overcurrent and overload devices

Upload: gratzredoble

Post on 02-Apr-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Overcurrent and Overload Devices

    1/36

    OVERCURRENT

    DEVICE TYPES

  • 7/27/2019 Overcurrent and Overload Devices

    2/36

    Standard (Non-Time Delay, Single Element) Fuses

    Standard fuses protect against short circu

    and ground faults using thermal features sense a heat buildup in the circuit.

    Once blown, standard fuses are no longeusable and must be replaced.

  • 7/27/2019 Overcurrent and Overload Devices

    3/36

    Standard (Non-Time Delay, Single Element) Fuses

    The NEC allows standard fuses as overcurrent protectiodevices sized up to a maximum of 300% of the motorsallow the motor to start.

    An exception allows the use of the next higher size fusthe table value does not correspond to a standard size

    An additional exception allows the use of the next size device until an adequate size is found if the motor will without operating the device.

    Standard fuses will hold 500% of their current rating foapproximately one-fourth of a second.

  • 7/27/2019 Overcurrent and Overload Devices

    4/36

    Standard (Non-Time Delay, Single Element) Fuses

  • 7/27/2019 Overcurrent and Overload Devices

    5/36

    Standard (Non-Time Delay, Single Element) Fuses

    NOTES: Some special standard fuses will hold 500% of their cu

    rating for up to two seconds.

    In order for a standard fuse to be used as motor overloprotection, the motor would have to start and reach its

    speed in one-fourth of a second or less.

  • 7/27/2019 Overcurrent and Overload Devices

    6/36

    Standard (Non-Time Delay, Single Element) Fuses

    NOTES: Some special standard fuses will hold 500% of their cu

    rating for up to two seconds.

    In order for a standard fuse to be used as motor overloprotection, the motor would have to start and reach its

    speed in one-fourth of a second or less. Standard fuses will not generally provide any overload

    protection for hard starting installations because they msized well above 125% of a motors FLA to allow the mstart.

  • 7/27/2019 Overcurrent and Overload Devices

    7/36

    Time-Delay (Dual Element) Fuses

    These are generally dual element fuses w

    both thermal and instantaneous trip featuthat allow the motor starting current to flfor a short time without blowing the fuse

  • 7/27/2019 Overcurrent and Overload Devices

    8/36

    Time-Delay (Dual Element) Fuses

    NOTES: Time delay fuses can also be used to provide some deg

    overload protection which standard fuses cannot.

    The NEC allows time delay fuses to be sized up to a mof 175% of a motors FLA for overcurrent protection.

    Time-delay fuses will hold 500% of their amp rating foseconds which will allow most motors to start without othe circuit.

  • 7/27/2019 Overcurrent and Overload Devices

    9/36

    Time-Delay (Dual Element) Fuses

    Under normal conditions, a 100-amp time

    delay fuse will start any motor with a lockrotor current rating of 500 amps or less.

  • 7/27/2019 Overcurrent and Overload Devices

    10/36

    Inverse Time Circuit Breakers

    Inverse time circuit breakers

    have both thermal andinstantaneous trip featuresand are preset to trip atstandardized levels.

    This is the most commontype of circuit breaker used inthe building trades forresidential, commercial, andheavy construction.

  • 7/27/2019 Overcurrent and Overload Devices

    11/36

    Inverse Time Circuit Breakers

    NOTES:

    The thermal action of this circuit breaker responds to h

    If a motors ventilation inlets and outlets are not adequdissipate heat from the windings of the motor, the heatdetected by the thermal action of the circuit breaker.

  • 7/27/2019 Overcurrent and Overload Devices

    12/36

    Inverse Time Circuit Breakers

    NOTES:

    If a short should occur, the magnetic action of the circubreaker will detect the instantaneous values of current the circuit breaker.

    The National Electrical Code requires inverse time circu

    breakers to be sized to a maximum of 250% of the mo

  • 7/27/2019 Overcurrent and Overload Devices

    13/36

    Inverse Time Circuit Breakers

    NOTES:

    The thermal action of this circuit breaker responds to h

    If a motors ventilation inlets and outlets are not adequdissipate heat from the windings of the motor, the heatdetected by the thermal action of the circuit breaker.

  • 7/27/2019 Overcurrent and Overload Devices

    14/36

    Inverse Time Circuit Breakers

    NOTES:

    The rating of an inverse time circuit breakcan be multiplied by 3 and this totalamperage will start any motor with lesslocked-rotor amperage.

  • 7/27/2019 Overcurrent and Overload Devices

    15/36

    Inverse Time Circuit Breakers

  • 7/27/2019 Overcurrent and Overload Devices

    16/36

    Instantaneous Trip Circuit Breakers

    Instantaneous trip circuit breakers respond toimmediate (almost instantaneous) values of curr

    from a short circuit, ground fault, or locked rotorcurrent.

  • 7/27/2019 Overcurrent and Overload Devices

    17/36

    Instantaneous Trip Circuit Breakers

    NOTES: This type of circuit breaker will never trip from a slow heat b

    due to motor windings overheating.

    A stuck bearing or a blanket of lint covering the inlets and othe motors enclosure will cause the motor to overheat and

    the windings.

  • 7/27/2019 Overcurrent and Overload Devices

    18/36

    Instantaneous Trip Circuit Breakers

    NOTES:

    The National Electrical Code allows instantaneous trip circuito be sized to a maximum of 800% of a motors FLA value.

    They are used where time-delay fuses set at five times theircircuit breakers at three times their rating will not hold the s

    current of a motor.

  • 7/27/2019 Overcurrent and Overload Devices

    19/36

    Instantaneous Trip Circuit Breakers

    NOTES:

    Some instantaneous trip circuit breakers have adjustable tri

    The instantaneous trip ratings of an instantaneous trip circucan be adjusted above the locked-rotor current of a motor tthe motor to start and come up to its running speed.

  • 7/27/2019 Overcurrent and Overload Devices

    20/36

    Instantaneous Trip Circuit Breakers

    Example:

    An instantaneous trip circuit breaker can be set at 700 ampsa motor with a locked-rotor current of 650 amps to start.

  • 7/27/2019 Overcurrent and Overload Devices

    21/36

  • 7/27/2019 Overcurrent and Overload Devices

    22/36

    Motor Overload Protection

    Motors larger than 1 horsepower must be provided separatoverload protection devices.

    The most common devices typically used include:

    1) magnetic or thermal overload devices

    2) electronic overload relays

    3) fuses

  • 7/27/2019 Overcurrent and Overload Devices

    23/36

    Magnetic & Thermal Overloads

    Overload devices are usually located in the motors starter aconnected in series with the motors electrical supply circuitbe operated by either magnetic or thermal action.

    The same amount of current passes through the overload rethe motor.

    If the current or heat through the overload device is higher devices rating, it trips and shuts down the electric power tomotor.

  • 7/27/2019 Overcurrent and Overload Devices

    24/36

    Magnetic Overload Relays

    A magnetic overload relay is an electro-mechanical relay opethe current flow in a circuit.

    When the level of current in the circuit reaches a preset valuincreased magnetic field opens a set of contacts.

    Electromagnetic overload relays operate on the magnetic acthe load current flowing through a coil.

  • 7/27/2019 Overcurrent and Overload Devices

    25/36

    Magnetic Overload Relays When the load current becomes too high, a plun

    is pulled up into the coil interrupting the circuit.

    The tripping current is adjusted by altering the inposition of the plunger with respect to the coil.

  • 7/27/2019 Overcurrent and Overload Devices

    26/36

    Thermal Overload Relays

    A thermal overload relay is an electro-mechanical relay thatoperated by heat developed in the relay.

    When the level of current in a circuit reaches a preset valueincreased temperature opens a set of contacts.

    The increased temperature opens the contacts through a bistrip or by melting an alloy that activates a mechanism that contacts.

    Two types include melting alloy and the bi-metallic strip.

  • 7/27/2019 Overcurrent and Overload Devices

    27/36

    Melting-Alloy Thermal Overload Relays:

    These are probably the most popular type ofoverload protection.

  • 7/27/2019 Overcurrent and Overload Devices

    28/36

    Thermal Overload Relays

    The motor current passes through a small heater winding anoverload conditions, the heat causes a special solder to mela ratchet wheel to spin thus opening the control circuit cont

    Must be reset by hand operation

    Heater coil and solder pot in one unit: non-tamperable

  • 7/27/2019 Overcurrent and Overload Devices

    29/36

  • 7/27/2019 Overcurrent and Overload Devices

    30/36

    Bimetallic Thermal Overload Relays:

    When an overload occurs, the heat causes the bimetal to deactuate a tripping mechanism which opens a set of contactscontrol circuit interrupting power to the coil and opening thcontacts.

    Most relays are adjustable over a range from 85% to 115% ovalue.

    They are available with ambient compensation. An ambientcompensated devices trip point is not affected by ambienttemperature and performs consistently at the same value of

  • 7/27/2019 Overcurrent and Overload Devices

    31/36

    Automatic Reset Devices

    Automatic reset is an advantage where thestarter is inaccessible and the motor is providthree wire control from a magnetic starter.

  • 7/27/2019 Overcurrent and Overload Devices

    32/36

    Automatic Reset Devices

    This control doesnt allow the motor to restart until the star

    button is manually pushed.

    This permits the overload condition to be removed before trestarts.

  • 7/27/2019 Overcurrent and Overload Devices

    33/36

    Electronic Overloads

    Electronic overloads sense the load current and the heating

    the motor is computed.

    If an overload condition exists, the sensing circuit interruptspower circuit.

    The tripping current can be adjusted to suit the particular applicat

    Electronic overloads often perform additional protective functions

    ground fault and phase loss protection.

  • 7/27/2019 Overcurrent and Overload Devices

    34/36

    Fuses

    Fuses have limited application as the primary means of overload

    for motors but can be effectively used to provide back up overloprotection.

    Single-element fuses are not designed to provide overload prote

    Their basic function is to protect against short circuits and groun

    If sized to provide overload protection, they would blow when thstarts due to high motor inrush current.

    Dual-element fuses can provide motor overload protection, but to be replaced when they blow which can be a disadvantage.

    There is a risk of single-phasing damage to the motor when onlyblows unless single-phase protection is provided.

  • 7/27/2019 Overcurrent and Overload Devices

    35/36

    Fuses: Overload Trip Time

    The time it takes an overload to trip dependsthe length of time the overload current exists

  • 7/27/2019 Overcurrent and Overload Devices

    36/36

    Fuses

    A Heater Trip Characteristics chart shows the relationship be

    the time an overload takes to trip and the current flowing incircuit based on the standard 40C ambient temperature inst

    The larger the overload (horizontal axis), the shorter the timrequired to trip the overload (vertical axis).

    Any change from ambient temperature affects the tripping toverload.

    For temperatures higher than 40EC, the overloads trip at a crating less than the value of the overload.