moehlesmrf
TRANSCRIPT
-
7/29/2019 MoehleSmrf
1/33
Special Moment Frames1by Jack P. Moehle
Pacific Earthquake Engineering Research Center
University of California, Berkeley
1. Target Yield Mechanism
designlateral
loads
designlateral
loads
Figure 1.1 Target yield mechanism
One of the guiding principles of seismic design
is to spread yielding throughout the structure so
that large inelastic deformations do not
concentrate in isolated locations. In design of a
Special Moment Resisting Frame (SMRF) it is
important to avoid a yielding mechanism
dominated by yielding of the columns in a single
story, as this can result in very large local
demands in the columns. Instead, it is desirable
in a SMRF that yielding be predominantly in thebeams (Figure 1.1). This is a fundamental
objective in the design of a SMRF.
Note that even if the beams are targeted as the
main elements to yield, some column yielding
must be anticipated. For example, yielding at the
foundation seems likely (Figure 1.1). Also, it is
difficult to completely protect the columns from
yielding in other stories, as will be discussed
later.
Given this capacity-design approach of having plastic hinges in the beams, the beams will be
sized for the design seismic loads (usually based on analysis under code-specified loading), theywill be detailed for ductile response, and the rest of the system will be proportioned to reduce the
likelihood of inelastic action away from the beam plastic hinges.
2. Beams
2.1 Design objective
As discussed above, the design objective in a SMRF is to provide a stiff and strong spine of
columns up the height of the building so that concentrations of inelastic action in isolated stories
are avoided. Therefore, the objective is for beams to form flexural plastic hinges at targetedlocations through the height of the frame. The design also should attempt to avoid inelastic
response in shear as well as anchorage or bond failures.
1
1 Prepared for CE 244, Reinforced Concrete Structures, a graduate class taught at the University of
California, Berkeley
-
7/29/2019 MoehleSmrf
2/33
2.2 Design actions on beams
The seismic demands imposed on building frames are a complicated function of the earthquake
as well as the building stiffness, strength, mass, and configuration. Therefore, it is not possible to
state with any accuracy the demands that beams in SMRFs, in general, need to sustain. However,
some approximations of the level of inelasticity can be made.
According to the International Building Code and Uniform Building Code, SMRFs are allowed
to be designed for a force reduction factor ofR = 8, that is, they are allowed to be designed for a
base shear equal to one-eighth of the value obtained from elastic response analysis. Assuming an
average building overstrength ratio of about 2.5 (actual building strength about 2.5 times the
design value) owing to material overstrengths, section oversizing, strain-hardening, and
interactions among structural components and among structural and nonstructural components
that were not considered in design, the effective strength is about one-third of the strength
required for elastic response. Accepting the equal displacement rule, the global displacement
ductility for the building would be approximately 3. Local concentrations of interstory drift
[Moehle, 1992] reasonably could result in local ductility demand about twice the global value, or
equal to 6. For a typical beam span-to-depth ratio of ten, the local rotational ductility demand
within the flexural plastic hinge would be approximately 2.5 times the local displacement
ductility, resulting in an estimate of rotational ductility equal to 15. (See companion paper on
seismic design principles for more detailed discussion of this topic.)
An alternative approach views demands directly in terms of drift and member rotation
demands. Assuming a global drift angle of 0.015 for a design-level event, the local drift ratio
could reasonably be 0.03. The yield curvature for a typical beam is on the order ofy/0.7h, andthe flexural plastic hinge length can be approximated as being equal to h/2. Assuming that the
gravity load results in moments at the beam ends less than half the moment capacity, and
assuming that the columns do not contribute to drift (that is, they are relatively stiff), the
curvature ductility for a given drift ratio can be calculated. For the drift ratio of 0.03, and for
reasonable aspect ratios, the curvature ductility demand for a beam is approximately 20. This
value is reasonably close to the value obtained in the preceding paragraph.
Both approximations assume that the curvature demand is directly related to the building drift.
This is only approximately correct, and even then only in the case of reversing plastic hinges.
This subject is considered in more detail later.
2.3 Beam behavior
2.3.1 Formation of plastic hinges
An objective in design of SMRFs is to restrict most yielding to beams, which are speciallydetailed to resist the imposed actions. To get an understanding of the actions on a beam, consider
the framing shown in Figure 2.1.
Plastic moment strength can be assumed to be equal to the moment that will develop as theframe is deformed to the maximum deformation under the design earthquake loading. ACI 318
Chapter 21 definesMpras being equal to at least 1.25Mn. It is likely that larger moments will
develop in a beam if it responds to the curvatures that are commonly anticipated for a SMRF. As
discussed previously, curvature ductility demands on the order of 15 to 20 can be anticipated in
some SMRFs.
Under gravity loading shown in gray, the beam develops the moment diagram shown. Under
service level gravity loads, it is expected that the moments will be less than half the nominal
2
-
7/29/2019 MoehleSmrf
3/33
moment strengths. Also, it is unlikely that the full
service load will be present when the earthquake
occurs, so even smaller moments are likely.
If under earthquake loading the frame sways to
the right, the column shears would be as shown by
the black arrows. The moment diagram would shiftunder this loading, shown by the blue, dashed
curve. The first section likely to reach the plastic
moment is the negative-moment section. This
section will begin to develop plastic rotation before
the positive moment section yields.
As the loading continues, the positive-moment
section may yield and develop plastic rotation.
While this is happening, the rotations at the
negative-moment section continue to grow.
2.3.2 Behavior of reversing plastic hinges
As a building sways back and forth during an
earthquake, the motion of the building drives the
beam plastic hinges through displacement or
deformation histories.
Envision the building drift history as shown by
the simple waveform (Figure 2.2). Assume the
frame sways to point I. While this happens, the end
of the beam that has negative moment (top in tension) under gravity loads is deformed as shown
on the moment-curvature plot by the blue curve to point I. The strain distribution is also shown
next to the beam, showing the top in tension, the bottom in compression note that the tensile
strains exceed the compressive strains for a beam with modest amounts of tension longitudinal
reinforcement. The stress-strain histories of the top and bottom bars also are shown below thebeam.
Mpr-
Mpr+
L R
Bottom in tension
y
y
Mpr-
Mpr+
L R
Bottom in tension
y
y
Figure 2.1 Plastic hinge formation
As the building drifts from point I to II (shown in red), the curvature of the beam reverses, as
shown in the moment-curvature diagram. For the beam cross section shown, the cross-sectional
area of the top reinforcement is larger than that of the bottom reinforcement. As a result, the total
tension force developed by the beam bottom reinforcement is insufficient to yield the top
reinforcement in compression. Therefore, unless other effects dominate (such as loss of bond
through a beam-column joint and subsequent pull-through of the top reinforcement) the top beam
reinforcement will be in compression but will not be strained to the yield point in this case the
cracks that opened at state I remain open through the depth of the beam. If shear forces are high,this can lead to sliding along the cracked interface such sliding can lead to a moment-curvature
relation that is pinched, with slackness occurring for low moment and curvature values. Note thestress-strain histories for the longitudinal reinforcement. The top reinforcement is in compression
stress while showing tensile strain. Because the top reinforcement is in tension strain, the bottom
reinforcement is driven to very large tensile strain in order to achieve the curvatures demanded ofthe beam.
As the beam is flexed to position III, the situation reverses.
3
-
7/29/2019 MoehleSmrf
4/33
I
II
III
time
M
drift
As
As
I II III
fs
s
fs
s
start here
curvature
II
I
IIII
IIIII
IIIIII
I
II
III
time
M
drift
As
As
I II III
fs
s
fs
s
fs
s
start here
curvature
II
I
IIII
IIIII
IIIIII
Figure 2.2 Reversing plastic hinge behavior
2.3.3 Reversing and non-reversing plastic hingesIf the beam is relatively short and/or the gravity loads relative low compared with seismic
design effects, the beam behavior is likely to be as shown on the left of Figure 2.3. As the beam
is deformed by the building response to the earthquake motions, the moments reach the plastic
moment capacities at the beam ends (adjacent to the column face). As the earthquake sway
reverses, the plastic hinges form again at the same locations, and a reversing plastic hinge forms,
as presumed in the previous discussion.
If the span or gravity loads are relatively large compared with earthquake effects, then a less
desirable behavior can result. This is illustrated on the right-hand side of Figure 2.3. As the
beam is deformed by the earthquake, the moments reach the plastic moment capacities in
negative moment at the column face and in positive moment away from the column face. The
deformed shape is shown. Upon reversal, the same situation occurs, but on opposite ends of thebeam. In this case, the sections that had yielded previously do not yield in the opposite direction,
but instead the plastic hinge forms in a different location. Note the deformed shape. As the
deformations continue to reverse, the plastic hinges do not reverse, but instead continue to build
up rotation. This results in progressively increasing rotations of the plastic hinges, so that for along earthquake the rotations can be very large and the vertical movement of the floor can exceed
serviceable values. This type of behavior should be avoided through design. In evaluation of
existing buildings, this type of behavior should be investigated because if it does occur, the
rotations can well exceed values estimated based on static inelastic analysis.
4
-
7/29/2019 MoehleSmrf
5/33
Mp-
Mp+
Mp-
Mp+
low gravity loadshigh gravity loads
reversingplastic hingereversingplastic hinge
non-reversingplastic hingenon-reversingplastic hingenon-reversingplastic hinge
Figure 2.3 Reversing and non-reversing plastic hinges
It is possible to determine whether non-reversing plastic hinges are likely. As shown in
the two moment diagrams, reversing plastic hinges are expected if the slope of thepositive moment diagram is negative, while non-reversing plastic hinges are anticipated if
the slope is positive this of course
assumes that the moment strength doesnot change appreciably along the span.
For the case of uniformly distributedload, consider equilibrium of the freebody shown in Figure 2.4. Summing
moments about VR:
wu
ln
MpM
p
+
VRVL
wu
ln
MpM
p
+
VRVL
Figure 2.4 Free-body diagram cut through plastic
hin es at end of beam02
2
=+ + nunLpplw
lVMM
Setting the slope of the moment diagram (the shearVL) equal to zero, we find that a
non-reversing plastic hinge is likely if
+ + ppnu MM
lw
2
2
2.3.4 Computed flexural ductility of beam cross sections
Response of beams in bending can be computed readily using computer programs (e.g.,
UCFyber). Most programs consider only monotonic loading response, though some are able to
represent reversed cyclic loading effects. Regardless the program, the output is only as good as
the input, the computation algorithm, and the ability of the user to make sensible interpretations.
5
-
7/29/2019 MoehleSmrf
6/33
To gain a sense of the important variables, Figure 2.5 presents results computed using
UCFyber. Longitudinal reinforcement was assumed to have typical Grade 60 reinforcement
properties, including strain-hardening. Concrete confinement was considered within the
boundary of perimeter hoops, and followed the Mander relations. All other concrete was
unconfined. Unconfined concrete had maximum strain capacity of 0.005. Confined concrete was
assumed to have maximum compressive strain capacity of 0.02 (a practical limit for such sections
considering reinforcement buckling and subsequent fracture). The sections were flexed so the topwas in tension.
Unconfined sections (Figure 2.5) were unable to reach the curvature ductilities estimated for
SMRFs (approximately 15 to 20). Sections with the confinement were able to reach
approximately the expected curvature ductility demand. ACI 318, Chapter 21, limits the ratio of
area of tension reinforcement to area of compression reinforcement. Sections 1c and 1u represent
cases that approach the ACI limit. For those sections, the available curvature ductility is barely
equal to the required value even with transverse reinforcement.
Beam 1c Beam 2c
24
18No. 3 stirrups
@ 6 inches
Beam 1u
0
2000
4000
6000
8000
10000
12000
14000
0 0.001 0.002 0.003 0.004 0.005
curvature, 1/inch
moment,kip-inch
Beam 1c
Beam 2c
Beam 2u
20y
y
Beam 1u Beam 2u
No. 9 Grade 60 longitudinal bars,fc = 4 ksi
Beam 1c Beam 2c
24
18No. 3 stirrups
@ 6 inches
Beam 1c Beam 2c
24
18No. 3 stirrups
@ 6 inches
Beam 1uBeam 1u
0
2000
4000
6000
8000
10000
12000
14000
0 0.001 0.002 0.003 0.004 0.005
curvature, 1/inch
moment,kip-inch
Beam 1c
Beam 2c
Beam 2uBeam 2u
20y
y
Beam 1u Beam 2u
No. 9 Grade 60 longitudinal bars,fc = 4 ksi
Beam 1u Beam 2u
No. 9 Grade 60 longitudinal bars,fc = 4 ksi
Figure 2.5 Computed moment-curvature relations for unconfined and confined concrete sections. Top
in tension.
2.3.5 Shear behavior
Consider a member subjected to a concentrated lateral load as shown in Figure 2.6. Assume
that the 45-degree truss model effectively represents behavior in flexure and shear. Also, assume
6
-
7/29/2019 MoehleSmrf
7/33
web member
tension stress
fy0web member
tension stress
fy0
Figure 2.6 Truss model
that the tension chord is designed so that
it does not yield, and that the
compression diagonals are sufficiently
strong that they do not crush. Yielding is
controlled by yielding of the web
reinforcement, shown in blue.
In this case, on the first cycle of
inelastic loading, the relation between
reinforcement strain and applied shear
will be nonlinear, as shown qualitatively
in Figure 2.7. Upon unloading, the
transverse reinforcement will unload and
show a residual tension strain. Upon
loading in the opposite direction, the
transverse reinforcement will yield in
tension again. Under repeated loading,
the tension strain in the transverse
reinforcement will tend to increase
progressively. The result is lateral
dilation of the member cross section,
with widening cracks and eventual
breakdown of the integrity of the
concrete core. The ability to resist
transverse loading decreases with
continued loading. V
transverse
steel strain
V
transverse
steel strain
Figure 2.7 Idealized strains in hoop reinforcement ofshear- ieldin member
Reinforced concrete elements behave
very differently depending on whether
the inelastic action is predominantly in
shear versus predominantly in flexure.
The data shown in Figure 2.8 are fromJirsa [1977]. The upper load-
deformation relation is for a member
where shear dominates; the lower
relation is one where flexure dominates.
Inelastic response in shear shows
strength degradation associated with the
shear-yielding mechanism of Figure 2.7.
The flexural mechanism shows stable
response for this configuration.
Figure 2.8 Load-deformation response of shear-yielding
and flexure-yielding members
2.4 Beam design
2.4.1 Longitudinal reinforcement
The ACI Building Code limits the
longitudinal reinforcement ratio to 0.025.
This limit is based on construction
7
-
7/29/2019 MoehleSmrf
8/33
considerations (it is difficult to place concrete with this much or more reinforcement), shear
considerations (members with this much reinforcement tend to have excessively high shear
stresses), and bond considerations (reinforcement must be anchored in joints, and this becomes
increasingly difficult as the reinforcement ratio increases).
Some codes limit the reinforcement ratio to some fraction of the balanced reinforcement ratio.
Under reversed loading, where stresses are not uniquely related to strains (Figure 2.2), and inmembers with heavy hoop reinforcement (where concrete compression strains are enhanced),
conditions are considerably different from those on which balanced failure computations are
based, so this concept has been abandoned in the seismic provisions of the ACI code.
As noted previously (Figure 2.2), if the cross-sectional areas of top and bottom longitudinal
reinforcement differ significantly, cracks that open when the larger area of reinforcement yields
will remain open on load reversal, unless the bars slip through the joint because of bond failure.
To reduce consequences of this behavior, ACI limits the ratio of top to bottom reinforcement
areas to between 0.5 and 2.0.
The limits on reinforcement ratios also relate to conventional considerations of flexural
ductility capacity. Figure 2.5 shows moment-curvature relations for some beam cross sections.
When the ratio of tension to compression reinforcement areas differs significantly for large
reinforcement ratios, the flexural ductility capacity is reduced. Confinement of the cross section
with moderate transverse reinforcement considerably improves the computed behavior.
Because of uncertainty in the moment requirements in seismic conditions as the frame responds
to horizontal and vertical excitations, ACI 318 requires that the positive and negative moment
strengths along the span be not less than one-fourth the strength provided at the face of the joint.
Lap splices of longitudinal reinforcement are permitted in ACI 318 only if hoop reinforcement
is provided over the lap length. The maximum spacing of the hoops is not to exceed d/4 or 4
inches. Laps are not to be used within joints, within a distance of twice the member depth of
joints, and at locations where analysis indicates flexural yielding. The requirement for close
spacing is based on the understanding that laps are effective only if closely spaced hoop
reinforcement confines the splice after cover concrete spalls. Mechanical splices can be used, but
should be Type 2.
Mp-
Mp+
low gravity loads
Mp-
Mp+
low gravity loads
Figure 2.9 Moment diagrams of a yielding frame
2.4.2 Transverse reinforcement
Current building codes require special
hoops to confine core concrete and restrain
buckling of longitudinal reinforcement in
plastic-hinge regions of beams. The special
reinforcement is specified to extend a
distance equal to twice the member depth
from the center of the yielding region. The
length of actual plastic hinge is likely to
depend on the details of the moments andshears. One could argue that in the positive
moment region the plastic hinge spreads over
an extended length because the moment
diagram is relatively flat (Figure 2.9). On the
other hand, one could also argue that in the
negative moment region the plastic hinge
spread also is large because the plastic
rotations are larger there and because the
8
-
7/29/2019 MoehleSmrf
9/33
shear forces and resulting tension shift are more significant there. The practical consideration is
that it is difficult to identify the hinging zone with precision, and inexpensive to provide hoops
over a generous length to cover the lack of precision.
Hoop details within the target plastic-hinge region are designed to confine the core concrete so
that it can reach strains well beyond the spalling strain and so that it can resist shear during these
inelastic excursions; the close spacing of hoops also serves to restrain the longitudinalreinforcement from buckling when in compression. Specific details will depend on the
configuration of the cross section. Figures
2.10 and 2.11 show some typical details of
hoops as required by ACI 318-99. To
restrain buckling, longitudinal reinforcement
is to be restrained as required for columns in
nonseismic construction, that is, corner bars
are to be restrained in corners of hoops, at
least alternate bars are to be restrained by
crossties or intermediate hoop legs, and no
unrestrained bar is to be more than 6 inches
from a restrained bar.
Figure 2.11 Examples of overlapping hoops (/ACI
Detail A Detail B
Detail C
Detail ADetail A Detail B
Detail C
Figure 2.10 Beam hoop details
It is common in US practice to use
crossties having 135-degree bends on one
end and 90-degree bends on the other end.
Although the 90-degree bends are known to
be less effective in restraining buckling after
loss of cover concrete (because the hook is
not embedded in core concrete), it has been
found to produce satisfactory behavior in
members with low axial compression, and it
improves contructibility.
Cap ties sometimes are used (detail B in
Figure 2.10) to ease construction. Whenused, the 90-degree hook should be restrained
by an adjacent slab, as shown. Multiple
hoops can be used as shown in detail C, but
these details can be difficult to construct.
New machinery for bending hoops is making
it feasible to construct complex hoop
configurations from a single piece of steel.
These should be used where economical.
Figure 2.12 is a photograph of beam
reinforcement details in a building
constructed in 2000 in Emeryville,California. The beam stood above the floor
slab, so the details were visible for this
photograph.
According to the ACI 318 code, maximum
spacing of hoop reinforcement within the
plastic hinge region is the smallest of (a) d/4,
(b) 8db, where db is the diameter of the
9
-
7/29/2019 MoehleSmrf
10/33
Figure 2.13 Design shears for girders and columns(ACI 318)
Figure 2.12 Details in a building in Emeryville, CA
longitudinal reinforcement, (c) 24 db,
where db is the diameter of the transverse
reinforcement, and (d) 12 inches. These
requirements relate to the objective of
confining the core concrete so it can resist
shear under deformation reversals and can
be strained to reasonable compressionstrains, as well as providing resistance to
longitudinal bar buckling. Figure 2.5shows computed behavior of cross sections
with transverse reinforcement satisfying
these provisions.
Also, the beam is to be designed to resist
the shear corresponding to development of
Mprat both ends of the member (Figure
2.13). Within the plastic-hinge region,
when the shear due to seismic effects is
equal to or greater than the gravity shear,
the hoop reinforcement is to be designed to
provide Vs assuming Vc = 0. Of course, this
is not to imply that the concrete carries no
shear, a misinterpretation that could
mislead the engineer to think the concrete
section is unimportant when in fact a stout
section will improve section behavior.
Instead, the intent is to increase the amount
of hoop reinforcement to enable the
concrete section to resist shear under
adverse moment and shear reversals that
are anticipated.
Outside the plastic hinge region, stirrups
are to be provided at spacing not to exceed
d/2. Hoops are not required along this
length.
Figure 2.14 shows a beam detail with
lap-spliced longitudinal reinforcement.
The lap splices are placed near midspan,
which is where the stresses are lowest for
many SMRF frames (seismic actions
predominate over gravity actions). Hoops
are closely spaced near the ends
(presuming flexural plastic hinges form atthose locations). Hoops also are spaced
closely along the lap splice to confine the
splice.
Rather than splice the reinforcement as shown in Figure 2.14, sometimes the reinforcement is
curtailed at alternating positions along the span as shown in Figure 2.15. By cutting the bars in
alternate spans, no lap splices are required.
10
-
7/29/2019 MoehleSmrf
11/33
Alternatively, mechanical splices can be
used. Type 2 splices (capable of
developing the specified bar ultimate
tensile strength strength) can be placed
anywhere along the span, though it is
advisable to remove these from plastic-
hinge regions.
Figure 2.15 Beam longitudinal reinforcement avoiding laps
gravityseismic + gravity
gravityseismic + gravity
Figure 2.14 Beam reinforcement with lap splices
3. Columns
3.1 Design objective
Design of a SMRF aims to achieve a beam-yield mechanism (Figure 1.1) and avoid a story-
yield mechanism in which the columns in a story yield at the bottom and top of their clear length.
Therefore, a capacity-design approach is used to promote flexural yielding in the beams and
avoid flexural or shear yielding in columns.
The capacity-design process begins by identifying where the inelastic action is intended to
occur. For a SMRF, the inelastic action is intended to be predominantly in the form of flexural
yielding of the beams. The building is analyzed under the design loads to determine the required
flexural strengths of the beam plastic hinges. The beam sections are designed so that the reliable
moment strength is at least equal to the design strength, that is, . Once the beam is
proportioned, the plastic moment strengths of the beam can be determined based on the expectedmaterial properties and the selected cross section. ACI 318 uses the strengthM
un MM
prfor this purpose.
This moment is calculated using conventional ACI procedures with reinforcement yield stress
taken equal to 1.25 times the nominal yield stress. The result is effectively the same as 1.25Mn.
Knowing the beam plastic-moment strengths, it is possible to approach the problem of
designing the columns so that they are stronger than the beams. The design problem is
complicated by uncertainty in the seismic loading demands. Some aspects of the design problem
are discussed in the following text.
11
-
7/29/2019 MoehleSmrf
12/33
3.2 Design actions on columns
3.2.1 Moments
Figure 3.1 shows schematically the beam and column
moments that are obtained from a code analysis of a building
frame under gravity and lateral loads. Beam moments varynonlinearly because of the presence of distributed loads.
Columns moments equilibrate the beam moments. Assuming
no lateral inertial effect from the columns, the column
moment diagrams are linear. The corresponding shears are
constant along the height of a column in a story.
P
Mx
My
design axial load
corresponding Mx and
My moment strengths
Mb4
Mb1 Mb3
Mb2
(a) P-M interaction diagram
(b) Plan view of joint
directio
nof
build
ingsw
ay
P
Mx
My
design axial load
corresponding Mx and
My moment strengths
P
Mx
My
design axial load
corresponding Mx and
My moment strengths
Mb4
Mb1 Mb3
Mb2
Mb4Mb4
Mb1 Mb3
Mb2
(a) P-M interaction diagram
(b) Plan view of joint
directio
nof
build
ingsw
ay
directio
nof
build
ingsw
ay
Figure 3.3 Biaxial loading
Mb2
Vb2
Mb1
Vb1
Mc2
Mc1
Vc2
Vc1
hb
hc
Vb2
Vb1
Vc2
Vc1
Mb2
Vb2
Mb1
Vb1
Mc2
Mc1
Vc2
Vc1
hb
hc
Vb2
Vb1
Vc2
Vc1
Figure 3.2 Planar equilibrium
beam centerline
column centerline
Figure 3.1 Beam and column
moments
The upper portion of Figure 3.2 shows a free-body
diagram of a portion of a SMRF. The beams and
columns have been cut at inflection points along the
spans. The lower portion of Figure 3.2 shows the
free-body diagram of the joint. Equilibrium of the
joint requires the following relation:
( ) ( )
( ) ( )2
2
2121
2121
cbbbb
bcccc
hVVMM
hVVMM
+++=
+++
For simplicity in expression, this relation often is
written as follows:
= bc MM
The latter expression is mathematically correct only ifthe beam and column dimensions are such that the
terms involving the shears in the previous expression
cancel.
Codes commonly require that the sum of the
column moment strengths exceed the sum of the
beam moment strengths at joints. The intent of this
requirement is to avoid formation of a story yieldmechanism. Usually, the requirement is applied
separately along each principal axis of the building.
In three-dimensional SMRFs, loading along a
diagonal can increase the moment demand on the
columns. This is illustrated in Figure 3.3. Figure3.3(a) shows a P-M interaction diagram for biaxial
bending. A horizontal plane is located at the axial
load corresponding to the loading considered. The
plane cuts the P-M interaction surface as shown.
This defines the column moment strength as a
function of the direction of loading. For a circular
column cross section with symmetric reinforcement,
12
-
7/29/2019 MoehleSmrf
13/33
the moment strength for bending along any direction is constant for a given axial load. For a
square section with symmetric reinforcement, the moment strength for bending along the
diagonal is somewhat less than for bending along any principal direction, the exact relation
depending on the materials and reinforcement.
Figure 3.3(b) shows an interior beam-column joint in plan. Moment vectors indicate the
directions of the moments in the beams for building sway in the direction indicated. In this case,the sum of the moment strengths of the columns above and below the joint, for loading along the
diagonal, must balance the vector sum of the beam moment strengths. For beams of equal
strengths in the two directions, this can be expressed as
( ) ( )314321 22
1bbbbbbbc MMMMMMMM +=+++==
Because the column moment strength is the same (for circular sections) or less (for square
sections) for loading along the diagonal in comparison with loading along a principal axis, it is
clear that the column demand is increased significantly by diagonal loading. The column
moment strength must be increased by at least 40% for diagonal loading as compared with
loading along a principal axis, if it is to be stronger than the adjacent beams.
(T. Kelly, U. Canterbury, 1974)
+ =
first higher combined
(T. Kelly, U. Canterbury, 1974)
+ =
first higher combined
Figure 3.4 Higher-mode effects on column moment
diagrams
Dynamic response of SMRFs furthercomplicates column moment design. As
shown in Figure 3.4, the column moment
diagrams follow a fairly regular pattern for
first-mode loading (for a yielding system,
modes do not exist in the sense defined by
classical linear dynamics, but the concept
of modes is convenient for discussion and
design purposes). Note that even for this
loading the moment diagrams are
somewhat skewed in the bottom story
because of the greater fixity provided by
the foundation than by the first story abovegrade. For lateral force distributions that
occur during dynamic response and that
represent higher-mode loadings, the
moment diagrams are less regular.
Note that in some cases the column may
not be in contraflexure.
Case A Case B
moments
shear
Case A Case B
moments
shear
Figure 3.5 Relation between shear and moment
Note also that at some times (e.g., 2.73
seconds shown), the moments at a joint are
carried almost entirely by either the columnbelow or above the joint. Unless the
column is much stronger than the beam,yielding in the column is likely.
3.2.2 Shears
Shear is equal to the slope of the moment
diagram (Figure 3.5), so the moment
patterns of Figure 3.4 indicate column
shears as well as moments. In cases where
13
-
7/29/2019 MoehleSmrf
14/33
the column moments are relatively large at both ends, a
case that can be identified in some stories at time 2.73 in
Figure 3.4, the shear also is relatively large. This case is
shown as Case B in Figure 3.5. Therefore, the shears
obtained from a first-mode or inverted triangular lateral
loading are likely to underestimate the shears under
dynamic response.
The maximum column shear can be estimated by
assuming formation of plastic moments at both ends, as
shown in Figure 3.6; this shear may be unnecessarily
large, so alternative estimates are often made. When
using this approach, the axial load should be selected to
obtain a conservatively high estimate of the column
plastic-moment strength.
3.2.3 Axial Loads
Axial loads in SMRFs are
the sum of the shears in the
beams framing into the column
plus the self weight of the
column. As illustrated in
Figure 3.7, the axial loads will
vary around the building as a
function of the column location
and instantaneous earthquake
loading. As shown, for
earthquake inertial loading
from the left toward the right,the gravity and earthquake-
induced axial loads will be
additive for the exterior
columns on the right hand side
of the building. The gravity
and earthquake-induced axial
loads will act in opposite directions for the exterior columns on the left-hand side of the building,
and may result in column tension. For interior columns, the axial loads will tend to be dominated
by gravity loads; variations due to earthquake loading will depend on the stiffness and strength of
the beams framing into the column on either side this determines the shear forces in the beams
and therefore determines the axial load variation. For regular buildings with equal spans and
equal-size and strength beams in all spans, the axial load variation due to earthquake effects willbe relatively small for interior columns.
Figure 3.7 Gravity and earthquake axial loads on columns indifferent locations of a SMRF
earthquake and
gravity effects
additive
predominantly
gravity loads
earthquake and
gravity effects
opposite
earthquake and
gravity effects
additive
predominantly
gravity loads
earthquake and
gravity effects
opposite
Mpr
Pu
Vu
Mpr
Pu
Vu
lnn
pru l
MV =
Mpr
Pu
Vu
Mpr
Pu
Vu
lnn
pru l
MV =
Figure 3.6 Upper-bound column
shear
Limit analysis (plastic analysis) procedures can be used to calculate upper-bounds to column
axial loads. For this purpose, a plastic mechanism is assumed for the building. For a SMRF, itmay be reasonable to assume formation of beam flexural plastic hinges over the height of the
building (Figure 3.8). With this assumption, the beam shears are summed over the height and
added to the column weight to obtain the column axial force.
14
-
7/29/2019 MoehleSmrf
15/33
Corner columns tend to have the
largest fluctuation in axial forces
during an earthquake. This occurs
for two reasons. First the corner
columns usually support the
smallest gravity loads. Second, for
displacements along a diagonaldirection, the beam shears are
additive from both directions(Figure 3.9).
Plastic analysis gives an upper-
bound solution for column axial
forces. Actual values may be less
depending on how much inelastic
response develops in the frame and
depending on how it develops.
Figures 3.8 and 3.9 assume that beam flexural plastic hinges
form over the full height of the building. Studies show that
plastic hinging does not always form in this fashion. Figure
3.10 shows calculated results for a relatively flexible 12-story
building subjected to the 1940 El Center earthquake record.
As shown, beam flexural plastic hinges occur in discrete
locations, those locations migrating up and down the frame as
story drift concentrates in different stories at different times
during the dynamic response.
The patterns shown in Figure 3.10 are highly dependent on
the framing configuration, the dynamic characteristics of the
frame, and the characteristics of the ground motion. For
example, it is likely that a near-field ground motion pulse
could impose massive sway in a frame that would result innearly all the beams yielding at the same time. Even in this
case, and even if the columns are made stronger than the
beams, flexural yielding in general will not extend over the
MprMpr
VpVp
Mpr
Vp
Mpr
Vp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
P= Vp + WcolumnP= Vp + Wcolumn P= Vp + Wcolumn
MprMpr
VpVp VpVp
Mpr
Vp
Mpr
Vp
Mpr
Vp
Mpr
Vp
Mpr
Vp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
VpVp
P= Vp + WcolumnP= Vp + Wcolumn P= Vp + WcolumnP= Vp + Wcolumn P= Vp + Wcolumn
Figure 3.8 Plastic analysis to obtain upper-bound column
axial forces
Figure 3.9 Corner column axial
force
Figure 3.10 Calculated locations of beam flexural plastic hinges in a 12-story frame (T. Kelly, 1974)
VbeamVbeam
Pcolumn
Building displaced
toward corner
column
15
-
7/29/2019 MoehleSmrf
16/33
full building height instead, flexural plastic hinges will form in the columns at some height that
depends on the framing configuration, the relative column and beam strengths, and the
distribution of lateral inertial loading.
3.3 Column behaviorBehavior of column cross sections in flexure is essentially the same as that of beams. Analysis
generally follows the same assumptions and approach. The only significant difference for a
column section is that the axial force is not necessarily equal to zero.
Figure 3.11 shows a column cross section and associated analysis assumptions. Strain is
assumed to vary linearly across the section, with maximum compression strain in concrete
assumed to be the limiting parameter in some cases, fracture of longitudinal reinforcement is
the critical behavior, but that will not be considered in detail here. Material stresses are assumed
to be uniquely related to strains as discussed for beams, this assumption is not correct for
inelastic reversed cyclic loading.
b
h
d
Atr
s
cs
fs
fs
As
M
P
Ts
Cs
Cc
As
d
sfs
Ts
As
d
s
cs
fs
fs
M
P
Ts
Cs
Ccsfs
Cs
(a) Low axial load
(b) High axial load
b
h
d
Atr
s
cs
fs
fs
As
M
P
Ts
Cs
Cc
As
d
sfs
Ts
As
d
s
cs
fs
fs
M
P
Ts
Cs
Ccsfs
Cs
(a) Low axial load
(b) High axial load
Figure 3.11 Flexural analysis of column cross sections
For relatively small axial force (Figure 3.11a), the depth of compression zone required to
equilibrate the axial force is relatively small. Therefore, the curvature is relatively large when the
maximum compressive strain capacity is reached. For larger axial force, the depth of
compression zone required to equilibrate the axial force increases; therefore, the curvature
capacity decreases. This effect of axial load on moment strength and curvature capacity is shown
in Figure 3.12. The cross section shown is assumed to be unconfined. For unconfined sections,
the flexural ductility decreases rapidly as axial load increases.
16
-
7/29/2019 MoehleSmrf
17/33
Figure 3.13 plots
interaction diagrams for a
column with 24 inch by 24
inch cross section
reinforced with 16 No. 9
bars as longitudinal
reinforcement. Concretehas compressive strength
of 4000 psi, andreinforcement is Grade 60.
The continuous curves are
calculated behavior
assuming the
reinforcement yields at 60ksi without strain-
hardening, and assuming
concrete is unconfined.
Also shown in Figure
3.13 are plots for two other
assumptions. The broken
curve is calculated
response assuming
reinforcement yields at 60
ksi without strain-
hardening, and assuming
confined concrete
behavior. Transverse
reinforcement comprises a
perimeter hoop plus cross
tie of No 3 bars at
longitudinal spacing of 2.5
inches, which satisfies the
confinement requirements
of ACI 318. Confined
concrete stress-strain
relation is according to Manders model. Concrete confinement with transverse reinforcement
increases the strain capacity and compressive stress capacity of the compression zone. This has
the most significant impact on the P-M interaction diagram for axial forces exceeding the
balanced point (the balanced point in fact changes and becomes ill-defined for confined concrete),
as columns with high axial force are compression-controlled. However, the strength gain is
marginal because the cover concrete has spalled, reducing the effective concrete section.
Ultimate curvature capacity is increased for all axial loads.
unconfined nominal
confined nominal
confined strainhardening
0 0.002 0.004 0.006 0.008
Curvature, 1/inch
-2000
-1000
0
1000
2000
4000
0 5000 10000 15000
Moment, kip-inch
AxialLoad,
kip
3000
24
#9 Grade 60
#3 @ 2.5
fc= 4 ksi unconfined nominal
confined nominal
confined strainhardening
unconfined nominal
confined nominal
confined strainhardening
0 0.002 0.004 0.006 0.008
Curvature, 1/inch
-2000
-1000
0
1000
2000
4000
0 5000 10000 15000
Moment, kip-inch
AxialLoad,
kip
3000
0 0.002 0.004 0.006 0.008
Curvature, 1/inch
-2000
-1000
0
1000
2000
4000
0 5000 10000 15000
Moment, kip-inch
AxialLoad,
kip
3000
24
#9 Grade 60
#3 @ 2.5
fc= 4 ksi
24
#9 Grade 60
#3 @ 2.5
fc= 4 ksi
Figure 3.13 Calculated interaction diagrams
P P
Moment, MMoment, M Curvature, Curvature,
Balanced Axial
tension-
controlled
compression-
controlled
Lower Axial
Higher Axial
strains
Figure 3.12 Effect of axial load on flexural cross-section behavior
The dashed curve Figure 3.13 is for the same column cross section with confined concrete, but
now assuming more realistic properties for the longitudinal reinforcement, including yield stress
of 67 ksi, and strain-hardening to 110 ksi. This has the most significant effect on calculated
behavior for low axial loads, as the column is tension-limited in this region. Note, however, that
the effect of strain-hardening is realized mostly because the column has confined concrete, which
increases the compression-zone strain capacity, thereby increasing the curvature capacity,
resulting in increased tension reinforcement strain. Ultimate curvature capacity is reduced
somewhat compared with the case of confined concrete with elasto-plastic reinforcement.
17
-
7/29/2019 MoehleSmrf
18/33
3.4 Column design
3.4.1 Moment and Axial Load
According to US design codes, the reliable flexural strength of the column must be at leastequal to the ultimate design moment. This expression is written as follows:
un MM
Mu is the moment demand obtained from the code-required analysis of the building under thespecified code earthquake representation.
Furthermore, ACI 318 requires that the flexural strengths of the columns shall satisfy
Mc (6/5) Mg
Mc= sum of moments at the faces of the joint corresponding to the nominal flexural strengthof the columns framing into that joint. Column flexural strength is to be calculated for the
factored axial force, consistent with the direction of the lateral forces considered, resulting in thelowest flexural strength.
Mg= sum of moments at the faces of the joint corresponding to the nominal flexural strengthsof the girders framing into that joint. In T-beam construction, where the slab is in tension under
moments at the face of the joint, slab reinforcement within an effective slab width defined in 8.10
is to be assumed to contribute to flexural strength if the slab reinforcement is developed at the
critical section for flexure.
Flexural strengths are summed such that the column moments oppose the beam moments. Thecolumn strength requirement needs to be checked for loading along the two principle directions of
the frame, but it is permitted to consider one framing direction at a time.
Note that this is not a joint equilibrium statement, but simply a requirement that the column
moment strength exceed the girder moment strength by a set ratio.
An alternative approach, which is more
conservative, and which may be viewed as
being more consistent with the capacity-
design philosophy, is to amplify the column
design moments obtained from the code
analysis on the basis of the expected flexural
overstrength of the beams. The procedures is
illustrated in Figure 3.14. Specifically, a
flexural overstrength factoro is defined as
beam centerline
column centerline
Mu,beam
Mu,column
Mpr,beam
Mu,column
beam outline
beam centerline
column centerline
Mu,beam
Mu,column
Mpr,beam
Mu,column
beam outline
Figure 3.14 Column design moments
= beamubeampr
M
M
,
,0
where Mpr,beam = the sum of probablemoment strengths of the beams at the joint
and Mu,beam = the sum of the code-requiredstrengths of the beams at the joint (obtained
from application of the code-specified design
loading). The columns are then designed for
18
-
7/29/2019 MoehleSmrf
19/33
momentsMu,column = oMu,column, whereMu,column = the column moment obtained from the code-specified design loading.
Regardless the method used to obtain moments, the axial loads should be checked for
maximum and minimum values, as either may be critical, depending on the column configuration
and the values of axial loads and moments. Figure 3.15 shows two loading cases, one with lateral
load from the left, the other with lateral load from the right. The loadings are used to determinethe axial loadsPmax andPmin in the column shown. To obtainPmax, the lateral load is shown from
left to right, and a high estimate of the gravity load is imposed. The high estimate is obtained
using a factored load combination that maximizes the axial load. In contrast, to obtainPmin, the
lateral load is applied from right to left, and a low estimate of the gravity load is imposed. In this
latter case, use of a low estimate of gravity load results in a lower estimate of the axial load. As
shown in the interaction diagram of Figure 3.15, both axial load cases need to be checked, as
either one may be critical.
P
M
increasinghigh gravity loads
low gravity
loads
Pmax
Pmin
Pmax
Pmin
P
M
increasingP
M
increasinghigh gravity loads
low gravity
loads
Pmax
Pmin
Pmax
Pmin
Figure 3.15 Axial load combinations for design
3.4 2 Transverse reinforcement
Transverse reinforcement serves to confine the concrete core, thereby increasing its
compressive strain capacity for flexural and axial deformations and improving its toughness forresisting shear. Transverse reinforcement also helps to delay buckling of the longitudinal
reinforcement and improves anchorage and splice strength. Aspects of shear strength are coveredin the next section. The emphasis here is on transverse reinforcement for flexural and axial load
enhancement, as well as buckling and anchorage resistance.
Figure 3.16 idealizes the confining behavior of transverse reinforcement. As the core concrete
is strained longitudinally, it expands laterally. The transverse reinforcement acts passively to
restrain this dilation and thereby results in confining stress. To be most effective as confinement
19
-
7/29/2019 MoehleSmrf
20/33
s
Rectangular Hoop
effectively
confined
concrete
unconfined
concrete
Circular Hoops
s
Rectangular Hoop
effectively
confined
concrete
unconfined
concrete
Circular Hoops
Circular Hoops
Figure 3.16 Confinement effectiveness
reinforcement, transverse reinforcement should
be evenly distributed along the length and
around the perimeter. For circular-cross
section columns, the circular hoops or spiral
provides fairly uniform radial confinement
because of the uniform curvature of the hoops
or spirals. Close spacing of the circular hoopsor spirals improves the uniformity of
confinement along the length, and thereforeimproves confinement effectiveness. For
rectangular-cross section columns, the
rectangular hoops provide resistance effectively
only at their corners or where crossties are
placed. Therefore, confinement effectiveness isimproved by placing longitudinal bars
uniformly around the perimeter and providing
hoops and crossties to restrain their outward
movement. As with circular-cross section
columns, confinement is improved by usingrelatively small longitudinal spacing.
Figure 3.17 depicts
confinement effectiveness
relations obtained using the
model proposed by Mander.
The results are for a circular-
cross-section column, a square-
cross-section column with two
crossties in each direction, a
square-cross-section column
with one crosstie in each
direction, and a square-cross-
section column without
crossties. The relation shown
suggests that square-cross-
section columns without
crossties are much less
effective than columns with
crossties.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
s/h
Aeff/Acc
circular
hoop without cross ties
hoop + 1 crosstie
each direction
hoop + 2 crosstieseach direction
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
s/h
Aeff/Acc
circular
hoop without cross ties
hoop + 1 crosstie
each direction
hoop + 2 crosstieseach direction
Figure 3.17 Confinement effectiveness relations for circular- and
square-cross section columns
The specific requirements for transverse reinforcement for confinement depend on the specific
demands imposed on the column. For example, a column framing into a foundation wall may be
required to develop a plastic-hinge rotation equal to 0.01 or more for a design loading. Under this
imposed rotation demand, the compression strain demand, and therefore the required amount ofconfinement reinforcement, will increase with increasing axial load.
US codes for design of new buildings do not require computation of rotation demands. These
demands are difficult to assess, especially in upper stories where the intent is to maintain an
elastic column, but where yielding may occur owing to higher mode and multi-directional loading
effects. Furthermore, axial loads occurring during earthquakes are difficult to determine during
design. Prevailing design practice is to obtain the design axial load from the code-specified
lateral forces; actual axial forces may deviate significantly from these values during an
20
-
7/29/2019 MoehleSmrf
21/33
earthquake. Plastic analysis procedures, which are not required by US codes, likewise may not
produce an accurate estimate of axial loads.
Given the uncertainty in rotation demands and axial force demands, ACI 318 specifies
transverse reinforcement for confinement of critical regions that is independent of the level of
axial force. The quantities required are intended to produce a column core that is capable of
sustaining axial compression approximately equal to the axial compression capacity of thecolumn before spalling of the concrete shell. This procedure has some advantages. It produces a
column that is relatively tough and capable of sustaining axial forces due to unforeseen loadings
that may crush the column; the result is a column highly resistant to brittle axial compression
failure. The design, construction, and inspection processes are considerably simplified by using a
constant amount of confinement up the height of the column.
The required volume ratio of transverse reinforcement for circular cross sections is equal to
yc
y
c
core
g
s fff
f
A
A'
'
12.0145.0
=
Maximum spacing is not to exceed 3 inches.
For rectangular cross sections, the total cross-sectional area of rectangular hoop reinforcement
is not to be less than that required by either of the following two equations
Ash = 0.3(shcfc/fyh)[(Ag /Ach)_1]
Ash= 0.09shcfc/fyh
Transverse reinforcement is to be provided by either single or overlapping hoops (Figure 3.18).
Crossties are to be of the same bar size and spacing as the hoops, and each end of the crosstiemust engage a peripheral longitudinal reinforcing bar. While it is recognized that 90-degree hooks
on crossties are not as effective as 135-degree hooks, they are considered adequate for most
loadings, and ease construction considerably. Some studies suggest that for heavy axial loads or
confining
stress
Atrfy
Atrfy
Atrfy
Ash
= 3Atr
hc
confining
stressA
trf
yA
trf
yA
trf
yA
trf
y
hc
Ash
= 4Atr
confining
stress
Atrfy
Atrfy
Atrfy
Ash
= 3Atr
hc
confining
stress
AtrfyAtrfy
Atrfy
Atrfy
Ash
= 3Atr
hc
hc
confining
stressA
trf
yA
trf
yA
trf
yA
trf
y
hc
Ash
= 4Atr
confining
stressA
trf
yA
trf
yA
trf
yA
trf
y
hc
confining
stressA
trf
yA
trf
yA
trf
yA
trf
yA
trf
yA
trf
yA
trf
yA
trf
y
hc
Ash
= 4Atr
Figure 3.18 Rectangular hoops
21
-
7/29/2019 MoehleSmrf
22/33
unusually large column rotation demands, 135-degree hooks should be used on both ends. Where
90-degree hooks are used, consecutive crossties shall be alternated end for end along the
longitudinal reinforcement. Perimeter hoops are required to have 135-degree hooks.
Figure 3.18 shows howAsh and hc are defined for a rectangular-cross-section column.
sx
hx8 14
4
6
sx
hx8 14
4
6
Figure 3.19 Spacing limits for hoop
reinforcement as function of horizontal
spacing of hoop legs.
As suggested by Figure 3.17, the same confinement
effectiveness can be achieved by differentcombinations of transverse and longitudinal spacings
of hoop legs. ACI 318 recognizes this by specifying
that the maximum longitudinal spacingsx vary as a
function of the maximum horizontal spacing hx
between legs of hoops or crossties around the column
perimeter (Figure 3.19). In addition, longitudinal
spacing of the transverse reinforcement is not to
exceed (a) one-quarter of the minimum member
dimension and (b) six times the diameter of the
longitudinal reinforcement. The former requirements
relates to confinement and to shear resistance
requirements. The latter requirement is intended torestrain buckling of longitudinal reinforcement until
deformations reach relatively large values.
According to ACI 318, crossties or legs of overlapping hoops shall not be spaced more than 14
in. on center in the direction perpendicular to the longitudinal axis of the structural member. This
longstanding limit is thought to be related to the intention to require crossties in significant
columns, such columns perhaps being considered to have dimensions of 18 inches or larger. As
suggested by Figure 3.17, crossties are desirable for confinement in all columns except very smalland structurally inconsequential columns.
Sometimes, architectural treatments result in thick concrete cover over the confined core. Such
cases should be avoided where possible, as loss of unconfined cover can result in significant and
relatively sudden loss of load-resisting capacity. As a minimum, ACI 318 requires that if thethickness of the concrete outside the confining transverse reinforcement exceeds 4 in., additional
transverse reinforcement shall be provided at a spacing not exceeding 12 in. Concrete cover on
the additional reinforcement shall not exceed 4 in.
The transverse reinforcement described in the preceding paragraphs is to be provided over a
length lo from each joint face and on both sides of any section where flexural yielding is likely to
occur as a result of inelastic lateral displacements of the frame (Figure 3.20). The length lo is not
to be less than (a) the depth of the member at the joint face or at the section where flexural
yielding is likely to occur, (b) one-sixth of the clear span of the member, and (c) 18 in.
Some studies suggest that the length of confinement at end regions should vary as a function of
axial load level. Furthermore, as shown in Figure 3.4 and 3.20, moments in columns in the first
story tend to be shifted toward the base, which may result in yielding extending over a greaterlength than in other typical stories. Some consideration should be given, therefore, to increasingthe length lo in the lower stories.
Also shown in Figure 3.20 is a typical detail at the first-floor level, where a slab on grade is
situated on compacted soil or lean concrete. Usually the structural drawings for such details will
include placement of a soft filler material between the column and slab on grade. If the fill is not
placed, if it hardens or becomes contaminated with debris during construction or during the life of
the building, or if the separation between the slab on grade and column is insufficient, the column
22
-
7/29/2019 MoehleSmrf
23/33
can be restrained by the slab on
grade, shifting the inelastic
action upward along the
column height. This problem
may have been a contributing
factor in the critical damage of
the Imperial County ServicesBuilding duringthe 1979
Imperial Valley Californiaearthquake (Figure 3.21).
Figure 3.20 suggests to
measure the length from the
top of the slab on grade, and
extend the confinement downto the top of the footing.
Where transverse
reinforcement as specified
above is not provided
throughout the full length of
the column, the remainder of
the column length is to contain
spiral or hoop reinforcement with center-to-center
spacing not exceeding the smaller of six times the
diameter of the longitudinal column bars or 6 in.
The specification of relatively close spacing
throughout the height is to avoid a sudden
transition in toughness along the length, which
could result in damage outside the heavily confined
region.
Mechanical splices of longitudinal reinforcementare permitted - Type 1 mechanical splices are not to
be used within a distance equal to twice the
member depth from the column or beam face or
from sections where yielding of the reinforcement
is likely to occur as a result of inelastic lateral
displacements; Type 2 mechanical splices are
permitted to be used at any location. Type 1
mechanical splices are those conforming to chapter
12 of ACI 318 (capable of 125% of the specified
yield strength). Type 2 mechanical splices are
capable of developing not less than the specified
tensile strength of the spliced bar, so that they willbe capable of developing significant inelastic strain
without failure.
Lap splices of longitudinal reinforcement are
permitted only within the center half of the member length, are to be designed as tension lap
splices, and are to be enclosed within transverse reinforcement having longitudinal spacing not
exceeding the minimum of (a) one-quarter of the minimum member dimension, (b) six times the
diameter of the longitudinal reinforcement, and (c)sx defined by Figure 3.19. Horizontal spacing
slab on grade
lo
lo
lo
>lo
closely spaced hoops
along lap splice
Moments
slab on grade
lo
lo
lolo
>lo
closely spaced hoops
along lap splice
Moments
Figure 3.21 Imperial County Servicesbuilding 1979 Imperial Valley
earthquake
Figure 3.20 Moments and hoop spacing along column height
23
-
7/29/2019 MoehleSmrf
24/33
-
7/29/2019 MoehleSmrf
25/33
is obtained not just for the maximum and minimum axial loads, but for all axial loads between
those extremes.
In some cases, the shear according to Figure 3.22a is significantly larger than the frame
mechanism (intended to be a beam-yielding mechanism) can sustain, so the approach of the
preceding paragraphs results in an excessively large design shear. Therefore, it is permitted to
design for the shear determined from joint strengths based on the probable moment strengthMprof the transverse members framing into the joint (Figure 3.22b). ACI 318 provides no guidance
on how this shear is to be determined. As illustrated in Figure 3.5, if the moment is distributed
unevenly between the columns above and below a joint, the shear in one column can be
disproportionately larger than the shear in columns adjacent stories.
Vu
Mu,column
Mu,column =
oMu,column
Vu,column
oVu,column
Vu
Mu,column
Mu,column =
oMu,column
Vu,column
oVu,column
Figure 3.24 Column shear design
Figure 3.24 illustrates one approach to satisfying
the preceding requirement. The approach assumes
that the frame mechanism is controlled by
development of flexural plastic hinges in the beams.
A flexural overstrength factoro is calculated asdescribed previously. Correspondingly, the column
moments are increased fromMu,column to oMu,column.Given that the shear is equal to the slope of themoment diagram, the shear is increased oVu,column,where Vu,column is the column shear calculated from the
code-specified loading. The column shear should be
determined from dynamic analysis rather than static
analysis, so that higher-mode effects are
approximately included. As noted previously,
dynamic response results in shears higher than those
that are obtained from a static lateral loading.
The design shear strength will vary
over the height of the column, in part
because the transverse reinforcementvaries, in part because the inelastic
demands vary over the height. This is
illustrated in Figure 3.25. Figure 3.25b
shows shear strength over height for high
axial loads. In this case, the strength is
greater at the ends than along the middle
because of the closer spacing of hoops
along the length lo. Figure 3.25c shows
the shear strength over height for lowaxial load, or axial tension. Shear
strength degrades with inelastic cyclic
loading, and this degradation may be
especially pronounced for tension
loading. According to ACI 318,
transverse reinforcement along the length lo is to be proportioned to resist shear assuming Vc = 0
when both the following conditions occur: (a) The earthquake-induced shear force represents one-
half or more of the maximum required shear strength within those lengths; and (b) The factored
axial compressive force including earthquake effects is less thanAgfc/20.
lo
lo
(a) column elevation (b) shear
strength for
high axial load
(c) shear strength
for low axial load
lo
lo
lolo
lolo
(a) column elevation (b) shear
strength for
high axial load
(c) shear strength
for low axial load
Figure 3.25 Shear strength
25
-
7/29/2019 MoehleSmrf
26/33
4. Beam-Column Joints
The reader is referred to the ACI 352 report in addition to ACI 318.
4.1 Design objective
The design objective for reinforced concrete beam-column joints in SMRFs is for them to bestronger than the adjacent framing members so the majority of inelastic action occurs in the
adjacent members, in particular, the beams. Sometimes this is referred to as keeping the joint
elastic. However, considering yield penetration of beam reinforcement into the joint and slip of
beam and column reinforcement from the joint, fully elastic behavior is not possible.
Nonetheless, the design should aim to reduce these actions to acceptable levels through
appropriate joint proportioning and reinforcement.
4.2 Design actions on joints
In a SMRF it is assumed
that the design actions can be
obtained from statics. Thebeam is assumed to develop
flexural plastic hinges at the
critical sections as shown in
the right-hand side of Figure
4.1. The corresponding
beam shear is obtained from
statics. The beam moments
and shears are applied to a
free-body diagram of the
column as shown in the left-
hand side of Figure 4.1. For
the purpose of determiningthe column shear for joint
design it usually is sufficient
to assume inflection points in
the column at midheight, as
shown. The column shears
can subsequently be obtained
by statics. The column shear
force thus obtained may not
be suitable for design of the
column; however, it usually
is sufficiently accurate for
determining the designactions on the joint. For
determination of the column
shear for column design see
previous discussion.
lnb
wu
Beam Section
Vb1
Mpr,b1Vb2
Mpr,b2
Vb2Vb1
Mpr,b1
Vc1
Vc2
lnb
wu
Beam Section
Beam Section
Vb1
Mpr,b1Vb2
Mpr,b2
Vb2Vb1
Mpr,b1
Vc1
Vc2
Figure 4.1 Design actions on a joint
Vc1
Vc2
Tb2
Tb1
Tc1
Tc2
Vb1Vb2
Cb1= Tb1
Cb2 = Tb2
Cc1
Cc2
Vc1
Vc2
Tb2
Tb1
Tc1
Tc2
Vb1Vb2
Cb1= Tb1
Cb2 = Tb2
Cc1
Cc2
Tb1 Tb2
Vc1
Vjoint
Tb1 Tb2
Vc1Vc1
Vjoint
(a) Free body diagram showing
external actions on joint
(b) Free body diagram to
determine joint shear
Figure 4.2 Free body diagrams of joint
Figure 4.2a shows a free
body diagram of an interior
joint. The beam moments
have been replaced by the
26
-
7/29/2019 MoehleSmrf
27/33
corresponding internal force resultants (tension in longitudinal reinforcement and compression in
concrete). It is assumed that the beam does not have axial force; therefore, the compression force
resultant on one side of the joint is equal to the tension force resultant acting on the same side of
the joint. For design purposes, ACI 318 assumes that the tension force is equal to 1.25Asfy, where
As is the cross-sectional area of longitudinal reinforcement andfy is the nominal yield stress. The
factor 1.25 is a low estimate of the overstrength for the reinforcement. According to ACI 318,As
need not include the slab reinforcement in tension, though it would be conservative to do so.
The column moment required to equilibrate the beam moments is obtained as the product of the
column shear and half the column clear height (Figure 4.1). The internal forces associated with
the combined moment and axial force (Figure 4.2a) need not be determined as part of the ACI
design procedure; however, it is worth noting that the values are not necessarily equal because the
column may have axial load.
The design horizontal joint shear is obtained by equilibrium of horizontal forces acting on a
free body diagram of the joint as shown in Figure 4.2b.
4.3 Joint behavior
Two simplified views of joint force-resistingmechanisms are shown in Figure 4.3 and 4.4.
Figure 4.3 depicts what is referred to as a joint
truss model. According to this model,
longitudinal reinforcement tension and
compression forces are resisted entirely by
bond with the concrete. The bond produces
diagonal compression forces in the joint
concrete, which in turn are equilibrated by joint
transverse reinforcement and longitudinal
reinforcement.
For example, referring to Figure 4.3, the
tension force in the beam longitudinalreinforcement entering the joint at the upper
right hand corner of the joint results in bond
forces along the bar length. At point 1, for
example, this bond force (shown by green
arrows) results in an inclined compression strut
in the concrete (shown red). To equilibrate this at point 1 there also is required to be bond stress
between the column longitudinal reinforcement and the concrete, as shown. At point 2, the
diagonal compression strut is resisting by horizontal force in the joint horizontal reinforcement
and by bond in the vertical column reinforcement. At point 3, the joint transverse reinforcement
tension force is equilibrated by another diagonal compression strut in concrete along with bond
stress in the column longitudinal reinforcement. At point 4 the diagonal compression strut is
equilibrated by bond in the horizontal beam reinforcement as well as compression in the concrete.
1
23
4
1
23
4
1
23
4
Figure 4.3 Joint truss model
The truss model as described above requires high bond stresses between the longitudinal
reinforcement and joint concrete, as it will be necessary to resist through bond both the
longitudinal reinforcement tension force on one side of the joint plus the longitudinal
reinforcement compression force from the other side of the joint. To resist this bond requires a
large volume of joint horizontal reinforcement. Joint vertical reinforcement may be required to
assist the column vertical bars in resisting the vertical forces in the joint. The ability of a joint to
resist the bond stresses is hampered by a number of factors. At point 1, for example, the joint is
27
-
7/29/2019 MoehleSmrf
28/33
in tension due to flexural tension action of the adjacent column. Also, the length through the joint
is not sufficient under normal conditions to develop the bar both in tension and compression. The
problem is exacerbated by cyclic loading, which, among other things, deteriorates the bond
capacity.
An alternative model is the diagonal
compression strut model, shown in Figure 4.4.According to this model, bond stress through
the joint is lost under cyclic loading, so the
reinforcement in tension on one side of the
joint is developed through the compression
zone on the opposite side of the joint, both
within the joint and beyond the joint into the
adjacent beam. This may result in the
longitudinal reinforcement being in tension on
both sides of the joint.
For example, consider the beam flexural
tension force at point a in Figure 4.4. Bond
is likely to be substantial only along thecompressed part of the joint near point b.
The bond stress at this point is likely to be
insufficient to fully develop the bar, so the bar
remains in tension as it emerges from the joint
at point c. Thus, the bar at point c is in
tension even though the concrete in the flexural compression zone of the beam at that same point
is in compression. Because both the top bars at c and bottom bars at d are in tension, the
compression force in the concrete at c may be much higher than would be calculated from
conventional flexural analysis. Confinement of the concrete in this region is important so that
likelihood of brittle compressive failure is reduced.
ab
c
d
ab
c
d
Figure 4.4 Diagonal compression strut model
A result of the model shown in Figure 4.4 is that the joint shear is carried mostly through a
diagonal compression strut as shown in yellow in the figure. Transverse reinforcement isrequired to confine the concrete. The transverse reinforcement strengthens the core concrete and
toughens it so that it can undergo inelastic strain without failure. It also reduces dilation and
crack opening under load reversals so that integrity of the concrete to resist compressive stresses
is maintained.
Note that both the truss model of Figure 4.3 and the diagonal compression stress model of
Figure 4.4 require horizontal joint reinforcement, in one case to equilibrate shear forces and
improve bond capacity, and in the other to enable the concrete to support the diagonal
compression strut. The truss model would predict that the joint strength is directly related to the
amount of transverse reinforcement, assuming that is the limiting component of the mechanism.
The diagonal strut model does not relate the strength directly to the amount of transverse
reinforcement.Also, note that both models require vertical reinforcement, in one case to resist vertical
components of shear forces and to provide bond resistance, and in the other case to provide some
vertical confinement. Either the column longitudinal reinforcement must be well distributed
around the perimeter and remain elastic under lateral loading so it can act as the vertical joint
reinforcement, or additional vertical steel must be added in the joint to resist dilation and vertical
shear.
28
-
7/29/2019 MoehleSmrf
29/33
Figure 4.5 Effect of transverse reinforcement
quantity on joint shear strength
Some alternative models for joint shear
strength (such as strut and tie models) can be
used to avoid vertical or horizontal joint
reinforcement, or both. These are not pursued
here.
Figure 4.5 shows test data on interior jointssubjected to simulated seismic loading, as
compiled by Otani [1991]. Open circles
correspond to cases where the beam failed in
flexure without apparent joint failure. Open
squares correspond to cases where joints failed
before beam yielding was apparent. Solid
triangles correspond to cases beams first yielded,
and then joints failed. The solid triangles follow
a simple trend for low amounts of joint
transverse reinforcement, the joint shear strength
increases with increasing joint transverse
reinforcement, but at a ratio of about 0.4 percent,
the strength no longer increases for increasing
joint transverse reinforcement ratio. This result
has been interpreted as indicating that the truss
model (Figure 4.3) does not model strength
behavior very well, and has led to the use of the
diagonal compression strut model (Figure 4.4) as
the basis for design according to ACI 318.
Figure 4.6 Effect of development length on
behavior of beam-column joints.
One of the outcomes of the ACI 318 design
procedure (actually, the diagonal compression
strut model) is that the beam longitudinal
reinforcement may sustain bond deterioration that
may result in inadequate performance as thereinforcement slips from (or slides through) the
joint. This slippage can result in a behavior that
is slack as the joint rotations pass near the origin.
Figure 4.6 depicts load-deformation behaviors
resulting from joints with different development
lengths through the joint, identified by the ratio
of the column dimension to the beam longitudinal
bar diameter. Clearly the behavior is improved,
with more stable and rounded hysteresis loops, as
the ratio hc/ db increases. Note the slack or
pinched behavior for small values ofhc/db.
Figure 4.5 shows that the strength of a joint canbe well represented by the ratio of the horizontal
joint shear stress to the compressive strength of
the concrete. This is reasonable considering that
failure is by failure of the diagonal compression
strut (Figure 4.4). In US practices, it has been
more traditional to relate the joint shear strength
to the square root of the compressive strength of
29
-
7/29/2019 MoehleSmrf
30/33
Figure 4.7 Behavior of joints conforming
with code details but having shear exceeding
code values
concrete, based on the traditional notion that
shear strength is a tension failure phenomenon
that can be more directly related to the square
root of the compressive strength rather than the
directly to the compressive strength.
Figure 4.7 shows test results for a jointdesigned with transverse reinforcement meeting
the requirements of ACI 318, but with joint shear
stress exceeding the allowable values of ACI 318
(to be described later) [Kurose, 1991]. The ACI
318 strength values are shown by Vu in the
figures. The joint was subjected to loading in
two horizontal directions, the upper load-
deformation relation for loading in one direction,
the lower load-deformation relation for loading in
the orthogonal direction. The joints were able to
reach shear stress values exceeding the design
value in both directions. However, under this
overload the joints failed in shear. The
deterioration in strength is apparent in the figures.
Although the deformation capacity is
considerable, by the 4% deformation cycles the
strength deterioration probably is unacceptably
high. Better behavior is obtained if the joint
shear stresses are at or below acceptable limits.
4.4 Joint design
According to ACI 318, joint design requires (a) provision of adequate joint shear strength, (b)anchorage of reinforcement, (c) provision of adequate joint transverse reinforcement, and (d)
provision of adequate column flexural strength.
4.4.1 Joint shear
The design horizontal joint shear is obtained by equilibrium of horizontal forces acting on a
free body diagram of the joint as shown in Figure 4.2b. The design joint shear is not to exceed
0.85 times the nominal shear strength. The nominal shear strength of the joint is not tobe taken
greater than the forces specified below for normalweight aggregate concrete. For lightweight
aggregate concrete, the nominal shear strength of the joint is not to be taken greater than three-
quarters of the limits given for normalweight concrete.
For joints confined on all four faces 20 cf Aj
For joints confined on three faces or on two opposite faces 15 cf Aj
For others 12 cf Aj
30
-
7/29/2019 MoehleSmrf
31/33
For the purpose of determining the appropriate joint shear strength, a member that frames into a
face is considered to provide confinement to the joint if at least three-quarters of the face of the
joint is covered by the framing member.
hbfVV jcnu' =
= 0.85
Values of24 20 15
20 15 12
nonseismic
seismic
Type
Note: To qualify for a geometry shown, the beam must
cover at least 75% of the face of the joint.
hbfVV jcnu' =
= 0.85
Values of24 20 15
20 15 12
nonseismic
seismic
Type
Values of24 20 15
20 15 12
nonseismic
seismic
Type
Note: To qualify for a geometry shown, the beam must
cover at least 75% of the face of the joint.
Figure 4.8 Summary of joint shear strength requirements
Figure 4.8 summarizes the joint
shear strength requirements. Note
that joint geometries typical ofconstruction at the roof level have
not been included here. At the
time of this writing, ACI
Committee 352 is developing
recommendations for joint shear
strength for those geometries.
4.4.2 Anchorage of
reinforcement
It is important for beam and
column longitudinalreinforcement to be anchored
adequately so that the joint can
resist the beam and column
moments.
In interior joints, reinforcement
typically extends through the
joint and is anchored in the
adjacent beam span (Figure 4.9).
ACI 318 requires that the column
dimension parallel to the beam
longitudinal reinforcement be not
less than 20 times the diameter of
the largest longitudinal bar for
normalweight concrete. For
lightweight concrete, the
required dimension is 26 times
the bar diameter. This
requirement helps improve performance of the joint by resisting slip of the beam bars through the
joint. Some slip, however, will occur even with this column dimensional requirement. See
Figure 4.6.
bd20
db
(a) Requirement forinterior connections
(a) Requirement forinterior connections
dhl
Note: Provide at
least ldh, and always
extend beam bars to
near the back of the
joint
bd20
db
(a) Requirement forinterior connections
(a) Requirement forinterior connections
dhl
Note: Provide at
least ldh, and always
extend beam bars to
near the back of the
joint
Figure 4.9 Anchorage/development requirements
ACI 352 recommends that the beam depth be not less than 20 times the diameter of the column
longitudinal reinforcement for the same reason. ACI 318 does not include this requirement.
For exterior joints, beam longitudinal reinforcement usually terminates in the joint with a
standard hook. The provided length for a standard 90 deg hook in normalweight aggregate
concrete must be the largest of8db, 6 in., and the length required by the following expression:
( )cbydh fdf = 65/l This expression assumes that the hook is embedded in a confined beam-column joint. The
expression is limited to for bar sizes No. 3 through No. 11. For lightweight aggregate concrete,