    About Nexans 3

    Symbols 4

    MV underground power cables 5

    IEC MV, XLPE Insulation, CWS, SWA, PVC (3C) 6

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC (1C) 9

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC (3C) 14

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC (1C) 18

    IEC/BS MV, XLPE Insulation, CWS, SWA, PE -DEWA 23

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC (3C) 27

    http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789
  • 8/10/2019 MV power cables

    3/32

    7/28/14 - http://www.nexans.ae Page 3 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    About Nexans

    Nexans is the worldwide leader in the cable industryWith energy as the basis of its development, Nexans is a global player in the infrastructure, industry, building and LocalArea Network (LAN) markets.

    As a worldwide leader in the cable industry, it offers an extensive range of cables and cabling systems to raise industrialproductivity, improve business performance, enhance security, enrich the quality of life, and assure long-term networkreliability.

    With an industrial presence in 40 countries and commercial activities worldwide, Nexans employs 25,000 people and hadsales in 2012 of 7.2 billion euros. Nexans is listed on NYSE Euronext Paris, compartment A.

    Infrastructure

    Nexans provides complete cables and cabling solutions for power transmission and distribution. New technologies,which are environmentally-friendly, increase capacity and reduce the danger of blackouts.

    To reinforce rail safety and efficiency, we have products especially designed for the demanding railroad environment.

    And to meet diverse needs of incumbent and new telecoms operators, Nexans has customized solutions aimed at loweringcapital expenditure and operating costs.

    For the worlds busy airports, we offer cables and cabling systems for energy and communication networks, terminals,baggage handling systems, runway lights, control towers, etc.

    Industry

    Nexans offers a complete portfolio of cables and solutions for market segments as diverse as the automotive, rollingstock and aerospace industries, shipbuilding, nuclear power, oil & gas and petrochemicals, medical and windapplications, material handling and automation, created industrial Ethernet solutions to unite the office and the factoryfloor platform, and ensured the highest standards of environmental friendliness and recyclability.

    We add value through advanced technologies and durable high-performance products.

    Building

    Nexans suppliescables and network solutions for structures of all types: from small residences to public and officebuildings and big industrial complexes.

    Nexans pioneered fire-performance cables for public safety.

    From standard products to renewable energy solutions, these products contribute to the substainable buildings of the future.

    Local Area Networks

    Nexans providescopper and optical fiber cabling systems for new resource-intensive applications, like Data Centers,Security services, and Storage Area Networks.

    Nexans advanced solutions are handling core business data, protecting operations in sensitive conditions, and givingorganizations highspeed transmission and the ability to protect and retrieve vital information.

    http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789
  • 8/10/2019 MV power cables

    4/32

    7/28/14 - http://www.nexans.ae Page 4 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Symbols

    Mechanical resistance to impacts

    Bending factor when laying

    Longitudinally watertight

    Flame retardant

    Conductor flexibility

    Bending factor when installed

    Max. conductor temperature in service

    http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789
  • 8/10/2019 MV power cables

    5/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    7/28/14 - http://www.nexans.ae Page 5 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    MV underground power cables

    Our two leading types of medium-voltage cable are XLPE (cross-linked

    polyethylene) and EPR (Ethylene Propylene Rubber). The former is usedworldwide, while the latter is mainly for selected markets.

    From a design point of view, medium-voltage cables are of three types:

    single-core cable,three single-core cables laid-up,three-core cable.

    Nexans cables are custom designed to meet your high performance standards.

    http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789http://www.nexans.ae/eservice/DirectToGroup.nx?CZ=MiddleEast&language=en&groupId=-536908789
  • 8/10/2019 MV power cables

    6/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 6 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    IEC 60502-2 & Kahramaa

    Multi-core XLPE-insulated cables with PVC sheath

    Standards

    InternationalIEC 60332-1;IEC 60502-2

    NationalBS 6622; EP-MS-P4/S3-030

    Description

    Application

    These power cables are used for electricity supply in medium voltage installationsystem. They are well adapted to underground use in industrial application wherechemical and mechanical protections are needed. This group is complying withIEC and Kahramaa specs.

    Design

    1. Conductor

    Stranded bare copper class 2 acc. to IEC 60228 or equivalent

    2. Insulation

    Triple extruded Inner semi conductive layer - Cross Linked Polyethylene 'XLPE' -

    Outer semi conductive layer

    3. Metalic Screen

    Copper wire screen with open helix copper tape "105 sqmm"

    4. Inner Sheathing or Bedding

    Extruded PVC

    5. Armour

    Galvanized Steel Wire Armour "SWA"+NCWB Tape under and above the armourlayer

    6. Outer Sheath

    Polyvinyl Chloride 'PVC'

    Options :

    - Flame retardant : IEC60332-1 or equivalent.

    Installation Conditions:

    1.Air Temperature : 30 Deg.

    2.Ground Temperature : 20 Deg

    3.Soil Thermal Resistivity : 1.5 km/w

    4.Depth of lay : 0.8 m

    All dimensions have tolerance +-7 %

    Marking

    no. of cores x conductor size mm2 Cu/XLPE/SWA/PVC Voltage grade

  • 8/10/2019 MV power cables

    7/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 7 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    V Standard MADE IN QATAR QICC - Nexans Year Meters

    Custom marking available

    Characteristics

    Construction characteristics

    Conductor material Copper

    Conductor flexibility Stranded class 2

    Conductor shape Circular compacted

    Material of the inner semi-conductor Semi-conducting compound

    Insulation XLPE (Cross-linked Polyethylene)

    Material of the external semi-conductor Semi-conducting compound

    Screen Copper wire + copper tapeInner sheath PVC

    Armour type Galvanized steel wires

    Outer sheath PVC compound

    Sheath colour Red

    Mechanical characteristics

    Mechanical resistance to impacts Good

    Usage characteristics

    Flame retardant IEC 60332-1

    Bending factor when laying 15 (xD)

    Bending factor when installed 30 (xD)

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 6/11 kV Kahramaa

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23035EXCVSB09EA0 3x35 53.0 5060 0.524 172 154 0.63 0.23

    23050EXCVSB09EA0 3x50 55.0 5720 0.387 205 158 0.48 0.25

    23070EXCVSB09EA0 3x70 60.0 6798 0.268 253 194 0.36 0.29

    23095EXCVSB09EA0 3x95 64.0 8085 0.193 307 263 0.28 0.3

    23120EXCVSB09EA0 3x120 67.0 9163 0.153 352 298 0.24 0.3323150EXCVSB09EA0 3x150 70.0 10472 0.124 397 332 0.21 0.37

    23185EXCVSB09EA0 3x185 75.0 12012 0.0991 453 374 0.18 0.4

    23240EXCVSB09EA0 3x240 82.0 15433 0.0754 529 431 0.15 0.45

    23300EXCVSB09EA0 3x300 90.0 18480 0.0601 599 482 0.14 0.49

    23400EXCVSB09EA0 3x400 96.0 21769 0.047 683 541 0.12 0.54

  • 8/10/2019 MV power cables

    8/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 8 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Selling information

    Note: On request we are delivering three single core laid up cables on one drum

  • 8/10/2019 MV power cables

    9/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 9 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    IEC 60502-2 & BS 6622

    Single-core XLPE-insulated cables with PVC sheath

    Standards

    InternationalIEC 60332-1;IEC 60502-2

    NationalBS 6622

    Description

    Application

    These power cables are used for electricity supply in medium voltage installationsystem. They are well adapted to underground use in industrial application wherechemical and mechanical protections are needed.This group is complying with IEC 60502-2 or BS 6622.

    Design

    1. Conductor

    Stranded bare copper class 2 acc. to IEC 60228 or equivalent

    2. Insulation

    Triple extruded Inner semi conductive layer - Cross Linked Polyethylene 'XLPE' -

    Outer semi conductive layer

    3. Metalic Screen

    Copper tape screen

    4. Inner Sheathing or Bedding

    Extruded PVC

    5. Armour

    Aluminum Wire Armour "AWA"

    6. Outer Sheath

    Polyvinyl Chloride 'PVC'

    Options :

    - Flame retardant : 'CAT A, CAT B, CATC' to IEC60332 or equivalent.

    - Ozone resistant.

    - Oil resistant.

    - Anti termite.

    Sheathing layers can be Halogen Free Flame Retardant "HFFR", or Polyethylene

    '"PE'

    Installation Conditions:

    1.Air Temperature : 30 Deg.

    2.Ground Temperature : 20 Deg

    3.Soil Thermal Resistivity : 1.5 km/w

    4.Depth of lay : 0.8 m

  • 8/10/2019 MV power cables

    10/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 10 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    All dimensions have tolerance +-7 %

    Marking

    no. of cores x conductor size mm2 Cu/XLPE/AWA/PVC Voltage gradeStandard MADE IN QATAR QICC - Nexans Year Meters

    Custom marking available

    Characteristics

    Construction characteristics

    Conductor material Copper

    Conductor flexibility Stranded class 2

    Conductor shape Circular compactedMaterial of the inner semi-conductor Semi-conducting compound

    Insulation XLPE (Cross-linked Polyethylene)

    Material of the external semi-conductor Semi-conducting compound

    Screen Copper tape

    Inner sheath PVC

    Armour type Aluminium Wire

    Outer sheath PVC compound

    Sheath colour Black

    Dimensional characteristics

    Number of cores 1

    Mechanical characteristics

    Mechanical resistance to impacts Good

    Usage characteristics

    Flame retardant IEC 60332-1

    Bending factor when laying 15 (xD)

    Bending factor when installed 30 (xD)

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC 3.6/6 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight

    [kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating open

    air[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase[V/A.km]

    Nom.phase capacitance[F / km]

    21025CXTVAB09DD0 1x25 23.0 820 0.727 163 144 0.84 0.25

    21035CXTVAB09DD0 1x35 24.0 930 0.524 198 172 0.63 0.28

    21050CXTVAB09DD0 1x50 26.0 1070 0.387 238 203 0.84 0.31

    21070CXTVAB09DD0 1x70 28.0 1300 0.268 296 246 0.63 0.45

    21095CXTVAB09DD0 1x95 28.0 1570 0.193 361 293 0.28 0.39

  • 8/10/2019 MV power cables

    11/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 11 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    21120CXTVAB09DD0 1x120 30.0 1800 0.153 417 332 0.24 0.43

    21150CXTVAB09DD0 1x150 31.0 2130 0.124 473 366 0.21 0.47

    21185CXTVAB09DD0 1x185 33.0 2490 0.0991 543 410 0.18 0.52

    21240CXTVAB09DD0 1x240 36.0 3050 0.0754 641 470 0.15 0.56

    21300CXTVAB09DD0 1x300 40.0 3660 0.0601 735 524 0.14 0.58

    21400CXTVAB09DD0 1x400 44.0 4580 0.047 845 572 0.12 0.6

    21500CXTVAB09DD0 1x500 47.0 5750 0.0366 950 810 0.11 0.63

    21630CXTVAB09DD0 1x630 51.0 7010 0.0283 1095 910 0.1 0.75

    21800CXTVAB09DD0 1x800 56.0 8590 0.0221 1240 1012 0.09 0.84

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC 6/10 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase[V/A.km]

    Nom.phase capacitance[F / km]

    21025CXTVAB09ED0 1x25 25.0 970 0.727 163 144 0.84 0.2

    21035CXTVAB09ED0 1x35 26.0 1090 0.524 198 172 0.63 0.23

    21050CXTVAB09ED0 1x50 28.0 1250 0.387 238 203 0.84 0.25

    21070CXTVAB09ED0 1x70 29.0 1510 0.268 296 246 0.63 0.29

    21095CXTVAB09ED0 1x95 31.0 1805 0.193 361 293 0.28 0.3

    21120CXTVAB09ED0 1x120 33.0 2070 0.153 417 332 0.24 0.33

    21150CXTVAB09ED0 1x150 34.0 2450 0.124 473 366 0.21 0.37

    21185CXTVAB09ED0 1x185 36.0 2870 0.0991 543 410 0.18 0.4

    21240CXTVAB09ED0 1x240 39.0 3450 0.0754 641 470 0.15 0.45

    21300CXTVAB09ED0 1x300 42.0 4070 0.0601 735 524 0.14 0.49

    21400CXTVAB09ED0 1x400 45.0 5005 0.047 845 572 0.12 0.54

    21500CXTVAB09ED0 1x500 50.0 6340 0.0366 950 810 0.11 0.6

    21630CXTVAB09ED0 1x630 54.0 7680 0.0283 1095 910 0.1 0.7

    21800CXTVAB09ED0 1x800 58.0 9430 0.0221 1240 1012 0.09 0.85

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC 8.7/15 kV

    Nexans ref. NameNom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.20C

    [Ohm/km]

    Perm.

    currentrating open

    air[A]

    Currentrating,buried

    [A]

    Voltagedrop, singlephase

    [V/A.km]

    Nom.phase capacitance[F / km]

    21025CXTVAB09GD0 1x25 27.0 1040 0.727 163 144 0.84 0.17

    21035CXTVAB09GD0 1x35 29.0 1180 0.524 198 172 0.63 0.18

    21050CXTVAB09GD0 1x50 30.0 1340 0.387 238 203 0.84 0.2

  • 8/10/2019 MV power cables

    12/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 12 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    21070CXTVAB09GD0 1x70 32.0 1600 0.268 296 246 0.63 0.23

    21095CXTVAB09GD0 1x95 34.0 1880 0.193 361 293 0.28 0.25

    21120CXTVAB09GD0 1x120 36.0 2180 0.153 417 332 0.24 0.27

    21150CXTVAB09GD0 1x150 36.0 2550 0.124 473 366 0.21 0.29

    21185CXTVAB09GD0 1x185 38.0 2930 0.0991 543 410 0.18 0.32

    21240CXTVAB09GD0 1x240 40.0 3480 0.0754 641 470 0.15 0.35

    21300CXTVAB09GD0 1x300 43.0 4140 0.0601 735 524 0.14 0.39

    21400CXTVAB09GD0 1x400 49.0 5290 0.047 845 572 0.12 0.43

    21500CXTVAB09GD0 1x500 51.0 6330 0.0366 950 810 0.11 0.48

    21630CXTVAB09GD0 1x630 55.0 7650 0.0283 1095 910 0.1 0.53

    21800CXTVAB09GD0 1x800 60.0 9450 0.0221 1240 1012 0.09 0.65

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC 12/20 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase[V/A.km]

    Nom.phase capacitance[F / km]

    21035CXTVAB09HD0 1x35 30.0 1310 0.524 198 172 0.63 0.15

    21050CXTVAB09HD0 1x50 31.0 1470 0.387 238 203 0.84 0.17

    21070CXTVAB09HD0 1x70 33.0 1735 0.268 296 246 0.63 0.2

    21095CXTVAB09HD0 1x95 35.0 2080 0.193 361 293 0.28 0.22

    21120CXTVAB09HD0 1x120 37.0 2335 0.153 417 332 0.24 0.24

    21150CXTVAB09HD0 1x150 38.0 2730 0.124 473 366 0.21 0.26

    21185CXTVAB09HD0 1x185 40.0 3135 0.0991 543 410 0.18 0.27

    21240CXTVAB09HD0 1x240 43.0 3705 0.0754 641 470 0.15 0.3

    21300CXTVAB09HD0 1x300 46.0 4510 0.0601 735 524 0.14 0.33

    21400CXTVAB09HD0 1x400 50.0 5550 0.047 845 572 0.12 0.37

    21500CXTVAB09HD0 1x500 53.0 6650 0.0366 950 810 0.11 0.41

    21630CXTVAB09HD0 1x630 57.0 7980 0.0283 1095 910 0.1 0.46

    21800CXTVAB09HD0 1x800 62.0 9810 0.0221 1240 1012 0.09 0.54

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC 18/30 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase[V/A.km]

    Nom.phase capacitance[F / km]

    21050CXTVAB09JD0 1x50 36.0 1870 0.387 238 203 0.84 0.14

    21070CXTVAB09JD0 1x70 38.0 2050 0.268 296 246 0.63 0.15

  • 8/10/2019 MV power cables

    13/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 13 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    21095CXTVAB09JD0 1x95 40.0 2430 0.193 361 293 0.28 0.17

    21120CXTVAB09JD0 1x120 42.0 2670 0.153 417 332 0.24 0.18

    21150CXTVAB09JD0 1x150 43.0 3060 0.124 473 366 0.21 0.2

    21185CXTVAB09JD0 1x185 46.0 3690 0.0991 543 410 0.18 0.21

    21240CXTVAB09JD0 1x240 49.0 4220 0.0754 641 470 0.15 0.23

    21300CXTVAB09JD0 1x300 52.0 4950 0.0601 735 524 0.14 0.25

    21400CXTVAB09JD0 1x400 55.0 5850 0.047 845 572 0.12 0.27

    21500CXTVAB09JD0 1x500 59.0 7055 0.0366 950 810 0.11 0.3

    21630CXTVAB09JD0 1x630 62.0 8445 0.0283 1095 910 0.1 0.34

    21800CXTVAB09JD0 1x800 67.0 10170 0.0221 1240 1012 0.09 0.39

    Selling information

    Note: On request we are delivering three single core laid up cables on one drum

  • 8/10/2019 MV power cables

    14/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC (3C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 14 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    IEC 60502-2 & BS 6622

    Multi-core XLPE-insulated cables with PVC sheath

    Standards

    InternationalIEC 60332-1;IEC 60502-2

    NationalBS 6622

    Description

    Application

    These power cables are used for electricity supply in medium voltage installationsystem. They are well adapted to underground use in industrial application wherechemical and mechanical protections are needed. This group is complying withIEC 60502-2 or BS 6622.

    Design

    1. Conductor

    Stranded bare copper class 2 acc. to IEC 60228 or equivalent

    2. Insulation

    Triple extruded Inner semi conductive layer - Cross Linked Polyethylene 'XLPE' -

    Outer semi conductive layer

    3. Metalic Screen

    Copper tape screen

    4. Inner Sheathing or Bedding

    Extruded PVC

    5. Armour

    Galvanized Steel Wire Armour "SWA"

    6. Outer Sheath

    Polyvinyl Chloride 'PVC'

    Options :

    - Flame retardant : 'CAT A, CAT B, CATC' to IEC60332 or equivalent.

    - Ozone resistant.

    - Oil resistant.

    - Anti termite.

    Sheathing layers can be Halogen Free Flame Retardant "HFFR", or Polyethylene

    '"PE'

    Installation Conditions:

    1.Air Temperature : 30 Deg.

    2.Ground Temperature : 20 Deg

    3.Soil Thermal Resistivity : 1.5 km/w

    4.Depth of lay : 0.8 m

  • 8/10/2019 MV power cables

    15/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC (3C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 15 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    All dimensions have tolerance +-7 %

    Marking

    no. of cores x conductor size mm2 Cu/XLPE/SWA/PVC Voltage gradeV Standard MADE IN QATAR QICC - Nexans Year Meters

    Custom marking available

    Characteristics

    Construction characteristics

    Conductor material Copper

    Conductor flexibility Stranded class 2

    Conductor shape Circular compactedMaterial of the inner semi-conductor Semi-conducting compound

    Insulation XLPE (Cross-linked Polyethylene)

    Material of the external semi-conductor Semi-conducting compound

    Screen Copper tape

    Inner sheath PVC

    Armour type Galvanized steel wires

    Outer sheath PVC compound

    Sheath colour Black

    Mechanical characteristics

    Mechanical resistance to impacts Good

    Usage characteristics

    Flame retardant IEC 60332-1

    Bending factor when laying 15 (xD)

    Bending factor when installed 30 (xD)

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC 3.6/6 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025CXTVSB09DD0 3x25 42.0 3040 0.727 143 129 0.84 0.2523035CXTVSB09DD0 3x35 45.0 3450 0.524 172 154 0.63 0.28

    23050CXTVSB09DD0 3x50 48.0 4410 0.387 205 158 0.48 0.31

    23070CXTVSB09DD0 3x70 53.0 5330 0.268 253 194 0.36 0.45

    23095CXTVSB09DD0 3x95 56.0 6305 0.193 307 263 0.28 0.39

    23120CXTVSB09DD0 3x120 60.0 7275 0.153 352 298 0.24 0.43

    23150CXTVSB09DD0 3x150 63.0 8600 0.124 397 332 0.21 0.47

  • 8/10/2019 MV power cables

    16/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC (3C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 16 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    23185CXTVSB09DD0 3x185 67.0 9950 0.0991 453 374 0.18 0.52

    23240CXTVSB09DD0 3x240 72.0 11945 0.0754 529 431 0.15 0.56

    23300CXTVSB09DD0 3x300 83.0 15640 0.0601 599 482 0.14 0.58

    23400CXTVSB09DD0 3x400 89.0 19120 0.047 683 541 0.12 0.6

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC 6/10 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025CXTVSB09ED0 3x25 48.0 3770 0.727 143 129 0.84 0.2

    23035CXTVSB09ED0 3x35 50.0 4280 0.524 172 154 0.63 0.23

    23050CXTVSB09ED0 3x50 52.0 4840 0.387 205 158 0.48 0.25

    23070CXTVSB09ED0 3x70 57.0 5750 0.268 253 194 0.36 0.29

    23095CXTVSB09ED0 3x95 61.0 6835 0.193 307 263 0.28 0.3

    23120CXTVSB09ED0 3x120 64.0 7750 0.153 352 298 0.24 0.33

    23150CXTVSB09ED0 3x150 67.0 9140 0.124 397 332 0.21 0.37

    23185CXTVSB09ED0 3x185 71.0 10485 0.0991 453 374 0.18 0.4

    23240CXTVSB09ED0 3x240 78.0 13470 0.0754 529 431 0.15 0.45

    23300CXTVSB09ED0 3x300 86.0 16130 0.0601 599 482 0.14 0.49

    23400CXTVSB09ED0 3x400 91.0 19400 0.047 683 541 0.12 0.54

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC 8.7/15 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025CXTVSB09GD0 3x25 52.0 4330 0.727 143 129 0.84 0.17

    23035CXTVSB09GD0 3x35 55.0 4740 0.524 172 154 0.63 0.18

    23050CXTVSB09GD0 3x50 57.0 5330 0.387 205 158 0.48 0.2

    23070CXTVSB09GD0 3x70 62.0 6370 0.268 253 194 0.36 0.23

    23095CXTVSB09GD0 3x95 66.0 7415 0.193 307 263 0.28 0.25

    23120CXTVSB09GD0 3x120 68.0 8410 0.153 352 298 0.24 0.27

    23150CXTVSB09GD0 3x150 71.0 9760 0.124 397 332 0.21 0.29

    23185CXTVSB09GD0 3x185 78.0 12175 0.0991 453 374 0.18 0.32

    23240CXTVSB09GD0 3x240 83.0 14270 0.0754 529 431 0.15 0.35

    23300CXTVSB09GD0 3x300 90.0 16900 0.0601 599 482 0.14 0.39

    23400CXTVSB09GD0 3x400 96.0 20070 0.047 683 541 0.12 0.43

  • 8/10/2019 MV power cables

    17/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC (3C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 17 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC 12/20 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23035CXTVSB09HD0 3x35 59.0 5310 0.524 172 154 0.63 0.15

    23050CXTVSB09HD0 3x50 62.0 5920 0.387 205 158 0.48 0.17

    23070CXTVSB09HD0 3x70 66.0 6900 0.268 253 194 0.36 0.2

    23095CXTVSB09HD0 3x95 69.0 8020 0.193 307 263 0.28 0.22

    23120CXTVSB09HD0 3x120 73.0 8995 0.153 352 298 0.24 0.24

    23150CXTVSB09HD0 3x150 78.0 11420 0.124 397 332 0.21 0.26

    23185CXTVSB09HD0 3x185 82.0 12880 0.0991 453 374 0.18 0.27

    23240CXTVSB09HD0 3x240 86.0 14990 0.0754 529 431 0.15 0.3

    23300CXTVSB09HD0 3x300 93.0 17510 0.0601 599 482 0.14 0.33

    23400CXTVSB09HD0 3x400 100.0 20705 0.047 683 541 0.12 0.37

    IEC/BS MV, XLPE Insulation, CTS, SWA, PVC 18/30 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23050CXTVSB09JD0 3x50 74.0 8080 0.387 205 158 0.48 0.14

    23070CXTVSB09JD0 3x70 78.0 9300 0.268 253 194 0.36 0.15

    23095CXTVSB09JD0 3x95 82.0 10400 0.193 307 263 0.28 0.1723120CXTVSB09JD0 3x120 85.0 11450 0.153 352 298 0.24 0.18

    23150CXTVSB09JD0 3x150 87.0 13055 0.124 397 332 0.21 0.2

    23185CXTVSB09JD0 3x185 91.0 14545 0.0991 453 374 0.18 0.21

    23240CXTVSB09JD0 3x240 97.0 16630 0.0754 529 431 0.15 0.23

    23300CXTVSB09JD0 3x300 105.0 19300 0.0601 599 482 0.14 0.25

    23400CXTVSB09JD0 3x400 110.0 22225 0.047 683 541 0.12 0.27

    Selling information

    Note: On request we are delivering three single core laid up cables on one drum

  • 8/10/2019 MV power cables

    18/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 18 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    IEC 60502-2 & BS 6622

    Single-core XLPE-insulated cables with PVC sheath

    Standards

    InternationalIEC 60332-1;IEC 60502-2

    NationalBS 6622

    Description

    Application

    These power cables are used for electricity supply in medium voltage installationsystem. They are well adapted to underground use in industrial application wherechemical and mechanical protections are needed. This group is complying withIEC 60502-2 or BS 6622.

    Design

    1. Conductor

    Stranded bare copper class 2 acc. to IEC 60228 or equivalent

    2. Insulation

    Triple extruded Inner semi conductive layer - Cross Linked Polyethylene 'XLPE' -

    Outer semi conductive layer

    3. Metalic Screen

    Copper wire screen with open helix copper tape

    4. Inner Sheathing or Bedding

    Extruded PVC

    5. Armour

    Aluminum Wire Armour "AWA"

    6. Outer Sheath

    Polyvinyl Chloride 'PVC'

    Options :

    - Flame retardant : 'CAT A, CAT B, CATC' to IEC60332 or equivalent.

    - Ozone resistant.

    - Oil resistant.

    - Anti termite.

    Sheathing layers can be Halogen Free Flame Retardant "HFFR", or Polyethylene

    '"PE'

    Installation Conditions:

    1.Air Temperature : 30 Deg.

    2.Ground Temperature : 20 Deg

    3.Soil Thermal Resistivity : 1.5 km/w

    4.Depth of lay : 0.8 m

  • 8/10/2019 MV power cables

    19/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 19 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    All dimensions have tolerance +-7 %

    Marking

    no. of cores x conductor size mm2 Cu/XLPE/AWA/PVC Voltage gradeV Standard MADE IN QATAR QICC - Nexans Year Meters

    Custom marking available

    Characteristics

    Construction characteristics

    Conductor material Copper

    Conductor flexibility Stranded class 2

    Conductor shape Circular compactedMaterial of the inner semi-conductor Semi-conducting compound

    Insulation XLPE (Cross-linked Polyethylene)

    Material of the external semi-conductor Semi-conducting compound

    Screen Copper wire + copper tape

    Inner sheath PVC

    Armour type Aluminium Wire

    Outer sheath PVC compound

    Sheath colour Black

    Dimensional characteristics

    Number of cores 1

    Mechanical characteristics

    Mechanical resistance to impacts Good

    Usage characteristics

    Flame retardant IEC 60332-1

    Bending factor when laying 15 (xD)

    Bending factor when installed 30 (xD)

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC 3.6/6 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight

    [kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating open

    air[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase[V/A.km]

    Nom.phase capacitance[F / km]

    21025CXCVAB09DD0 1x25 24.0 926 0.727 163 144 0.84 0.278

    21035CXCVAB09DD0 1x35 25.0 1051 0.524 198 172 0.63 0.309

    21050CXCVAB09DD0 1x50 27.0 1215 0.387 238 203 0.84 0.345

    21070CXCVAB09DD0 1x70 29.0 1473 0.268 296 246 0.63 0.401

    21095CXCVAB09DD0 1x95 30.0 1777 0.193 361 293 0.28 0.447

  • 8/10/2019 MV power cables

    20/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 20 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    21120CXCVAB09DD0 1x120 32.0 2038 0.153 417 332 0.24 0.492

    21150CXCVAB09DD0 1x150 33.0 2430 0.124 473 366 0.21 0.531

    21185CXCVAB09DD0 1x185 35.0 2821 0.0991 543 410 0.18 0.585

    21240CXCVAB09DD0 1x240 38.0 3459 0.0754 641 470 0.15 0.632

    21300CXCVAB09DD0 1x300 42.0 4160 0.0601 735 524 0.14 0.652

    21400CXCVAB09DD0 1x400 46.0 5209 0.047 845 572 0.12 0.706

    21500CXCVAB09DD0 1x500 50.0 6559 0.0366 950 810 0.11 0.725

    21630CXCVAB09DD0 1x630 54.0 7950 0.0283 1095 910 0.1 0.808

    21800CXCVAB09DD0 1x800 59.0 9778 0.0221 1240 1012 0.09 0.894

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC 6/10 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase[V/A.km]

    Nom.phase capacitance[F / km]

    21025CXCVAB09ED0 1x25 26.0 1010 0.727 163 144 0.84 0.2

    21035CXCVAB09ED0 1x35 27.0 1130 0.524 198 172 0.63 0.23

    21050CXCVAB09ED0 1x50 29.0 1300 0.387 238 203 0.84 0.25

    21070CXCVAB09ED0 1x70 30.0 1570 0.268 296 246 0.63 0.29

    21095CXCVAB09ED0 1x95 32.0 1880 0.193 361 293 0.28 0.3

    21120CXCVAB09ED0 1x120 34.0 2155 0.153 417 332 0.24 0.33

    21150CXCVAB09ED0 1x150 35.0 2540 0.124 473 366 0.21 0.37

    21185CXCVAB09ED0 1x185 37.0 2990 0.0991 543 410 0.18 0.4

    21240CXCVAB09ED0 1x240 40.0 3577 0.0754 641 470 0.15 0.45

    21300CXCVAB09ED0 1x300 43.0 4240 0.0601 735 524 0.14 0.49

    21400CXCVAB09ED0 1x400 46.0 5200 0.047 845 572 0.12 0.54

    21500CXCVAB09ED0 1x500 51.0 6600 0.0366 950 810 0.11 0.6

    21630CXCVAB09ED0 1x630 55.0 8000 0.0283 1095 910 0.1 0.7

    21800CXCVAB09ED0 1x800 59.0 9810 0.0221 1240 1012 0.09 0.85

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC 8.7/15 kV

    Nexans ref. NameNom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.20C

    [Ohm/km]

    Perm.

    currentrating open

    air[A]

    Currentrating,buried

    [A]

    Voltagedrop, singlephase

    [V/A.km]

    Nom.phase capacitance[F / km]

    21025CXCVAB09GD0 1x25 28.0 1110 0.727 163 144 0.84 0.17

    21035CXCVAB09GD0 1x35 30.0 1260 0.524 198 172 0.63 0.18

    21050CXCVAB09GD0 1x50 31.0 1430 0.387 238 203 0.84 0.2

  • 8/10/2019 MV power cables

    21/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 21 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    21070CXCVAB09GD0 1x70 33.0 1710 0.268 296 246 0.63 0.23

    21095CXCVAB09GD0 1x95 35.0 2010 0.193 361 293 0.28 0.25

    21120CXCVAB09GD0 1x120 37.0 2330 0.153 417 332 0.24 0.27

    21150CXCVAB09GD0 1x150 38.0 2720 0.124 473 366 0.21 0.29

    21185CXCVAB09GD0 1x185 40.0 3130 0.0991 543 410 0.18 0.32

    21240CXCVAB09GD0 1x240 42.0 3720 0.0754 641 470 0.15 0.35

    21300CXCVAB09GD0 1x300 45.0 4420 0.0601 735 524 0.14 0.39

    21400CXCVAB09GD0 1x400 51.0 5650 0.047 845 572 0.12 0.43

    21500CXCVAB09GD0 1x500 53.0 6770 0.0366 950 810 0.11 0.48

    21630CXCVAB09GD0 1x630 57.0 8180 0.0283 1095 910 0.1 0.53

    21800CXCVAB09GD0 1x800 62.0 10100 0.0221 1240 1012 0.09 0.65

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC 12/20 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, single

    phase[V/A.km]

    Nom.phase capacitance[F / km]

    21035CXCVAB09HD0 1x35 32.0 1370 0.524 198 172 0.63 0.15

    21050CXCVAB09HD0 1x50 33.0 1550 0.387 238 203 0.84 0.17

    21070CXCVAB09HD0 1x70 35.0 1830 0.268 296 246 0.63 0.2

    21095CXCVAB09HD0 1x95 37.0 2190 0.193 361 293 0.28 0.22

    21120CXCVAB09HD0 1x120 39.0 2460 0.153 417 332 0.24 0.24

    21150CXCVAB09HD0 1x150 40.0 2870 0.124 473 366 0.21 0.26

    21185CXCVAB09HD0 1x185 42.0 3300 0.0991 543 410 0.18 0.27

    21240CXCVAB09HD0 1x240 45.0 3900 0.0754 641 470 0.15 0.3

    21300CXCVAB09HD0 1x300 48.0 4750 0.0601 735 524 0.14 0.33

    21400CXCVAB09HD0 1x400 52.0 5850 0.047 845 572 0.12 0.37

    21500CXCVAB09HD0 1x500 55.0 7000 0.0366 950 810 0.11 0.41

    21630CXCVAB09HD0 1x630 59.0 8400 0.0283 1095 910 0.1 0.46

    21800CXCVAB09HD0 1x800 64.0 10330 0.0221 1240 1012 0.09 0.54

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC 18/30 kV

    Nexans ref. NameNom. phasecapacitance

    [F / km]

    Approx.weight[kg/km]

    Max. DC Resist.Cond. 20C[Ohm/km]

    Perm. currentrating open air

    [A]

    Currentrating,buried

    [A]

    Voltage drop,single phase

    [V/A.km]

    21050CXCVAB09JD0 1x50 0.14 2000 0.387 238 203 0.84

    21070CXCVAB09JD0 1x70 0.15 2200 0.268 296 246 0.63

    21095CXCVAB09JD0 1x95 0.17 2600 0.193 361 293 0.28

  • 8/10/2019 MV power cables

    22/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, AWA, PVC (1C)

    Conductor flexibilityStranded class 2

    Mechanical resistance toimpactsGood

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factor installed30 (xD)

    7/28/14 - http://www.nexans.ae Page 22 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. NameNom. phasecapacitance

    [F / km]

    Approx.weight[kg/km]

    Max. DC Resist.Cond. 20C[Ohm/km]

    Perm. currentrating open air

    [A]

    Currentrating,buried

    [A]

    Voltage drop,single phase

    [V/A.km]

    21120CXCVAB09JD0 1x120 0.18 2850 0.153 417 332 0.24

    21150CXCVAB09JD0 1x150 0.2 3280 0.124 473 366 0.21

    21185CXCVAB09JD0 1x185 0.21 3950 0.0991 543 410 0.18

    21240CXCVAB09JD0 1x240 0.23 4520 0.0754 641 470 0.15

    21300CXCVAB09JD0 1x300 0.25 5290 0.0601 735 524 0.14

    21400CXCVAB09JD0 1x400 0.27 6270 0.047 845 572 0.12

    21500CXCVAB09JD0 1x500 0.3 7550 0.0366 950 810 0.11

    21630CXCVAB09JD0 1x630 0.34 9050 0.0283 1095 910 0.1

    21800CXCVAB09JD0 1x800 0.39 10900 0.0221 1240 1012 0.09

    Selling information

    Note: On request we are delivering three single core laid up cables on one drum

  • 8/10/2019 MV power cables

    23/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PE -DEWA

    Conductorflexibility

    Stranded class2

    Longitudinallywatertight

    Yes

    Mechanical resistanceto impacts

    Good

    Max.conductortemp.in service

    90 C

    Flameretardant

    IEC 60332-1

    Bending factorwhen laying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 23 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    IEC 60502-2 & BS 6622 & DEWA

    Multi-core XLPE-insulated cables with PVC sheath

    Standards

    InternationalIEC 60332-1;IEC 60502-2

    NationalBS 6622

    Description

    Application

    These power cables are used for electricity supply in medium voltage installationsystem. They are well adapted to underground use in industrial application wherechemical and mechanical protections are needed. This group is complying withIEC and DEWA specs.

    Design

    1. Conductor

    Stranded bare copper class 2 acc. to IEC 60228 or equivalent

    2. Insulation

    Triple extruded Inner semi conductive layer - Cross Linked Polyethylene 'XLPE' -

    Outer semi conductive layer

    3. Metalic Screen

    Copper wire screen + Swelling layer in between the screen layer + Aluminumpolymer laminated tape

    4. First Sheathing

    Extruded Polyethylene armound the core

    5. Inner Sheath or BeddingExtruded PVC

    5. Armour

    Galvanized Steel Wire Armour "SWA"

    6. Outer Sheath

    Extruded Polyethylene with outer semi conductive layer

    Installation Conditions:

    1.Air Temperature : 30 Deg.

    2.Ground Temperature : 20 Deg

    3.Soil Thermal Resistivity : 1.5 km/w

    4.Depth of lay : 0.8 m

    All dimensions have tolerance +-7 %

    Marking

    no. of cores x conductor size mm2 Cu/XLPE/SWA/PVC Voltage grade

  • 8/10/2019 MV power cables

    24/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PE -DEWA

    Conductorflexibility

    Stranded class2

    Longitudinallywatertight

    Yes

    Mechanical resistanceto impacts

    Good

    Max.conductortemp.in service

    90 C

    Flameretardant

    IEC 60332-1

    Bending factorwhen laying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 24 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    V Standard MADE IN QATAR QICC - Nexans Year Meters

    Custom marking available

    Characteristics

    Construction characteristics

    Conductor material Copper

    Conductor flexibility Stranded class 2

    Conductor shape Circular compacted

    Material of the inner semi-conductor Semi-conducting compound

    Insulation XLPE (Cross-linked Polyethylene)

    Material of the external semi-conductor Semi-conducting compound

    Screen Copper wireLongitudinally watertight Yes

    Inner sheath PVC

    Armour type Galvanized steel wires

    Outer sheath Polyethylene

    Sheath colour Black

    Dimensional characteristics

    Number of cores 3

    Mechanical characteristics

    Mechanical resistance to impacts Good

    Usage characteristics

    Max. conductor temperature in service 90 C

    Flame retardant IEC 60332-1

    Bending factor when laying 15 (xD)

    Bending factor when installed 30 (xD)

    Short-circuit max. conductor temperature 250 C

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 3.6/6 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair

    [A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025KXCVSM00DZ0 3x25 48.0 3370 0.727 143 129 0.84 0.25

    23035KXCVSM00DZ0 3x35 51.0 3810 0.524 172 154 0.63 0.28

    23050KXCVSM00DZ0 3x50 55.0 4840 0.387 205 158 0.48 0.31

    23070KXCVSM00DZ0 3x70 60.0 5830 0.268 253 194 0.36 0.45

    23095KXCVSM00DZ0 3x95 63.0 6880 0.193 307 263 0.28 0.39

    23120KXCVSM00DZ0 3x120 67.0 7920 0.153 352 298 0.24 0.43

  • 8/10/2019 MV power cables

    25/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PE -DEWA

    Conductorflexibility

    Stranded class2

    Longitudinallywatertight

    Yes

    Mechanical resistanceto impacts

    Good

    Max.conductortemp.in service

    90 C

    Flameretardant

    IEC 60332-1

    Bending factorwhen laying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 25 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    23150KXCVSM00DZ0 3x150 70.0 9070 0.124 397 332 0.21 0.47

    23185KXCVSM00DZ0 3x185 74.0 10465 0.0991 453 374 0.18 0.52

    23240KXCVSM00DZ0 3x240 80.0 12545 0.0754 529 431 0.15 0.56

    23300KXCVSM00DZ0 3x300 91.0 16390 0.0601 599 482 0.14 0.58

    23400KXCVSM00DZ0 3x400 98.0 19570 0.047 683 541 0.12 0.6

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 6/10 kV

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight

    [kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating open

    air[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    23025KXCVSM00EZ0 3x25 54.0 4130 0.727 143 129 0.84 0.2

    23035KXCVSM00EZ0 3x35 57.0 4700 0.524 172 154 0.63 0.23

    23050KXCVSM00EZ0 3x50 59.0 5300 0.387 205 158 0.48 0.25

    23070KXCVSM00EZ0 3x70 64.0 6280 0.268 253 194 0.36 0.29

    23095KXCVSM00EZ0 3x95 68.0 7450 0.193 307 263 0.28 0.3

    23120KXCVSM00EZ0 3x120 71.0 8430 0.153 352 298 0.24 0.33

    23150KXCVSM00EZ0 3x150 74.0 9620 0.124 397 332 0.21 0.37

    23185KXCVSM00EZ0 3x185 79.0 11020 0.0991 453 374 0.18 0.4

    23240KXCVSM00EZ0 3x240 86.0 14130 0.0754 529 431 0.15 0.45

    23300KXCVSM00EZ0 3x300 94.0 16900 0.0601 599 482 0.14 0.49

    23400KXCVSM00EZ0 3x400 100.0 19890 0.047 683 541 0.12 0.54

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 8.7/15 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025KXCVSM00GZ0 3x25 59.0 4750 0.727 143 129 0.84 0.17

    23035KXCVSM00GZ0 3x35 62.0 5200 0.524 172 154 0.63 0.18

    23050KXCVSM00GZ0 3x50 64.0 5830 0.387 205 158 0.48 0.2

    23070KXCVSM00GZ0 3x70 69.0 6950 0.268 253 194 0.36 0.23

    23095KXCVSM00GZ0 3x95 73.0 8070 0.193 307 263 0.28 0.25

    23120KXCVSM00GZ0 3x120 76.0 9130 0.153 352 298 0.24 0.27

    23150KXCVSM00GZ0 3x150 79.0 10260 0.124 397 332 0.21 0.29

    23185KXCVSM00GZ0 3x185 86.0 12780 0.0991 453 374 0.18 0.32

    23240KXCVSM00GZ0 3x240 91.0 14950 0.0754 529 431 0.15 0.35

    23300KXCVSM00GZ0 3x300 99.0 17700 0.0601 599 482 0.14 0.39

  • 8/10/2019 MV power cables

    26/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PE -DEWA

    Conductorflexibility

    Stranded class2

    Longitudinallywatertight

    Yes

    Mechanical resistanceto impacts

    Good

    Max.conductortemp.in service

    90 C

    Flameretardant

    IEC 60332-1

    Bending factorwhen laying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 26 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    23400KXCVSM00GZ0 3x400 105.0 20580 0.047 683 541 0.12 0.43

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 12/20 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23035KXCVSM00HZ0 3x35 66.0 5810 0.524 172 154 0.63 0.15

    23050KXCVSM00HZ0 3x50 69.0 6460 0.387 205 158 0.48 0.17

    23070KXCVSM00HZ0 3x70 73.0 7515 0.268 253 194 0.36 0.2

    23095KXCVSM00HZ0 3x95 77.0 8720 0.193 307 263 0.28 0.22

    23120KXCVSM00HZ0 3x120 81.0 9770 0.153 352 298 0.24 0.24

    23150KXCVSM00HZ0 3x150 86.0 11995 0.124 397 332 0.21 0.26

    23185KXCVSM00HZ0 3x185 90.0 13515 0.0991 453 374 0.18 0.27

    23240KXCVSM00HZ0 3x240 95.0 15710 0.0754 529 431 0.15 0.3

    23300KXCVSM00HZ0 3x300 102.0 18340 0.0601 599 482 0.14 0.33

    23400KXCVSM00HZ0 3x400 109.0 21230 0.047 683 541 0.12 0.37

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 18/30 kV

    Nexans ref. Name

    Nom.

    outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DC

    Resist. Cond.20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Current

    rating,buried

    [A]

    Voltage

    drop, 3conductors

    [V/A.km]

    Nom.

    phase capacitance[F / km]

    23050KXCVSM00JZ0 3x50 82.0 8780 0.387 205 158 0.48 0.14

    23070KXCVSM00JZ0 3x70 86.0 10100 0.268 253 194 0.36 0.15

    23095KXCVSM00JZ0 3x95 90.0 11280 0.193 307 263 0.28 0.17

    23120KXCVSM00JZ0 3x120 93.0 12400 0.153 352 298 0.24 0.18

    23150KXCVSM00JZ0 3x150 96.0 13700 0.124 397 332 0.21 0.2

    23185KXCVSM00JZ0 3x185 100.0 15250 0.0991 453 374 0.18 0.21

    23240KXCVSM00JZ0 3x240 106.0 17420 0.0754 529 431 0.15 0.23

    23300KXCVSM00JZ0 3x300 114.0 19930 0.0601 599 482 0.14 0.25

    Selling information

    Note: On request we are delivering three single core laid up cables on one drum

  • 8/10/2019 MV power cables

    27/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductorflexibility

    Stranded class 2

    Mechanical resistance toimpactsGood

    Max.conductor temp.inservice90 C

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 27 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    IEC 60502-2 & BS 6622

    Multi-core XLPE-insulated cables with PVC sheath

    Standards

    InternationalIEC 60332-1;IEC 60502-2

    NationalBS 6622

    Description

    Application

    These power cables are used for electricity supply in medium voltage installationsystem. They are well adapted to underground use in industrial application wherechemical and mechanical protections are needed. This group is complying withIEC 60502-2 or BS 6622.

    Design

    1. Conductor

    Stranded bare copper class 2 acc. to IEC 60228 or equivalent

    2. Insulation

    Triple extruded Inner semi conductive layer - Cross Linked Polyethylene 'XLPE' -

    Outer semi conductive layer

    3. Metalic Screen

    Copper wire screen with open helix copper tape

    4. Inner Sheathing or Bedding

    Extruded PVC

    5. Armour

    Galvanized Steel Wire Armour "SWA"

    6. Outer Sheath

    Polyvinyl Chloride 'PVC'

    Options :

    - Flame retardant : 'CAT A, CAT B, CATC' to IEC60332 or equivalent.

    - Ozone resistant.

    - Oil resistant.

    - Anti termite.

    Sheathing layers can be Halogen Free Flame Retardant "HFFR", or Polyethylene

    '"PE'

    Installation Conditions:

    1.Air Temperature : 30 Deg.

    2.Ground Temperature : 20 Deg

    3.Soil Thermal Resistivity : 1.5 km/w

    4.Depth of lay : 0.8 m

  • 8/10/2019 MV power cables

    28/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductorflexibility

    Stranded class 2

    Mechanical resistance toimpactsGood

    Max.conductor temp.inservice90 C

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 28 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    All dimensions have tolerance +-7 %

    Marking

    no. of cores x conductor size mm2 Cu/XLPE/SWA/PVC Voltage gradeV Standard MADE IN QATAR QICC - Nexans Year Meters

    Custom marking available

    Characteristics

    Construction characteristics

    Conductor material Copper

    Conductor flexibility Stranded class 2

    Conductor shape Circular compactedMaterial of the inner semi-conductor Semi-conducting compound

    Insulation XLPE (Cross-linked Polyethylene)

    Material of the external semi-conductor Semi-conducting compound

    Screen Copper wire + copper tape

    Inner sheath PVC

    Armour type Galvanized steel wires

    Outer sheath PVC compound

    Sheath colour Black

    Dimensional characteristics

    Number of cores 1

    Mechanical characteristics

    Mechanical resistance to impacts Good

    Usage characteristics

    Max. conductor temperature in service 90 C

    Flame retardant IEC 60332-1

    Bending factor when laying 15 (xD)

    Bending factor when installed 30 (xD)

    Short-circuit max. conductor temperature 250 C

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 3.6/6 kV

    Nexans ref. NameNom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025CXCVSB09DD0 3x25 44.0 3270 0.727 143 129 0.84 0.25

    23035CXCVSB09DD0 3x35 47.0 3710 0.524 172 154 0.63 0.28

    23050CXCVSB09DD0 3x50 51.0 4740 0.387 205 158 0.48 0.31

  • 8/10/2019 MV power cables

    29/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductorflexibility

    Stranded class 2

    Mechanical resistance toimpactsGood

    Max.conductor temp.inservice90 C

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 29 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    23070CXCVSB09DD0 3x70 56.0 5730 0.268 253 194 0.36 0.45

    23095CXCVSB09DD0 3x95 59.0 6780 0.193 307 263 0.28 0.39

    23120CXCVSB09DD0 3x120 63.0 7820 0.153 352 298 0.24 0.43

    23150CXCVSB09DD0 3x150 66.0 8970 0.124 397 332 0.21 0.47

    23185CXCVSB09DD0 3x185 70.0 10365 0.0991 453 374 0.18 0.52

    23240CXCVSB09DD0 3x240 76.0 12445 0.0754 529 431 0.15 0.56

    23300CXCVSB09DD0 3x300 87.0 16290 0.0601 599 482 0.14 0.58

    23400CXCVSB09DD0 3x400 94.0 19470 0.047 683 541 0.12 0.6

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 6/10 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025CXCVSB09ED0 3x25 50.0 4030 0.727 143 129 0.84 0.2

    23035CXCVSB09ED0 3x35 53.0 4600 0.524 172 154 0.63 0.23

    23050CXCVSB09ED0 3x50 55.0 5200 0.387 205 158 0.48 0.25

    23070CXCVSB09ED0 3x70 60.0 6180 0.268 253 194 0.36 0.29

    23095CXCVSB09ED0 3x95 64.0 7350 0.193 307 263 0.28 0.3

    23120CXCVSB09ED0 3x120 67.0 8330 0.153 352 298 0.24 0.33

    23150CXCVSB09ED0 3x150 70.0 9520 0.124 397 332 0.21 0.37

    23185CXCVSB09ED0 3x185 75.0 10920 0.0991 453 374 0.18 0.4

    23240CXCVSB09ED0 3x240 82.0 14030 0.0754 529 431 0.15 0.45

    23300CXCVSB09ED0 3x300 90.0 16800 0.0601 599 482 0.14 0.49

    23400CXCVSB09ED0 3x400 96.0 19790 0.047 683 541 0.12 0.54

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 8.7/15 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23025CXCVSB09ED0 3x25 50.0 4030 0.727 143 129 0.84 0.2

    23035CXCVSB09ED0 3x35 53.0 4600 0.524 172 154 0.63 0.23

    23050CXCVSB09ED0 3x50 55.0 5200 0.387 205 158 0.48 0.25

    23070CXCVSB09ED0 3x70 60.0 6180 0.268 253 194 0.36 0.29

    23095CXCVSB09ED0 3x95 64.0 7350 0.193 307 263 0.28 0.3

    23120CXCVSB09ED0 3x120 67.0 8330 0.153 352 298 0.24 0.33

    23150CXCVSB09ED0 3x150 70.0 9520 0.124 397 332 0.21 0.37

  • 8/10/2019 MV power cables

    30/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductorflexibility

    Stranded class 2

    Mechanical resistance toimpactsGood

    Max.conductor temp.inservice90 C

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 30 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Nexans ref. Name

    Nom.outerdiam.

    [mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C

    [Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors

    [V/A.km]

    Nom.phase capacitance

    [F / km]

    23185CXCVSB09ED0 3x185 75.0 10920 0.0991 453 374 0.18 0.4

    23240CXCVSB09ED0 3x240 82.0 14030 0.0754 529 431 0.15 0.45

    23300CXCVSB09ED0 3x300 90.0 16800 0.0601 599 482 0.14 0.49

    23400CXCVSB09ED0 3x400 96.0 19790 0.047 683 541 0.12 0.54

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 12/20 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23035CXCVSB09HD0 3x35 62.0 5710 0.524 172 154 0.63 0.15

    23050CXCVSB09HD0 3x50 65.0 6360 0.387 205 158 0.48 0.17

    23070CXCVSB09HD0 3x70 69.0 7415 0.268 253 194 0.36 0.2

    23095CXCVSB09HD0 3x95 73.0 8620 0.193 307 263 0.28 0.22

    23120CXCVSB09HD0 3x120 77.0 9670 0.153 352 298 0.24 0.24

    23150CXCVSB09HD0 3x150 82.0 11895 0.124 397 332 0.21 0.26

    23185CXCVSB09HD0 3x185 86.0 13415 0.0991 453 374 0.18 0.27

    23240CXCVSB09HD0 3x240 91.0 15610 0.0754 529 431 0.15 0.3

    23300CXCVSB09HD0 3x300 98.0 18240 0.0601 599 482 0.14 0.33

    23400CXCVSB09HD0 3x400 105.0 21130 0.047 683 541 0.12 0.37

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC 18/30 kV

    Nexans ref. Name

    Nom.outerdiam.[mm]

    Approx.weight[kg/km]

    Max. DCResist. Cond.

    20C[Ohm/km]

    Perm.current

    rating openair[A]

    Currentrating,buried

    [A]

    Voltagedrop, 3

    conductors[V/A.km]

    Nom.phase capacitance[F / km]

    23050CXCVSB09JD0 3x50 78.0 8680 0.387 205 158 0.48 0.14

    23070CXCVSB09JD0 3x70 82.0 10000 0.268 253 194 0.36 0.15

    23095CXCVSB09JD0 3x95 86.0 11180 0.193 307 263 0.28 0.17

    23120CXCVSB09JD0 3x120 89.0 12300 0.153 352 298 0.24 0.18

    23150CXCVSB09JD0 3x150 92.0 13600 0.124 397 332 0.21 0.2

    23185CXCVSB09JD0 3x185 96.0 15150 0.0991 453 374 0.18 0.21

    23240CXCVSB09JD0 3x240 102.0 17320 0.0754 529 431 0.15 0.23

    23300CXCVSB09JD0 3x300 110.0 19830 0.0601 599 482 0.14 0.25

    23400CXCVSB09JD0 3x400 116.0 22680 0.047 683 541 0.12 0.27

  • 8/10/2019 MV power cables

    31/32

    ContactNexans QatarPhone: + 974 4467 [email protected]

    IEC/BS MV, XLPE Insulation, CWS, SWA, PVC (3C)

    Conductorflexibility

    Stranded class 2

    Mechanical resistance toimpactsGood

    Max.conductor temp.inservice90 C

    Flame retardantIEC 60332-1

    Bending factor whenlaying

    15 (xD)

    Bending factorinstalled30 (xD)

    7/28/14 - http://www.nexans.ae Page 31 / 32

    All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation ofNexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

    Selling information

    Note: On request we are delivering three single core laid up cables on one drum

  • 8/10/2019 MV power cables

    32/32

    Global expert in cables and cabling systems

    Distributed by :