Nexus 1-8 Loop (XP95) Analogue Nexus 1-8 Loop (XP95) Analogue Addressable Control PanelsAddressable Control Panels
• From 1 to 8 loops
• Powerful processing and extensive panel and loop I/O capability
• Fully compatible with all XP95 devices
• User-friendly controls and a clear, unambiguous screen
• Alarm threshold adjustments by device
• Day/night alarm delay feature
• Messages edited by PC or keyboard
Nexus 1-8 Loop (XP95) Analogue Nexus 1-8 Loop (XP95) Analogue Addressable Control PanelsAddressable Control Panels
• Multiple, fully functional panel displays
• Radio pager facility
• Easy to use, Windows-based PC
software package
• Fully networkable with graphics
package, network repeaters & other
Nexus panels
• Designed to meet BS5839 Part 4
Panel EnhancementsPanel Enhancements
Individual panels and Nexus panel networks are
programmable via Windows PC package.
Individual panels and Nexus panel networks are
programmable via Windows PC package.
Up to 31 8-way panel enhancement boards may be added. Two types are available:
1) fully-programmable inputs and relay outputs
2) fully-programmable inputs and alarm outputs
Up to 31 8-way panel enhancement boards may be added. Two types are available:
1) fully-programmable inputs and relay outputs
2) fully-programmable inputs and alarm outputs
Up to 13 remote panel displays, providing full user & engineer facilities may be connected via RS485 cable.
Up to 13 remote panel displays, providing full user & engineer facilities may be connected via RS485 cable.
Fully programmable
network comprising other Nexus multi-loop panels, graphics
systems and network repeaters.
Fully programmable
network comprising other Nexus multi-loop panels, graphics
systems and network repeaters.
Remote Inputs for Silence Alarms, Reset, Evacuate,
Class Change, Fault, Buzzer Silence.
Remote Inputs for Silence Alarms, Reset, Evacuate,
Class Change, Fault, Buzzer Silence.
A wide variety of loop devices are supported, including XP95 detectors, call points, loop sounders, outstations and intrinsically safe devices.
A wide variety of loop devices are supported, including XP95 detectors, call points, loop sounders, outstations and intrinsically safe devices.
Cabinet OptionsCabinet Options
For details of panel dimensions
see Application Guide.
For details of panel dimensions
see Application Guide.
Surface Cabinets
Cabinet colour reference is: RAL 7035 textured (Light Grey)
All cabinets are manufactured from sheet steel and finished in satin texture epoxy powder stove paint.
Semi-Flush Cabinets
The semi-flush bezel locates to the rear of the bevelled edge of the back box, leaving the bevelled edge and door raised out from the wall.
It is finished in the same colour as the back box and is fitted by means of pinch bolts, thus avoiding the need to drill the cabinet.
Fully Flush Cabinet (Illustrated)
Custom-made to a high quality, full-flush bezels are available in brass, stainless steel, or painted.This option is achieved by fixing a flat bezel assembly to the standard back box, replacing the standard door. The panel comes with assembly already fitted but may be supplied for later on-site fitting (this may be a little time-consuming).
Surface Cabinets
Cabinet colour reference is: RAL 7035 textured (Light Grey)
All cabinets are manufactured from sheet steel and finished in satin texture epoxy powder stove paint.
Semi-Flush Cabinets
The semi-flush bezel locates to the rear of the bevelled edge of the back box, leaving the bevelled edge and door raised out from the wall.
It is finished in the same colour as the back box and is fitted by means of pinch bolts, thus avoiding the need to drill the cabinet.
Fully Flush Cabinet (Illustrated)
Custom-made to a high quality, full-flush bezels are available in brass, stainless steel, or painted.This option is achieved by fixing a flat bezel assembly to the standard back box, replacing the standard door. The panel comes with assembly already fitted but may be supplied for later on-site fitting (this may be a little time-consuming).
Mechanical AssemblyMechanical Assembly
Motherboard holds Konex network card
and 2 loop cards.
Motherboard holds Konex network card
and 2 loop cards.
Display assembly located on removable
door.
Display assembly located on removable
door.
Motherboard and power supply located on removable chassis to assist cabinet installation.
Motherboard and power supply located on removable chassis to assist cabinet installation.
Zone LEDs and option printer are located on
display board.
Zone LEDs and option printer are located on
display board. Space for internal 12Ah battery set.
Space for internal 12Ah battery set.
A1535 programmable relay board / A1536 programmable alarm board - a maximum of
2 boards may be housed internally and up to 29
externally.
A1535 programmable relay board / A1536 programmable alarm board - a maximum of
2 boards may be housed internally and up to 29
externally.
Loop extension motherboard - this
chassis is located in the right hand section of the
enclosure.
Loop extension motherboard - this
chassis is located in the right hand section of the
enclosure.
FAULT
DATAMORE
ALERT
ON
TEST
SYSTEMDELAY
ACCEPT
FAULTHEALTHY
DISABLEDFIRE
GENERALSUPPLY
BUZZER
EVACUATE
OVERRIDE
DELAY
ENTER
ESCAPE
DISPLAY DISPLAY
ALARMS
TEST
ENGINEER
DISPLAY
SILENCE
TEST
SILENCE
CYCLE
ALARMS SYSTEM
CLEAR
RESET
6
5
4
*
#
0
3
2
1
9
8
7
User Controls User Controls
The engineer accesses panel configuration
functions using the numerical
designations. The menu structure on
the LCD display guides the engineer through the different
set-up facilities.
The engineer accesses panel configuration
functions using the numerical
designations. The menu structure on
the LCD display guides the engineer through the different
set-up facilities.
System LED indications are
provided in addition to the LCD display.
System LED indications are
provided in addition to the LCD display.
The backlit LCD display gives information of
loop, device and zone number,
device type and event condition, together with a user-definable
text description.
The backlit LCD display gives information of
loop, device and zone number,
device type and event condition, together with a user-definable
text description.
The text descriptions give
the user clear, single-operation
functional controls.
The text descriptions give
the user clear, single-operation
functional controls.
Typical LCD IllustrationTypical LCD Illustration
The device types which may be indicated are as follows:
SOU - Loop sounder/sounder circuit controllerO/S - Input/Output deviceION - Ionisation smoke sensorMON - Monitor (zone monitor, control monitor) OPT - Optical smoke sensorHEAT - Heat sensorBGU - Call point or call point monitor
The device types which may be indicated are as follows:
SOU - Loop sounder/sounder circuit controllerO/S - Input/Output deviceION - Ionisation smoke sensorMON - Monitor (zone monitor, control monitor) OPT - Optical smoke sensorHEAT - Heat sensorBGU - Call point or call point monitor
Display /Repeater PCB (A1575) Display /Repeater PCB (A1575) Viewed from Inside CabinetViewed from Inside Cabinet
LCD display.LCD display.
Power supply fault input when used as a repeater with a local
power supply unit.
Power supply fault input when used as a repeater with a local
power supply unit.
Comms link to the main panel
motherboard.
Comms link to the main panel
motherboard.
System Eprom.System Eprom.
S13 Display number Address switch (Node
Address Switch)
S13 Display number Address switch (Node
Address Switch)
16 way ribbon connector to the printer interface.
16 way ribbon connector to the printer interface.
16 way ribbon connector to the zone
board.
16 way ribbon connector to the zone
board. DC power in.DC power in.
Zone IndicationsZone Indications
The Nexus 1-8 loop panel provides 64
fully programmable zone LEDs.
The Nexus 1-8 loop panel provides 64
fully programmable zone LEDs.
The zone identification label may be inserted from
inside the cabinet
The zone identification label may be inserted from
inside the cabinet
Engineer FacilitiesEngineer Facilities
The fault LEDs, fuses and DIL
switch are easily accessible for the engineer
when the user display board
has been removed.
The fault LEDs, fuses and DIL
switch are easily accessible for the engineer
when the user display board
has been removed.
12V
+
12V
+
Power SupplyPower SupplyThe fault LEDs, fuses and DIL switch are easily accessible for the engineer
when the user display board has been removed.
The fault LEDs, fuses and DIL switch are easily accessible for the engineer
when the user display board has been removed.
These LED indications give the engineer more details of the fault when the “Power Supply Fault” message has
appeared on the panel display.
These LED indications give the engineer more details of the fault when the “Power Supply Fault” message has
appeared on the panel display.
Test lamp switch.
Test lamp switch.
Decoupling link.Decoupling link.
230V AC supply.
230V AC supply.
Battery supply fuse - 6.3 Amps.
Battery supply fuse - 6.3 Amps.
PrinterPrinter
Designed for easy replacement of the paper roll
onto the carrier.
Designed for easy replacement of the paper roll
onto the carrier.
This good quality printer uses a reliable Epson
mechanism.
This good quality printer uses a reliable Epson
mechanism.
This button advances the
paper.
This button advances the
paper.
Open access to feed paper
through mechanism.
Open access to feed paper
through mechanism.
Engineer’s printer test
button.
Engineer’s printer test
button.
Hinged access to allow easy ribbon
change.
Hinged access to allow easy ribbon
change.
A1535 8 Way Relay Board A1535 8 Way Relay Board
RS485 comms from panel
motherboard.
RS485 comms from panel
motherboard.
8 inputs may be normally open or
normally closed and will register as fire or non-fire on the panel as configured. Inputs
are fully programmable via the
panel or PC cause/effect.
8 inputs may be normally open or
normally closed and will register as fire or non-fire on the panel as configured. Inputs
are fully programmable via the
panel or PC cause/effect.
24V DC power.24V DC power.
8 x 1Amp changeover relay
outputs may be fully programmed via the
panel or PC cause/effect programme.
8 x 1Amp changeover relay
outputs may be fully programmed via the
panel or PC cause/effect programme.
Engineer’s DIL switches to set board address, enable O/C
or S/C inputs and disable
inputs/outputs.
Engineer’s DIL switches to set board address, enable O/C
or S/C inputs and disable
inputs/outputs.
Engineer’s links to disable
functions for set-up or
maintenance purposes.
Engineer’s links to disable
functions for set-up or
maintenance purposes.
A1536 8 Way Alarm BoardA1536 8 Way Alarm Board
Engineer’s buzzer disable link for set-up or maintenance
purposes.
Engineer’s buzzer disable link for set-up or maintenance
purposes.
8 x 1Amp two-stage alarm
outputs may be fully programmed via the panel or PC cause/effect.
8 x 1Amp two-stage alarm
outputs may be fully programmed via the panel or PC cause/effect.
Engineer’s DIL switches to isolate
alarm outputs individually.
Engineer’s DIL switches to isolate
alarm outputs individually.
8 normally open inputs which will register as fire or
non-fire on the panel as
configured. Inputs are fully programmable via panel or PC
cause/effect.
8 normally open inputs which will register as fire or
non-fire on the panel as
configured. Inputs are fully programmable via panel or PC
cause/effect.
24V DC power.24V DC power.
Test alarms when switched
to 0V.
Test alarms when switched
to 0V.
Alarm Fault LEDs.
Alarm Fault LEDs.
RS485 comms from panel
motherboard.
RS485 comms from panel
motherboard.
Engineer’s DIL switches to set board address, disable
inputs and outputs, test LEDs and test alarms.
Engineer’s DIL switches to set board address, disable
inputs and outputs, test LEDs and test alarms.
Windows-based PC ProgrammingWindows-based PC Programming
A Windows-based PC programming package is available for panel set up, zones, text, local and network cause/effect.
A Windows-based PC programming package is available for panel set up, zones, text, local and network cause/effect.
Typical Radio Pager ConfigurationTypical Radio Pager Configuration
The radio pager system, when connected to the control panel, can be used to transmit both text and numeric messages direct to pocket pagers. Pagers will display Fire / Fault conditions including Sensor location text. Up to 9,999 pagers can be connected to system.
The radio pager system, when connected to the control panel, can be used to transmit both text and numeric messages direct to pocket pagers. Pagers will display Fire / Fault conditions including Sensor location text. Up to 9,999 pagers can be connected to system.
Connection to panel printer port.
Connection to panel printer port.
Interface boardInterface board
Opto isolatorOpto isolator
TransmitterTransmitter
XP95 Test ToolXP95 Test Tool
The XP95 Test Tool is an engineer’s tool to assist with commissioning and fault finding on XP95 loop systems. Loop
configurations and the status of each device may be interrogated, device LEDs may be turned on/off. The test tool
may be connected to an entire loop without the panel connected or connected to individual devices around the
circuit.
The XP95 Test Tool is an engineer’s tool to assist with commissioning and fault finding on XP95 loop systems. Loop
configurations and the status of each device may be interrogated, device LEDs may be turned on/off. The test tool
may be connected to an entire loop without the panel connected or connected to individual devices around the
circuit.
Alpha-numeric LCD display.
Alpha-numeric LCD display.
Engineer’s keypad.
Engineer’s keypad.
On/off switch and LED indication.
On/off switch and LED indication.
Battery charger socket.
Battery charger socket.
Sockets for flying leads to connect to loop and/or
individual XP95 devices.
Sockets for flying leads to connect to loop and/or
individual XP95 devices.