New Site External alarm implementation guide
For new site External we have two scenario:
1. ZTE ODU External Alarm Configuration (With Sceco)
2. ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)
ZTE ODU External Alarm Configuration (With Sceco)
Alarm
No. Designation
DDF
SLOT Remarks Connection
1 Door Cabinet Open(WHITE /
BLUE)
1 Connected directly to
BBU SA Card
Sensor - DDF 1 - BBU SA
2 High Temperature(WHITE /
ORANGE)
2 Connected directly to
BBU SA Card
Sensor - DDF 2 - BBU SA
3 Tower Light Failure
Alarm(WHITE / GREEN)
3 Connected directly to
BBU SA Card
Sensor - DDF 3 - BBU SA
4 Rectifier Alarm (WHITE /
BROWN)
4 From B201 SIB Board
(Power Unit) - X15 port
X15 - DDF 4 - BBU SA
5 AC Power Fail(WHITE / GRAY) 5 From B201 SIB Board
(Power Unit) - X16 port
X16 - DDF 5 - BBU SA
6 Environmental Over
Humidity(RED / BLUE)
6 From B201 SIB Board
(Power Unit) - X16 port
X16 - DDF 6 - BBU SA
7 DC Low Voltage alarm(RED /
ORANGE)
7 From B201 SIB Board
(Power Unit) - X17 port
X17 - DDF 7 - BBU SA
8 SMOKE Alarm(RED / Green) 8 From B201 SIB Board
(Power Unit) - X17 port
X17 - DDF 8 - BBU SA
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 2 页
SA card
(BS8800)
D
D
F
Medium light alarm cable
Door open alarm
DDF Port 1
Rectifier alarm
DDF Port 4
Tower Light Failre Alarm
DDF Port 3
High tep. Alarm
DDF Port 2
Door 1 sensor
AC1(1500W) alarm cable
Smoke alarm
DDF Port 8
DC Low voltage alarm
DDF Port 7
Environmental over humidity alarm
DDF Port 6
AC power fail alarm
DDF Port 5
ODU Cabinet
Door 2 sensor
AC2(1500W) alarm cable
AC3(500W) alarm cable
Smoke sensor
B201 X15 Port(NC/COM)
B201 X16 Port(NC/COM)
B201 X16 Port(NC/COM)
B201 X17 Port(NC/COM)
B201 Module
Tower
ZTE ODU External Alarm Drawing (With Sceco)
Low light alarm cable
Low light alarm cable
Junction
box
Control
box
B201 X17
Port(NC/COM)
Actual
virtual
B201 X24
Port
NodeB(BS8800) part:
SA card
(BS8800)
D
D
F
For New site External alarm we through BS8800 SA card report to EMS/OMC.all external alarm sensor
should be connect to SA card through DDF terminal.before connect sensor,please make loop back test
from DDF to OMC,make sure 8channel no any cross.it very important for test external alarm.
External alarm connection :
SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor
1. SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 3 页
2.SA E1 Cable: material code: 052740402185 DS-91223-002|Digital Signal Cable
We used core color(new)
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 4 页
3.connection picture:
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 5 页
No1. Door Cabinet Open(WHITE / BLUE)(in DOU cabinet)
SA card
(BS8800)
D
D
F
Door open alarm
DDF Port 1
Door 1 sensorODU Cabinet
Door 2 sensor
Door1 and Door2 Sensor cable need parallel connect to DDF port1
Door 1 Sensor :
Door2 Sensor
Door 1&Door 2 Sensor cable :
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 6 页
No 2.High Temperature(WHITE / ORANGE) (in DOU cabinet)
SA card
(BS8800)
D
D
F
High tep. Alarm
DDF Port 2
AC1(1500W) alarm cable
ODU Cabinet
AC2(1500W) alarm cable
AC3(500W) alarm cable
AC1&AC2&AC3 Alarm cable need parallel connect to DDF port2
1.AC1(1500W)alarm cable:(Location:in Door1 up area Port:NC/COM)
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 7 页
2.AC2(1500W)alarm cable:(Location:in Door2 up area Port:NC/COM)
3.AC3(500W)alarm cable:(Location:in Door2 down area Port:NC/COM)
4.alarm cable in ODU location
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 8 页
No 3.Tower Light Failure Alarm(WHITE / GREEN)-on tower
SA card
(BS8800)
D
D
F
Medium light alarm cable
Tower Light Failre Alarm
DDF Port 3
Tower
Low light alarm cable
Low light alarm cable
Junction
box
Control
box
Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3
Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal,
From Junction box connect to Control box alarm input terminal, From Control box alarm output
connect to DDF port3 terminal. For detail connection please reference installation and operation
manual in the box.
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 9 页
No 4. Rectifier Alarm (WHITE / BROWN)
No 5. AC Power Fail(WHITE / GRAY)
No 6.Environmental Over Humidity(RED / BLUE)
No 7.DC Low Voltage alarm(RED / ORANGE)
SA card
(BS8800)
D
D
F
Rectifier alarm
DDF Port 4
DC Low voltage alarm
DDF Port 7
Environmental over humidity alarm
DDF Port 6
AC power fail alarm
DDF Port 5
B201 X15 Port(NC/COM)
B201 X16 Port(NC/COM)
B201 X16 Port(NC/COM)
B201 X17 Port(NC/COM)
Rectifier Alarm From X15 NC/COM connect to DDF port4
AC Power Fail From X16 NC/COM connect to DDF port5
Environmental Over Humidity From X16 NC/COM connect to DDF port6
DC Low Voltage alarm From X17 NC/COM connect to DDF port7
Below description detail how to setting external alarm in ZXDU68 B201 system.
About the relay alarm of the ZXDU68B201 power supply system
The boards of the zxdu68 B201system is integrated in the signal transfer box. Figure as below:
shown the board layout.
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 10 页
1. Network interface board(IP/SNMP);
2. Modem power board(MPB);
3. Signal interface board(SIB)
And the signal interface board provides external communication interfaces and monitoring
unit signal interfaces. The signal board is shown in figure as below. Refer to table for the
signal board interfaces description.
Figure signal board:
Table signal interface name
Interface Interface name Interface Interface name
X4 Battery 1 temperature X21 RS485 interface
X5 Battery 2 temperature X22 Rs232 interface
X12 Temperature control X23 Flood alarm
X14 Input relays 1,2,3,4 X24 Smoke alarm
X15 Out relays 1,2 X25 Ambient temperature
X16 Out relays 3,4 X26 Intrusion alarm
X17 Out relays 5,6
Then the relays alarm function need to three interface: X15、X16、X17.
So the relays alarm function of the signal interface definition as belowTable-1:
Interface Pin Signal
definition
Signal description Relay alarm definition
(monitor parameters)
X15
Output relays
1,2
1 2NO Relay output 2-NO(normally open) A3
2 2COM Relay output 2-Common end A3
3 2NC Relay output 2-NC(normally closed) A3
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 11 页
4 1NO Relay output 1-NO --
5 1COM Relay output 1-Common end --
6 1NC Relay output 1-NC --
X16
Output
relays3,4
1 4NO Relay output 4-NO A5
2 4COM Relay output 4-Common end A5
3 4NC Relay output 4-NC A5
4 3NO Relay output 3-NO A2
5 3COM Relay output 3-Common end A2
6 3NC Relay output 3-NC A2
X17
Output relays
5,6
1 6NO Relay output 6-NO A4
2 6COM Relay output 6-Common end A4
3 6NC Relay output 6-NC A4
4 5NO Relay output 5-NO A5
5 5COM Relay output 5-Common end A5
6 5NC Relay output 5-NC A5
The relays alarm function has two options on the signal board, one relay output-NO(normal open)
and one relay output-NC(normal close). So need to know the BTS interface alarm definition
which it is NO or NC.
If it is ‘NO’, and connect relay alarm cables step:
1、 One group relay out need two signal cables , and one terminal connect with relay out –ON and
relay output –common end on the signal board interface, another terminal connect with the
BTS interface.
DDF
NO
COMMON
2、 Other relays alarm as above the connection step, until it finished.
After finished to connect the signal cables , and set parameters in the monitor.
Step:
1、check the monitor screen, find the CTRL menu.
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 12 页
2、press the button ENTER of the monitor.
3、 Entering the password: 0000.
4、 Enter the setup parameter system: 1. Setup Para, press the Enter button.
5、 Find the Alarm Para in the Setup Para.
6、 Enter the Alarm Para menu, find the 1.Set Relay to Enter
7、 And find the relays alarm parameter. According to the relays alarm requirements, set the relay
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 13 页
alarm.
Setup procedures:
If the relay alarm connected the X15(1,2) of the signal board, it mean what it is SMR Alarm.
So the relay alarm parameter set A2.
Refer to above the Table-1.
Figure (set parameter:
No 8. SMOKE Alarm(RED / Green)
SA card
(BS8800)
D
D
F
Smoke alarm
DDF Port 8
ODU Cabinet
Smoke sensorB201 X17
Port(NC/COM)
B201 X24
Port
Smoke alarm From Smoke sensor first connect to X24,then X17 NC/COM connect to DDF port8
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 14 页
ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)
Alarm
No. Designation
DDF
SLOT
DRY Contact Alarm
Connection Connection
1 Door Cabinet Open(WHITE / BLUE) 1 Connected directly to BBU SA
Card Sensor - DDF 1 - BBU SA
2 High Temperature(WHITE / ORANGE) 2 Connected directly to BBU SA
Card Sensor - DDF 2 - BBU SA
3 Rectifier Alarm (WHITE / GREEN) 3 From B201 SIB Board
(Power Unit) - X15 port X15 - DDF 3 - BBU SA
4 AC Power Fail(WHITE / BROWN) 4 From B201 SIB Board
(Power Unit) - X16 port X16 - DDF 4 - BBU SA
5 Environmental Over Humidity(WHITE /
GRAY) 5
From B201 SIB Board
(Power Unit) - X16 port X16 - DDF 5 - BBU SA
6 DC Low Voltage alarm(RED / BLUE) 6 From B201 SIB Board
(Power Unit) - X17 port X17 - DDF 6 - BBU SA
7 Generator Fault(RED / ORANGE) 7 From Generator Control Port
connected directly to SA Card Generator Control - DDF 7 - BBU SA
8 Generator Low Fuel(RED / GREEN) 8 From the Storage Tank
Connected directly to SA Card Storage Tank Sensor - DDF 8 - BBU SA
SA card
(BS8800)
D
D
F
Generator
Door open alarm
DDF Port 1
Rectifier alarm
DDF Port 3
Generator Fault
DDF Port 7
High tep. Alarm
DDF Port 2
Door 1 sensor
AC1(1500W) alarm cable
DC Low voltage alarm
DDF Port 6
Environmental over humidity alarm
DDF Port 5
AC power fail alarm
DDF Port 4
ODU Cabinet
Door 2 sensor
AC2(1500W) alarm cable
AC3(500W) alarm cable
B201 X15 Port(NC/COM)
B201 X16 Port(NC/COM)
B201 X16 Port(NC/COM)
B201 X17 Port(NC/COM)
B201 Module
Generator
ZTE ODU External Alarm Drawing (With Genset)
Genterator tank
Actual
virtual
Generator Low Fuel
DDF Port 8
内部公开 Internal Use Only▲
<以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE
第 15 页
For alarm No.1—No.6,please refer ZTE ODU EXTERNAL ALARM CONFIGURATION TEST
(With Sceco) installation.
No7. Generator Fault(RED / ORANGE)
No8 Generator Low Fuel(RED / GREEN)
SA card
(BS8800)
D
D
F
Generator Generator Fault
DDF Port 7
Generator
Genterator tankGenerator Low Fuel
DDF Port 8