9
ALAM FLORA SDN BHD (Company No. 367713-X) 22 JUNE 2012 ENVIRONMENTAL NOISE MONITORING REPORT 1.0 OBJECTIVE The objective of this monitoring is 1.1 To measure noise exposure level from air compressor and welder generator at Jalan 6 Depot. 1.2 To enforce the use of hearing protection devices for workers who are working near to or air compressor or engine driven with in order to prevent them from hearing loss. 2.0 BACKGROUND 2.1 As stated in Section 9, Factories and Machineries (Noise Exposure) Regulations, the noise monitoring should be carried out according to Department Occupational Safety and Health Requirement. 2.2 Therefore, noise monitoring has been conducted at Jalan 6 Depot on 21 June 2012. 2.3 The monitoring has covered all possible noise source (Machines), and Area (Working Sections). 2.4 Monitoring was conducted at two high noise level areas which are air compressor and welder generator. 3.0 LEGAL REQUIREMENT According to the Factories and Machinery (Noise Exposure) Regulations 1989, states that

Upload: syoolove

Post on 28-Oct-2015

23 views

Category:

Documents


3 download

DESCRIPTION

Report during practical

TRANSCRIPT

Page 1: Noise monitoring at Depot Jalan 6.docx

ALAM FLORA SDN BHD

(Company No. 367713-X)

22 JUNE 2012

ENVIRONMENTAL NOISE MONITORING REPORT

1.0 OBJECTIVE

The objective of this monitoring is

1.1 To measure noise exposure level from air compressor and welder generator at Jalan 6 Depot.

1.2 To enforce the use of hearing protection devices for workers who are working near to or air

compressor or engine driven with in order to prevent them from hearing loss.

2.0 BACKGROUND

2.1 As stated in Section 9, Factories and Machineries (Noise Exposure) Regulations,

the noise monitoring should be carried out according to Department Occupational Safety and

Health Requirement.

2.2 Therefore, noise monitoring has been conducted at Jalan 6 Depot on 21 June 2012.

2.3 The monitoring has covered all possible noise source (Machines), and Area (Working Sections).

2.4 Monitoring was conducted at two high noise level areas which are air compressor and welder

generator.

3.0 LEGAL REQUIREMENT

According to the Factories and Machinery (Noise Exposure) Regulations 1989, states that

3.1 No employee shall be exposed to noise level exceeding equivalent continuous sound level of 90

dB (A) or exceeding the limits specified in the First Schedule or exceeding the daily noise dose

of unity.

3.2 Where an initial workers exposure monitoring shows the possibility of any workers exposure to

noise level at or above the action level, the employer shall provide approved hearing protection

devices to their exposed workers.

3.3 Warning signs shall be posted at defined work areas in which workers may be exposed at or

above the limits.

3.4 The warning signs shall clearly indicate that the area is a high noise area and that hearing

protection devices shall be worn.

Page 2: Noise monitoring at Depot Jalan 6.docx

3.5 Any person who contravenes any provision of these Regulations shall be guilty of an offence

and shall, on conviction, be liable to a fine not exceeding one thousand ringgit.

4.0 Result

4.1 Air compressor noise level

No. Decibel level at

distance from

noise source (dB)

Time Duration

(minutes)

LAeqt LAFmin LAFmax Permissible Exposure

Limits of Factories

And Machinery (Noise

Exposure)Reg. 1989

1. Noise source 11.49 2.00 91 81.1 95.7 90 dB

2. 1 meter 11.51 2.00 82.9 78.8 86.4 90 dB

3. 2 meter 11.54 2.00 75.9 73 85 90 dB

4. 3 meter 11.56 2.00 89.0 74.1 105.9 90 dB

5. 4 meter 11.58 2.00 83.2 74.7 97.7 90 dB

* Noise level exceed permissible exposure limit

4.2 Welder generator noise level

No. Location Time Duration

(minutes)

LAeqt LAFmin LAFmax Permissible Exposure

Limits of Factories

And Machinery (Noise

Exposure)Reg. 1989

1. Noise source 12.08 2.00 96.9 95.9 97.4 90 dB

2. 1 meter 12.10 2.00 93.5 91.1 94.8 90 dB

3. 2 meter 12.12 2.00 90.1 89.0 92.5 90 dB

4. 3 meter 12.19 2.00 87.7 86.1 91.3 90 dB

5. 4 meter 12.20 2.00 86.9 86.0 87.5 90 dB

* Noise level exceed permissible exposure limit

5.0 RECOMMENDATION

Based on Factories and Machinery (Noise Exposure) Regulations 1989, Regulation 15, the employer

shall reduce and maintain employee exposure to noise level below the limits by -

(a) Personal protective equipment (PPE)

Provide an approved hearing protection device (i.e., earplugs, earmuffs) to, and ensure its use

by an employee exposed to noise level at or above the limits

Earplugs can reduce the noise by 15 to 30 dB.

Below are the example of earplug with cord

Page 3: Noise monitoring at Depot Jalan 6.docx

(b) Place noise warning sign at noise source area (air compressor and engine driven generator noise).

(Noise warning sign) (Ear plug)

Prepared by:

.........................................

(Aisahatikah Mustafa)

Practical Student

Approved by:

....................................

(Ramizu Abdul Rahim)

(Manager Environment Health & Safety)

Page 4: Noise monitoring at Depot Jalan 6.docx

(Schedule 1)

Page 5: Noise monitoring at Depot Jalan 6.docx

Noise Level (dB (A)-slow) Duration of Exposure Permitted per day (hours-minute)

85 16-086 13-5687 12-888 10-3489 9-1190 8-091 6-5892 6-493 5-1794 4-3695 4-096 3-2997 3-298 2-5099 2-15

100 2-0101 1-44102 1-31103 1-19104 1-9105 1-0106 0-52107 0-46108 0-40109 0-34110 0-30111 0-26112 0-23113 0-20114 0-17115 0-15

Page 6: Noise monitoring at Depot Jalan 6.docx

Source : Permissible Exposure Limits of Factories And Machinery (Noise Exposure)

Regulations 1989

Environmental Noise Monitoring Activity

(Noise monitoring at air compressor) (Noise monitoring atwelder generator)

Page 7: Noise monitoring at Depot Jalan 6.docx