objectives more hvac systems - sorption (absorption) chillers - economizers (psychrometrics) and...
TRANSCRIPT
Objectives
More HVAC systems
- Sorption (absorption) chillers
- Economizers (Psychrometrics) and control
- Desiccant systems (Psychrometrics)
Absorption Cycle
• Water is typical refrigerant• Strong vacuum - ~0.116 psi or 0.0008 MPa• Boiling point of water?
• Differences from vapor compression• No compressor
• Chemical (e.g. LiBr - hygroscopic) – Absorbs water vapor turns it into a liquid
– Regenerated by removing water
• Requires heat
EconomizerEconomizer (fresh air volume flow rate control)
mixing
damper
fresh
air
T & RH sensors
recirc.
air
Controlled device is damper
- Damper for the air
- Valve for the CC
Economizer – cooling regime
How to control the fresh air volume flow rate?
% fresh air
Minimum for
ventilation
100%
If TOA < Tset-point → Supply more fresh air than the minimum required
The question is how much?
Open the damper for the fresh air
and compare the Troom with the Tset-point .
Open till you get the Troom = Tset-point
If you have 100% fresh air and your
still need cooling use cooling coil.
What are the priorities:
- Control the dampers and then the cooling coils or
- Control the valves of cooling coil and then the dampers ?
Defend by SEQUENCE OF OERATION
the set of operation which HVAC designer provides to the automatic control
engineer
Economizer – cooling regime
Example of SEQUENCE OF OERATIONS:
If TOA < Tset-point open the fresh air damper the maximum position
Then, if Tindoor air < Tset-point start closing the cooling coil valve
If cooling coil valve is closed and T indoor air < Tset-point start closing the damper
till you get T indoor air = T set-point
Other variations are possible