the front grille) to release the claws. If it is diffi cult to release, remove the front grille.
Mountingplate
Clip
Mark (rear side)Bottom frame
Front grille
Mounting plate
Interconnectingwires
Hang indoor unit's hook here.
Wire guide
When stripping theends of interconnectingwires in advance, bindright ends of wires withinsulating tape.
•
•
•
•
•
21
Application Information M5MSY-2010
Water Drainage PipingThe indoor drain pipe must be downward gradient for smooth drainage. Avoid situation as shown in fi gure below.
Enddippedintowater
Waterleaking
Waterleaking
Waterleaking
Wrong Wrong Wrong
Drain
Water Drainage
WaterRetention
Correct
Drain work. (Heat Pump Unit Only)1) Use drain plug for drainage.2) If the drain port is covered by a mounting base or fl oor surface, place additional foot bases of at least 30mm
in height under the outdoor unit’s feet.3) In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain water may freeze, impairing
heating performance.)
Drain-water hole
Bottom frame
Drain plug
Hose (available commercially,inner dia. 16mm)
•
22
M5MSY-2010 Application Information
Ceiling CassetteDrain Piping
Front Panel
Air Filter(behind the grille)
Air Intake Grille
Air Discharge Louver
Thermal Insulation
Wrap the insulated pipe with thefinishing tape from bottom to top
Preliminary Site SurveyElectrical supply and installation is to confi rm to local authority’s (e.g. National Electrical Board) codes and regulations.Voltage supply fl uctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fl uctuation.Ensure that the location is convenient for wiring, piping and drainage.The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and warm air return, and must allow spreading or air throughout the room (near the centre of the room).Clearance must be provided for the indoor unit from the wall and obstacles as shown in the fi gure.
Min
1.0
m
Max
3.0
m
Floor
Obstacles
Min 0.5 m Min 0.5 m Min 0.5 m
Max
3.0
mBea
m
The installation place must be strong enough to support a load of 4 times the indoor unit weight to avoid amplifying noise and vibration.The installation place (handling ceiling surface) must be level and the height in the ceiling is 350mm or more.
•
•
••
•
•
•
23
Application Information M5MSY-2010
Unit Installation
15.0 538.0 18.0
88.0
448.
0
19.0529.032.0
505.
0
)TNEMERUSAE MGN I NE PO
GNI LI E C(mm 01 6~0 .0 85
580.0 ~ 610mm (CEILING OPENING MEASUREMENT)
38.0
770.0 mm (Hanging rod)
)dorgnigna
H(m
m0.226
Piping Direction
M5CKY-C M5CKY-E
The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fi x the hanging rod.The installation template is extended according to temperature and humidity. Check on dimensions in using.The dimensions of the installation template are same as those of the ceiling opening dimensions.Before ceiling laminating work is completed, be sure to fi t the installation template to the indoor unit.
Note: Be sure to discuss the ceiling drilling work with the installers concerned.
Unit Hanging
Indoor Unit
CeilingBo
30.0mm
ard
M5CKY-C/E
Confi rm the pitch of the hanging rod is 770mm x 622mm sharp (M5CKY-E)Hold the unit and hand it on the hanging rod with the nut and washer.Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.Confi rm with a level gauge that the unit is installed horizontally and tighten the nut and bol to prevent unit falling and vibration.Open the ceiling board along the outer edge of the paper installation template.
••
•
••
••••
•
24
M5MSY-2010 Application Information
Drain Piping Work
INDOOR UNIT
Pipe clamp
Good Bad
Drain pipe must be downward gradient for smooth drainage.Avoid the drain pipe from up and down slope to prevent reversal fl ow.During the drain pipe connection, be careful not to exert extra force on the drain connector at the indoor unit.The outside diameter of the drain connection at the fl exible drain hose is 20mm.Be sure to provide heat insulation (polyethylene foam with thickness more than 8.0mm) on the drain piping to avoid the condensed water dripping inside the room.
•
•
•
•
•
Drain Test
MAIN DRAIN PIPEFEED WATER
FLEXIBLEDRAIN HOSE
Connect the main drain pipe to the fl exible drain hose.Feed water from fl exible drain hose and check the piping for leakage.When the test is completed, connect the fl exible drain hose to the drain connector on the indoor unit.
••
•
Note: This indoor unit use drain pump for condensed water drainage. Install the unit horizontally to prevent water leakage or condensation around the air outlet.
Panel InstallationThe front panel can only be fi tted in one direction, follow the piping direction. (Follow piping arrow sticker on the front panel).Be sure to remove the installation template before installing the front panel.
Open the air intake grille by pulling back the catchers and remove it together with fi lter from panel.Install the front frame panel onto the indoor unit by using 4 screws and tighten it completely to prevent cool air leakage.Connect the LED wire and air swing wire to the indoor unit (Optional).
•
•
••
•
25
Application Information M5MSY-2010
Note: Install the front frame panel fi rmly to prevent cool air leakage which will cause condensation and water dripping.
Fresh Air Intake For M5CKY-E Unit
Take off the panel from the indoor unit
Remove the PE foam from the drain pan and another one on the unit.Remove the pre-punched panel on the CKC unit with a screwdriver.The diameter of the air intake knock out hole is 65mm.Then, fi x the fresh air kit (refer to parts list) to the hole. Finally, a fl exible duct is connected to let the fresh air moving in.
26
M5MSY-2010 Application Information
Fig. 2
The direction of the fresh air intake is shown as fi g. 2.
Sealing MaterialIt is possible to seal one of the four air discharge outlet (sealing two or more air discharge outlet could cause a malfunction).Remove the front panel and inserting the seal material into the air discharge outlet at the indoor unit to sealthe air outlet.The sealing material is the same length as the length air discharge outlet. If it is desired to seal the shorter air discharge outlet, cut the sealing material to shorten it.Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not touch the air louver. Be sure not to push the sealing material in any farther than about 10mm.
Short Duct Specifi cation For M5CKY-E Unit
The indoor unit is provided with air discharge and air intake “knock-out” hole for duct connection. However the connection of the short duct for air discharge is possible on only one side.The use of short duct for air discharge will improve air fl ow distribution if there is an obstruction (such as alighting fi xture) or in a long, narrow room or an L-shaped room. It is also used for air-conditioning of two rooms simultaneously.
Possible Direction For Air Discharge and Air Intake
Air Intake
Air DischargeAir Discharge
egrahcsiDriAegrahcsiDriA
•
•
•
•
•
•
27
Application Information M5MSY-2010
Possible Opening Dimension for Duct Connection
Note: 1. Avoid to use the short duct on which the air discharge grille can be completely closed, to prevent evaporator freezing.
2. In order to prevent condensation forming, be sure that there is suffi cient thermal insulation and no leakage of cool air when installing the short duct.
3. Keep the introduction of fresh air intake within 20% of total air fl ow. Also provide a chamber and use a booster fan.
Ceiling Concealed
Thermal insulation
Wrap the insulated pipe with thefinishing tape from bottom to top
DrainpipingCeiling
Supply duct
Return duct
Hanger
28
M5MSY-2010 Application Information
Preliminary SurveyElectrical supply and installation is to confi rm to local authority’s (e.g. National Electrical Board) codes and regulations.Voltage supply fl uctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fl uctuation.Ensure that the location is convenient for wiring, piping and drainage.The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and warm air return, and must allow spreading or air throughout the room (near the centre of the room).Clearance must be provided for the indoor unit from the wall and obstacles as shown in the fi gure.Use the hanger supplied with the unit.Ensure the support is strong enough to withstand the weight of the unit.Use the supplied drain socket to connect the drain pipe (the drain socket is only available for 10˚C to 25˚C)
Install the unit in such a way that the condensate water can flow out smoothly.
The diagrams below show the screws position for duct work connection.
•
•
••
••••
29
Application Information M5MSY-2010
Ceiling Convertible
Preliminary Site SurveyElectrical supply and installation is to confi rm to local authority’s (e.g. National Electrical Board) codes and regulations.Voltage supply fl uctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fl uctuation.Ensure that the location is convenient for wiring, piping and drainage.
Standard MountingEnsure that the overhead supports are strong enough to hold the weight of the unit. Position the hangerrods (wall mounting bracket for fl oor standing), and check for its alignment with the unit as shown in Fig. 3.Also,check that the hangers are secured and the base of the fan coil unit is leveled in both horizontaldirections, taking into account the gradient for drainage fl ow as recommended under section Piping and Drain Hose Installation.
Fig. 3
•
•
•
30
M5MSY-2010 Application Information
Please ensure that the following steps are taken:Check the gradient for drainage fl ow as recommended in Figure 4.Provide clearance for easy servicing and optimal air fl ow as shown in Figure 5.The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.Don not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping and drainage installation. The unit must be a large distance away from the door.
Fig.4
Fig.5
Under ceiling type
Floor standing type
•••
•
31
Application Information M5MSY-2010
Under Ceiling Installation
Install the Suspension Bolts1. Install the suspension bolts so that it can support the indoor unit.2. Adjust the distance to ceiling before installation.3. Refer to the dimension given (Fig. 5) to install the unit.
Install the Indoor Unit1. Insert the suspension bolts into the fi ttings of the hanger bracket.2. Set the nuts and washer on the both side of the metal fi ttings.3. Secure it with nuts.4. Attach the hanger cover (4 pcs) to the units.
32
M5MSY-2010 Application Information
Floor Standing Installation
1. Refer to the dimension as illustrated when installing the mounting bracket.2. Determine the pipe hose position using the rear piping hole. Drill the pipe hole at the slight downward slant
to the outdoor side.
WALL
MOUNTING BRACKET
HOCK THE UNIT ON THEMOUNTING BRACKET
33
Application Information M5MSY-2010
Piping and Drain Hose Installation
Under Ceiling Type1. The piping direction can be 2 ways as illustrated.2. The drain hose is only 1 way.
OR
Floor Standing Type
OR
How to Install the Drain Hose1. Remove the 2 screws and the drain pipe holder.2. Cut a slit for the drain hose hole.3. Place the drain hose on the v-shape area and secure it with drain pipe holder and 2 screws.
34
M5MSY-2010 Application Information
How to Remove the Air Inlet Grille1. Remove the air inlet grille by both hands as the direction shown.2. Loosen the screws for fi xing the panel arm (3 screws – Left, Right and Center). Do not remove the screws
at this time.3. Move the air inlet grille upward, and then turn it backwards. (Do not use too much force).4. Remove the grille holder (both left and right side). After that, remove the air intake grille.5. Remove the grille holder (center) from the panel.
35
Application Information M5MSY-2010
How to Install the Air Filter
To Adjust the Vane DirectionAdjust the vane linkage as the direction shown to get the required vane direction.
Dimension of the Fresh Air Intake Hole
70.0
70.0 3.064.0
36
M5MSY-2010 Application Information
INSTALLATION OF OUTDOOR UNIT
AIR FILTER FRONT FRAME
SIGNAL RECEIVER
INDICATOR LIGHT & ON/OFF SWITCH
DRAIN HOSE
INDOOR UNIT
RETURN AIR
AIR DISCHARGE NOZZLE
OUTDOOR UNIT
Indoor Unit Combination for Outdoor Unit M5MSY20BR, M5MSY25BR and M5MSY30BRIndoor Units with model name M5WMY10JR, M5WMY15JR and M5WMY20JR could be coupled with this outdoor unit.The following table shows the possible coupling combinations available.
No. ofindoorunits
M5MSY20BR M5MSY25BR M5MSY30BR
Indoor A Indoor B Indoor A Indoor B Indoor C Indoor A Indoor B Indoor C Indoor D
2
10 10 10 10 - 10 10 - -10 15 10 15 - 10 15 - -15 15 10 20 - 10 20 - -10 20 15 15 - 15 15 - -15 20 15 20 - 15 20 - -- - 20 20 - 20 20 - -
3
- - 10 10 10 10 10 10 -- - 10 10 15 10 10 15 -- - 10 10 20 10 10 20 -- - 10 15 15 10 15 15 -- - 10 15 20 10 15 20 -- - 15 15 15 15 15 15 -
4- - - - - 10 10 10 10- - - - - 10 10 10 15
For further details on operation combinations, total capacity and other technical specifi cations, please refer to the technical manual.* Multi-split inverter outdoor unit should not be coupled to one indoor unit only
37
Application Information M5MSY-2010
The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to the smooth air fl ow. Please follow the installation clearance shown in the fi gures below. Select the coolest possible place where intake air temperature is not greater than the outside air temperature (maximum 45°C/113°F)Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airfl ow, follow the installation guidelines below.For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
•
•
•
More than 100
Wall facing two sidesWall facing one side
Wall facing three sides
More than 350
More than 50 More than 50
Top View
Top View
Side View
Morethan 100
More than 350
More than 100
More than 350More than 50Unit : mm
1200or less
There are 2 holes on the base of Outdoor Unit forcondensed water to fl ow out. Insert the drain elbow to one of the holes.To install the drain elbow, fi rst insert one portion of the hook to the base (portion A), then pull the drain elbow in the direction shown by the arrow while inserting the other portion to the base. After installation, check to ensure that the drain elbow clings to base fi rmly.If the unit is installed in a snowy and chilly area, condensed water may freeze in the base. In such case, please remove plug at the bottom of unit to smooth the drainage.
•
•
•
PLEASE REMOVE ACCESS PANEL & PLASTIC VALVECOVER WHENCONNECTINGTHE PIPING ANDCONNECTINGCORD.
PUSH & PULL UP
A
DRAINELBOW
Plug
BASE
DRAINELBOW
Before installing the piping and connecting cord, please remove the access panel and plastic valve cover for easy access. Refer to fi gures shown below.
•
38
M5MSY-2010 Application Information
REFRIGERANT PIPINGPiping Length & ElevationIf the pipe is too long, both capacity and reliability of the unit will drop. As the number of bends increases, resistance to the fl ow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always choose the shortest path and not exceed the maximum piping length as tabulated below.
ModelMaximum
Total PipingLength (m)
Single IndoorMaximum
Piping Length(m)
Maximumheight
Difference(m)
Pre-chargedTotal Pipinglength (m)
Outdoor UnitPre-charged
(kg)
Amount ofAdditional
Charge (g/m)
M5MSY20BR(2 Ports) L1+ L2 ≤ 50 L ≤ 25 H ≤ 15 30 2.0 20
M5MSY25BR(3 Ports)
L1+ L2+ L3 ≤60 L ≤ 25 H ≤ 15 30 2.6 20
M5MSY30BR(4 Ports)
L1+ L2+ L3+ L4≤ 60 L ≤ 25 H ≤ 15 30 2.6 20
INDOOR UNIT
OUTDOOR UNIT
VERTICAL HEIGHTDIFFERENCE MAX. H
39
Application Information M5MSY-2010
Piping WorksDo not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nuts from the valves, fi ttings, tubings and coils until you are ready to connect suction or liquid line into valves or fi ttings.If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside walls of the copper tubings.Cut the connection pipe with a pipe cutter.
•
•
•
1/4t
Cutting copper tube
Remove burrs from cut edges of the pipes with remover. Hold the end of the pipe downwards to prevent metal chips from entering the pipe.
•
Remove burr indoor
Insert the fl are nuts, mounted on the connection parts of both the indoor unit and outdoor unit onto the copper pipes.Flare the pipe with extra length above the fl aring tool as shown in the table.
•
•
Copper tubeSwaging block
Ø Tube, D A (mm)Inch mm Imperial Rigid1/4” 6.35 1.3 0.73/8” 9.52 1.6 1.01/2” 12.70 1.9 1.35/8” 15.88 2.2 1.73/4” 19.05 2.5 2.0
The fl ared edge must be even and not cracked or scratched.
•
Piping Connection To The UnitsThe outdoor unit is equipped with two to four sets of fl are joints depending on O/D unit model. Refer to the table below for fl are joint size and location.
•
Model Pipe A B C D
M5MSY20BRLiquid 1/4” 1/4” - -Gas 1/2” 1/2” - -
M5MSY25BRLiquid 1/4” 1/4” 1/4” -Gas 3/8” 1/2” 1/2” -
M5MSY30BRLiquid 1/4” 1/4” 1/4” 1/4”Gas 3/8” 3/8” 1/2” 1/2”
In the case where the gas pipe from the indoor unit does not match the outdoor fl are joints, fl are joint connectors shall be used. The piping connection size shall follow the size of the indoor unit’s fl are joint. The connector should be connected as shown in fi gure.
•
FLARETUBE
FLARE JOINT
INDOORPIPING
SPANNER TORQUE WRENCH
FLARE NUT
CONNECTOR
Align the center of the piping and tighten the fl are nut suffi ciently with fi ngers.Finally, tighten the fl are nut with the torque wrench until the wrench clicks.Do not exceed the recommended tightening torque as this may cause damage on the fl are surface and refrigerant leakage.
•
•
•
Pipe Size mm/(in) Torque Nm/(ft-lb)6.35 (1/4) 18 (13.3)9.52 (3/8) 42 (31.0)12.70 (1/2) 55 (40.6)15.88 (5/8) 65 (48.0)19.05 (3/4) 78 (57.6)
40
M5MSY-2010 Application Information
ELECTRICAL WIRING CONNECTIONIMPORTANT: The fi gures shown in the table are for information purpose only. They should be checked and selected to comply with the local/national codes of regulations. This is also to the type of installation and conductors used.
Indoor Unit A Indoor Unit B Indoor Unit C Indoor Unit D
PowerSupply
Power SupplyDCBA
1 2 SIG N L 1 2 SIG N L1 2 SIG N L1 2 SIG N L
SIGN GISL N GISL N GISL N LNL
0 There must be a double pole switch with a minimum 3 mm contact gap and fuse/ circuit breaker as recommended in the fi xed installation circuit.
All wiring must be connected accordingly to the diagram above, with reference to the piping connection. Mismatch any wiring with different piping will cause severe damage to the system.All wires must be fi rmly connected.All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps and the cable tie (push releasable) at the indoor unit and outdoor unit respectively as shown in the fi gures.The power supply cord must be equivalent to H07RN-F (245IEC57) or higher.Remove the detachable part of the access cover to allow wire routing.All wires must not be clamped by the access panel cover.
•
••
•
•
•
•
Detachable part
Wiresmustn't be clamped
Wire Clamp
InterconnectionCable
Model M5WMY 10/15 JR M5WM Y20/25 JRVoltage Range 220-240V/1Ph/50Hz + Power supply cable size mm2
Number of wires3.03
Interconnection cable size mm2
Number of wires1.54
2.54
Recommended time delay fuse for O/D unit Amp 25
41
Application Information M5MSY-2010
VACUUMING AND CHARGINGPurging the piping and the indoor unitExcept for the outdoor unit which is pre-charged withrefrigerant R410A, the indoor unit and the refrigerantconnection pipes must be air-purged because the aircontaining moisture that remains in the refrigerant cycle may cause malfunction of the compressor.
Make sure all pipes are connected securely to the outdoor and indoor valves.Remove the caps from the fl are valves and the service. Take note that there are a total of two service ports for 5MSY20BR, three service ports for 5MSY25BR and four service ports for 5MSY30BR.Connect the center of the charging gauge to the vacuum pump.Connect the charging gauge to the 3-way valve’s service port. (The numbers of service ports depend on the O/D unit model).Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different vacuum pump capacity. Confi rm that the charging gauge needle has moved towards -760mmHg.Proceed to the next 3-way valve and repeat the steps above.
•
•
•
•
•
•
0CAUTIONIf the gauge needle does not move towards -760mmHg, be sure to check for gas leaks (using the refrigerant detector) at fl are type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step.Close the valve of the charging gauge and stop the vacuum pump.On the outdoor unit, open the suction valve (3-way) and liquid valve (2-way) (in anti-clockwise direction) with 4mm key for hexagon sacked screw.
•
•
•
Allen key
Service port
Flare nut
Outdoor unit 3 way valve
Refrigerant piping
HiLow
Indoor Unit Liquid side Outdoor Unit
Close
Close
Gas side
Close
OpenVacuumpump
Discharge valve
Suction valve
Additional chargeThe refrigerant is pre-charged in the outdoor unit for specifi c piping length. Please refer to for further details on additional charge.
Charge operationThis operation must be done by using a cylinder and a precise weighing machine. The additional charge is topped up into the outdoor unit using the suction valve via the service port.
Remove the service port cap.Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose.Start the air conditioner unit.Open the cylinder and low pressure charging valve.When the required refrigerant quantity is pumped into the unit, close the low pressure side and the cylinder valve.Disconnect the service hose from service port. Put back the service port cap.
••
••
•
•
HiLow
Indoor Unit Liquid side Outdoor Unit
Open
Open
Gas side
Close
Checkvalve
Discharge valve
Suction valve
Open
CAUTIONR410A must be charged as liquid. Usually R410A cylinder is equipped with a dip-pipe for liquid withdrawal. If there is no dip-pipe, the cylinder should be inverted so as to withdraw liquid R410A from the valve.Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit thoroughly and then charge the unit with fresh R410A according to the amount recommended in the specifi cation.
•
•
0
42
M5MSY-2010 Engineering & Physical Data
Engineering & Physical DataGeneral Data - Heat pump
MODEL INDOOR UNIT M5WMY 10JR M5WMY 15JR M5WMY 20JR M5WMY 25JR
INDOOR UNITAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 153 / 324 160 / 337 250 / 529 309 / 654
MEDIUM l/s / CFM 119 / 252 124 / 262 222 / 471 276 / 585
LOW l/s / CFM 93 / 197 101 / 213 197 / 418 239 / 507
SOUND PRESSURE LEVEL (H/M/L) dBA 40 / 34 / 29 41 / 34 / 30 41 / 39 / 35 44 / 41 / 37
UNIT DIMENSION
HEIGHT mm/in 288 / 11.3 288 / 11.3 310 / 12.2 310 / 12.2
WIDTH mm/in 800 / 31.5 800 / 31.5 1065 / 42.0 1065 / 42.0
DEPTH mm/in 204 / 8.0 204 / 8.0 224 / 8.8 224 / 8.8
PACKING DIMENSION
HEIGHT mm/in 350 / 13.8 350 / 13.8 386 / 15.2 386 / 15.2
WIDTH mm/in 894 / 35.2 894 / 35.2 1136 / 44.7 1136 / 44.7
DEPTH mm/in 280 / 11.0 280 / 11.0 285 / 11.2 285 / 11.2
UNIT WEIGHT kg/lb 9 / 19.9 9 / 19.9 6.3 / 14 6.3 / 14
CONDENSATE DRAIN SIZE mm/in 16 / 0.63 16 / 0.63 19.1 / 0.75 19.1 / 0.75
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
MODEL INDOOR UNIT M5CKY 10CR M5CKY 15CR M5CKY 20CR
CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS OR WIRED REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 193 / 400 193 / 410 212 / 450
MEDIUM l/s / CFM 184 / 390 184 / 390 203 / 430
LOW l/s / CFM 170 / 360 170 / 360 193 / 410
SOUND PRESSURE LEVEL (H/M/L) dBA 44 / 43 / 42 44 / 42 / 41 47 / 46 / 44
UNIT DIMENSION(WITH PANEL)
HEIGHT mm/in 250 (295) / 9.8 (11.6) 250 (295) / 9.8 (11.6) 250 (295) / 9.8 (11.6)
WIDTH mm/in 570 (640) / 22.4 (25.2) 570 (640) / 22.4 (25.2) 570 (640) / 22.4 (25.2)
DEPTH mm/in 570 (640) / 22.4 (25.2) 570 (640) / 22.4 (25.2) 570 (640) / 22.4 (25.2)
PACKING DIMENSION (WITH PANEL)
HEIGHT mm/in 317 (127) / 12.5 (5.0) 317 (127) / 12.5 (5.0) 317 (127) / 12.5 (5.0)
WIDTH mm/in 630 (700) / 24.8 (27.6) 630 (700) / 24.8 (27.6) 630 (700) / 24.8 (27.6)
DEPTH mm/in 630 (700) / 24.8 (27.6) 630 (700) / 24.8 (27.6) 630 (700) / 24.8 (27.6)
UNIT WEIGHT (UNIT + PANEL) kg/lb 22 + 2.0 / 49 + 4.0 23 + 2.0 / 51 + 4.0 23 + 2.0 / 51 + 4.0
CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75 19.1 / 0.75
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
43
Engineering & Physical Data M5MSY-2010
General Data - Heat pump
MODEL INDOOR UNIT M5CKY 20ER M5CKY 25ER
CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS OR WIRED REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 283 / 600 321 / 680
MEDIUM l/s / CFM 250 / 530 283 / 600
LOW l/s / CFM 203 / 430 250 / 530
SOUND PRESSURE LEVEL (H/M/L) dBA 34 / 31 / 28 37 / 34 / 31
UNIT DIMENSION(WITH PANEL)
HEIGHT mm/in 265 (340) / 10.4 (13.4) 265 (340) / 10.4 (13.4)
WIDTH mm/in 820 (990) / 32.3 (39.0) 820 (990) / 32.3 (39.0)
DEPTH mm/in 820 (990) / 32.3 (39.0) 820 (990) / 32.3 (39.0)
PACKING DIMENSION (WITH PANEL)
HEIGHT mm/in 335 (410) / 13.2 (16.1) 335 (410) / 13.2 (16.1)
WIDTH mm/in 900 (1070) / 35.4 (42.1) 900 (1070) / 35.4 (42.1)
DEPTH mm/in 900 (1070) / 35.4 (42.1) 900 (1070) / 35.4 (42.1)
UNIT WEIGHT (UNIT + PANEL) kg/lb 29 + 6.0 / 64 + 13.2 29 + 6.0 / 64 + 13.2
CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
MODEL UNIT NAME M5CCY 10CR M5CCY 15CR M5CCY 20CR M5CCY 25CR
INDOOR UNITAIR DISCHARGE DUCTED
OPERATION WIRELESS OR WIRED REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 172 / 365 194 / 410 269 / 570 326 / 690
MEDIUM l/s / CFM 160 / 340 175 / 370 255 / 540 302 / 640
LOW l/s / CFM 137 / 290 118 / 250 213 / 450 245 / 520
EXTERNAL STATIC PRESSURE (H/M/L) Pa / mmAq 29 / 25 / 19
(0.12 / 0.10 / 0.08)29 / 20 / 10
(0.12 / 0.08 / 0.04)29 / 20 / 10
(0.12 / 0.08 / 0.04)29 / 20 / 10
(0.12 / 0.08 / 0.04)
SOUND PRESSURE LEVEL (H/M/L) dBA 35 / 32 / 26 37 / 34 / 29 38 / 36 / 34 40 / 39 / 36
UNIT DIMENSION
HEIGHT mm/in 261 / 10.3 261 / 10.3 261 / 10.3 261 / 10.3
WIDTH mm/in 765 / 30.1 765 / 30.1 1065 / 41.9 1200 / 47.2
DEPTH mm/in 411 / 16.2 411 / 16.2 411 / 16.2 411 / 16.2
PACKING DIMENSION
HEIGHT mm/in 376 / 14.8 376 / 14.8 376 / 14.8 376 / 14.8
WIDTH mm/in 1091 / 43.0 1091 / 43.0 1251 / 49.3 1386 / 54.6
DEPTH mm/in 541 / 21.3 541 / 21.3 541 / 21.3 541 / 21.3
UNIT WEIGHT kg/lb 21 / 9.5 21 / 9.5 9.5 / 21 11.3 / 25
CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75 19.1 / 0.75 19.1 / 0.75
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
44
M5MSY-2010 Engineering & Physical Data
General Data - Heat pump
MODEL INDOOR UNIT M5CMY 15ER M5CMY 20ER M5CMY 25ER
INDOOR UNITAIR DISCHARGE AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS OR WIRED REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 240 / 508 245 / 520 274 / 580
MEDIUM l/s / CFM 182 / 386 217 / 460 250 / 530
LOW l/s / CFM 165 / 350 192 / 406 231 / 490
SOUND PRESSURE LEVEL (H/M/L) dBA 48 / 43 / 41 50 / 43 / 41 53 / 51 / 49
UNIT DIMENSION
HEIGHT mm/in 218 / 8.6 218 / 8.6 218 / 8.6
WIDTH mm/in 1080 / 42.5 1080 / 42.5 1080 / 42.5
DEPTH mm/in 630 / 24.8 630 / 24.8 630 / 24.8
PACKING DIMENSION
HEIGHT mm/in 297 / 11.7 297 / 11.7 297 / 11.7
WIDTH mm/in 1197 / 47.1 1197 / 47.1 1197 / 47.1
DEPTH mm/in 740 / 29.1 740 / 29.1 740 / 29.1
UNIT WEIGHT kg/lb 25 / 55.1 27 / 59.5 27 / 59.5
CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75 19.1 / 0.75
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
45
Engineering & Physical Data M5MSY-2010
General Data - Heatpump
MODELUNIT NAME M5MSY20BR
TYPE 1-to-2
NOMINAL COOLING CAPACITY (Min - Max)Btu/h 18400 (5100 - 21200)
W 5400 (1500 - 6200)
NOMINAL HEATING CAPACITY (Min - Max)Btu/h 21800 (2400 - 23500)
W 6400 (700 - 6900)
NOMINAL TOTAL INPUT POWER (COOLING) W 1378
NOMINAL TOTAL INPUT POWER (HEATING) W 1492
NOMINAL RUNNING CURRENT (COOLING) A 6.05
NOMINAL RUNNING CURRENT (HEATING) A 6.57
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
EER W/W 3.92
COP W/W 4.29
REFRIGERANT TYPE R-410A
AIR FLOW l/s / CFM 780 / 1638
SOUND PRESSURE LEVEL dBA 48
UNIT DIMENSION
HEIGHT mm/in 756 / 29.7
WIDTH mm/in 855 / 33.6
DEPTH mm/in 348 / 13.7
PACKING DIMENSION
HEIGHT mm/in 793 / 31.2
WIDTH mm/in 990 / 39.0
DEPTH mm/in 415 / 16.3
UNIT WEIGHT kg/lb 45 / 99.2
PIPE CONNECTION
TYPE FLARE
SIZELIQUID mm/in 2 x 6.35 / 1/4
GAS mm/in 2 x 12.7 / 1/2
REFRIGERANT CHARGE kg/lb 2.0 / 4.41
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
46
M5MSY-2010 Engineering & Physical Data
General Data - Heat pump
MODELUNIT NAME M5MSY25BR
TYPE 1-to-3
NOMINAL COOLING CAPACITY (Min - Max)Btu/h 22200 (3400 - 26100)
W 6500 (1000 - 7650)
NOMINAL HEATING CAPACITY (Min - Max)Btu/h 25200 (3100 - 28000)
W 7400 (900 - 8200)
NOMINAL TOTAL INPUT POWER (COOLING) W 1702
NOMINAL TOTAL INPUT POWER (HEATING) W 1749
NOMINAL RUNNING CURRENT (COOLING) A 7.56
NOMINAL RUNNING CURRENT (HEATING) A 7.77
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
EER W/W 3.82
COP W/W 4.23
REFRIGERANT TYPE R-410A
AIR FLOW l/s / CFM 850 / 1786
SOUND PRESSURE LEVEL dBA 49
UNIT DIMENSION
HEIGHT mm/in 756 / 29.7
WIDTH mm/in 855 / 33.6
DEPTH mm/in 348 / 13.7
PACKING DIMENSION
HEIGHT mm/in 793 / 31.2
WIDTH mm/in 990 / 39.0
DEPTH mm/in 415 / 16.3
UNIT WEIGHT kg/lb 55 / 121.2
PIPE CONNECTION
TYPE FLARE
SIZELIQUID mm/in 3 x 6.35 / 1/4
GAS mm/in 1 x 9.52 / 3/82 x 12.7 / 1/2
REFRIGERANT CHARGE kg/lb 2.6 / 5.74
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
47
Engineering & Physical Data M5MSY-2010
General Data - Heat pump
MODELUNIT NAME M5MSY30BR
TYPE 1-to-4
NOMINAL COOLING CAPACITY (Min - Max)Btu/h 26100 (4100 - 31000)
W 7650 (1200 - 9100)
NOMINAL HEATING CAPACITY (Min - Max)Btu/h 28700 (3100 - 30700)
W 8400 (900 - 9000)
NOMINAL TOTAL INPUT POWER (COOLING) W 2113
NOMINAL TOTAL INPUT POWER (HEATING) W 2054
NOMINAL RUNNING CURRENT (COOLING) A 9.31
NOMINAL RUNNING CURRENT (HEATING) A 9.08
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
EER W/W 3.62
COP W/W 4.09
REFRIGERANT TYPE R-410A
AIR FLOW l/s / CFM 850 / 1786
SOUND PRESSURE LEVEL dBA 49
UNIT DIMENSION
HEIGHT mm/in 756 / 29.7
WIDTH mm/in 855 / 33.6
DEPTH mm/in 348 / 13.7
PACKING DIMENSION
HEIGHT mm/in 793 / 31.2
WIDTH mm/in 990 / 39.0
DEPTH mm/in 415 / 16.3
UNIT WEIGHT kg/lb 55 / 121.2
PIPE CONNECTION
TYPE FLARE
SIZELIQUID mm/in 4 x 6.35 / 1/4
GAS mm/in 2 x 9.52 / 3/82 x 12.7 / 1/2
REFRIGERANT CHARGE kg/lb 2.6 / 5.74
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
48
M5MSY-2010 Engineering & Physical Data
Components Data - Heat pump
MODEL INDOOR UNIT M5WMY 10JR M5WMY 15JR M5WMY 20JR M5WMY 25JR
INDOOR FAN
TYPE CROSS FLOW FAN
QUANTITY 1
MATERIAL ACRYLO NITRILE STYRENE + GLASS FIBER
DRIVE DIRECT
DIAMETER mm/in 92 / 3.6 102 / 4.0
LENGTH mm/in 607 / 23.8 867 / 34.1
INDOOR FAN MOTOR
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP44 IP20
INDOOR COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009
FIN
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
THICKNESS mm/in 0.11 / 0.004
FACE AREA m2/ft2 0.18 / 1.938 0.29 / 3.10
ROW 2
FIN PER INCH 18
AIR QUALITY FILTERTYPE WASHABLE SARANET FILTER
QUANTITY pc 2
CASING INDOOR UNIT
MATERIAL HIGH IMPACT POLYSTYRENE
FINISHING ETCHING
COLOUR WHITE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
49
Engineering & Physical Data M5MSY-2010
Components Data - Heat pump
MODEL INDOOR UNIT M5CKY 10CR M5CKY 15CR M5CKY 20CR
INDOOR FAN
TYPE TURBO
QUANTITY 1
MATERIAL ABSG20
DRIVE DIRECT
DIAMETER mm/in 315 / 12.4
LENGTH mm/in 163 / 6.4
INDOOR FAN MOTOR
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP20
INDOOR COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER mm/in 7.00 / 0.28
THICKNESS mm/in 0.24 / 0.009
FIN
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
THICKNESS mm/in 0.11 / 0.004
FACE AREA m2/ft2 0.25 / 2.73
ROW 2
FIN PER INCH 20
AIR QUALITY FIL-TER
TYPE WASHABLE SARANET FILTER
QUANTITY pc 1
CASING INDOOR UNIT
MATERIAL GALVANISED IRON
FINISHING WITH PE INSULATION
COLOUR GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
50
M5MSY-2010 Engineering & Physical Data
Components Data - Heat pump
MODEL INDOOR UNIT M5CKY 20ER M5CKY 25ER
INDOOR FAN
TYPE TURBO
QUANTITY 1
MATERIAL ASG 10%
DRIVE DIRECT
DIAMETER mm/in 486 / 19.1
LENGTH mm/in 172 / 6.8
INDOOR FAN MOTOR
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP20
INDOOR COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER mm/in 7.00 / 0.28
THICKNESS mm/in 0.24 / 0.009
FIN
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
THICKNESS mm/in 0.11 / 0.004
FACE AREA m2/ft2 0.39 / 4.15
ROW 2
FIN PER INCH 18
AIR QUALITY FILTERTYPE WASHABLE SARANET FILTER
QUANTITY pc 1
CASING INDOOR UNIT
MATERIAL GALVANISED IRON
FINISHING WITH PE INSULATION
COLOUR GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
51
Engineering & Physical Data M5MSY-2010
Components Data - Heat pump
MODEL INDOOR UNIT M5CCY 10CR M5CCY 15CR M5CCY 20CR M5CCY 25CR
INDOOR FAN
TYPE SIROCCO
QUANTITY 2
MATERIAL GALVANISED STEEL
DRIVE DIRECT
DIAMETER mm/in 164 / 6.5 164 / 6.5 160 / 6.3 160 / 6.3
LENGTH mm/in 202 / 8.0 202 / 8.0 200 / 7.9 200 / 7.9
INDOOR FAN MOTOR
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) - - IP20 IP21
INDOOR COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009
FIN
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
THICKNESS mm/in 0.11 / 0.004
FACE AREA m2/ft2 0.13 / 1.43 0.13 / 1.43 0.16 / 1.76 0.19 / 2.03
ROW 3
FIN PER INCH 18
AIR QUALITY FIL-TER
TYPE WASHABLE SARANET FILTER
QUANTITY pc 1
CASING INDOOR UNIT
MATERIAL GALVANISED STEEL
FINISHING WITH PE INSULATION
COLOUR WITHOUT POWDER PAINT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
52
M5MSY-2010 Engineering & Physical Data
Components Data - Heat pump
MODEL INDOOR UNIT M5CMY 15ER M5CMY 20ER M5CMY 25ER
INDOOR FAN
TYPE SIROCCO
QUANTITY 2
MATERIAL ABS
DRIVE DIRECT
DIAMETER mm/in 145 / 5.7
LENGTH mm/in 200 / 8.9
INDOOR FAN MOTOR
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) - IP20
INDOOR COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009
FIN
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
THICKNESS mm/in 0.11 / 0.004
FACE AREA m2/ft2 0.27 / 2.89
ROW 2
FIN PER INCH 18
AIR QUALITY FIL-TER
TYPE WASHABLE SARANET FILTER
QUANTITY pc 2
CASING INDOOR UNIT
MATERIAL PS
FINISHING ETCHING SURFACE
COLOUR LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
53
Engineering & Physical Data M5MSY-2010
Components Data - Heatpump
MODEL UNIT NAME M5MSY20BR M5MSY25BR M5MSY30BR
OUTDOOR FAN
TYPE PROPELLER
QUANTITY 1
MATERIAL POLYPROPYLENE + GLASS FIBER + MICA
DRIVE DIRECT
DIAMETER mm/in 455 / 18
OUTDOOR FAN MOTOR
TYPE DC BRUSHLESS
QUANTITY 1
INDEX OF PROTECTION (IP) IP23
COMPRESSOR
TYPE HERMATIC SWING COMPRESSOR
OIL TYPE POLYESTER OIL (PVE)
OIL AMOUNT cm3 / fl .oz. 650 / 21.9
OUTDOOR COIL
TUBE
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.010
FIN
MATERIAL ALUMINIUM (HYDROPHILIC FIN)
THICKNESS mm/in 0.11 / 0.004
FACE AREA m2/ft2 0.62 / 6.67
ROW 2
FIN PER INCH 18 20
CASING OUTDOOR UNITMATERIAL GALVANISED MILD STEEL
COLOUR LIGHT GREY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
54
M5MSY-2010 Performance Data
Performance DataModel: M5MSY20BRCooling Mode
Combination of indoor unit Each capacity (kW) Total capacity (kW) Total input (W)
EERTotal current (A)
A room B room Rated Max Rated Max Rated Max
10 2.50 --- 2.50 3.00 620 800 4.03 2.80 3.60
15 3.50 --- 3.50 3.70 980 1280 3.57 4.30 5.60
20 --- 5.00 5.00 5.80 1620 2100 3.09 7.10 9.20
10 + 10 2.50 2.50 5.00 5.80 1470 1910 3.40 6.40 8.40
10 + 15 2.17 3.03 5.20 6.00 1550 2140 3.35 6.90 9.40
10 + 20 1.75 3.45 5.20 6.00 1500 2070 3.47 6.60 9.10
15 + 15 2.60 2.60 5.20 6.00 1400 2140 3.71 6.20 9.40
15 + 20 2.22 3.18 5.40 6.20 1378 1720 3.92 6.10 7.60
Heating Mode
Combination of indoor unit Each capacity (kW) Total capacity (kW) Total input (W)
COPTotal current (A)
A room B room Rated Max Rated Max Rated Max
10 3.00 --- 3.00 4.00 1000 1260 3.00 4.50 5.60
15 3.80 --- 3.80 4.50 1250 1680 3.04 5.60 7.50
20 --- 5.60 5.60 6.50 1850 2510 3.03 8.20 11.00
10 + 10 3.00 3.00 6.00 6.50 1570 2150 3.82 6.90 9.50
10 + 15 2.54 3.56 6.10 6.50 1640 2000 3.72 7.20 8.80
10 + 20 2.03 4.07 6.10 6.70 1600 1800 3.81 7.00 7.90
15 + 15 3.05 3.05 6.10 6.50 1600 1970 3.81 7.00 8.70
15 + 20 2.64 3.76 6.40 6.90 1492 1680 4.29 6.60 7.50
Note : It is impossible to connect the indoor unit to 1 room only
55
Performance Data M5MSY-2010
Model: M5MSY25BRCooling Mode
Combination of indoor unit Each capacity (kW) Total capacity (kW) Total input (W)
EERTotal current (A)
A room B room C room Rated Max Rated Max Rated Max
10 2.50 --- --- 2.50 3.00 590 850 4.24 2.67 3.80
15 3.50 --- --- 3.50 3.70 910 960 3.85 4.10 4.20
20 --- --- 5.00 5.00 5.80 1700 2200 2.94 7.50 9.70
10 + 10 2.50 2.50 --- 5.00 5.90 1580 2000 3.16 7.00 8.80
10 + 15 2.50 3.50 --- 6.00 6.40 2060 2370 2.91 9.10 10.40
10 + 20 2.17 --- 4,33 6.50 7.00 2300 2750 2.83 10.10 12.10
15 + 15 3.22 3.22 --- 6.44 7.40 2250 3190 2.86 9.90 14.10
15 + 20 2.68 --- 3.82 6.50 7.40 2300 3200 2.83 10.30 14.20
20 + 20 --- 3.22 3.22 6.44 7.80 1850 2930 3.48 8.30 12.90
10 + 10 + 10 2.16 2.16 2.16 6.48 7.80 2200 2750 2.95 9.70 12.10
10 + 10 + 15 1.91 1.91 2.68 6.50 7.90 2120 2800 3.07 9.40 12.20
10 + 10 + 20 1.63 1.63 3.24 6.50 8.10 1880 2900 3.46 8.30 12.80
10 + 15 + 15 1.70 2.40 2.40 6.50 8.00 2030 2650 3.20 8.90 11.70
10 + 15 + 20 1.48 2.07 2.95 6.50 8.40 1702 2800 3.82 7.60 12.30
15 + 15 + 15 2.16 2.16 2.16 6.48 8.00 1900 2900 3.41 8.50 12.70
Heating Mode
Combination of indoor unit Each capacity (kW) Total capacity (kW) Total input (W)
COPTotal current (A)
A room B room C room Rated Max Rated Max Rated Max
10 3.00 --- --- 3.00 4.00 1030 1370 2.91 4.70 6.10
15 3.80 --- --- 3.80 4.50 1420 1610 2.68 6.50 7.10
20 --- --- 5.60 5.60 5.70 1840 2260 3.04 8.40 9.90
10 + 10 3.60 3.60 --- 7.20 7.50 2240 2560 3.21 9.90 11.20
10 + 15 3.08 4.32 --- 7.40 7.90 2120 2580 3.49 9.40 11.30
10 + 20 2.47 --- 4.93 7.40 8.60 2050 2700 3.61 9.00 11.80
15 + 15 3.66 3.66 --- 7.32 8.60 2300 3000 3.18 10.20 13.20
15 + 20 3.05 --- 4.35 7.40 8.60 2040 2650 3.63 9.00 11.60
20 + 20 --- 3.66 3.66 7.32 8.60 1860 2680 3.94 8.30 11.80
10 + 10 + 10 2.46 2.46 2.46 7.38 8.40 1870 2750 3.95 8.20 12.10
10 + 10 + 15 2.18 2.18 3.04 7.40 8.40 1860 2720 3.98 8.20 11.90
10 + 10 + 20 1.85 1.85 3.70 7.40 8.60 1800 2660 4.11 8.00 11.60
10 + 15 + 15 1.94 2.73 2.73 7.40 8.40 2090 2680 3.54 9.30 11.70
10 + 15 + 20 1.68 2.36 3.36 7.40 8.60 1749 2500 4.23 7.80 10.90
15 + 15 + 15 2.46 2.46 2.46 7.38 8.40 1850 2700 3.99 8.10 11.80
Note : It is impossible to connect the indoor unit to 1 room only
56
M5MSY-2010 Performance Data
Model: M5MSY30BRCooling Mode
Combination of indoor unit Each capacity (kW) Total capacity
(kW) Total input (W)EER
Total current (A)
A room B room C room D room Rated Max Rated Max Rated Max
10 2.50 --- --- --- 2.50 3.00 590 850 4.24 2.70 3.80
15 3.50 --- --- --- 3.50 3.70 910 960 3.85 4.10 4.20
20 --- --- 5.00 --- 5.00 5.80 1700 2200 2.94 7.50 9.70
10 + 10 2.50 2.50 --- --- 5.00 5.90 1580 2000 3.16 7.00 8.80
10 + 15 2.50 3.50 --- --- 6.00 6.40 2060 2370 2.91 9.10 10.40
10 + 20 2.17 --- 4.33 --- 6.50 7.00 2300 2750 2.83 10.10 12.10
15 + 15 3.45 3.45 --- --- 6.90 7.40 2650 3190 2.60 11.70 14.10
15 + 20 3.01 --- 4.29 --- 7.30 7.40 2600 3200 2.81 11.50 14.20
20 + 20 --- 3.75 3.75 --- 7.50 7.80 2490 2930 3.01 11.20 12.90
10 + 10 + 10 2.55 2.55 2.55 --- 7.65 7.80 2450 2750 3.12 10.90 12.10
10 + 10 + 15 2.25 2.25 3.15 --- 7.65 7.90 2430 2800 3.15 10.60 12.20
10 + 10 + 20 1.91 1.91 3.83 --- 7.65 8.10 2400 2900 3.19 10.50 12.80
10 + 15 + 15 2.01 2.82 2.82 --- 7.65 8.00 2400 2650 3.19 10.50 11.70
10 + 15 + 20 1.74 2.43 3.48 --- 7.65 8.40 2370 2800 3.23 10.50 12.30
15 + 15 + 15 2.55 2.55 2.55 --- 7.65 8.00 2200 2900 3.48 9.70 12.70
10 + 10 + 10 + 10 1.91 1.91 1.91 1.91 7.64 8.40 2200 2680 3.47 9.80 11.80
10 + 10 + 10 + 15 1.74 1.74 1.74 2.43 7.65 9.10 2113 2950 3.62 9.30 13.00
Heating Mode
Combination of indoor unit Each capacity (kW) Total capacity
(kW) Total input (W)COP
Total current (A)
A room B room C room D room Rated Max Rated Max Rated Max
10 3.00 --- --- --- 3.00 4.00 1030 1370 2.91 4.70 6.10
15 3.80 --- --- --- 3.80 4.50 1420 1610 2.68 6.50 7.10
20 --- --- 5.60 --- 5.60 5.70 1840 2260 3.04 8.40 9.90
10 + 10 3.60 3.60 --- --- 7.20 7.50 2240 2560 3.21 9.90 11.20
10 + 15 3.08 4.32 --- --- 7.40 7.90 2120 2580 3.49 9.40 11.30
10 + 20 2.80 --- 5.60 --- 8.40 8.60 2610 2700 3.22 11.60 11.80
15 + 15 4.22 4.22 --- --- 8.44 8.60 2920 3000 2.89 12.80 13.20
15 + 20 3.46 --- 4.94 --- 8.40 8.60 2600 2650 3.23 11.50 11.60
20 + 20 --- 4.22 4.22 --- 8.44 8.60 2340 2680 3.61 10.40 11.80
10 + 10 + 10 2.73 2.73 2.73 --- 8.19 8.40 2700 2750 3.03 11.80 12.10
10 + 10 + 15 2.41 2.41 3.38 --- 8.20 8.40 2550 2720 3.22 11.20 11.90
10 + 10 + 20 2.05 2.05 4.10 --- 8.20 8.60 2250 2660 3.64 9.90 11.60
10 + 15 + 15 2.16 3.02 3.02 --- 8.20 8.40 2330 2680 3.52 10.30 11.70
10 + 15 + 20 1.86 2.61 3.73 --- 8.20 8.60 2130 2500 3.85 9.40 10.90
15 + 15 + 15 2.73 2.73 2.73 --- 8.19 8.40 2300 2700 3.56 10.20 11.80
10 + 10 + 10 + 10 2.05 2.05 2.05 2.05 8.20 8.60 2200 2400 3.73 9.70 10.50
10 + 10 + 10 + 15 1.91 1.91 1.91 2.67 8.40 9.00 2054 2550 4.09 9.10 11.16
Note : It is impossible to connect the indoor unit to 1 room only
57
Outline and Dimension M5MSY-2010
Outline and DimensionOutdoor UnitModel: M5MSY20/25/30BR
Note: Dimension in mm
Dimension A B C D E F G H I J K L
mm(inch)
940(37)
348(13.7)
756(29.8)
855(33.7)
392(15.4)
733(28.9)
603(23.7)
328(12.9)
303(11.9)
370(14.6)
362(14.3)
271(10.7)
Dimension M N O P Q R S T U V W X
mm(inch)
448(17.6)
190(7.5)
80(3.1)
58(2.3)
180(7.1)
32(1.3)
39(1.5)
126(5)
32(1.3)
15(0.6)
23(0.9)
44(1.7)
58
M5MSY-2010 Outline and Dimension
Indoor UnitModel: M5WMY 10/15JR
80028
8
206
288
Note: Dimension in mm
Indoor UnitModel: M5WMY 20/25JR
1065
310
224
310
Note: Dimension in mm
59
Outline and Dimension M5MSY-2010
Indoor UnitModel: M5CKY 10/15/20CR
Note: Dimension in mm
Indoor UnitModel: M5CKY 20/25ER
A
BC
D E
F
H
K
J I G
Note: Dimension in mm
MODEL A B C D E F G H I J K
M5CKY 10/15/20CR 570 570 295 275 20 640 640 408 408 364 364
MODEL A B C D E F G H I J K
M5CKY 20/25ER 820 820 350 290 60 990 990 627 627 607 607
60
M5MSY-2010 Outline and Dimension
Indoor UnitModel: M5CCY 10/15/20/25CR
Note: Dimension in mm
Indoor UnitModel: M5CMY 15/20/25ER
Note: Dimension in mm
MODEL A B C D E F G H I J K L M N O
M5CCY 10/15CR 31 881 842 802 10 905 72 261 411 351 225 211 232 212,8 114
M5CCY 20CR 31 1041 1002 962 10 1065 72 261 411 351 225 211 232 212,8 114
M5CCY 25CR 31 1176 1137 1097 10 1200 72 261 411 351 225 211 232 212,8 114
61
Electrical Data M5MSY-2010
Electrical DataIndoor
MODEL INDOOR UNIT M5WMY 10JR M5WMY 15JR M5WMY 20JR M5WMY 25JR
INDOOR MOTOR
INSULATION GRADE EPOWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50RATED INPUT POWER W 34 42 37 63RATED RUNNING CURRENT A 0.19 0.21 0.32 0.56MOTOR OUTPUT W 18 40POLES 4 8
MODEL INDOOR UNIT M5CKY 10CR M5CKY 15CR M5CKY 20CR
INDOOR MOTOR
INSULATION GRADE BPOWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50RATED INPUT POWER W 62 62 74RATED RUNNING CURRENT A 0.28 0.28 0.31MOTOR OUTPUT W 16 22POLES 6
MODEL INDOOR UNIT M5CKY 20ER M5CKY 25ER
INDOOR MOTOR
INSULATION GRADE BPOWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50RATED INPUT POWER W 89 103RATED RUNNING CURRENT A 0.40 0.45MOTOR OUTPUT W 20 30POLES 6
MODEL INDOOR UNIT M5CCY 10CR M5CCY 15CR M5CCY 20CR M5CCY 25CR
INDOOR MOTOR
INSULATION GRADE BPOWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50RATED INPUT POWER W 89 100 133 164RATED RUNNING CURRENT A 0.39 0.42 0.61 0.74MOTOR OUTPUT W 40 50 80 100POLES 4
MODEL INDOOR UNIT M5CMY 15ER M5CMY 20ER M5CMY 25ER
INDOOR MOTOR
INSULATION GRADE BPOWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50RATED INPUT POWER W 83.6 101 109RATED RUNNING CURRENT A 0.37 0.46 0.49MOTOR OUTPUT W 40 50 65POLES 4
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
62
M5MSY-2010 Electrical Data
Electrical Data - Heat pumpOutdoor
MODEL OUTDOOR UNIT M5MSY20BR M5MSY25BR M5MSY30BR
OUTDOOR MOTOR
INSULATION GRADE CLASS E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
RATED INPUT POWER W 72 68.3 68.3
RATED RUNNING CURRENT A 0.93 0.79 0.79
MOTOR OUTPUT W 61 61 61
COMPRESSOR
INSULATION GRADE CLASS E
POWER SOURCE V/Ph/Hz Inverter
CAPACITOR mF - - -
RATED INPUT POWER (COOLING) W 1183 1420 1420
RATED INPUT POWER (HEATING) W 1264 1491 1491
RATED RUNNING CURRENT (COOLING) A 4.69 6.7 6.7
RATED RUNNING CURRENT (HEATING) A 4.09 5.58 5.58
LOCKED ROTOR AMP. A 30 30 30
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
63
Wiring Diagram M5MSY-2010
Wiring DiagramOutdoor UnitModel: M5MSY20BR
64
M5MSY-2010 Wiring Diagram
Outdoor UnitModel: M5MSY25BR
65
Wiring Diagram M5MSY-2010
Outdoor UnitModel: M5MSY30BR
66
M5MSY-2010 Wiring Diagram
Indoor UnitModel: M5WMY10/15JR
Model: M5WMY20/25JR
67
Wiring Diagram M5MSY-2010
Indoor UnitModel: M5CKY10/15/20CR
Model: M5CKY20/25ER
68
M5MSY-2010 Wiring Diagram
Indoor UnitModel: M5CCY10/15CR
Model: M5CCY20/25CR
69
Wiring Diagram M5MSY-2010
Indoor UnitModel: M5CMY15ER
Model: M5CMY20/25ER
70
M5MSY-2010 Service and Maintenance
Service and MaintenanceWarning
Disconnect from main supply before servicing the air conditioner.The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.
••
Components Maintenance Procedures PeriodAir Filter(Indoor Unit)
1. Remove any dust adhering to the fi lter by using a vacuum cleaner or wash in lukewarm water (below 40˚C) with a neutral cleaning detergent.
2. Rinse the fi lter well and dry before placing it back onto the unit.3. Note: Never use gasoline, volatile substances or chemicals to
clean the fi lter.
At least once every 2 weeks.More frequently if necessary.
Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40˚C) and a neutral detergent solution.
2. Note: Never use gasoline, volatile substances or chemicals to clean the indoor unit.
At least once every 2 weeks.More frequently if necessary.
Condense Drain Pan & Pipe
1. Check the cleanliness and clean it if necessary.2. Check the condensate water fl ow.
Every 3 months.
Indoor Fan Check if there is any abnormal noise. If necessary.Indoor / Outdoor Coil
1. Check and remove the dirt between the fi ns.2. Check and remove any obstacles which hinder air fl ow through
the indoor or outdoor.3. Note: Avoid direct contact of any coil treatment material on the
plastic part. This may cause plastic part to deform as a result of chemical reaction.
Every month.
Power Supply 1. Check the running current and voltage for indoor and outdoor unit.
2. Check the electrical wiring and tighten the wire onto the terminal block if necessary.
Every 2 months.
Every year.
Compressor No maintenance needed if refrigerant circuit remains sealed. How-ever, check for refrigerant leak at joint and fi tting.
Every 6 months.
Indoor Models1. Open the front panel
Hold the panel at the recesses on the main unit (2 recesses on right and left sides) and lift it until it stops.
2. Remove the front panelWhile lifting the front panel further, slide it to the right and pull it to the front side. The left rotating shaft is detached. Slide the right rotating shaft to the left and pull it to the front side to remove it.
3. Attach the front panelAlign the right and left rotating shafts of the front panel with the grooves and push them all the way in.Gently close the front panel. (Push both ends and the center on the front panel.)
•
•
•
•
Rotatingshaft
Recess onmain unit
71
Service and Maintenance M5MSY-2010
Air Filter1. Open the front panel.
Hold the panel at the recesses on the main unit (2 recesses on right and left sides) and lift it until it stops.
Recess onmain unit
2. Pull out the air fi lters.Push a little upwards the tab at the center of each air fi lter, then pull it down.
3. Clean or replace each fi lter.When shaking off remaining water, do not wring the fi lter.
4. Set the air fi lter and close the front panel.Insert claws of the fi lters into slots of the front panel. Close the front panel slowly and push the panel at the 3 points. (1 on each side and 1 in the middle.)The air fi lter have a symmetrical form in the horizontal direction.
FRONT
CautionDon’t touch the metal parts of the indoor unit. It may cause an injury.When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing compound, scrubbing brushes, nor other hand stuff.After cleaning, make sure that the front panel is securely fi xed.
••••
•
Pre Start Up Maintenance(After Extended Shutdown)
Inspect thoroughly and clean indoor and outdoor units.Clean or replace air fi lters.Clean condensates drain line.Clean clogged indoor and outdoor coils.Check fan imbalance before operation.Tighten all wiring connections and panels.Check for refrigerant leakage.
Outdoor ModelsThe design of the M5MSY outdoor series allows servicing to be carried out easily. The removal of the top, front and side panels makes almost every part accessible. Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface once every 3 months. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be regularly cleaned by qualifi ed Air Conditioner Service Technicians to ensure suffi cient heat exchange and proper operation. Otherwise, the systems life span may be shortened.
Caution
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when performing a leakage test or an airtight test. These gases could cause severe explosion and damage if exposed to high temperature and pressure.It is recommended that only nitrogen or refrigerant be charged when performing the leakage or airtight test.
•
•
•
•
•
•
•
•••••••
72
M5MSY-2010 Troubleshooting
TroubleshootingFault ConditionWhen a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures.The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.
No Fault conditions Possible causes / corrective actions
1 The air conditioner unit will not resume after power failure.
The auto restart function is not functioning. Please turn on the unit with the wireless / wired controller.
•
2 The airfl ow is too slow or room cannot be cooled suffi ciently.
The air fi lter is dirty.The doors and windows are opened.The air suction and discharge of both indoor and outdoor units are clogged or blocked.The regulated temperature or temperature setting is not low enough.
•••
•
3 Discharge airfl ow has bad odor. Cigarettes, smoke particles, perfume and others, which might have adhered onto the coil, may cause odor.Contact your nearest dealer.
•
•4 Condensation on the front air grille of the indoor
unit.This is caused by air humidity after an extended period of operation.The set temperature is too low. Increase the temperature setting and operate the unit at high fan speed.
•
•
5 Water fl owing out from the air conditioner. Switch off the unit and contact your nearest dealer. This might be due to tilted installation.
•
6 Hissing airfl ow sound from the air conditioner unit during operation.
Liquid refrigerant fl owing into the evaporator coil.
•
7 The wireless controller display is dim. The batteries are discharged.The batteries are not correctly inserted.The assembly is not good.
•••
8 Compressor operates continuously. Dirty air fi lter. Clean the air fi lter.Temperature setting too low (cooling). Use higher temperature setting.Temperature setting too high (heating), Use lower temperature setting.
••
•
9 No cool air comes out during cooling cycle, or no hot air comes out during heating cycle.
Temperature setting too high (cooling). Use lower temperature setting.Temperature setting too low (heating). Use higher temperature setting.
•
•
10 On heating cycle, warm air does not come out. Unit is in defrost mode. Heating operation will resume after defrost cycle ends.
•
73
Troubleshooting M5MSY-2010
By means of diagnostic fl ow chart:
Generally, there are two kinds of problems, i.e. starting failure and insuffi cient cooling / heating. “Starting failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes “Insuffi cient cooling / heating”.
i ) Diagnosis of Electric circuit
: Faulty : Check : Cause : Remedy
No cooling/heating (Unit fails to start)
No voltage or low voltage
Wrong phase/missing phase (applicable to 3 phase model)
Components shorted
Connections loose
High or low voltage
Wrong phase/missing phase (applicable to 3 phase model)
Faulty
Blown
Tripped
Coil burned
Contact faulty
Faulty
Faulty fan motor
Defective operation switch
Evaporatorfan contactor
Over current relay for
evaporator fan
Fuse for operation
circuit
Unit powersupply
Condenser fan motor
Evaporator fan motor
Over current relay for
condenser fan
Running
21
No voltage or low voltage
Wrong phase/missing phase (applicable to 3 phase model)
Tripped
Get the right voltage
Repair the power line
Repair or replace the components
Tighten the connections
Get the right voltage
Check the power supply to the motor: repair when necessary
Change the contactor
Repair or change the motor
Repair the contacts
Repair or change the switch
Get the right voltage
Check the power supply to the motor: repair when necessary
Stop
Running
Stop
74
M5MSY-2010 Troubleshooting
Coil burnt
Fan motor faulty
Faulty
Blown
Coil burnt
Contact faulty
Faulty
Open compressor windings
Incorrect wiring
Condenserfan contactor
21
Change the contactor
Change the contacts
Repair or replace the motor contactor
Repair or change if necessary
Change the contactor
Change the compressor
Change the contacts
Correct the wiring
Contact faulty
Other electricalcomponent faulty
Evaporatorcontactor
The most common causes of air conditioner failure to “start” are :a) Voltage not within ±10% of rated voltage.b) Power supply interrupted.c) Improper control settings.d) Air conditioner is disconnected from main power source.e) Fuse blown or circuit breaker off.
75
Troubleshooting M5MSY-2010
ii ) Diagnosis of Refrigerant Circuit / Application
There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insuffi cient cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge air as well as running current.
: Faulty : Check : Cause : Remedy
Insuffi cient cooling
Indoor/outdoor coil dirty (clogged)
Indoor air fi lter dirty
Restriction e.g. at strainer, capillary, fi lter dryer, etc.
Restricted
Compressor
Refrigerant circuit
High coolingload
Aircirculation
Clean the coil
Clean the fi lter
Fan motor malfunction Change or repair the motor
Obstruction at air inlet /outlet of indoor / outdoor unit
Remove the obstruction
Excessive heat source.e.g. electric kettle Remove or reduce heat source
Room overcrowded with people Reduce number of people in the room
Windows / doors wide open Close the windows / doors
Refrigerant short charge or refrigerant leakage
Add refrigerant. Repair leakage if detected
Repair clogging or replace faulty components
Less or no compression (Low running current)
Replace compressor
Satisfactory operation with temperature difference of air intake & discharge of indoor unit 8°C to 13°C. *( * value is for reference only )
76
M5MSY-2010 Troubleshooting
Insuffi cient heating
Indoor/outdoor coil dirty (clogged)
Indoor air fi lter dirty
Restriction e.g. at strainer, capillary, fi lter dryer, etc.
Restricted
Compressor
Refrigerant circuit
High heating load
Aircirculation
Clean the coil
Clean the fi lter
Fan motor malfunction Change or repair the motor
Obstruction at air inlet /outlet of indoor / outdoor unit
Remove the obstruction
Windows / doors wide open Close the windows / doors
Refrigerant short charge or refrigerant leakage
Add refrigerant. Repair leakage if detected
Repair clogging or replace faulty components
Less or no compression (Low running current)
Replace compressor
Satisfactory operation with temperature difference of air intake & discharge of indoor unit 14°C to 20°C. *( * value is for reference only )
77
Troubleshooting M5MSY-2010
Indicator Lights
IR Signal ReceiverWhen an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit will respond as below to confi rm acceptance of the signal transmission.
ON to OFF 1 Long BeepOFF to ONPump down/Cool force on 2 Short Beep
Others 1 Short Beep
Heat Pump UnitThe table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions.The LED indicator lights are located at the side of the air conditioner unit.The heat pump units are equipped with an “auto” mode sensor whereby it will provide reasonable room temperature by switching automatically to either “cool” or “heat” mode according to the temperature set by the user.
IR Receiver
ON/OFF
Cool / Heat
TimerSleep
ON/OFF switch
IR Receiver
LED Indicator Lights: Normal Operation and Fault Conditions for Heat Pump Unit
1COOL/HEAT
(GREEN/RED)
Normal Operation / Fault Indication
Green Cool mode
Red Heat mode
Red Auto mode in Heating operation
Green Auto mode in Cooling operation
Time off (when unit is on)
Time on (when unit is off)
Sleep mode on
Green Fan mode on
Green Dry mode on
Red Defrost operation
Green Error indication
ON Blinking
78
M5MSY-2010 Troubleshooting
Error Code Diagnosis by Wireless Handset GS01
TURBO QUIET
SLEEP
ON OFF
MODE
TIMER
CANCEL CANCELCLOCK ON TIMER CANCEL
OFF TIMER CANCEL
Diagnosis Step1. Hold down ON TIMER CANCEL button or OFF TIMER CANCEL button for 5 seconds, a “ ” indication
fl ashes on the temperature display section.
2. Press ON TIMER CANCEL or OFF TIMER CANCEL repeatedly until indoor buzzer produces a long beep. This indicates the error code, refers to Error Codes table and is displayed on the temperature display section.
3. A short beep or two consecutive beeps indicate non-corresponding error codes.
4. To cancel the error code display, hold down ON TIMER CANCEL or OFF TIMER CANCEL button for 5 seconds. Alternatively, the code display will cancel itself if the button is not pressed for 1 minute.
Error Code Diagnosis by Wired Handset Netware 3C
79
Troubleshooting M5MSY-2010
Error Codes
ERROR CODE ERROR DESCRIPTION
00 NORMAL
A1 INDOOR PCB ERROR
A3 DRAIN PUMP ABNORMAL
A5 ANTIFREEZE (COOLING)/HEAT EXCHANGER OVERHEAT (HEATING)
A6 INDOOR FAN MOTOR ABNORMAL
AH ELECTRICAL AIR CLEANER ABNORMAL
C4 INDOOR HEAT EXCHANGER (1) THERMISTOR SHORT/OPEN
C5 INDOOR HEAT EXCHANGER (2) THERMISTOR SHORT/OPEN
C7 LOUVER LIMIT SWITCH ERROR
C9 INDOOR ROOM THERMISTOR SHORT/OPEN
E1 OUTDOOR PCB ERROR
E3 HIGH PRESSURE PROTECTION
E4 LOW PRESSURE PROTECTION
E5 COMPRESSOR MOTOR LOCK/COMPRESSOR OVERLOADED
E6 COMPRESSOR START-UP ERROR
E7 OUTDOOR DC FAN MOTOR LOCK
E8 AC INPUT OVER CURRENT
E9 EXV ERROR
EA 4 WAY VALVE ERROR
F3 DISCHARGE PIPE OVERHEAT
F6 HEAT EXCHANGER OVERHEAT
HO COMPRESSOR SENSOR SYSTEM ERROR
H3 HIGH PRESSURE SWITCH ERROR
H6 COMPRESSOR FEEDBACK DETECTION ERROR
H7 FAN MOTOR OVERLOADED/OVERCURRENT/SENSOR ABNORMAL
H8 AC CURRENT SENSOR ERROR
H9 OUTDOOR AIR THERMISTOR SHORT/OPEN
J1 PRESSURE SENSOR ERROR
J3 COMPRESSOR DISCHARGE PIPE THERMISTOR SHORT/OPEN/MISPLACED
J5 SUCTION PIPE THERMISTOR SHORT/OPEN
J6 OUTDOOR HEAT EXCHANGER THERMISTOR SHORT/OPEN
J7 SUBCOOLING HEAT EXCHANGER THERMISTOR SHORT/OPEN
J8 LIQUID PIPE THERMISTOR SHORT/OPEN
J9 GAS PIPE THERMISTOR SHORT/OPEN
L1 INVERTER OUTDOOR PCB ERROR
L3 OUTDOOR CONTROL BOX OVERHEAT
L4 HEAT SINK OVERHEAT
L5 IPM ERROR/IGBT ERROR
L8 INVERTER COMPRESSOR OVERCURRENT
L9 COMPRESSOR OVERCURRENT PREVENTION
80
M5MSY-2010 Troubleshooting
ERROR CODE ERROR DESCRIPTION
LC COMMUNICATION ERROR (OUTDOOR CONTROL PCB AND INVERTER PCB)
P1 OPEN PHASE OR VOLTAGE UNBALANCE
P4 HEAT SINK THERMISTOR SHORT/OPEN
PJ CAPACITY SETTING ERROR
U0 INSUFFICIENT GAS
U2 DC VOLTAGE OUT OF RANGE
U4 COMMUNICATION ERROR
U7 COMMUNICATION ERROR (OUTDOOR CONTROL PCB AND IPM PCB)
UA INSTALLATION ERROR
UF PIPING & WIRING INSTALLATION MISMATCH/WRONG WIRING/INSUFFICIENT GAS
UH ANTIFREEZE (OTHER ROOMS)
Outdoor LED error indicationThe outdoor unit LED indicates the running condition of the system:
LED INDICATIONDescriptionGreen Red
A 1 2 3 4NORMALINSTALLATION ERRORANTIFREEZE (OTHER ROOMS)
HEAT SINK OVERHEAT
IPM ERROR/IGBT ERROR
INSUFFICIENT GAS
AC INPUT OVER CURRENT
COMPRESSOR START-UP ERROR
COMMUNICATION ERROR (OUTDOOR CONTROL PCB AND IPM PCB)
4 WAY VALVE ERROR
DC VOLTAGE OUT OF RANGE
COMPRESSOR MOTOR LOCK/COMPRESSOR OVER-LOADED
DISCHARGE PIPE OVERHEAT
81
Troubleshooting M5MSY-2010
ANTIFREEZE (COOLING)/HEAT EXCHANGER OVER-HEAT (HEATING)HEAT EXCHANGER OVERHEATCOMPRESSOR SENSOR SYSTEM ERRORCOMPRESSOR FEEDBACK DETECTION ERRORAC CURRENT SENSOR ERROROUTDOOR AIR THERMISTOR SHORT/OPENCOMPRESSOR DISCHARGE PIPE THERMISTOR SHORT/OPEN/MISPLACEDCOMPRESSOR DISCHARGE PIPE THERMISTOR SHORT/OPEN/MISPLACEDLIQUID PIPE THERMISTOR SHORT/OPENGAS PIPE THERMISTOR SHORT/OPENHEAT SINK THERMISTOR SHORT/OPEN
OUTDOOR CONTROL BOX OVERHEAT
OUTDOOR PCB ERROR
OUTDOOR DC FAN MOTOR LOCK
Legend Blinks Off On
If faulty condition occurs, please contact the nearest local dealer or qualifi ed service personnel. Do not attempt to troubleshoot the unit yourself. For any enquiries on spare parts please contact your authorized dealer.
Error Code Diagnosis by Unit Last State Memory Using Wireless Handset1. Remove battery from wireless handset.2. Wait for the display to fi nally go off (as this handset uses very small amount of power, hence it takes
longer for the memory to reset).3. Replace battery again and immediately (before display comes back on the LCD screen), press on Mode
and ON/OFF buttons together until you see “00” is being displayed.4. Press Mode button to 5:00. 5. Press ON/OFF button once.6. After that, remove battery from wireless handset and wait until the display has gone off. Then, replace
battery again into the handset.7. Finally, repeat the fault diagnosis steps by wireless handset GS01 above.
Error Code Diagnosis by Unit Last State Memory Using Wired Handset1. Press SLEEP and TIMER ACTIVE buttons together until error code starts fl ashing on the last 2 digits of
the clock display area.
82
M5MSY-2010 Exploded View and Part List
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
No Description1 Assy. Front Grille
2 Panel, McQuay
3 Disch. Grille Hor.Blade Assy.
4 Assy. Bottom Frame
5 Assy. Control Box
6 Assy. Service Cover
7 Assy. Piping Fixture
8 Motor
9 Motor Mounting Plate (1)
10 Motor Mounting Plate (2)
No Description11 Blower
12 Assy. Installation Plate
13 Right Side Panel
14 Cover, Drip Proof
15 Clip, Coil Sensor
16 Assy. Heat Exchanger
17 Assy. Drain Hose
18 Fan Bearing Vibration Absorber
19 Air Filter
20 Assy. Control Module
1
2
3
8
10
12
15
18
4
11
13
14
9
17
7
5
6
20
19
16
Exploded View and Part ListIndoor UnitModel: M5WMY10/15JR
83
Exploded View and Part List M5MSY-2010
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: M5WMY 20/25JR
No Description1 Assy. Chasis2 Motor3 Blower4 Fan Bush5 Cover, Motor6 Assy. Heat Exchanger7 Assy. Air Discharge Housing8 Assy. Louver9 Hose
No Description10 Assy. Control Box11 Assy. Control Module12 Cover, Control Box13 Cover, Service14 Assy. Mounting Plate15 Assy. Front Cover16 Cover, Front17 Intake Grille18 Filter
84
M5MSY-2010 Exploded View and Part List
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: PLCKY-CR
No Description1 Frame2 Assy. Intake Grille B3 Filter4 Lock, Grille5 Discharge, Foam6 Discharge, Foam LED7 Discharge, Foam Short8 Louver9 Louver, LED
10 Lingkage, Cover
No Description11 Lingkage, Motor Cover12 Assy. Bracket Receiver (LED/SLM)13 Assy. Motor14 Crank, Connector15 Louver, Holder16 Cross, Crank17 Ins. Long18 Ins. Short19 Ins. Corner
85
Exploded View and Part List M5MSY-2010
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: M5CKY 10/15/20CR
86
M5MSY-2010 Exploded View and Part List
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: M5CKY 10/15/20CR
No Description1 Assy. Base2 Assy. Casing3 Assy. Heat Exchanger4 Cover, Fan5 Blower6 Plate, Wire7 Motor8 Bush, Motor9 Bush, Motor Ring
10 Assy. Control Box11 Pump, Water12 Switch, Water Level13 Bush, Wire
No Description14 Bush, Pump15 Assy. Drain Pump Support Bracket16 Assy. End Plate Support17 Clip, Coil Sensor18 Support, Heat Exchanger19 Cover, Terminal20 Assy. Cover Wire21 Connector, Drain22 Hose, Drain23 Assy. Cover Valve24 Assy. Drain Pan25 Bush, Wire26 Cover, Wire Bracket
87
Exploded View and Part List M5MSY-2010
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: PLCKY-ER
No Description1 Front, Frame
2 Assy., Intake Grille
3 Assy., Air Discharge Main
4 Assy., Air Discharge Main Right
5 Assy., Air Discharge Main Left
6 Air Filter, CK-A/AR
7 Assy., Air Swing Motor
No Description8 Crank Connector
9 Assy., LED
10 Wire, Guide
11 Cover, Cross Connector
12 Assy., Cover Corner A
13 Assy., Cover Corner B
14 Mounting Plate
88
M5MSY-2010 Exploded View and Part List
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: M5CKY 20/25ER
No Description
1 Assy. Base Pan
2 Assy. Coil
3 Assy. Coil Bracket
4 Assy. Drain Pump Mounting
5 Assy. Panel Side Back
6 Assy. Side Panel Front
7 Assy. Motor & Rubber
8 Blower, Turbo Fan DIA462 X 171.5 3P085496-1
9 Assy. Drain Pan
10 Assy. Fan Cover
11 Assy. Cover Control Box
12 Assy. Control Box
13 Assy. Cover Terminal
14 Support, Coil
15 Cover, Wire A
No Description
16 Cover, Wire B
17 Bracket, Hanger A
18 Bracket, Hanger B
19 Bracket, Hanger C
20 Fresh Air Adaptor
21 Assembly, Valve Plate
22 Assy. Air Guide
23 Assy. Partition Holder
24 Cover, Wire
25 Switch Water Level 1A - CK Drain Pump
26 Pump, Water PC-04226-OYOB YCK
27 Hose, Drain PE 18.3 X 0.5 X 315.0
28 Connector, Drain
29 Ins., Drain Connector
89
Exploded View and Part List M5MSY-2010
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: M5CCY 10/15/20/25CR
No Description1 Cabinet2 Assy. Fan Deck3 Assy. Heat Exchanger4 Assy. Drain Pan5 Assy. Secondary Drain Pan6 Hanger7 Control Module8 Assy. Blower Right
No Description9 Assy. Blower Left10 MotorParts Not in Diagram
Handset, Wired
Air Filter
Holder, Thermistor
Clip, Coil Sensor
90
M5MSY-2010 Exploded View and Part List
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: M5CMY 15/20/25ER
91
Exploded View and Part List M5MSY-2010
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Indoor UnitModel: M5CMY 15/20/25ER
No Description1 Assy. Top Panel2 Assy. Heat Exchanger3 Assy. Vane4 Assy. Drain Pan5 Assy. Control Box6 Terminal Box Cover7 Motor8 Bracket, Motor9 Blower
10 Housing, Blower11 Motor, Louver
No Description12 Assy. Panel Bottom13 Cover, Hanger L1 (C)14 Cover, Hanger L2 (D)15 Cover, Hanger R1 (A)16 Cover, Hanger R2 (B)17 Bracket, Mounting18 Control Box CoverParts Not in Diagram
Handset, Wireless
Control Module
Intake Grille
92
M5MSY-2010 Exploded View and Part List
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Outdoor UnitModel: M5MSY20BR
No Description No Description1 Assy. Base Pan 14 Assy. Comp. Mounting Plate2 Assy. Outdoor Coil 15 Grommet, Comp.3 Flat Washer 16 Compressor4 Washer, Spring 17 Terminal Cover5 Screw 18 Motor, Bracket6 Assy. Panel Right Back 19 Plate, Seal Board7 Assy. Panel Top 20 Assy. Valve Plate Main8 Plastic, Handle 21 Assy. 4WV9 Partition 22 Panel, Service10 Assy. Control Box 23 Plastic, Front Grille11 Assy. Propeller Fan 24 Plastic, Valve Cover12 Motor 25 Access, Cover13 Panel, Front/ Left 26 Compressor, Felt
93
Exploded View and Part List M5MSY-2010
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Outdoor UnitModel: M5MSY25BR
No Description No Description1 Assy. Base Pan 15 Grommet, Comp.2 Assy. Outdoor Coil 16 Accumulator3 Flat Washer 17 Compressor4 Washer, Spring 18 Terminal Cover5 Screw 19 Motor, Bracket6 Assy. Panel Right Back 20 Plate, Seal Board7 Assy. Panel Top 21 Assy. Valve Plate Main8 Plastic, Handle 22 Assy. 4WV9 Partition 23 Panel, Service10 Assy. Control Box 24 Plastic, Front Grille11 Assy. Propeller Fan 25 Plastic, Valve Cover12 Motor 26 Access, Cover13 Panel, Front/ Left 27 Compressor, Felt14 Assy. Comp. Mounting Plate
94
M5MSY-2010 Exploded View and Part List
Note: All exploded view and part list are subjected to change by the manufacturer without prior notice
Outdoor UnitModel: M5MSY30BR
No Description No Description1 Assy. Base Pan 15 Grommet, Comp.2 Assy. Outdoor Coil 16 Accumulator3 Flat Washer 17 Compressor4 Washer, Spring 18 Terminal Cover5 Screw 19 Motor, Bracket6 Assy. Panel Right Back 20 Plate, Seal Board7 Assy. Panel Top 21 Assy. Valve Plate Main8 Plastic, Handle 22 Assy. 4WV9 Partition 23 Panel, Service10 Assy. Control Box 24 Plastic, Front Grille11 Assy. Propeller Fan 25 Plastic, Valve Cover12 Motor 26 Access, Cover13 Panel, Front/ Left 27 Compressor, Felt14 Assy. Comp. Mounting Plate
© 2010 McQuay International www.mcquayup.com+1 (800) 432-1342
Products manufactured in an ISO certified facility.This document contains the most current product information as of this printing. For the
most up-to-date product information, please go to www.mcquayup.com