NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements

Upload: hatram

Post on 21-Apr-2018

306 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems

Safe energy distribution that meets the highest industrial requirements

Page 2: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

NATUS systems offer you high per-sonal and operating safety, secureengineering, easy operation andhigh efficiency through low life-cycle costs. Take our word for it!Our engineers give you competentsupport and advice and see yourproject through from design all theway to commissioning.

ApplicationPower plants, transformer substati-ons and distribution systems andindustrial operations such as:◆ mining industry◆ iron and steel works◆ automobile industry◆ chemical works◆ petrochemical plants◆ paper plants◆ cement industry◆ waste disposal

The switchgearsNATUS switchgear systems are air-insulated, tested for resistanceto internal arc faults and are metal-enclosed with a fourfold compart-ment.

NATUS switchgear systems aredeveloped and manufactured in our factories in Trier and complywith the highest quality require-ments. They are factory-assem-bled and type-tested in accordancewith current standards and speci-fications.

Upon request, we can also deliverdifferent makes of switching devi-ces as well as innovative technicalsolutions.

NATUS switchgear systems standapart because of their minimal use of insulant volumes, use of

high-quality standard components,easy operation and utmost perso-nal safety.

NATUS switchgear systems haveproven themselves thousandfoldworldwide.

The standardsConstruction of the switchgears asper IEC 62271-200 / VDE 0671 part200. Tested for resistance to inter-nal arc faults IAC AFLR as per IEC62271-200 / VDE 0671 part 200and IEC 60298 App. AA, criteria 1–6, earthquake testing in accor-dance with UBC 1997, zone 4.

NATUS medium voltage switch-gears are standardly performed inaccordance to availability classesLSC2B as per IEC 62271-200. Thepartition class can either be PM orPI, depending on the design.

NATUS Medium Voltage Switchgears: utmost personal safety, optimal availability

NATUS switchgear systems – your advantages

◆ minimal use of insulant volumes◆ use of standard components with

the highest quality◆ easy operation◆ utmost personal safety

2

Page 3: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

Compact, type-tested switch-gears for indoor installation inaccordance with IEC 62271-200 /VDE 0671 part 200

◆ four individually metal-clad com-partments for: the main busbar,the switching device, the cableconnection and low voltage devices

◆ arc safe◆ different panel widths: 1000 mm,

800 mm, 650 mm, 500 mm◆ pressure is released upward in

all compartments◆ optional: delivery with a tested

pressure release duct

High personal and operatingsafety◆ all electrical and mechanical ope-

rating procedures take placewhen the enclosure is closed

◆ maximized operating safetyowing to serial production, com-plete mechanical interlockingsystem

◆ shutters automatically protectthe isolating contacts when theunit is withdrawn

◆ high availability resulting fromthe quick exchange of the with-drawable units by means of theuniversal trolley

◆ make-proof earthing switch◆ optional: motor operated with-

drawable unit and earthingswitch

Durable and geared for the future◆ panels are air-insulated and use

a minimum amount of insulantvolumes

◆ ideal assembly is possible due totechnical and economical factors

◆ assembly of state-of-the-art, lowmaintenance vacuum- or SF6-switching devices by renowned,leading manufacturers

◆ one can obtain spare parts easilyby virtue of the use of standardinsulators, standard instrumenttransformers, standard switchingdevices and standard coppersections

Highest quality requirements ◆ state-of-the-art manufacturing

techniques thanks to a high pre-cision laser cutting system whichguarantees perfect dimensionalaccuracy

◆ distortion resistant cubicle framemade of top quality galvalumedsheet steel that is bolted toge-ther

◆ internal arc resistant doublesheet steel partitions betweenpanels

◆ busbar partitioning from panel topanel

◆ electrostatic powder coating ofthe front door and side panels

◆ engineering and manufacturing in accordance with the qualitymanagement system EN ISO 9001

Draw out Type Medium Voltage Switchgears NES / NES-H

NATUS – Industrial Solution Systems

SWITCH

GEARS

SERVICES

SOLUTIONS

AUTOMATION

Demanding customers across the world have

put their faith in NATUS switchgear systems,

and thus also in the quality and safety of our

solutions.

Type of protection as per IEC60259 / VDE 0470 part 1◆ standard make of the enclosure:

IP3XD◆ further values upon request

Operating conditionsThe standard make of our switch-gears are designed for the following:◆ ambient temperature:

maximum temperature + 40 °C24-hour mean + 35 °Cminimum temperature – 5 °C

◆ installation altitude maximum 1000 m above sea level

◆ humidity24-hour mean 95 %

3

Page 4: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

The switchgear for multifunctional use◆ draw-out type switchgears for the indoor installation, type-tested, factory-

assembled, air-insulated, metal-enclosed with a fourfold compartment◆ compact panel for contactor feeder that is 500 mm wide ◆ application as a single bus system or as a duplex system◆ optional: motor operated withdrawable units and earthing switches

The following variations are possible for the conduction of hot gases that result from arc faults:

- deflector plate- arc absorber- pressure release duct

Medium Voltage Switchgear NES:

L3

L2

L1

NATUS switchgear systems – safe and versatile

◆ type, arc fault and earthquake tested◆ metal-enclosed and air-insulated◆ draw-out type◆ single and double busbar system

Technical data: NESRated values up torated voltage 12 kVrated power-frequency withstand voltage 28 kVrated lightning impulse withstand voltage 75 kVrated busbar current 2,500 Arated short-time withstand current 40 kArated peak withstand current 100 kArated short-circuit duration 3 sinternal arc fault test 1 s** 40 kA

Dimensionsrated branch current up to: 2,500 2,000 1,100 350 Acubicle width 1,000 800 650 500 mmcubicle depth* 1,300 1,300 1,300 1,300 mmcubicle height 2,300 up to 2,500 mm

incl. control compartment H = 600 up to 800 mm* plus 92mm for front door and back wall** tested contactor panel 40 kA / 0.1sFurther values upon request

4

Page 5: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

NATUS – Industrial Solution Systems

The high-performance switchgear that meets the highest requirements◆ draw-out type switchgear system for the indoor installation, type-tested, factory-

assembled, air-insulated, metal-enclosed with a fourfold compartment◆ application as a single bus system or as a duplex system◆ optional: motor operated withdrawable units and earthing switches

The following variations are possible for the conduction of hot gases that resultfrom arc faults:

- deflector plate- pressure release duct

NATUS switchgear systems – best customer services

◆ our engineers advise you competently◆ they assist you and your project from design

right through to commissioning

L1 L2

L3

Medium Voltage Switchgear NES-H:

Technical data: NES-HRated values up to up torated voltage 12 24 kVrated power-frequency withstand voltage 28 50 kVrated lightning impulse withstand voltage 75 125 kVrated busbar current 4,000 2,500 Arated short-time withstand current 50 31.5 kArated peak withstand current 125 80 kArated short-circuit duration 3 3 sinternal arc fault test 1 s 50 31.5 kA

Dimensionsrated voltage 24 12 12 12 kVrated branch current up to:(natural / air cooled) 2,000 2,900 2,500 350 Arated branch current up to:(forced ventilation) – 3,800 3,300 – Acubicle width** 1,000 1,000 800 2x500 mmcubicle depth* 1,700 1,700 1,700 1,700 mmcubicle height 2,300 up to 2,500 mm

incl. control compartment H = 600 up to 800 mm

* plus 77mm for front door and back wall** 2x500mm = contactor panel with a maximum of 2 outgoing feeders Further values upon request

5

Page 6: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

The switchgear that meets high-current requirements ◆ draw-out type switchgear system for the indoor installation, type-tested, factory-

assembled, air-insulated, metal-enclosed with a fourfold compartment◆ circuit-breaker in truck types starting at 3.150 A◆ application as a single bus system or as a duplex system◆ optional: motor operated withdrawable units and earthing switches

The following variations are possible for the conduction of hot gases that resultfrom arc faults:

- deflector plate- pressure release duct

Medium Voltage Switchgear NES-H18:

NATUS switchgear systems – well proven worldwide

◆ well engineered technology◆ high profitability◆ low life-cycle costs

Technical data: NES-H18Rated values up to up torated voltage 12 17.5 kVrated power-frequency withstand voltage 28 38 kVrated lightning impulse withstand voltage 75 95 kVrated busbar current 4,000 4,000 Arated short-time withstand current 55 50 kArated peak withstand current 137.5 125 kArated short-circuit duration 3 3 sinternal arc fault test 1 s 50 50 kA

Dimensionsrated voltage 17.5 17.5 17.5 kVrated voltage switchgear 3,150 4,000 —- Arated branch current up to:(natural- / air cooled) 3,150 3,400 2,500 Arated branch current up to:(forced ventilation) 4,000 4,200 3,300 Acubicle width 1,000 1,000 800 mmcubicle depth* 1,800 1,800 1,800 mmcubicle height 2,300 up to 2,500 mm

Incl. control compartment H = 600 up to 800 mm* plus 77mm for front door and back wall Further values upon request

L1 L2

L3

6

Page 7: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

NATUS – Industrial Solution Systems

Busbar compartmentThe busbars are made of standardflat copper with rounded edges.The main busbars are screwedtogether panel-for-panel and aresegregated by cast-resin bushingspanel-for-panel. The electricstrength of the main busbar is guaranteed without additional insulation.

Circuit breaker compartmentThe withdrawable units can beequipped with a diverse amount ofcustomer specific switching devi-ces (vacuum, SF6). The operationof the withdrawble unit can only bedone behind closed doors. Mecha-nical interlocks prevent malopera-tion. When removing the withdraw-able unit, all live parts are automa-tically protected by metal shutters.

Cable terminal compartmentThe generously sized cable terminalcompartment is easily accessiblethrough its explosion proof frontdoor. The panel’s entire depth canbe used for the installation of instru-ment transformers, earthing swit-

ches, surge arresters and cablelooms for single-core cables up to 5 x 500 mm2 (NES) or 7 x 500 mm2

(NES-H).

Low voltage compartmentThe low voltage compartment pro-vides adequate space for all thenecessary secondary technicalcomponents and can be delivered

with the following heights: 600 mm,700 mm, 800mm. The withdra-wable unit’s position switch, forexample, is installed here for easyaccessibility. This means that onecan access it without coming incontact with the high voltage secti-ons. The distortion resistant door isadequate for the protective relays,measuring instruments, controllersand signalling units.

Pressure reliefPressure is generally releasedupward in our switchgear panelsand not in the cable basement. Werecommend that you use a pres-sure release duct for the targetedrelease in the switchgear buildingbecause of its utmost personalsafety. The hot gases that resultfrom arc faults can be conductedout of the switchgear buildingthrough the duct.

Depending on the type of switch-gear panel, you can alternatively use an arc absorber or a deflectorplate to release the pressure.

D

C

B

A

The compartments in accordance with the standard availability class LSC2B

Arc-fault tested pressure

release ducts fulfil the highest

safety requirements

A

B

D

C

7

Page 8: NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear ...€¦ · NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems ... application as a single bus system or as

NATUS GmbH & Co.KGIndustriegelände NordLoebstraße 12, 54292 Trier, GermanyPostfach 2960, 54219 Trier, GermanyTel.: +49 (0)651-1449-0, Fax: +49 (0)651-21600E-Mail: [email protected], www.natus.de

SWITCH

GEARS

SERVICES

SOLUTIONS

AUTOMATION

SWITCHGEARS For decades we have been setting standards in innovation,safety and quality in our core business of switchgear systems.

SERVICES Our comprehensive service package leaves no wish unanswered– we do everything from assembly to maintenance and a 24-hour emergencyservice, right through to a comprehensive spare parts service.

AUTOMATION We are constantly developing reliable solutions that are specifically tailored to customers’ needs in the field of automation and control systems.

SOLUTIONS We combine the products of selected partners with NATUS services and a comprehensive project management to come up with professional solutions.

NATUS products and services

Electrotechnical Solutions under one Roof