power www.ppi.ph pazifik Manufacturedby: Medium Voltage Switchgear and Switches MV Switchgear up to 24 kV, 1250 A SF 6 -Insulated, Modular Design BO-GAE1250/1 Maintenance-free concept with SF 6 -pressurised containers as a hermetically sealed pressure system Minimum space requirement High level of functional reliability Great operator safety Up to four-fold cable connection systems in circuit-breaker sections Metal-encapsulated plug-in voltage transformer can be retrofitted optionally on the busbar side or on the outgoing side on circuit-breaker sections Conventional current transformers can be easily exchanged together outside of the SF 6 -pressurised container

Upload: others

Post on 22-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

  • powerwww.ppi.ph

    pazifik

    Manufactured by:

    Medium Voltage Switchgear and SwitchesMV Switchgear up to 24 kV, 1250 ASF6-Insulated, Modular Design

    BO-GAE1250/1

    • Maintenance-freeconceptwithSF6-pressurisedcontainersasahermeticallysealedpressuresystem

    • Minimumspacerequirement

    • Highleveloffunctionalreliability

    • Greatoperatorsafety

    • Uptofour-foldcableconnectionsystemsincircuit-breakersections

    • Metal-encapsulatedplug-involtagetransformercanberetrofittedoptionallyonthebusbarsideorontheoutgoingsideoncircuit-breakersections

    • ConventionalcurrenttransformerscanbeeasilyexchangedtogetheroutsideoftheSF6-pressurisedcontainer

  • General Information/DescriptionBenefits of SF6-insulated, metal-encapsulated, modular switchgear assemblies

    • Largelyclimateresistant• Maintenance-free conceptwith SF6-pressurised containers as a

    hermeticallysealedpressuresystem• Minimumspacerequirement• Comprehensivepersonnelprotection• Highleveloffunctionalreliability• Greatreliabilityofsupply• Greatoperatorsafety• Greatversatilityduetoavailabilityofcircuit-breaker,isolatorand

    load-breakswitchsections• Straightforwardside-by-sidefittingofsectionsbymeansofinner

    coneplug-insystemsforthebusbarconnection• Uptofour-foldcableconnectionsystemsincircuit-breakersections• Metal-encapsulatedplug-involtagetransformercanberetrofitted

    – Optionally on the busbar side or on the outgoing side oncircuit-breakersections

    – Optionallyonthebusbarsideatriserpanels– Optionallywithisolating/earthingswitch

    • Conventional current transformers can be easily exchangedtogetheroutsideoftheSF6-pressurisedcontainer

    Features

    The switchgear assemblies are type-tested, factory-built, metal-encapsulated SF6-insulated switchgear installations made up ofsections.

    Applications

    Suitableforuseinsubstationsandswitchingstations,andalsoasloadcenters:

    • In electricity supply company networks, substations, maindistribution substations, combined heating & power stations,cavernsystems,etc.

    • Inindustrialnetworkswithmedium-voltagenetworkinfrastructure– Primary-levelmaindistributionboard/incomers/feeders,– Powerstations(ownproduction,combinalpowerstation),– Nodedistributionboards,

    • In buildings with medium-voltage network infrastructure, e.g.in railway stations, department stores, hospitals, barracks, lawcourts,administrativebuildings,etc.– Primary-levelmaindistributionboard/incomers/feeders,– Powerstations(ownproduction/stand-bypowersupply),

    • In environmental projects with medium-voltage networkinfrastructure, e.g. in wind energy, biogas, sludge digestion,resource-recycling/-recoveryplant,etc.– Primary-levelmaindistributionboards,– Combinedheating&powerstations.

    Voltage transformer

    Plug-in, metal-encapsulated, single-pole voltage transformers to IEC60044-2andVDE0414Part2areoptionallyflangeddirectlyabovethegas tank to the bus-sectionalizer panelswith vacuum circuit-breaker-1LSV(G)-/6/, the riser sections -1HT-/6/and thecable riser sections-1AT-/6/.

    Theyareoptionallyswitchedasbusbarvoltagetransformersoroutgoervoltagetransformers.

    AnupstreamisolatingorearthingswitchinSF6isoptionallyavailable(with outgoing voltage transformers it is standard). This isolating orearthingswitchisoperatedviaadrivefeaturethatislocatedbehindtheinterlockedfrontcoverofthecableterminationarea.Thedrivefeaturemustbeequippedwithapadlock.

    Thevoltagetransformerscanbeoptionallysuppliedwithcertifiableorcalibratedmeasuringcore.

    Front view

    Front view with open front cover

  • Current transformer

    Inoutgoingpanelsandbussectionalizerpanelswithcircuitbreakersand thosewith load-break switches, low-voltage ringandspectacle-corecurrenttransformerstoIEC600441-1andVDE0414Part1arelaidaroundtheextendedexternalconebushings.

    Theprotectiveandoptionalmeasuringcoresaretogetherbuilt intoatransformerblock.

    Thevoltagetransformerscanbeoptionallysuppliedwithcertifiableorcalibratedmeasuringcore.

    The current transformers can be fitted or exchanged easily withoutinterventioninthegastank.

    In addition, it is possible to use split-core current transformers laidaroundtheearthedcablescreensofthesingle-corecablesinthecableconnectioncompartmentorthecableduct.

    Technical DataSwitchgear panels (rated values)

    Rated voltage Ur7.2 kV 12 kV 17.5 kV 24 kV1)

    Rated insulation level Rated power-frequency withstand voltage, AC Ud kV 20 28 38 50 Rated lightning impulse withstand voltage Up kV 60 75 95 125Rated frequency fr Hz 50/60 50/60 50/60 50/60Rated normal current Ir For busbars A 1 250 1 250 1 250 1 250

    Rated short-time current Ik at tk = 3sUp tokA 20 20 16 16

    Rated peak withstand current IpUp tokA 50 50 40 40

    Rated short-circuit making current ImaUp tokA 50 50 40 40

    Ambient temperture T °C -5 to +402), 3)

    With reduced current ratings °C Above +40Relative humidity % Maximally 95Rated filling pressure of insulating gas at 20°C and 101.3 kPa kPa 130 (30 kPa overpressure)/LSF panel 150 (50 kPa overpressure)Insulating gas SF6Rated density of insulating gas kg/m3 7.9Encapsulation of the HV compartment IP Hermetically welded tank, IP65

    Encapsulation of fuse compartment IP Single-pole arcing-free encapsulation and 3-phase metal encapsulation, IP44Encapsulation of the drive housing, relay cabinet IP IP44/IP3XD

    Enclosure of the cable connection compartment IP IP44

    Internal arc test compliant with VDE 0671, Part 200, Appendix AA and resp. IEC 62271-200

    kA IAC AFL 20 kA, 1 s for HV compartmentskA IAC AFL 20 kA, 1 s for terminal compartments

    Colour of panel paint finish RAL 7 035 (light grey)Loss of service continuity category LSC 2APartition class PM1) Higher rated voltage (25kV) on request

    2) Operation at lower temperatures on request

    3) Depending to secondary technic

    StandardsThe switchgear installation complies with the following standards and regulations:

    IEC 60265-1 (62271-103*)/ VDE 0670 Part 301 IEC 62271-105 / VDE 0671 Part 105(VDE 0671 Part 103*) IEC 62271-200 (60298**) / VDE 0671 Part 200

    IEC 60282-1 / VDE 0670 Part 4 (VDE 0670 Part 6**)

    IEC 62271-1 (IEC 60694**)/ VDE 0670 Part 1000(VDE 0671 Teil 1*) * = future

    IEC 62271-100 / VDE 0671 Part 100 ** = up to now

    IEC 62271-102 / VDE 0671 Part 102

  • RangeOutgoing feeder panel with vacuum circuit-breakerType -1LSV-/6/

    Standard equipment• Vacuum circuit-breaker with stored energy operated– ON

    andOFF–:– Auxiliarycontacts:10NOand10NC,– Trippingdevice–ON,OFF–DCorAC,– Signallingcontactfor“Startingsectionscharged“,– Mechanicalcounter,

    • SF6three-positionisolatingandearthingswitch:

    – Interlockedwithcircuit-breaker,– Manualoperation,– Earthingswitchwithspringoperated–ONandOFF–,

    • 3-poleSF6-insulatedbusbarintheSF6compartment,

    • OnbothsidesoftheSF6-gastank:innerconeplug-insystemsforexternalbusbarconnection,

    • Capacitive voltage indication ledges in relay cabinet frontcover,

    • Gasleakageindication• Pressurereliefintheeventofarcingdirectedintothecable

    well,panelflooropen,• Lockableoperators,• Arc-faultresistantcableterminationcompartments,• Single set of cable connection bushings for maximally

    doublecableconnectionviaexternalconeplugXLPE2x1x500mm2:– Oneconnectionplugreplaceableforsurgearrester,

    • Relay-andcontrolcompartmentheight600mm.

    Outgoing panel with vacuum circuit-breakerType -1LSVG-/6/

    Standard equipment• Vacuumcircuit-breakerwithstoredenergyoperated–ON

    andOFF–:– Auxiliarycontacts:10NOand10NC,– Trippingdevice–ON,OFF–DCorAC,– Signallingcontactfor“Startingsectionscharged“,– Mechanicalcounter,

    • SF6three-positionisolatingandearthingswitch:

    – Interlockedwithcircuit-breaker,– Manualoperation,– Earthingswitchwithspringoperated–ONandOFF–,

    • 3-poleSF6-insulatedbusbarintheSF6compartment,• OnonesideoftheSF6-gastank:innerconeplug-insystems

    forexternalbusbarconnection,• Silicone insulated, controlled, externalbusbar to the riser

    panel-1HT-/6/,• Capacitivevoltage indication ledges in relaycabinet front

    cover,• Gasleakageindication,• Pressurereliefintheeventofarcingdirectedintothecable

    well,panelflooropen,• Lockableoperators,• Arc-faultresistantcableterminationcompartments,• Relay-andcontrolcompartmentheight600mm.

    Plug-involtagetransformersPlug-involtagetransformerswithisolating-andearthingfeatureCurrenttransformerCapacitivevoltageindicationledge

    Plug-involtagetransformersPlug-involtagetransformerswithisolating-andearthingfeatureCurrenttransformerMaximallydoublecableconnectionMaximallyfourfoldcableconnectionwithdoublesetofbushingsSurgearrester

    2000

    (230

    0)

    385 5

    75

    1400

    600

    (900

    )

    405

    575757570315 7600

    417 185770 2530

    630A1250A

    1250A

    2000

    (230

    0)

    1400

    600

    (900

    )

    405

    600 770 2530

  • Busbar riser panel with isolating switchType -1HT-/6/

    Standard equipment• SF

    6three-positionisolatingandearthingswitch:

    – Interlocked– Handle– Earthingswitchwithspringoperated–ONandOFF–

    • 3-poleSF6-insulatedbusbarintheSF6compartment• On one side of the SF6-gas tank: inner cone plug-in

    systemsforexternalbusbarconnection• Silicone insulated, controlled, external busbar to the

    bussectionalizerpanel-1LSVG-/6/• Gasleakageindication• Pressure relief in the event of arcing directed into the

    cablewell,panelflooropen• Lockableoperators• Arc-faultresistantterminalcompartments• Relay-andcontrolcompartmentheight600mm• Intermediate frame B = 50 mm to the bus-sectionalizer

    panel.

    Cable riser panel with isolating switchType -1AT-/6/

    Standard equipment• SF

    6three-positionisolatingandearthingswitch:

    – Interlocked– Handle– Earthingswitchwithspringoperated–ONandOFF–

    • 3-poleSF6-insulatedbusbarintheSF6compartment

    • On both sides of the SF6-gas tank: inner cone plug-insystemsforexternalbusbarconnection

    • Gasleakageindication• Pressure relief in the event of arcing directed into the

    cablewell,panelflooropen,• Lockableoperators• Arc-faultresistantterminalcompartments• Single set of cable connection bushings for maximally

    doublecableconnectionviaexternalconeplugXLPE2x1x500mm2,(Oneconnectionplugreplaceableforsurgearrester)

    • Relay-andcontrolcompartmentheight600mm• Intermediate frame B = 50 mm to the bus-sectionalizer

    panel.

    1250A

    Plug-involtagetransformersPlug-involtagetransformerswithisolating-andearthingfeatureCurrenttransformerCapacitivevoltageindicationledge

    630A1250A

    Plug-involtagetransformersPlug-involtagetransformerswithisolating-andearthingfeatureMaximallydoublecableconnectionMaximallyfourfoldcableconenctionwithdoublesetofbushings

    2000

    (230

    0)

    1400

    600

    (900

    )

    405

    650 770 2530

    2000

    (230

    0)

    385 57

    5

    1400

    600

    (900

    )

    405

    417 185770 2530

    575757570815 7650

  • 2000

    (230

    0)

    500

    690

    1035

    210

    600

    (900

    )

    357

    15 150250

    600

    540730 25

    630A

    CurrenttransformerMaximallydoublecableconnectionSurgearrester

    MaximallydoublecableconnectionSurgearrester

    Outgoing feeder panel with SF6 circuit-breaker based on arc quenching coil Type -1LSF-/6/

    Standard equipment• SF6three-positioncircuit-breakerandearthingswitch:

    – Includinginterlock,– Handle,– Circuit-breakerwithspringoperated–ON,andstoredenergyoperated–OFF,

    – Earthingswitchwithspringoperated–ONandOFF–,• ManualEmergency-Stoppush-button,• 3-poleSF6insulatedbusbarintheSF6compartment,• OnbothsidesoftheSF6gastank:innerconeplug-insystems

    forexternalbusbarconnections,• Capacitivevoltageindicationledges,• Gasleakageindication,• Pressurereliefintheeventofarcingdirectedintothecable

    well,panelflooropen,• Lockableoperators,• Arc-faultresistantcableterminationcompartments,• Single set of cable connection bushings for maximally

    double cable connection via external cone plug XLPE 2 x1 x 500mm2, (One connection plug replaceable for surgearrester),

    • Relay-andcontrolcompartment,height600mm.

    Cable panel with load-break switch and vertically arranged bushings Type -1K-/4/

    Standard equipment• SF6three-positionload-breakandearthingswitch:

    – Includinginterlock,– Manualoperation,– Load-breakandearthingswitcheswithspring-operated–ONandOFF–,

    • 3-poleSF6-insulatedbusbarintheSF6compartment,• On both sides of the SF6-gas tank: inner cone plug-in

    systemsforexternalbusbarconnection,• Capacitivevoltageindicationledges,• Gasleakageindication• Pressurereliefintheeventofarcingdirectedintothecable

    well,panelflooropen,• Lockableoperators,• Arc-faultresistantcableterminationcompartments,• Single set of cable connection bushings for maximally

    double cable connection via external cone plug XLPE 2 x1 x 500mm2, (One connection plug replaceable for surgearrester),

    • Relay-andcontrolcompartmentheight600mm.

    2000

    (230

    0)

    500

    690

    185

    185

    210

    600

    (900

    )

    357

    8686200

    400470

    665 2535

    87

    887 887

    021021

    630A

  • MaximallydoublecableconnectionSurgearrester

    Cable panel with load-break switch and horizontally arranged bushings Type -1K-/6/

    Standard equipment• SF6three-positionload-breakandearthingswitch:

    – Includinginterlock,– Handle,– Load-break and earthing switches with spring-operated–ONandOFF–,

    – 3-poleSF6-insulatedbusbarintheSF6compartment,• On both sides of the SF6 gas tank: inner cone plug-in

    systemsforexternalbusbarconnection,• Capacitivevoltageindicationledges,• Gasleakageindication• Pressure relief in the event of arcing directed into the

    cablewell,panelflooropen,• Lockableoperators,• Arc-faultresistantcableterminationcompartments,• Single set of cable connection bushings for maximally

    doublecableconnectionviaexternalconeplugXLPE2x1x500mm2,(Oneconnectionplugreplaceableforsurgearrester),

    • Relay-andcontrolcompartmentheight600mm.

    Transformer feeder panel with fused load-break switch Type -1TS-/4/

    Standard equipment• SF6three-positionload-breakandearthingswitch:

    – Includinginterlock,– Manualoperation,– Load-break switch with spring operated – ON, andstoredenergyoperated–OFF,

    – Earthingswitchwithspringoperated–ONandOFF–,• Indicationoftrippedfuse,• 3-poleSF6-insulatedbusbarintheSF6compartment,• On both sides of the SF6-gas tank: inner cone plug-in

    systemsforexternalbusbarconnection,• 3-phaseplug-onfusearrangement,• EarthingswitchinSF6downstreamoftheHRCfuse,• 3-pole slip-on type cable termination for transformer

    cables,maximallyXLPE1x240mm2,• Capacitive voltage indication ledges upstream and

    downstreamofthefuse,• Gasleakageindication,• Pressurereliefintheeventofarcingdirectedintothecable

    well,panelflooropen,• Lockableoperators,• Arc-faultresistantterminalcompartment,• Relay-andcontrolcompartment,height600mm.

    630A

    2000

    (230

    0)

    500

    690

    537

    570

    210

    600

    (900

    )

    357

    200400

    480665 2535

    126 126

    500

    690

    1035

    210

    600

    (900

    )

    357

    47066535

    2000

    (230

    0)

    150 150300

    60025

  • Busbar earthing panel with earthing switchType -1E-/4/

    Standard equipment• SF6-insulated3-poleearthingswitchforbusbarearthing:

    – Earthingfunctionasthree-positionswitch,– Manualoperation,– Springoperated–ONandOFF–,

    • 3-poleSF6-insulatedbusbarintheSF6compartment,• OnbothsidesoftheSF6-gastank:innerconeplug-insystemsfor

    externalbusbarconnection,• Earthed short-circuit bridge via vertical, frontal external cone

    bushingarrangement,• Gasleakageindication,• Pressurereliefintheeventofarcingdirectedintothecablewell,

    panelflooropen,• Lockableoperators,• Arc-faultresistantterminalcompartments,• Relay-andcontrolcompartment,height600mm.

    Metering panel with busbar riserType -1M1-/12,5/

    Standard equipment• 3-polebusbarforbus-sectionalizercircuit-breakerpanel-1LSVG-,• Ononesideofthemeteringpanel:innerconeplug-insystemsfor

    externalbusbarconnections,• Compact insulators - current- and/or voltage transformers, DIN

    42660part8resp.9,IEC600441,• Arc-faultresistantterminalcompartments,• Relay-andcontrolcompartment,height600mm.

    2000

    (230

    0)

    500

    400 665 2535

    690

    210

    600

    (900

    )

    357

    VoltagetransformerCurrenttransformer

    3 6 0

    7 7 0 2 51 0 5 0 2 0 0

    20

    00

    (

    23

    00

    )

    14

    006

    00

    (

    90

    0)

    011011

    49

    5

  • Type -1K-

    Type -1TS-

    Type -1LSV-

    Front panel

    Frontpanelwith:• Mimicdiagram• Switchpositionindication• Operatorsurfacefortheactuators• Capacitivevoltageindicators• Gasleakageindication• Short-circuitindicators• Padlockingfacility• Drivesealedagainstdust,sandandinsects• HousingIP44

    Gas leakage indication

    Each gas tank has a pressure display for verification of the SFoverpressurewithin,allowingitsfunctionalsafetytobeinspected.

    Pressure switch/ Density monitor

    Each gas tank can be fitted with a pressure switch and/or densitymonitorforremotemonitoring(auxiliarycontact).Thelowerswitchingpoint corresponds to the crossoverpoint to the redmeasuring rangeon thegas leakage indication.Thedensitymonitorcanbeoptionallyequippedwithalarmandtrippingindicatorauxiliarycontacts.

    Phase sequence indication

    Meaning of the indication:Green = operating pressure OKRed = operating pressure not OK.

    Voltage display and Testing

    Each system is equippedwith the necessary three-phase capacitivevoltagedetectionsystem,TypeKSO,forvoltagetestingtoVDE0682Part415andIEC61243-5withHRsystem(othersystemsonrequest).Thisenablestheabsenceofvoltageinindividualphasestobeverifiedby inserting thevoltage indicationplugs into thecorrespondingpairsof sockets. The voltage detection system circuitry is designed forrated operational voltages of 10, 15 and 20 kV.TheminimumandmaximumvaluesoftheStandardforthesevoltagerangesareadheredtointhestandardsystem.Itisnotnecessarythereforetoadjustthemagainwhenchangingtheratedoperationalvoltagewithinthisrange.Ratedoperationalvoltage6kVcanbeimplementedinaspecialversion.Thelivecontactsocketsaretouch-protected.

    Voltage detection system in sealed version

    Voltage indication plug

    (Picture shows Horstmann device)

    The following devices may be used:

    Pfisterer Type DSA-2

    Horstmann Type HMO-ST-1

    Indication devices are also suitable for continuous duty.

  • Single-line diagram of a voltage indicator

    Phase Sequence Indication by Interface Tester

    (Picture shows Horstmann device, Type ORION 3.0)

    Make Phase sequence indication

    Interface tester

    Horstmann - H-OM measuring module with Fluke

    ammeter Type 87 or matrix Type Mx55 (II

    to IV)

    Horstmann Type: Orion Type: Orion

    Pfisterer Type: EPV Type: Euro test-HO

    Voltageindicationviacapacitivevoltagedivider,HRsystem.

    Voltageindicationpluggedin.

    C1Capacitorintegratedinthebushings.

    C2Capacitanceoftheconnectingcablesandthevoltageindicationdevicetoearth.

    ULE=UN/√3Duringratedoperationinathree-phasesystem.

    U2=UA=Voltageatthecapacitiveinterfaceofthesystemoratthevoltageindicationdevice.

    T connection fittingsT connection fittings are to be used as the operator thinks fit.Connectable to bushings toDIN EN50181 connection typeC (630A)withexternalconeandboltcontact(M16).Withnon-controlledsystems,themanufacturer’smountinginstructionsaretobeadheredtoimplicitly.

    Short-circuit/Earth-fault indicator.

    Othertypesandproductsondemand.

    Manufacturer TypeHorstmann ALPHAM

    Accessories for the system

    Operatinglevers,keysforfasteners

    Operating lever (optional) for the load-break switchactuatingshaftwithmotoroperator(formanualswitchinge.g.incaseoflossofsupplyvoltage).

    Operatingleverfortheearthingswitch(optionalredshaft).

    Operating lever for the load-break switch (optional plainshaft).

    Charginghandleforvacuumcircuit-breakers

    Keyforthefasteneronthefrontcover(controlstheanti-reverseinterlock).

    Cable clamps

    Size IClampingrange26to55mmforcables,suchas

    • 12kV:35mm2 240mm2

    • 24kV:25mm2 185mm2

    Size IIClampingrange36to52mmforcables,suchas

    • 12kV: 300mm2

    • 24kV: 240mm2

    Theprecisecablediametermustbecomparedwith theclampingrange.

    Figure13Operating levers

    The following devices may be used:

    Allringcablepanelscanbeequippedeitherwitha3-phaseshortcircuitorearth-faultindicator.

    ALPHAE

    ALPHAautomatic

    DELTAM

    DELTAE

    EKA-3

    EKA3/1

    GAMMA4.0

    Opto

    Sigma

  • Coupling and bolt connection kits

    Busbar coupling kit with double gasket

    Shown: 1 phase

    Busbar end cover with single gasket

    Shown: 1 phase

    Parts for bolt connection of panels

    Shown: 1 set

    Arc fault protection, panel installationForstandardpanelversionwithpressurereliefintothecablewellorcableduct.

    Pressure relief into the cable well or cable duct

    600

    100

    Forpanelversionforpressurereliefviareartowardsthetop(panelforfloorbulkhead).

    Pressure relief via rear absorber channel towards the top

    Switchgear related pressure calculations can be enquired as part of services.

    ca. 1150 100

    Protection technology

    All commercially available protection relays can be installed intheswitchgearfor theLSVcircuitbreakerpanelsandLSFcircuitbreakerpanels.

    Thevariantsrangefromtransformer-operatedprotectionrelaystocombinedprotectionandcontrolsystems.

    Lowenergytrips0.5VAand0.1VAareavailableforthetransformer-operatedrelays.

    Inthiscontextspecialrelay-transformercombinationsaretested.

    Commonprotocolsand interfaces,e.g.ProfibusDP,Modbus, IEC60870-5-103,IEC60870-5-101andIEC61850canbeprovidedwithrelatedrelays.

    Installationisinlow-voltagecompartment/relayniche.

    Optionally,theprotectionrelaycanalsobeinstalledintherelatedcover.

    It isalsopossible toconfigure theparameters for theprotectionrelayinaccordancewithcustomerrequirements.

    Afewcommerciallyavailableprotectionrelaysasexamples:

  • http://www.ppi.ph/dlfiles/orgae.pdf