molded case circuit breakers overviewcontrol.sdindustrial.com.mx/especificaciones/especifica... ·...

15
Circuit Protection www.automationdirect.com/circuit-protection e31-5 Company Information Systems Overview Programmable Controllers Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index Volume 13 Molded Case Circuit Breakers Overview Overview Fuji Molded Case Circuit Breakers are more compact (especially 100A, 125A, 250A frames) than any breakers on the market, so they take up less space in control panels. This product group maintains conformity to all Worldwide standards. Agency Approvals • UL listed, MCCB, File: E90584 • UL listed, Accessories, File E93289 • CE marked • CCC marked • TUV certified Standards • UL 489 • CSA C22.2 No.5 • IEC 60947-2 • EN 60947-2 • GB 14048.2 • JIS C8201-2-1, 2 (ANN.1, 2) Features • Thermal-magnetic 15A through 800A • Suitable for branch circuit protection • Rated current of 15 to 800A, max 600V • Standard type and high-interrupting capacities available in identically sized breakers • Shunt Trip, Undervoltage Release and other accessories available • Line & load lug terminals included on all MCCBs • Auxiliary switch, Alarm switch and Shunt Trip can be installed in the field • Door-mounted or flange-mounted, flex shaft operating handles • All frame sizes suitable for reverse-feed use • All breakers include mounting hardware • Terminal covers included for BW125 and BW250 frames. Terminal covers available for BW400, BW630 and BW800 frames. BW125JAGU - 3P 015 SB Fuji MCCB Frame Size 3 Pole Amp Rating Terminal Structure Fuji Molded Case Circuit Breakers Part Numbering System *Note: N.I.T.U denotes non-interchangeable trip unit. **Note: For DC or 1-phase AC applications, use the two outside poles of the 3-pole circuit breaker Fuji Electric Molded Case Circuit Breakers Technical Specifications Circuit Breaker Type Ampere Rating at 40°C No. Poles Volts Type of Trip* UL 489 Interrupting Ratings (rms Symmetrical Amperes) (kA) AC DC Volts AC (50/60 Hz) Volts DC 240 480 600 250** BW125JAGU 15-125 3 600 250 N.I.T.U 50 30 10 10 BW250JAGU 125-250 3 600 250 N.I.T.U 50 30 10 10 BW400SAGU 250-400 3 480 250 N.I.T.U 50 35 10 BW630RAGU 500-600 3 480 250 N.I.T.U 100 50 10 BW800RAGU 700-800 3 480 250 N.I.T.U 100 50 10

Upload: others

Post on 26-Jan-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t - p r o t e c t i o n e31-5

    CompanyInformation

    SystemsOverview

    ProgrammableControllers

    Field I/O

    Software

    C-more & other HMI

    Drives

    SoftStarters

    Motors &Gearbox

    Steppers/Servos

    Motor Controls

    ProximitySensors

    Photo Sensors

    Limit Switches

    Encoders

    CurrentSensors

    PressureSensors

    TemperatureSensors

    Pushbuttons/Lights

    Process

    Relays/Timers

    Comm.

    TerminalBlocks & Wiring

    Power

    CircuitProtection

    Enclosures

    Tools

    Pneumatics

    Appendix

    ProductIndex

    Part #Index

    Volume 13

    Molded Case Circuit Breakers Overview

    OverviewFuji Molded Case Circuit Breakers aremore compact (especially 100A, 125A,250A frames) than any breakers on themarket, so they take up less space incontrol panels.

    This product group maintains conformityto all Worldwide standards.

    Agency Approvals• UL listed, MCCB, File: E90584 • UL listed, Accessories, File E93289 • CE marked• CCC marked• TUV certified

    Standards• UL 489• CSA C22.2 No.5• IEC 60947-2 • EN 60947-2• GB 14048.2• JIS C8201-2-1, 2 (ANN.1, 2)

    Features • Thermal-magnetic 15A through 800A• Suitable for branch circuit protection • Rated current of 15 to 800A, max 600V• Standard type and high-interrupting

    capacities available in identically sizedbreakers

    • Shunt Trip, Undervoltage Release andother accessories available

    • Line & load lug terminals included on allMCCBs

    • Auxiliary switch, Alarm switch and ShuntTrip can be installed in the field

    • Door-mounted or flange-mounted, flexshaft operating handles

    • All frame sizes suitable for reverse-feeduse

    • All breakers include mounting hardware • Terminal covers included for BW125 and

    BW250 frames. Terminal covers availablefor BW400, BW630 and BW800 frames.

    BW125JAGU - 3P 015 SBFuji MCCB Frame Size

    3 PoleAmp Rating

    Terminal Structure

    Fuji Molded Case Circuit Breakers Part Numbering System

    *Note: N.I.T.U denotes non-interchangeable trip unit.

    **Note: For DC or 1-phase AC applications, use the two outside poles of the 3-pole circuit breaker

    Fuji Electric Molded Case Circuit Breakers Technical Specifications

    CircuitBreaker Type

    Ampere Ratingat 40°C

    No.Poles

    Volts Typeof

    Trip*

    UL 489 Interrupting Ratings (rmsSymmetrical Amperes) (kA)

    AC DC Volts AC (50/60 Hz) Volts DC240 480 600 250**

    BW125JAGU 15-125 3 600 250 N.I.T.U 50 30 10 10BW250JAGU 125-250 3 600 250 N.I.T.U 50 30 10 10BW400SAGU 250-400 3 480 250 N.I.T.U 50 35 – 10BW630RAGU 500-600 3 480 250 N.I.T.U 100 50 – 10BW800RAGU 700-800 3 480 250 N.I.T.U 100 50 – 10

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-10

    Fuji Molded Case Circuit Breakers – 250A Frame

    BW250-Frame Accessory Selection GuidePart Number Price Description

    BW9W1SG0 Field installable auxiliary contact for BW250frame MCCBs. SPDT. Lead wires: 20AWG, 19.69” long. Left and right side mountBW9FRG0 Field installable 24 VDC/VAC shunt trip for BW250-frame MCCBs. Lead wires: 20AWG, 19.69” long. Left and right side mountBW9FAG0 Field installable 100-120 VAC, 100-110 VDC shunt trip for BW250-frame MCCBs. Lead wires: 20AWG, 19.69” long. Left and right side mountBW9RGAR Field installable 24 VDC undervoltage release for BW250-frame MCCBs. Lead wires: 20AWG, 19.69” long. Left side mount onlyBW9RGAT Field installable 110-130 VAC undervoltage release for BW250-frame MCCBs. Lead wires: 20AWG, 19.69” long. Left side mount onlyBW9SL0GA-3 ! Replacement lugs for BW250-frame MCCBs up to 175A, package of 3BW9SL1GA-3 Replacement lugs for BW250-frame MCCBs 175A to 250A, package of 3BW9V0GA NEMA 12 rotary handle for BW250-Frame. Position indicating; lock-off feature. Shaft length: 0.39”BW9VSG0 NEMA 12 rotary handle shaft for BW9V0GA for BW250-Frame. Shaft length: 6.06”BW9F0GA-15A NEMA 12 flexible shaft handle for BW250-Frame. Flange mounted. Lockable. Flex cable shaft length: 4.92’ (1.5m)BW9F0GA-20A NEMA 12 flexible shaft handle for BW250-Frame. Flange mounted. Lockable. Flex cable shaft length: 6.56 (2m)BW9Q1CA Lockout attachment. Lock not included.Note: Short-type terminal covers (gray-white) are supplied as standard.

    BW250JAGU-3P125SBshown

    BW9V0GA BW9F0GA-15A

    BW250-Frame Series Three-Pole Molded Case Circuit Breakers

    Part Number Price Frequency

    Rated Interrupting Capacity (kA)Rated

    CurrentUL489 CAN/CSA

    C22.2 No. 5IEC60947-2, JIS C8201-2-1 Icu/Ics

    GB14048.2 Icu/Ics

    AmpereRating Voltage

    InterruptCapacity Voltage

    InterruptCapacity Voltage

    InterruptCapacity

    BW250JAGU-3P125SB

    50/60 Hz

    125

    600V/Y AC480V/� AC480V/Y AC240V AC250V DC

    10 kA30 kA30 kA50 kA10 kA

    500V AC440V AC400V AC380V AC240V AC250V DC

    18/9 kA30/15 kA30/15 kA30/15 kA50/25 kA20/10 kA

    400V AC230V AC

    30/15 kA50/25 kA

    BW250JAGU-3P150SB 150BW250JAGU-3P160SB 160BW250JAGU-3P175SB 175BW250JAGU-3P200SB 200BW250JAGU-3P225SB 225BW250JAGU-3P250SB 250Note: SCCR = UL489 interrupting capacity

    BW9FRG0 BW9RGAR BW9Q1CA

    Wiring Specifications chart is on page 31-30

    Fuji BW250A series MCCBs are 250 ampframe, 3-pole, non-adjustable magnetic trip,molded case circuit breakers (MCCB). TheBW250 series is suitable for reverse feed

    applications. Included with each MCCB areLine and Load-side lug terminals, terminalcovers and mounting hardware. Accessoriesare not pre-installed and are sold separately.

    Volume 13

    http://www.automationdirect.com/pn/BW250JAGU-3P125SBhttp://www.automationdirect.com/pn/BW250JAGU-3P125SBhttp://www.automationdirect.com/pn/BW250JAGU-3P150SBhttp://www.automationdirect.com/pn/BW250JAGU-3P160SBhttp://www.automationdirect.com/pn/BW250JAGU-3P175SBhttp://www.automationdirect.com/pn/BW250JAGU-3P200SBhttp://www.automationdirect.com/pn/BW250JAGU-3P225SBhttp://www.automationdirect.com/pn/BW250JAGU-3P250SBhttp://www.automationdirect.com/pn/BW9F0GA-15Ahttp://www.automationdirect.com/pn/BW9F0GA-20Ahttp://www.automationdirect.com/pn/BW9F0GA-15Ahttp://www.automationdirect.com/pn/BW9SL0GA-3http://www.automationdirect.com/pn/BW9SL1GA-3http://www.automationdirect.com/pn/BW9W1SG0http://www.automationdirect.com/pn/BW9FRG0http://www.automationdirect.com/pn/BW9FAG0http://www.automationdirect.com/pn/BW9RGARhttp://www.automationdirect.com/pn/BW9RGAThttp://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9VSG0http://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9Q1CAhttp://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9FRG0http://www.automationdirect.com/pn/BW9RGARhttp://www.automationdirect.com/pn/BW9Q1CA

  • Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t - p r o t e c t i o n e31-11

    CompanyInformation

    SystemsOverview

    ProgrammableControllers

    Field I/O

    Software

    C-more & other HMI

    Drives

    SoftStarters

    Motors &Gearbox

    Steppers/Servos

    Motor Controls

    ProximitySensors

    Photo Sensors

    Limit Switches

    Encoders

    CurrentSensors

    PressureSensors

    TemperatureSensors

    Pushbuttons/Lights

    Process

    Relays/Timers

    Comm.

    TerminalBlocks & Wiring

    Power

    CircuitProtection

    Enclosures

    Tools

    Pneumatics

    Appendix

    ProductIndex

    Part #Index

    Volume 13

    Fuji Molded Case Circuit Breakers – 250A Frame Characteristic Curves

    BW250

    Ambient temp. (˚C)

    Rat

    ed c

    urre

    nt

    corr

    ectio

    n ra

    tio (%

    )

    Reference temp. 40˚C

    050403020 010150

    100

    1501246

    1246

    0.010.02

    0.040.06

    0.10.20.40.6

    10

    20

    40

    1020

    4060

    120180

    1 1.5 2 3 4 5 6 78 10 15 20 30 40506080Multiple of rated current

    Max. value

    Min. valueMax. total fault clearing time

    Instantaneous trippingcharacteristic10 In±20%

    Min

    ute

    Sec

    ond

    Ope

    ratin

    g tim

    e

    100

    Note: Instantaneous tripping = 10 x (rated current) ± 20% In = rated current

    BW250 Current Range 125 - 250A

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-18

    15 to 125ABW125A Frame

    125 to 250ABW250A Frame

    Fuji Molded Case Circuit Breakers –Dimensions

    Note: All dimensions shown in mm [inches]

    Volume 13

  • Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t - p r o t e c t i o n e31-19

    CompanyInformation

    SystemsOverview

    ProgrammableControllers

    Field I/O

    Software

    C-more & other HMI

    Drives

    SoftStarters

    Motors &Gearbox

    Steppers/Servos

    Motor Controls

    ProximitySensors

    Photo Sensors

    Limit Switches

    Encoders

    CurrentSensors

    PressureSensors

    TemperatureSensors

    Pushbuttons/Lights

    Process

    Relays/Timers

    Comm.

    TerminalBlocks & Wiring

    Power

    CircuitProtection

    Enclosures

    Tools

    Pneumatics

    Appendix

    ProductIndex

    Part #Index

    400ABW400 Frame

    Fuji Molded Case Circuit Breakers –Dimensions

    250A to 350ABW400 Frame

    Note: All dimensions shown in mm [inches]

    Volume 13

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-22

    Fuji Molded Case Circuit Breakers –Products And Accessory Compatibility

    Match the Accessories with Fuji Molded Case Circuit BreakersPart Number Description BW125JAGU BW250JAGU BW400SAGU BW630RAGU BW800RAGUBW9W1SG0 Auxiliary Switch (Mounting Left and right side) X XBW9W1SHA Auxiliary Switch (Mounting Left side ONLY) X X X

    BW9FRG0 Shunt Trip 24 VAC/VDC (Mounting both Left and Right sides) X XBW9FHA-R Shunt Trip 24-48 VAC/VDC (Mounting Left side ONLY) X X X

    BW9FAG0 Shunt Trip 100-120 VAC, 100-110 VDC (Mounting both Left and Right sides) X X

    BW9FHA-A Shunt Trip 100-280 VAC, 100-220 VDC (Mounting Left side ONLY) X X X

    BW9RGAR UnderVoltage Release 24VDC (Left side ONLY) X XBW9RHA-R UnderVoltage Release 24 VAC/VDC (Left side ONLY) X X XBW9RGAT UnderVoltage Release 110-130 VAC (Left side ONLY) X XBW9RHA-1 UnderVoltage Release 120-130 VAC, 125VDC (Left side ONLY) X X X

    BW9SL0CA-3 Replacement Lugs Kit for 125 Amp frame XBW9SL0GA-3 Replacement Lugs Kit for 250 Amp frame up to 175A XBW9SL1GA-3 Replacement Lugs Kit for 250 Amp frame 200A to 250A X

    BW9V0CA Rotary Handle, H = 4.134"(shaft is shorter) XBW9V0GA Rotary Handle, H = 4.134"(shaft is shorter) XBW9VSG0 Optional Shaft for BW9V0CA and BW9V0GA, H = 9.843" (shorter shaft) X XBW9V0HA Rotary Handle, H = 7.48"(shaft is shorter) XBW9V0JA Rotary Handle, H = 7.48"(shaft is shorter) X XBZ-VS2 Optional Shaft for BW9V0HA and BW9V0JA, H = 9.843" (shorter shaft) X X X

    BW9F0CA-15A Flange Handle (flex shaft), NEMA 12, 59“ (1.5m) cable, 125 Amp frame XBW9F0CA-20A Flange Handle (flex shaft), NEMA 12, 78.7” (2.0m) cable, 125 Amp frame XBW9F0GA-15A Flange Handle (flex shaft), NEMA 12, 59“ (1.5m) cable, 250 Amp frame XBW9F0GA-20A Flange Handle (flex shaft), NEMA 12, 78.7” (2.0m) cable, 250 Amp frame XBW9F0HA-15A Flange Handle (flex shaft), NEMA 12, 59“ (1.5m) cable, 400 Amp frame XBW9F0HA-20A Flange Handle (flex shaft), NEMA 12, 78.7” (2.0m) cable, 400 Amp frame X

    BW9BTHA-L3W Terminal Cover for the 400A frame XBW9BTJA-L3W Terminal Cover for the 630A AND 800A frame X X

    BW9Q1CA Lockout Attachment 125A and 250A frames X XBW9QNHA Lockout Attachment 400A, 630A and 800A frames X X X

    Internal Accessory Combinations for BW Series

    Available configurations

    Auxiliary switchSPDTShunt trip

    Undervoltage trip

    Auxiliary Switch + Shunt Trip

    Undervoltage + Auxiliary Switch

    MCCB

    Pole 3 3

    BW400BW630BW800

    BW125BW250

    Handle

    3-pole

    Left Right Shunt trip Undervoltage trip Auxiliary switch

    Volume 13

    http://www.automationdirect.com/pn/BW9F0CA-15Ahttp://www.automationdirect.com/pn/BW9F0CA-20Ahttp://www.automationdirect.com/pn/BW9F0GA-15Ahttp://www.automationdirect.com/pn/BW9F0GA-20Ahttp://www.automationdirect.com/pn/BW9F0HA-15Ahttp://www.automationdirect.com/pn/BW9F0HA-20Ahttp://www.automationdirect.com/pn/BW9BTHA-L3Whttp://www.automationdirect.com/pn/BW9BTJA-L3Whttp://www.automationdirect.com/pn/BW9SL0CA-3http://www.automationdirect.com/pn/BW9SL0GA-3http://www.automationdirect.com/pn/BW9SL1GA-3http://www.automationdirect.com/pn/BW9W1SG0http://www.automationdirect.com/pn/BW9W1SHAhttp://www.automationdirect.com/pn/BW9FHA-Rhttp://www.automationdirect.com/pn/BW9FHA-Ahttp://www.automationdirect.com/pn/BW9RHA-Rhttp://www.automationdirect.com/pn/BW9RHA-1http://www.automationdirect.com/pn/BW9FRG0http://www.automationdirect.com/pn/BW9FAG0http://www.automationdirect.com/pn/BW9RGARhttp://www.automationdirect.com/pn/BW9RGAThttp://www.automationdirect.com/pn/BW9V0CAhttp://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9VSG0http://www.automationdirect.com/pn/BW9V0CAhttp://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9V0HAhttp://www.automationdirect.com/pn/BW9V0JAhttp://www.automationdirect.com/pn/BW9V0HAhttp://www.automationdirect.com/pn/BW9V0JAhttp://www.automationdirect.com/pn/BW9Q1CAhttp://www.automationdirect.com/pn/BW9QNHAhttp://www.automationdirect.com/pn/BZ-VS2

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-30Volume 13

    Maximum Wire Sizes and Tightening Torque

    Type RatedCurrent (A)Wire Size AWG or MCM (mm2)

    TighteningTorqueLugTerminal*

    BW125

    15 14 AWG (2.1mm2)

    51 lb.-in.(5.8 N-m)

    20 12 AWG (3.3mm2)30 10 AWG (5.3mm2)40 8 AWG (8.4mm2)50 8 AWG (8.4mm2)60 6 AWG (13.3mm2)70 4 AWG (21.1mm2)75 4 AWG (21.1mm2)80 4 AWG (21.1mm2)90 3 AWG (26.7mm2)100 3 AWG (26.7mm2)125 1 AWG (42.4mm2)

    BW250

    125 1 AWG (42.4mm2)

    204 lb.-in.(23 N-m)

    150 1/0 AWG (53.5mm2)175 2/0 AWG (67.4mm2)200 3/0 AWG (85.0mm2)225 4/0 AWG (107.2mm2)250 250 MCM (127mm2)

    BW400

    250 250 MCM (127mm2)385 lb.-in(43.5 N-m)

    300 350 MCM (177mm2)350 500 MCM (253mm2)

    400 3/0 AWGx2 (85.0mm2x2)282 lb-in (31.9 N-m)

    BW630500 250-500 MCMx2 275 lb.-in.

    (31.07 N-m)600 250-500 MCMx2

    BW800700 250-500 MCMx2 275 lb.-in.

    (31.07 N-m)800 3/0 AWG-300 MCMx3

    Fuji Molded Case Circuit Breakers – Wire Range Specifications

    Wiring • When connecting the wires, follow NEC (National Electric Code,

    USA) or CEC (Canadian Electrical code Part 1, Canada) instruc-tions.

    • Use copper wire rated for 75°C for connecting. UL or CSAapproved wire is recommended.

    • Tighten the wire connections adequately, as a very large elec-tromagnetic force will be generated when short circuit current isgenerated.

    • Perform additional tightening of the terminal screws periodically.

    Caution• Adhere to the number of strands of wire indicated in the

    table.• Multiconductor wire can not be connected. • Two wires cannot be connected to the lug terminal at once.• Do not solder the end of the wire.

    Allowable Wire Specifications for Lug TerminalsWire Size AWG or MCM (mm2) Number of Wire Strands

    14 to 2 (2.1 to 33.6) 71 to 4/0 (42.4 to 107.2) 19250 to 500 (127 to 250) 37

    *Note: Lug terminals are supplied as standard.

  • Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t - p r o t e c t i o n e31-23

    CompanyInformation

    SystemsOverview

    ProgrammableControllers

    Field I/O

    Software

    C-more & other HMI

    Drives

    SoftStarters

    Motors &Gearbox

    Steppers/Servos

    Motor Controls

    ProximitySensors

    Photo Sensors

    Limit Switches

    Encoders

    CurrentSensors

    PressureSensors

    TemperatureSensors

    Pushbuttons/Lights

    Process

    Relays/Timers

    Comm.

    TerminalBlocks & Wiring

    Power

    CircuitProtection

    Enclosures

    Tools

    Pneumatics

    Appendix

    ProductIndex

    Part #Index

    Volume 13

    Fuji Molded Case Circuit Breakers – Field-mountable Accessories

    Rotary Operating Handles for Fuji MCCBs – Selection Guide

    BreakerType

    V-typeHandle Price

    Standard Type With the optional shaft (x= 6.063 (154)) MountingScrew

    Mass lb. (kg)H: inch(mm) H: inch(mm) Area in which the hinge with H can be installed

    BW125 BW9V0CA 4.134±0.078 (105±2) 9.843±0.078 (250±2) 5.512 to 9.843 (140 to 250) M4 x 3.35 (85) 1.48 (0.67)BW250 BW9V0GA 4.134±0.078(105±2) 9.843±0.078 (250±2) 5.512 to 9.843 (140 to 250) M4 x 3.35 (85) 1.48 (0.67)BW400 BW9V0HA

    7.48±0.078 (190±2) 9.843±0.078 (250±2) 7.953 to 9.843 (202 to 250) M6 x 4.33 (110) 4.85 (2.2)BW630BW800 BW9V0JA

    Notes: • Handle is an operating mechanism only; not for sealing enclosure door.

    • Not available for side mounting

    • When mounting a terminal cover, cut away part of it because it hides the mounting screws for the breaker.

    Defeatable Rotary Handle Operating Mechanisms

    125A, 250A Frame V type handle

    • BW9V0CA, BW9V0GA (BW9VSG0: optional shaft)

    Area in which the hingewith H can be installed

    H: inch(mm)Standard typeH: inch(mm)

    Breaker type Handle type With the optional shaft (X=6.063(154)) Mountingscrew

    M4 x 3.35(85)

    M4 x 3.35(85)

    Mass lb. (kg)

    1.48 (0.67)

    1.48 (0.67)

    BW125

    BW250

    BW9V0CA

    BW9V0GA

    4.134±0.078(105±2)

    4.134±0.078(105±2)

    5.512 to 9.843(140 to 250)

    5.512 to 9.843(140 to 250)

    9.843±0.078(250±2)

    9.843±0.078(250±2)

    Door panel cuttingHandle

    C/L4-0.591 dia (ø15)

    MCCBHandle C/L

    3.071(78)

    3.07

    1 (7

    8)1.929 (49)

    Padlock size 0.157 dia to 0.315 dia (ø4 to ø8)

    LC

    4.44

    9 (1

    13)

    4.449 (113)2.677 (68)

    LC

    2.559 (65) H

    MCCBhandle

    C/L

    MCCBLine

    Load

    Panel

    Note: Align the center of the hole cut in the panel with the center of the breaker handle.

    Handle C/L

    P4 P3 P2

    Door hinge installation areaOptional shaft BW9VSG0X = H - 3.74 (95)

    Install the door hinge in the shaded area.

    2.362 (60) 2.362 (60)

    4.724 (120) 4.724 (120)

    C/L

    1.06

    3 (2

    7)1.

    614

    (41)

    1.06

    3 (2

    7)0.

    315

    (8)

    1.18

    1 (3

    0)0.

    039

    (1)

    1.92

    9 (4

    9)0.

    591

    (15)

    X

    Notes: • The handle does not have any means to hold the door. Provide it separately.• Not available for side mounting.* For BW250 series only: When mounting a terminal cover, cut away part of it because it hides the mounting screws for the breaker. Remove the shaded parts in the figure .

    Panel thickness:0.047 to 0.126 (1.2 to 3.2)

    3.543 dia

    (ø90)

    BW9V0CA shown

    Dimensions: inch (mm)

    Dimensions

    http://www.automationdirect.com/pn/BW9V0CAhttp://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9V0HAhttp://www.automationdirect.com/pn/BW9V0JAhttp://www.automationdirect.com/pn/BW9V0CAhttp://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9VSG0http://www.automationdirect.com/pn/BW9V0CAhttp://www.automationdirect.com/pn/BW9V0GAhttp://www.automationdirect.com/pn/BW9VSG0http://www.automationdirect.com/pn/BW9V0CA

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-24Volume 13

    Fuji Molded Case Circuit Breakers – Field-mountable Accessories

    400A, 630A, 800A Frame V type handle

    • BW9V0HA, BW9V0JA (BZ-VS2: optional shaft)

    Breaker type Handletype

    Standard typeH: inch(mm)

    With the optional shaft (X = 3.48 (88.5) Mass lb. (kg)H: inch(mm) Area in which the hinge

    with H can be installed

    BW400

    BW630, BW800

    BW9V0HA

    BW9V0JA

    7.48±0.078(190±2)

    9.843±0.078(250±2)

    7.953 to 9.843 (202 to 250) 4.85 (2.2)

    Note: • The handle is an operating mechanism only; not for sealing enclosure door. • Not available for side mounting

    X

    Optional shaft (BZ-VS2)

    2.16

    5 (5

    5)

    3.937 (100)

    H 2.48 (63)

    0.39

    4 (1

    0)

    7.874 (200)

    OFF

    1.18

    1 (3

    0)

    Panel Decorativeplate

    Mountingscrew

    Load

    Install the door hinge in the shaded area.

    Line5.906 (150)

    5.90

    6 (1

    50)

    5.90

    6 (1

    50)

    Lock platePadlock size 0.157 dia (ø4) to

    0.315 dia (ø8)(Up to two 0.315 dia (ø8) padlocks can be mounted.)

    MCCB handle C/L

    4.40

    9 (1

    12)

    4.409 (112)

    4-0.39

    4 dia

    (ø10)

    MCCBhandle C/L

    MCCBhandle C/L

    Door panel cutting

    Note: Align the center of the hole cut in the panel with the center of the breaker handle.

    When using the BZ-VS2 extension shaft to adjust dimension H, cut it according to the equation below.X=H−6.358 (161.5)

    Panel thickness: 0.063-0.126 (1.6-3.2)

    5.433 di

    a (ø138

    )

    M6 x 4.33 (110)

    Dimensions: inch (mm)

    Dimensions

    http://www.automationdirect.com/pn/BW9V0HAhttp://www.automationdirect.com/pn/BW9V0JAhttp://www.automationdirect.com/pn/BW9V0HAhttp://www.automationdirect.com/pn/BW9V0JAhttp://www.automationdirect.com/pn/BZ-VS2http://www.automationdirect.com/pn/BZ-VS2http://www.automationdirect.com/pn/BZ-VS2

  • Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t - p r o t e c t i o n e31-25

    CompanyInformation

    SystemsOverview

    ProgrammableControllers

    Field I/O

    Software

    C-more & other HMI

    Drives

    SoftStarters

    Motors &Gearbox

    Steppers/Servos

    Motor Controls

    ProximitySensors

    Photo Sensors

    Limit Switches

    Encoders

    CurrentSensors

    PressureSensors

    TemperatureSensors

    Pushbuttons/Lights

    Process

    Relays/Timers

    Comm.

    TerminalBlocks & Wiring

    Power

    CircuitProtection

    Enclosures

    Tools

    Pneumatics

    Appendix

    ProductIndex

    Part #Index

    Flex Handle Specifications

    Operating instructions

    • Operating handle facing up, Breaker is in ON position.• Operating handle facing down, Breaker is in OFF position or is reset.• Panel door cannot be opened when in ON, OFF or Trip position. In order to

    open the door, the handle must be turned toward reset position.• Release screw is standard. If you want to open a panel door in ON position,

    please turn the release screw using flat head screwdriver.

    Frame Size 125A frame 250A frame 400A frameMechanical Endurance(cycles) 10,000 8,000 6,000

    Ambient Temperature 14 to 140F (- 10 to 40°C)Relative Humidity less than 95% RHProtection NEMA Type12 IP54 (IEC60529)Conforming Standards NFPA 79(2007), ANSI(Lockout), OSHA(1910.147, Lockout/tagout), UL489(cUL)Environment No excessive dust, smoke, corrosive gases, flammable gases, steam or salt.

    Flex Shaft Handles for Fuji MCCBs – Selection GuideBreakerType Handle Type Price Description

    BW125BW9F0CA-15A Nema 12 flexible shaft handle for 125A frame. 59.06” (1.5m)cableBW9F0CA-20A Nema 12 flexible shaft handle for 125A frame. 78.74” (2m) cable

    BW250BW9F0GA-15A Nema 12 flexible shaft handle for 250A frame. 59.06” (1.5m)cableBW9F0GA-20A Nema 12 flexible shaft handle for 250A frame. 78.74” (2m) cable

    BW400BW9F0HA-15A Nema 12 flexible shaft handle for 400A frame. 59.06” (1.5m)cableBW9F0HA-20A Nema 12 flexible shaft handle for 400A frame. 78.74” (2m) cable

    Defeatable Flexible Handle Operating Mechanisms

    Fuji Molded Case Circuit Breakers – Field-mountable Accessories

    BW9F0CA-15A shown

    Terminal cover Mounting screwM4 x 90

    Drive section Operation section

    Insulation barrier

    Terminal cover

    To operation section

    Panel drilling

    0.197dia(M4 or ø5)

    Handle

    Panel

    Panel

    Cable

    Release lever

    Lock lever

    Release screw

    OFF lock

    Concave for ON lock*2

    1.102(28) or more RESET

    6.10

    2 (1

    55)

    5.19

    7 (1

    32)

    0.86

    6(2

    2)

    1.08

    3(2

    7.5)

    0.49

    2(1

    2.5)

    1.08

    3 (2

    7.5)

    5.19

    7 (1

    32) 10

    .827

    (275

    )

    Max

    . 2.7

    17( 6

    9)

    5.866 (149)

    5.70

    9 (1

    45)

    150˚

    2.95

    3 (7

    5)

    4.68

    5 (1

    19)

    1.14

    2 (2

    9)

    2.55

    9 (6

    5)

    3.937 (100)MCCB/ELCB

    ELCB

    MCCB/ELCB

    MCCB/ELCB

    4.094 (104)2.756 (70)

    3.543 (90)

    1.181 (30)

    4.606 (117)

    2.362 (60)

    1.772 (45)

    3.15 (80) ON 1.063(27)

    1.142 (29)

    2.244(57)

    2.244 (57)

    0.512(13)

    2-0.27

    6 dia

    (ø7)

    R0.256 (R6.5)

    2-0.217 dia (ø5.5)

    *1

    • BW9F0CA

    • This product consists of a drive section and an operation section.• The operation section can be mounted either to the right or to the left on the panel depending on the mounting position of the release lever.• For the OFF lock, up to three 0.394 dia (φ10) padlocks can be used at one time

    *1 Set the height to 20mm or 30mm (0.787” or 1.181”). Adjust the lock lever depending on the setting.*2 In the ON position, up to two padlocks or lockout hasps up to 0.394 dia (10mm) can be

    used at one time.

    Volume 13

    http://www.automationdirect.com/pn/BW9F0CA-15Ahttp://www.automationdirect.com/pn/BW9F0CA-20Ahttp://www.automationdirect.com/pn/BW9F0GA-15Ahttp://www.automationdirect.com/pn/BW9F0GA-20Ahttp://www.automationdirect.com/pn/BW9F0HA-15Ahttp://www.automationdirect.com/pn/BW9F0HA-20Ahttp://www.automationdirect.com/pn/BW9F0CA-15A

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-26

    Fuji Molded Case Circuit Breakers – Field-mountable Accessories

    35

    g

    Operation sectionDrive section

    To operation section

    Panel drilling

    Handle

    Panel

    Mounting screwM4 x 90

    Panel

    Cable

    Release lever

    Lock lever

    Release screw

    OFF lock

    Concave for ON lock*2

    1.102 (28) or more

    RESET

    0.86

    6 (2

    2)

    4.96

    1 (1

    26)

    1.08

    3 (

    27.5

    )

    0.49

    2 (

    12.5

    )

    1.08

    3 (2

    7.5)

    5.19

    7 (1

    32)

    10.8

    27 (

    275)

    6.49

    6 (

    165)

    3.46

    5(8

    8)

    Max

    . 2.7

    17 (

    69)

    5.866 (149)

    5.70

    9 (1

    45)

    150˚

    2.95

    3 (

    75)

    4.68

    5 (1

    19)

    1.14

    2 (2

    9)

    2.362 (60)

    1.772 (45)

    3.15 (80) ON 1.063 (27)

    1.142 (29)2.244 (57)

    4.094 (104)4.528 (115)

    2.756 (70)

    4.606 (117)3.543(90)

    Insulationbarrier

    Terminalcover 2.244 (57)

    1.378 (35)

    0.197 dia(M4 or ø5)

    0.512 (13)

    2-0.2

    76 di

    a (ø7

    )

    R0.256 (R6.5)

    2-0.217 dia (ø5.5)

    *1

    MCCB/ELCB

    MCCB/ELCB

    MCCB/ELCB

    MCCB/ELCB

    • BW9F0GA

    • This product consists of a drive section and an operation section.• The operation section can be mounted either to the right or to the left on the panel depending on the mounting position of the release lever.• For the OFF lock, up to three 0.394 dia (φ10) padlocks can be used at one time

    *1 Set the height to 20mm or 30mm (0.787” or 1.181”). Adjust the lock lever depending on the setting.*2 In the ON position, up to two padlocks or lockout hasps up to 0.394 dia (10mm) can be

    used at one time.

    Dimensions: inch (mm)• BW9F0HA

    Mounting screwM6 x 110

    Operation sectionDrive section

    To operation section

    Panel drilling

    Handle

    Panel

    Panel

    Cable

    Release lever

    Lock lever

    Release screw

    OFF lock

    Concave for ON lock*2

    1.102 (28) or moreRESET

    0.86

    6 (2

    2)

    8.42

    5 (2

    14)

    to 8

    .504

    (21

    6)

    1.08

    3(2

    7.5)

    0.49

    2 (1

    2.5)

    1.08

    3 (2

    7.5)

    5.19

    7 (1

    32) 10

    .827

    (27

    5)

    10.8

    27 (

    275)

    Max

    . 2.7

    17

    (69)

    5.866 (149)

    5.70

    9 (1

    45)

    150˚

    4.68

    5 (1

    19)

    1.14

    2 (2

    9)

    2.362 (60)

    1.772 (45)

    3.15 (80) ON1.063 (27)

    1.142 (29)2.244 (57)

    6.102(155)Terminalcover

    Insulationbarrier

    6.732 (171)

    2.244 (57)

    1.732 (44)0.276 dia (M6 or ø7)

    0.512 (13)

    2-0.

    276

    (ø7)

    R0.256 (R6.5)

    2-0.217 dia (ø5.5)

    *1

    • This product consists of a drive section and an operation section.• The operation section can be mounted either to the right or to the left on the panel depending on the mounting position of the release lever.• For the OFF lock, up to three 0.394 dia (φ10) padlocks can be used at one time

    *1 Set the height to 20mm or 30mm (0.787” or 1.181”). Adjust the lock lever depending on the set*2 In the ON position, up to two padlocks or lockout hasps up to 0.394 dia (10mm) can be

    used at one time.

    MCCB/ELCB

    MCCB/ELCB

    MCCB/ELCB

    MCCB/ELCB

    7.48 (190)

    5.512 (140)

    4.252 (108)

    2.95

    3 (7

    5)

    Volume 13

  • Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t - p r o t e c t i o n e31-27

    CompanyInformation

    SystemsOverview

    ProgrammableControllers

    Field I/O

    Software

    C-more & other HMI

    Drives

    SoftStarters

    Motors &Gearbox

    Steppers/Servos

    Motor Controls

    ProximitySensors

    Photo Sensors

    Limit Switches

    Encoders

    CurrentSensors

    PressureSensors

    TemperatureSensors

    Pushbuttons/Lights

    Process

    Relays/Timers

    Comm.

    TerminalBlocks & Wiring

    Power

    CircuitProtection

    Enclosures

    Tools

    Pneumatics

    Appendix

    ProductIndex

    Part #Index

    Volume 13

    Shunt Trips

    Shunt Trips for Fuji MCCBs – Selection GuidePart Number Price Description

    BW9FRG0 Field installable 24 VAC/VDC shunt trip for BW125 and BW250 series MCCB.Left and right side mounting. Lead wires 20AWG, 19.69” long.

    BW9FHA-R Field installable 24/48 VAC/VDC shunt trip for BW400, BW630 and BW800 series MCCB.Left side mounting only. Lead wires 20AWG, 19.69” long.

    BW9FAG0 Field installable 100/120 VAC, 100-110 VDC shunt trip for BW125 and BW250 series MCCB.Left and right side mounting. Lead wires 20AWG, 19.69” long.

    BW9FHA-A Field installable 100/240 VAC, 100-220 VDC shunt trip for BW400, BW630 and BW800 seriesMCCB.Left side mounting only. Lead wires 20AWG, 19.69” long.

    Fuji Molded Case Circuit Breakers – Accessories

    Auxiliary Contacts for Fuji MCCBs – Selection GuideBreakerType Part Number Price Description

    BW125BW250 BW9W1SG0

    Auxiliary switch for for 125A and 250A frame. Mounting left and right side

    BW400BW630BW800

    BW9W1SHA Auxiliary switch for for 400A , 630A and 800A frame. Mounting left side

    ONLY

    Ratings of Auxiliary SwitchesStandard Type

    Breaker TypeRatedThermalCurrent (A)

    Make/Break Current (A)MinimumLoad CurrentAC DC

    Voltage (V) Res. Load Ind. Load Voltage (V) Res. Load Ind. Load

    BW125,BW250, BW400BW630, BW800

    5

    24 5 5 24 4 35V DC 160 mA

    30V DC 30 mA

    48 5 5 48 2.5 1

    125 5 3 125 0.4 0.4

    250 3 2 250 0.2 0.2

    Ratings of Shunt Trips

    Breaker TypeAC DC

    Time Rating of Coil Operating Time (ms)Voltage (V) VA Voltage (V) W

    BW125, BW25024 50 24 50 Continuous

    (with 1 N.O. contact to prevent coil burnout)

    13-21100-120 50 100-110 50

    BW400,BW630, BW800

    24-48 2 24-48 2Continuous 8-20

    100-240 3 100-220 3

    Note: Allowable operating voltage AC voltage: 85% to 110% of coil rated voltageDC voltage: 75% to 125% of coil rated voltage

    Auxiliary Contacts

    BW9W1SHA shown

    BW9FRG0 shown

    The auxiliary contacts are accessory contacts for the indication of circuit breaker open-closed or tripped.

    Shunt Trip is for remote tripping (opening) of crircuit breaker.

    Operation of auxiliary switches Accessory

    Auxiiary switch

    SPDT(1)

    Handle position

    ON OFF Trip

    11/AXcL

    12/AXbL

    14/AXaL11/AXcL

    12/AXbL

    14/AXaL

    http://www.automationdirect.com/pn/BW9FHA-Rhttp://www.automationdirect.com/pn/BW9FHA-Ahttp://www.automationdirect.com/pn/BW9W1SG0http://www.automationdirect.com/pn/BW9W1SHAhttp://www.automationdirect.com/pn/BW9W1SHAhttp://www.automationdirect.com/pn/BW9FRG0http://www.automationdirect.com/pn/BW9FAG0http://www.automationdirect.com/pn/BW9FRG0

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-28Volume 13

    Fuji Molded Case Circuit Breakers – Accessories

    Replacement Lugs

    Replacement Lug Kits for Fuji MCCBs – Selection GuidePart Number Price Description

    BW9SL0CA-3 Replacement lug kit for BW125 series MCCB. 75°C. Cu onlyPackage of 3

    BW9SL0GA-3 Replacement lug kit for BW250 series up to 175A MCCB. 75°C. Cu onlyPackage of 3

    BW9SL1GA-3 Replacement lug kit for BW250 MCCB series 200A to 250A. 75°C. Cu onlyPackage of 3

    Ratings of Undervoltage Trip

    Breaker TypeAC DCVoltage (V) VA Voltage (V) W

    BW125*1BW250*1

    – – 24 5

    110 - 130 5 – –

    BW400*2BW630*2BW800*2

    24 2 24 2

    120 - 130 3 125 3

    Undervoltage Releases for Fuji MCCBs – Selection GuideBreaker Type Part Number Price DescriptionBW125, BW250 BW9RGAR Undervoltage Release 24V DC (Left side ONLY)BW125, BW250 BW9RGAT Undervoltage Release 110 to 130 VAC VAC/VDC (Left side ONLY)BW400, BW630, BW800 BW9RHA-R Undervoltage Release 24 VAC/VDC (Left side ONLY)BW400, BW630, BW800 BW9RHA-1 Undervoltage Release 120 to 130 VAC 125 VDC (Left side ONLY)

    Note: Allowable operating voltage: AC voltage: 85% to 110% of coil rated voltageDC voltage: 75% to 125% of coil rated voltage.

    *1 Reset-allowed type: When the breaker handle is in the OFF or RESET state, trippingdoes not occur, even if the undervoltage trip coil is not energized.Turning ON with the undervoltage trip coil not energized causes normal tripping.

    *2 Reset-prohibited type: When the undervoltage trip coil is not energized, reset oper-ation cannot reset the tripped breaker to the OFF state.

    Undervoltage Releases

    BW9SL0GA-3 shown

    BW9RGAR shown

    Undervoltage Release will trip the circuit breaker when connected voltage drops to lessthan 70% of undervoltage release voltage rating. It will allow the circuit breaker to close(ON) when voltage is approximately 85% of rated voltage.

    http://www.automationdirect.com/pn/BW9SL0CA-3http://www.automationdirect.com/pn/BW9SL0GA-3http://www.automationdirect.com/pn/BW9SL1GA-3http://www.automationdirect.com/pn/BW9SL0GA-3http://www.automationdirect.com/pn/BW9RHA-Rhttp://www.automationdirect.com/pn/BW9RHA-1http://www.automationdirect.com/pn/BW9RGARhttp://www.automationdirect.com/pn/BW9RGAThttp://www.automationdirect.com/pn/BW9RGAR

  • Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t - p r o t e c t i o n e31-29

    CompanyInformation

    SystemsOverview

    ProgrammableControllers

    Field I/O

    Software

    C-more & other HMI

    Drives

    SoftStarters

    Motors &Gearbox

    Steppers/Servos

    Motor Controls

    ProximitySensors

    Photo Sensors

    Limit Switches

    Encoders

    CurrentSensors

    PressureSensors

    TemperatureSensors

    Pushbuttons/Lights

    Process

    Relays/Timers

    Comm.

    TerminalBlocks & Wiring

    Power

    CircuitProtection

    Enclosures

    Tools

    Pneumatics

    Appendix

    ProductIndex

    Part #Index

    Volume 13

    Fuji Molded Case Circuit Breakers – Accessories

    Terminal CoversTerminal covers act as guards to shield theoperator from touching live terminations. Theyfit either the line or load side.

    Lockout Attachment

    Terminal Covers for Fuji MCCBs – Selection Guide

    Breaker Series Part Number Price DescriptionDimensions inch (mm)

    A B C

    BW400 BW9BTHA-L3W Gray-white Long type terminal cover for FujiMCCBs. For line side and load side. 2/pk 6.772 (172) 4.331 (110) 3.858 (98)

    BW630, BW800 BW9BTJA-L3W Gray-white Long type terminal cover for FujiMCCBs. For line side and load side. 2/pk 8.268 (210) 6.102 (155) 3.858 (98)

    Note: Gray-white short type terminal covers are provided with breakers as standard for 125 and 250 Amp frames.

    Lockout Attachments for Fuji MCCBs – Selection Guide

    Breaker Series Part Number Price Description

    BW125BW250 BW9Q1CA

    Use to lock out BW125 and BW 250 series MCCBs. Lock not included

    BW400, BW630, BW800 BW9QNHA Use to lock out BW400, BW600 and BW800 MCCBs. Lock not included.

    BW9BTHA-L3Wshown

    BW9Q1CA shown

    Dimensions of Terminal Covers: inch (mm)

    Breaker

    A C

    B

    http://www.automationdirect.com/pn/BW9BTHA-L3Whttp://www.automationdirect.com/pn/BW9BTJA-L3Whttp://www.automationdirect.com/pn/BW9BTHA-L3Whttp://www.automationdirect.com/pn/BW9Q1CAhttp://www.automationdirect.com/pn/BW9QNHAhttp://www.automationdirect.com/pn/BW9Q1CA

  • Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5e31-30Volume 13

    Maximum Wire Sizes and Tightening Torque

    Type RatedCurrent (A)Wire Size AWG or MCM (mm2)

    TighteningTorqueLugTerminal*

    BW125

    15 14 AWG (2.1mm2)

    51 lb.-in.(5.8 N-m)

    20 12 AWG (3.3mm2)30 10 AWG (5.3mm2)40 8 AWG (8.4mm2)50 8 AWG (8.4mm2)60 6 AWG (13.3mm2)70 4 AWG (21.1mm2)75 4 AWG (21.1mm2)80 4 AWG (21.1mm2)90 3 AWG (26.7mm2)100 3 AWG (26.7mm2)125 1 AWG (42.4mm2)

    BW250

    125 1 AWG (42.4mm2)

    204 lb.-in.(23 N-m)

    150 1/0 AWG (53.5mm2)175 2/0 AWG (67.4mm2)200 3/0 AWG (85.0mm2)225 4/0 AWG (107.2mm2)250 250 MCM (127mm2)

    BW400

    250 250 MCM (127mm2)385 lb.-in(43.5 N-m)

    300 350 MCM (177mm2)350 500 MCM (253mm2)

    400 3/0 AWGx2 (85.0mm2x2)282 lb-in (31.9 N-m)

    BW630500 250-500 MCMx2 275 lb.-in.

    (31.07 N-m)600 250-500 MCMx2

    BW800700 250-500 MCMx2 275 lb.-in.

    (31.07 N-m)800 3/0 AWG-300 MCMx3

    Fuji Molded Case Circuit Breakers – Wire Range Specifications

    Wiring • When connecting the wires, follow NEC (National Electric Code,

    USA) or CEC (Canadian Electrical code Part 1, Canada) instruc-tions.

    • Use copper wire rated for 75°C for connecting. UL or CSAapproved wire is recommended.

    • Tighten the wire connections adequately, as a very large elec-tromagnetic force will be generated when short circuit current isgenerated.

    • Perform additional tightening of the terminal screws periodically.

    Caution• Adhere to the number of strands of wire indicated in the

    table.• Multiconductor wire can not be connected. • Two wires cannot be connected to the lug terminal at once.• Do not solder the end of the wire.

    Allowable Wire Specifications for Lug TerminalsWire Size AWG or MCM (mm2) Number of Wire Strands

    14 to 2 (2.1 to 33.6) 71 to 4/0 (42.4 to 107.2) 19250 to 500 (127 to 250) 37

    *Note: Lug terminals are supplied as standard.

    Search�������������Save File����������������Print this PDF���������������������E-mail this PDF����������������������Molded Case Circuit Breakers OverviewFuji Molded Case Circuit Breakers – 250A FrameFuji Molded Case Circuit Breakers –250A Frame Characteristic CurvesFuji Molded Case Circuit Breakers – DimensionsFuji Molded Case Circuit Breakers –DimensionsFuji Molded Case Circuit Breakers – Products And Accessory CompatibilityFuji Molded Case Circuit Breakers – Wire Range SpecificationsFuji Molded Case Circuit Breakers –Field-mountable AccessoriesFuji Molded Case Circuit Breakers – Field-mountable AccessoriesFuji Molded Case Circuit Breakers –Field-mountable AccessoriesFuji Molded Case Circuit Breakers – Field-mountable AccessoriesFuji Molded Case Circuit Breakers –AccessoriesFuji Molded Case Circuit Breakers – AccessoriesFuji Molded Case Circuit Breakers –AccessoriesFuji Molded Case Circuit Breakers – Wire Range Specifications