packed tower internals guide

56
 Packed Tower Internals Guide

Upload: rexx-mexx

Post on 04-Nov-2015

63 views

Category:

Documents


1 download

DESCRIPTION

Packed Tower Internals Guide

TRANSCRIPT

  • Packed Tower Internals Guide

  • TABLE OF CONTENTS

    Introduction Packed Tower Internals Guide

    A. Liquid Distributors Liquid Distributors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1Intalox Distributors for Demanding Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-5Model 106/107 Intalox Pan Distributor/Redistributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-6Model 116/117 lntalox Deck Distributor/Redistributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-7Model 126/127 Intalox Trough Distributor/Redistributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-8Model 136/137 Intalox Pan or Trough Distributor/Redistributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-9Model 166 Intalox Trough Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-10Model 186 Intalox Trough Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-11Traditional Distributors for Absorption, Stripping, or Heat Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-12Model 845 Pan Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-13Model 798 Pan Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-14Model 816/817/916/917 Deck Distributor/Redistributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-15Model 806 Trough Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-16Model 1016/1017 Trough Distributor/Redistributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-17Model 844 Pipe-Arm Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-18Model 1044 Spray-Type Liquid Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-19

    B. Feed Devices Feed Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1Model 119/129 Liquid Only Feed Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-3Model 719/729 Liquid Only Feed Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-4Model 755 Flashing Feed Gallery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-5Model 855 Flashing Feed Chamber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6Model 955 Flashing Feed Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-7Model 196 Vapor Diffuser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-8Model 198 Vapor Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-9Model 896 Vapor Distributor Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-10

    C. Bed Limiters Bed Limiters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1Model 823 Bed Limiter for Random Packing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2Model 103 Non-Interfering Bed Limiter for Random Packing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-3Model 133 Bed Limiter for Structured Packing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-3

    D. Support Plates Support Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-1Model 818 Gas Injection Support Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-2Model 804 Gas Injection Support Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-3Model 809 Light Duty Support Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-4Model 819/1019 Gas Injection Support Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-5Model 134 Support Grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D-6

    E. Collector Plates Liquid Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-1Model 633 Chevron-Type Liquid Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-2Model 733 Trough Liquid Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-3Model 833 Deck Liquid Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E-4

    F. Liquid/Liquid Extraction Liquid/Liquid Extraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F-1Model 834 Disperser/Support Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F-2Model 835 Disperser/Support Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F-3Model 644 Dispersed-Phase Feed Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F-4Model 744 Continuous-Phase Distributor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F-4

    G. Other Topics Typical Tower Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G-1General Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G-2Materials of Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G-3Special Tower Internals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G-4Other Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G-5

  • PACKED TOWER INTERNALS GUIDE

    Saint-Gobain NorPros (formerly NortonChemical Process Products Corporation)dedication to providing state-of-the-artmass transfer equipment has resulted inmajor developments with packed towerinternals. Liquid distribution has long beenregarded as the key to precise packedtower performance. Saint-Gobain NorPromade the commitment to determine whatfactors are really important toward perfect liquid distribution. We installed a10 ft [3 m] diameter by 40 ft [12 m] tallhydraulic simulation column at ourresearch facility. With this column, westudy the effects of various liquid andvapor flow rates. The result: Saint-GobainNorPro confidently designs internals forany size tower from the beginning withoutthe need to test each internal before shipping, although such testing is available on request.

    We recognize that not all packed towersrequire state-of-the-art liquid distributionuniformity. For those towers, we still offerour traditional style internals. The traditional style internals have been usedfor many years in services that requirematerials ranging from carbon steel to zirconium, thermoplastics, fiberglass,graphite and ceramics.

    This guide is intended to assist in the selection of appropriate towerinternals for use in packed towers. Thewide range of applications does notallow us to cover all the choices andvariation Saint-Gobain NorPro offers.As always, we offer our expertise incustom design of proper equipmentfor your exact requirements. Call onour application experience to helpsolve your mass transfer needs.

  • LIQUID DISTRIBUTORS

    Introduction

    Liquid distributors are used in packed towers above each bed of packing.

    The liquid distributor is located above the bed, usually 6 to 8 in. [150 200 mm] above the packing. This provides sufficient space for the gas to disengage from the bed before it passes through the distributor.

    An ideal distributor possesses the following attributes, each with a specificeffect on the overall performance of apacked tower:

    Uniform liquid distribution Resistance to plugging or fouling Proper turndown capability Low gas pressure drop Minimal distributor height to allow

    more packed bed heights

    Cross-mixing capability

    The introduction of high performancetower packings in the early 1980s accentuated design deficiencies of distributors available at the time. Inresponse, Saint-Gobain NorPro introduceddistributors with attributes designed to correct these deficiencies. These attributesare well-understood by us and have beenincorporated in NorPro Intalox

    distributors.

    We offer two major categories of liquid distributors to meet the requirementsof specific applications. In determiningwhich category to choose, it is necessaryto know how sensitive the tower perform-ance is to distribution uniformity. Will aslight variation of distribution quality significantly affect the tower performance?

    As a rule:

    NorPro Intalox distributorsUsed primarily for distillation services, typically where a high-efficiency packing (IMTP randompacking, Intalox wire gauze orIntalox structured packing) is used.Deep beds of any type of packingrequire Intalox distributors to maximize performance.

    NorPro traditional distributorsUsed for most absorption, stripping,and heat transfer services. Serviceswhere a traditional packing (Pallrings, Hy-Pak packing, Intalox

    saddles, Raschig rings, etc) isused will usually use these less costly distributors.

    Redistributors share the same mechanicaldesign characteristics as distributors, butthey also include gas riser covers and pos-sibly wall wipers to collect all liquid rainingdown from the packing above. The ques-tion of when to redistribute liquid is noteasy to answer.

    There are four reasons to have more thanone bed of packing in a tower: feed introduction, liquid cross-mixing, distribu-tion correction and product side-draws.Introduction of a feed (liquid or vapor) intoa tower with packing above and belownearly always requires a split in the bedsfor a redistributor.

    An important factor to keep in mind withthe introduction of an external feed is thatof mixing (homogenization of compositionor temperature). Mixing of liquid should beconsidered when:

    A tower has deep beds or; A feed is sub-cooled more than

    30 F [17 C] or;

    A feed composition differs from theinternal flow

    Cross-mixing is an optional feature onmost of our trough-type redistributors. Byeliminating the need for liquid collection ina separate collector plate, the cross-mixingoption saves equipment and frees towerspace for more packing.

    Based on our operating experience, a conservative rule-of-thumb to use whendetermining maximum depth is: A packedbed should be no higher than 15 times the tower diameter and contain less than20 theoretical stages. With proper attention to initial distribution uniformity,bed depths may be greater. However, we do not recommend exceeding this limitwithout consulting a Saint-Gobain NorProtechnical representative.A-1

  • LIQUID DISTRIBUTORS

    Distribution Quality

    Perfect liquid distribution could be definedas providing equal liquid rate per unit areaof the packed bed surface. Many practicalfactors restrict the achievement of this.

    Liquid can be applied by sprays, weirs, ororifices. Sprays can almost totally wet thesurface of a packed bed, but the point-to-point flow variation is high. Weir distribu-tors provide discrete streams but flow variation is difficult to control. Orifice distributors direct liquid to packing in discrete streams. Perfection requires aninfinite number of streams each of equalflow. However, orifice size, fouling considerations, and mechanical construc-tion details prevent high unit area pointcount from being achieved.

    Intalox distributors aim toward perfection:

    (a) Orifices are laid out on a triangularpattern, (preferred) or on a squarepattern, uninterrupted by gas chimneys or mechanical supports,properly spaced to the vessel wall.

    (b) Liquid flow from each orifice is nearly equal to all others.

    NorPro traditional distributor patterns arenot as good as Intalox patterns. The number of distribution points per unit areais generally below that of an Intalox distributor. Flow variations among the distribution points are greater than allowedfor Intalox distributors. However, the traditional distributors have been used suc-cessfully for many years in a wide range ofprocesses.

    Saint-Gobain NorPro developed a distributor rating system for quantifyingdistribution quality, or performance. Werate distribution uniformity as a percent-age, where 100% indicates ideal uniformdistribution and low percentage ratingsindicate that parts of the tower receive a liquid flow significantly different fromother parts.

    For more information regarding our rating system, request a copy of the publication, Liquid and Gas Distribution in Commercial Packed Towers.

    The significance of our distribution qualityrating system is that the distributor ratingcorrelates with tower performance.

    A tower containing deep beds of high-efficiency packing is sensitive to liquid distribution quality, whereas a tower containing shallow beds of a traditionalpacking is less sensitive to distributionquality.

    Stages Per Bed WithSystem Base HETP

    20

    16

    12

    8

    4

    10 20 30 40 50 60 70 80 100900

    The effect of liquid distribution quality on towerperformance is shown by these actual results:

    Distribution Quality (%)

    Act

    ual S

    tag

    es P

    er B

    ed o

    f P

    acki

    ng

    2

    4

    6

    8

    10

    12

    14

    16

    18

    20

    0

    Intalox distributors are always recommended in:

    High purity product distillation services

    Distillation services operating closeto minimum reflux

    Heat transfer services with closetemperature approach

    Services with high stage count per bed

    TOWER PERFORMANCE CORRELATES WITH DISTRIBUTION QUALITYA-2

  • IMTP PackingNo. 25/40/50/60/70

    Intalox Structured Packing1.5T/2T/3T/4T/5T

    5.6 7.5 pts/ft2

    60 80 pts/m2

    IMTP PackingNo. 15

    Intalox Structured Packing1T

    5.6 9.3 pts/ft2

    60 100 pts/m2

    Intalox Structured PackingHS-10 / HS-20

    7.9 10.2 pts/ ft2

    85 110 pts/m2

    Intalox Wire Gauze Packing

    9.3 11.1 pts/ ft2

    100 120 pts/m2

    LIQUID DISTRIBUTORS

    Point Count

    The number of distribution points per unitarea has an influence on the efficiency ofthe uppermost part of a packed bed.When using larger packings, with relativelylow efficiency, the effect of the number ofdistribution points is insignificant. However,the effect can be considerable when usingsmaller, high-efficiency packings.

    Saint-Gobain NorPro has establishedguidelines for Intalox distributors with high-performance packings as shown below.

    In practice, a lower number of distributionpoints per unit area may be the only way ofachieving acceptable orifice diameters.

    The number of distribution points per unitarea can be designed as required; however, mechanical considerations usually limit the number to about 18.6 pts/ft2 [200 pts/m2].

    Cross Flow

    As the liquid rate on a distributor isincreased, its cross flow capability and itsprimary (pre) distribution system becomemore important.

    The cross flow capability of a distributorreflects its ability to balance liquid from onepart of the distributor to another. It isimportant to balance liquid on all gravity-fed distributors. However, at high specificliquid rates the liquid cross flow capacitymust be large to correct for system imperfection.

    The primary distribution of liquid into a distributor has been shown to have a significant effect on overall distributor performance. It is important that the feedsystem meters flow to one or more appropriate points without excessive turbulence or horizontal velocity. This isachieved by use of feed pipes and/or parting boxes. The design of the primarydistribution system becomes increasinglycomplex as the specific liquid rate and thecolumn diameter increase.

    Fouling

    If a distributor is to perform correctly it isimportant that metering devices (orifices orweirs) do not become fouled, since foulingsignificantly reduces packing performance.

    There are several mechanisms of distributor fouling: polymerization, sedimentation, coking, scale, debris, etc.All precautions to eliminate fouling outsidethe column should be adopted since external strainers are far easier to cleanthan distributors. Regardless, the distributor should be considered for itsdegree of fouling resistance.

    V-shaped weirs are less prone to blockagethan orifices; orifices in a side wall are generally less prone to blockage than orifices in the bottom of a distributor; orifices protected by an orifice strainer areless prone to blockage by a particulatematerial than unprotected orifices. Orificestrainers are not recommended in systemsthat tend to coat surfaces.

    NorPro Intalox distributors with bottom orifices are not normally recommended fororifice sizes of 0.25 in. [6 mm] or less dueto their fouling propensity. Intalox distribu-tors designed with weirs may have flowvariation outside the high-performancerange.

    The list below ranks the fouling resistanceof the various metering arrangements atany given flow rate (most resistant - top, to least - bottom):

    V weir/spray Slotted weir Side wall orifice with orifice strainer Side wall orifice Bottom orifice with orifice strainer Bottom orifice

    Orifice strainers can protect a distributorfrom fouling with particulate matter such aswall/pipe scale. Each orifices flow passesthrough a higher-surface-area strainerbefore approaching the metering orifice.However, orifice strainers are not effectivewhen fouling material pastes, coats orsticks to metal. Other effective methods ofprotecting distributors from fouling includeusing sidewall orifices (positioned up from the bottom of the distributor) or using weirs.

    INTALOX DISTRIBUTOR POINT COUNTA-3

  • LIQUID DISTRIBUTORS

    Operating Range

    A distributor will generally give its best performance at liquid rates close to 100%of design flow, with the performance deteriorating as the liquid rate is reduced.At 100% design flow, NorPro Intalox distributors usually give a flow variation atany point of the distributor of better than5% and at minimum rates better than8%. This will generally give an operatingrange of 2:1 for a single-level orifice distributor. If the minimum rate specifica-tion is such that a wider flow variation canbe accepted, then a wider operating rangeis possible.

    NorPro traditional distributors operatewith much higher flow variations over atypically broader range of operations thanIntalox distributors.

    Figure 2 shows the flow variation for theflow through a single-level orifice. The useof a multi-level orifice enables the flow variation for the Intalox distributor to bemaintained over a very wide operatingrange.

    Special designs of Intalox distributors canbe made for processes requiring lower flowvariations. Designs of better than 3% at100% design rate and better than 5% ata 2:1 turndown are feasible. These designswill generally include special primary distribution systems (feed pipes, partingboxes, etc.)

    Orifice Size

    In gravity-fed orifice distributors, the orificesize is dependent mainly upon the holecount, the specific liquid rate and the liquid head. For Intalox distributors with an operating range of 60 to 120% of thedesign flow, the approximate orifice size isindicated in Figure 3.

    % Liquid Load

    Traditional Distributors

    Intalox Distributors

    Design Range

    IncreasedFlow

    Variation

    IntaloxDistributors

    Criteria

    Turndown 100%Design Turnup

    Flo

    w V

    aria

    tion

    FloodedDistributors

    11.2 PTS

    /ft2 (120

    PTS/M

    2 )

    No

    rmal

    Flo

    w (g

    pm

    /ft2

    )

    Orifice Diameter (inches)

    4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 2410080

    6050

    40

    30

    20

    10

    8

    654

    3

    2

    10.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

    9.3 PTS/f

    t2 (100

    PTS/M

    2 )

    7.4 PTS/f

    t2 (80 P

    TS/M2 )

    5.6 PTS/f

    t2 (60 P

    TS/M2 )

    Orifice Diameter (mm)

    250200

    150

    100

    50

    25

    20

    15

    10

    5

    (m

    3 /h

    m2 )

    EFFECT OF OPERATING RANGE

    APPROXIMATE ORIFICE SIZING

    Figure 2

    Figure 3A-4

  • INTALOX DISTRIBUTORS

    A specific Intalox distributor is chosen byconsidering tower diameter, flow rate, turndown ratio, available height and foulingresistance. Each distributor style featuresdesign options which adapt it to a particular application.

    The table to the right provides a preliminarychoice of a distributor suitable for yourservice conditions. A detailed descriptionthat will enable a final selection to be madeis given on the following pages. Consultyour Saint-Gobain NorPro representativefor assistance or for final confirmation.

    ColumnDiameterin. [mm]

    10 - 36[250 - 900]

    > 36 [900]

    *Flow variation will be outside normal Intalox distributor parameters.

    Specific Liquid Rategpm/ft2

    [m3/hm2]

    SystemFouling

    TendencyTurndown

    RatioSuggested

    Model

    < 0.3 gpm/ft2[0.75 m3/hm2]

    0.3 - 2 gpm/ft2[0.75 - 5 m3/hm2]

    2 - 12 gpm/ft2[5 - 30 m3/hm2]

    > 12 gpm/ft2[30 m3/hm2]

    > 0.8 gpm/ft2[2 m3/hm2]

    Low

    Low/Medium

    LowMedium

    High

    < 10:1

    2:12:1 - 10:1

    < 10:1

    2:1< 10:1

    < 10:1

    < 10:1< 10:1

    136 Special

    136

    106136136

    106136 Special

    136 with weirs*

    Low

    Medium

    0.3 - 2 gpm/ft2[0.75 - 5 m3/hm2]

    2 - 12 gpm/ft2[5 - 30 m3/hm2]

    > 12 gpm/ft2[30 m3/hm2]

    LowMedium

    LowMedium/High

    Low

    MediumHigh

    2:12:1 - 10:1

    < 10:1< 10:1

    2:1< 10:1

    186 Special166

    136 or 186166

    126136 or 186136 or 186

    166

    116136 Special

  • MODEL 106/107 INTALOX PAN DISTRIBUTOR/REDISTRIBUTOR

    Diameters 10 - 36 in. [250 900 mm]

    Orifices in base Liquid rates above 2 gpm/ft2

    [5 m3/hm2]

    The pan-type construction of the Model106 Intalox distributor and Model 107Intalox redistributor is designed for towersless than 36 in. [900 mm] ID with minimumliquid rates in excess of 2 gpm/ft2

    [5 m3/hm2]. Lower rates can be accom-modated but the Models 136/137 shouldbe considered first. This distributor can be leveled. In towers less than 24 in. [600 mm] ID, one-piece construction, for installation through a body flange, isstandard. A special multi-piece construction is available upon request.

    Orifices in the pan bottom are arranged toprovide optimum distribution quality, withgas risers set between the orifices. Smalldiameter pans may not have gas risers asgas passage is provided in the gapbetween the pan and the vessel wall.When used for higher flow rates, this distributor will have large orifices that willnot tend to foul. For lower flow rates, orifice strainer caps or the Model 136/137should be considered if the system is fouling. The standard turndown range is 2:1.

    For single-phase liquid feeds to the distributor, a feed pipe to control feedvelocity to the deck is required. Two-phaseliquid and vapor feeds require a flashingfeed device to adequately separate phases and assure proper liquid feedvelocity. Refer to Liquid/Vapor FeedDevices, Section B, for selection assistance.

    The Models 106/107 are available in anyweldable sheet metal. Carbon steel is notrecommended except for very high liquidrates where orifice corrosion will not significantly affect distribution quality. FRP and thermoplastic construction areavailable, although such constructionreduces distribution quality.

    Standard connection to the tower wall isby bolting to clips. Optionally, the distribu-tor can be suspended from a ring trappedbetween body flanges. Setting the distributor on an annular ring is not recommended.

    All joints in multi-piece pans are gasketed.See Section G for material requirements.

    The standard design for a Model 107redistributor includes gas riser covers anda weld-on wall wiper, as shown below.

    Orifice strainers Expandable and gasketed wall

    wiper (Model 107)

    Suspended mounting Non-standard point count

    (See Page A-3)

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Support cliparrangement

    Height varies with turndown.

    OF FEEDINLETNOZZLEWHEN USED

    CL

    40mm

    15mm DIA. HOLE

    120.0 REF.

    A

    B

    18"[450]

    12"[300]

    Model 106

    Model 107

    60.0 REF.A-6

  • MODEL 116/117 INTALOX DECK DISTRIBUTOR/REDISTRIBUTOR

    Diameters greater than 36 in. [900 mm]

    Liquid rates above 12 gpm/ft2[30 m3/hm2]

    Orifices in deckThe Model 116 Intalox distributor andModel 117 Intalox redistributor are for tow-ers with minimum liquid rates in excess of12 gpm/ft2 [30 m3/hm2]. Lower rates canbe accommodated by Models 126/127 or136/137.

    The deck-type construction allows goodliquid cross-flow between gas risers whichare set between orifices specifically spacedfor distribution quality. Because this platenormally handles higher liquid flow rates,the orifices are usually large and do nottend to foul. The standard turndown rangeis 2:1.

    For single-phase liquid feeds to the distributor, use a feed pipe to control feedvelocity. Two-phase liquid-vapor feedsrequire a flashing feed device to adequate-ly separate phases and assure proper liquid feed velocity. Refer to Liquid/VaporFeed Devices, Section B, for selectionassistance.

    The Models 116/117 are available in anyweldable sheet metal. Carbon steel is notrecommended except for very high liquidrates where orifice corrosion will not significantly affect distribution quality. FRP construction is available, although it reduces distribution quality.

    The Models 116/117 distributor areclamped onto an annular ring that is seal-welded to the tower wall, with clampsprovided. Hence, distributor levelness isdetermined by the ring levelness; we consider levelness tolerances in the116/117 design. All joints are gasketed.See Section G for ledge and materialrequirements.

    The standard design for a Model 117redistributor includes gas riser covers tocollect and redistribute liquid raining fromabove.

    Orifice strainers Anti-migration bars in gas risers Non-standard point count

    (See Page A-3)

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 116

    Height varies with turndown.

    Standard design passes through 18 in.[450 mm] nominal manway.

    Model 117

    A

    B

    14"[350]

    18"[450]A-7

  • MODEL 126/127 INTALOX TROUGH DISTRIBUTOR/REDISTRIBUTOR

    Diameters greater than 36 in. [900 mm]

    Orifices in base Liquid rates between 2 and

    16 gpm/ft2 [5 40 m3/hm2]

    The Model 126 Intalox distributor andModel 127 redistributor are designed fortowers greater than 36 in. [900 mm] IDwith minimum liquid rates in excess of 2 gpm/ft2 [5 m3/hm2]. Lower rates can beaccommodated but the Models 136/137should be considered first. For systemswith liquid rates in excess of 12 gpm/ft2

    [30 m3/hm2] the Model 116/117 should be considered first.

    The trough-type construction allows easyliquid sealing and distributor leveling, which is essential in large diameter towers.Because this distributor normally handlesintermediate liquid flow rates, the orificesare usually large enough to allow moderatefouling resistance. If the system is foulingand/or the orifices are small, orifice strainercaps or the Model 136/137 should be considered. The standard turndown range is 2:1.

    For single-phase liquid feeds to the distributor, use a feed pipe to control feedvelocity. Two-phase liquid-vapor feedsrequire a flashing feed device to adequate-ly separate phases and assure proper liquid feed velocity. Refer to Liquid/VaporFeed Devices, Section B, for selectionassistance.

    The Models 126/127 are available in anyweldable sheet metal. Carbon steel is notrecommended except for very high liquidrates where orifice corrosion will not significantly affect distribution quality. TheModel 126/127 rests on an annular ring oris suspended from a ring or beams. Alljoints are gasketed. See Section G forledge and material requirements.

    FRP or thermoplastic construction is available, although use of these materialsmay reduce distributor performance.Thermoplastic construction may be limitedto spans of less than 6 ft [2 m], depending on operating temperatures.

    The standard design for a Model 127redistributor includes a weld-on wall wiperand gas riser covers to collect and redistribute liquid raining from above. FRPand thermoplastic construction require aproperly designed wall wiper field connected/bonded to the vessel wall.

    Cross-mixing capability Orifice strainers Leveling screws Non-standard point count

    (See Page A-3)

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 126

    Height varies with turndown.

    Standard design passes through 18 in.[450 mm] nominal manway.

    Model 127

    A

    B

    20"[500]14"

    [350]A-8

  • MODEL 136/137 INTALOX PAN OR TROUGH DISTRIBUTOR/REDISTRIBUTOR

    Diameters greater than 10 in. [250 mm]

    Side-wall orifices High turndown ratio Standard liquid rates between 0.3

    and 12 gpm/ft2 [0.75 30 m3/hm2]

    The Model 136 Intalox distributor andModel 137 Intalox redistributor are for towers greater than 10 in. [250 mm] IDwith liquid rates between 0.3 and 12 gpm/ft2 [0.75 - 30 m3/hm2] where fouling protection and/or high turndown isrequired. Special designs can handle liquidrates from 0.08 to 0.3 gpm/ft2

    [0.2 - 0.75 m3/hm2]; for these cases, theModel 120 strainer basket should be considered to protect the small flow orifices. Special designs can also handleliquid rates above 12 gpm/ft2 [30 m3/hm2].

    The Models 136/137 are usually constructed as pans for diameters below30 inches [750 mm] and as troughs fordiameters above 30 inches [750 mm]. Thestandard turndown for a single sidewall orifice is 2:1; however, the turndown range can be extended by using two orthree orifices at different levels of the same discharge point. Turndown ratios up to 10:1 are achievable. The liquid fromeach discharge point is conducted into the lower vapor velocity region below thedistributor troughs. This results in lowentrainment levels.

    The resistance to fouling of this distributoris higher than that of deck-type distributorsbecause it features a debris collection zonebelow the sidewall orifices. Weirs can beused as an alternative to orifices in highfouling systems. However, flow variationwill be outside normal Intalox parameters.

    For single-phase liquid feeds to the distributor, a feed pipe or a feed pipe/parting box combination is required tocontrol feed velocity to the troughs. Two-phase liquid-vapor feeds require useof a flashing feed device to adequatelyseparate phases and assure proper liquidfeed velocity. Refer to Liquid/Vapor FeedDevices, Section B, for selection assistance.

    The Models 136/137 are available in anyweldable sheet metal. Carbon steel is notrecommended except for very high liquidrates where orifice corrosion will not significantly affect distribution quality.Thermoplastic construction is available,although such construction reduces distribution quality.

    The Model 136/137 rests on an annularring or is suspended from beams or clips.All joints are gasketed. See Section G forledge and material requirements.

    All distributors and redistributors includeoverflow orifices which help prevent distributor flooding during liquid surges.

    The standard design for a Model 137redistributor includes a weld-on wall wiperon the vessel wall and gas riser covers tocollect and redistribute liquid raining downfrom above.

    Cross-mixing capability (in towersgreater than 55 in. [1400 mm] ID)

    Orifice strainers Leveling screws Expandable and gasketed wall wiper

    (small Model 137)

    Non-standard point count(See Page A-3)

    CONSTRUCTION DETAILS

    DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 136

    Height varies with turndown.

    Standard design passes through 18 in.[450 mm] nominal manway.

    Model 137

    14"[350]

    20"[500]

    A

    BA-9

  • MODEL 166 INTALOX TROUGH DISTRIBUTOR

    Diameters greater than 30 in. [750 mm]

    Sidewall orifices with flow pointmultipliers

    Liquid rates between 0.2 and 4.0gpm/ft2 [0.5 10 m3/hm2]

    The Model 166 Intalox distributor is fortowers greater than 30 in. [750 mm] IDwith liquid rates between 0.2 and 4.0 gpm/ft2 [0.5 - 10 m3/hm2]. Thetroughs on the Model 166 liquid distributormeter liquid accurately at 0.8 - 2 points per ft2 [9 - 20 points per m2] through sidewall orifices. Because of the low pointdensity, the sidewall orifices are as large as possible for fouling resistance. The conductor tubes from each metering orificedischarge the liquid to spreading plates orchannels that greatly multiply the 0.8 - 2points/ft2 [9 - 20 points/m2] into many moredrip points before the liquid is releasedonto the packing.

    The standard turndown ratio of the Model166 liquid distributor with single-level orifices is 2:1; however, the turndownrange can be extended by using two orthree orifices at different levels for eachconductor tube.

    For single-phase liquid feeds to the distributor, a feed pipe or a feed pipe/parting box combination is required tocontrol feed velocity to the troughs. Two-phase liquid-vapor feeds require useof a flashing feed device to adequatelyseparate phases and assure proper liquid feed velocity. Refer to Liquid/VaporFeed Devices, Section B, for selectionassistance.

    The Model 166 liquid distributor is available in any weldable sheet metal.Carbon steel is not recommendedbecause of the potential for metering orifice corrosion. The Model 166 is suspended from beams or clips and isalways leveled during installation. Orificestrainers can be used over the primary distribution orifices.

    Orifice strainers

    DESIGN OPTIONSCONSTRUCTION DETAILS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Standard design passes through 18 in.[450 mm] nominal manway.

    Model 166

    A

    B

    HdA-10

  • MODEL 186 INTALOX TROUGH DISTRIBUTOR

    Diameters greater than 36 in. [900 mm]

    Sidewall orifice Standard liquid rates between 0.3

    and 8 gpm/ft2 [0.75 20 m3/hm2]

    The Model 186 liquid distributor is for towers greater than 36 in. [900 mm] IDwith liquid rates between 0.3 and 8 gpm/ft2

    [0.75 20 m3/hm2] where fouling protec-tion is required. Special designs can han-dle liquid rates from 0.08 to 0.3 gpm/ft2

    [0.2 0.75 m3/hm2]; for these cases, the Model 120 strainer basket should beconsidered to protect the small orifices.The standard turndown range of the Model186 is 2:1.

    The Model 186 liquid distributor is similarto the Model 136 liquid distributor, withtrough construction sidewall orifices, conductor tubes, and overflow orifices.Compared to the Model 136, however, theModel 186 distributor uses a parting boxover the distribution troughs instead of acenter trough at the same level as the lat-eral distribution troughs. The Model 186distributor therefore requires more columnheight, but it is easier to seal and requiresno gasket. Without the crossflow of a cen-ter trough, the parting box design is crucialto the Model 186 distributor performance.

    For singlephase liquid feeds to the distributor, a feed pipe is required to control feed velocity to the troughs. Two-phase liquid-vapor feeds require the use of a flashing feed device to adequatelyseparate phases and assure proper liquid feed velocity. Refer to Section B forselection assistance.

    The Model 186 is available in any weldable sheet metal. Carbon steel is not recommended because of the effect of minor corrosion on orifice flow characteristics.

    The Model 186 rests on an annular ring or is suspended from beams or clips. See Section G for ledge and materialrequirements.

    All distributors include overflow orificeswhich help prevent distributor flooding during liquid surges.

    Orifice strainers Leveling screws Non-standard point count

    (See Page A-3)

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Standard design passes through 18 in.[450 mm] nominal manway.

    A

    B

    Hd

    Model 186A-11

  • TRADITIONAL DISTRIBUTORS FOR ABSORPTION, STRIPPING, OR HEAT TRANSFER

    NorPro traditional distributors are used inapplications that are less demanding onpacking performance, such as generalheat transfer applications and absorptionand stripping services with less than fivetransfer units per bed.

    The traditional distributors generally havelower orifice count, less balanced liquidheads (lower liquid head with limited cross-flow capability) and less uniform distribution coverage than Intalox high-performance distributors.

    Tower size is the first consideration inselecting a traditional distributor. Typically,towers less than 39.37 in. [1 m] ID use apan-type distributor with orifices (Model845) or with weirs for fouling services (Model 798).

    Flow rate is the next consideration for distributor selection. Trough-type distribu-tors (Model 806) are recommended forseverely fouling services or low flow rateapplications because sealing is more reliable. Deck-type distributors (Model816/916) are best for high flow rates dueto their high cross-flow capacity. Higherflow rates also minimize the adverseeffects of leakage on overall performance.

    We offer two enclosed-type distributors(Model 844 and Model 1044). The Model844 is used in non-fouling services whereheight is limited in the feed zone and feedis liquid only. The Model 1044 with spray-style metering arrangement is used forfouling services where the towers externalfeed is liquid only. Neither device has anyredistribution capability. However, smallamounts of uniformly-distributed liquid may fall through the distributor from packing above without hydraulic or efficiency problems.

    The table shown gives the range of serviceconditions for each distributor model.Special designs may be possible if yourconditions fall outside the parameters listed.

    ModelNumber

    845

    816/817916/917

    806

    1016/1017

    1044

    Note: Liquid flow rates vary depending on diameter and gas flow rates; rates shown are typical.Do not confuse rates above with turndown see specific model number for turndown capability.Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    ColumnDiameterin. [mm]

    Liquid Flow Rategpm/ft2 [m3/hrm2]

    AllowableSystem Fouling

    Tendency

    < 48 [1200]

    < 48 [1200]

    > 12 [300]

    > 36 [900]

    > 55 [1400]

    1.0 - 30[2.5 - 75]

    1.0 - 8.0[2.5 - 20]

    0.8 - 50[2.0 - 120]

    best for > 10 [25]

    2 - 40[5 - 100]

    1 -20[2.5 - 50]

    Low/Med

    High

    844

    All

    1.5 - 10[4 - 25]

    798

    >17 [430]

    0.2 - 50[0.5 - 120]

    Low/Med

    Low/Med

    Low

    Low (Slotted)High (V)

    High(Special)

    SELECTION OF TRADITIONAL DISTRIBUTORSA-12

  • MODEL 845 PAN DISTRIBUTOR

    Diameters up to 48 in. [1200 mm] Liquid rates between 1 and 30

    gpm/ft2 [2.5 75 m3/hm2]

    Orifices in base The pan-type construction of the Model845 traditional distributor is designed fortowers less than 48 in. [1200 mm] ID withliquid rates between 1 and 30 gpm/ft2

    [2.5 - 75 m3/hm2]. In towers less than 15 in. [400 mm] ID, one-piece construc-tion, for installation through a body flange,is standard. A special multi-piece construction is available.

    Orifices are located in the pan bottom with gas risers set between the orifices. Atdiameters less than 19.7 in. [500 mm], thegas passage may be provided in the gapbetween the pan and the vessel wall,rather than by gas risers.

    The standard turndown range is 2.5:1.

    For liquid-only feeds to the distributor, usea feed pipe to control feed velocity. Two-phase liquid-vapor feeds require a flashingfeed device to adequately separate phasesand assure proper liquid feed velocity.Refer to Liquid/Vapor Feed Devices,Section B, for selection assistance.

    The Model 845 is available in any weldablesheet metal, thermoplastic or FRP material.PVC bolting is standard for multi-pieceFRP pans, although there are alternatives.

    The Model 845 distributor sits either on afull annular ring or lugs. Distributors withliquid rates below 4 gpm/ft2 (10 m3/hm2)are gasketed as standard. See Section Gfor ledge and material requirements.

    This distributor is not recommended for liquid redistribution; consider using theModel 817 instead.

    Corrosion allowance (metal only) One-piece construction in columns

    greater than 18 in. [450 mm] indiameter

    Gasketing for higher flow rates

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Standard design passes through 18 in.[450 mm] nominal manway.

    A

    B

    D

    7" - 11"[178 - 279]

    Model 845

    1 9/16" [40]A-13

  • TulrdpgHlf

    FapfaRm

    Ara

    Trf[MODEL 798 PAN DISTRIBUTOR

    Diameters 12 to 48 in.[300 1200 mm]

    Liquid rates between 1 and 8gpm/ft2 [2.5 20 m3/hm2]

    Weir in riserhe Model 798 weir riser distributor issed for highly fouling services in towers

    ess than 48 in. [1200 mm] ID. Cylindricalisers with V weirs are used as liquidowncomers. A wide turndown range isossible due to the weirs, which allowreater flow as the liquid head increases.owever, maximum liquid flow is severely

    imited by the gas flow since they competeor the same passage.

    or liquid-only feeds to the distributor, use feed pipe to control feed velocity. Two-hase liquid-vapor feeds require a flashing

    eed device to adequately separate phasesnd assure proper liquid feed velocity.efer to Feed Devices, Section B forore information.

    The Model 798 is available in any weldablesheet metal.

    This distributor is supported either by a fullledge or lugs. Gasketing is standard onplates with flow rates less than 4 gpm/ft2 [10 m3/hm2].

    This distributor is not recommended for liquid redistribution. Consider the Model 817 instead.

    Corrosion allowance One-piece construction in columns

    greater than 18 in. [450 mm] indiameter

    CONSTRUCTION DETAILS DESIGN OPTIONS

    sk your Saint-Gobain NorPro epresentative about other options t the time of inquiry.

    owers less than 18 in. [450 mm] IDequire full diameter access. Distributorsor larger towers pass through an 18 in.450 mm] nominal manway.

    Model 798

    B

    3.9" - 5.5"[100 - 140]

    A

    C

    1 9/16" [40]

    BA-14

  • MODEL 816/817/916/917 DECK DISTRIBUTOR/REDISTRIBUTOR

    Diameters greater than 12 in. [300 mm]

    Liquid rates between 0.8 and 50gpm/ft2 [2.0 120 m3/hm2]

    Orifices in deckThe Model 816 traditional distributors are for towers larger than 10 in. [250 mm]ID with liquid rates between 0.8 and 50 gpm/ft2 [2.5 - 120 m3/hm2]. The Model817 traditional redistributor has identicalfeatures but is provided with gas riser covers to collect liquid raining from above.

    The Model 916 distributor and 917 redistributor are similar to the 816/817,except that the distribution quality hasbeen improved via better pattern and closer attention to point-to-point flow variation. Because of this, however, the height of the plate is not known inadvance of design.

    The deck-type construction gives liquidlevel balance around the periphery of thedistributor and at large diameters addition-ally across the mid-span beam. The standard turndown is 2.5:1.

    For liquid-only feeds, use a feed pipe andpossibly a parting box. Two-phase liquid-vapor feeds require a flashing feed deviceto adequately separate phases. Refer to Feed Devices, Section B, for additionalinformation.

    The Models 816/817/916/917 are availablein any weldable sheet metal, thermoplasticor FRP material. The distributor rests on anannular ring with tray clamps.

    Distributors in services with liquid ratesbelow 4 gpm/ft2 [10 m3/hm2] are gasketedas standard. See Section G for ledge andmaterial requirements.

    Corrosion allowance (metal only) Cross-flow sump Parting boxes (second stage

    pre-distributor)

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Tower IDin. [mm]

    47.25 [1200]

    > 47.25 [1200]

    Model 816in. [mm]

    Model 817in. [mm]

    8.5 [215]

    10.2 [260]

    10.0 [253]

    13.4 [340] 22.0 [560]

    Model 816 or 817With Parting Box

    in. [mm]

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    PLATE HEIGHTS (Hd)

    Model 916

    Model 917

    Midspans may be required in towers larger than 10 ft [3000 mm] ID.

    Towers less than 18 in. [450 mm] IDrequire full diameter access. Distirbutorsfor larger towers pass through an 18 in.[450 mm] nominal manway with standardconstruction.

    A

    B

    18"[450]A-15

  • MODEL 806 TROUGH DISTRIBUTOR

    Diameters greater than 36 in. [900 mm]

    Liquid rates between 2 and 40gpm/ft2 [5 100 m3/hm2]

    Weirs in troughsThe Model 806 is a weir-trough distributorfor versatile liquid flow handling capabilityin towers larger than 36 in. [900 mm] ID.This distributor is particularly effective inhandling high liquid flow rates in severelyfouling services.

    Model 806 distributors designed for thehighest flow rates employ triangular weirs,also called V weirs. Distributors designedfor lower flow rates employ vertical-sidedweirs, also called slotted weirs, for betterflow control.

    Liquid is metered to the closed-endtroughs by one or more parting boxes. The number of parting boxes depends onthe tower diameter and liquid flow rate.The normal turndown ratio is 2.5:1. Higherturndown ratios can be achieved with special parting box design.

    For liquid-only feeds, use a Model 719feed pipe. Two-phase liquid-vapor feedsrequire a flashing feed device to adequately separate phases. Refer to Feed Devices, Section B, for additionalinformation.

    The Model 806 distributor is available inany weldable sheet metal, FRP or thermoplastic material. The Model 806rests on a full annular ring. See Section Gfor ledge and material requirements.

    This distributor cannot be used as a redistributor. Consider using the Model 817 instead.

    Corrosion allowance

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Model 806 distributor with triangular weirsand three parting boxes.

    Towers larger than 146 in. [3700 mm] ID may require midspans formetal construction; the maximum span is smaller for other materials.

    Standard design of the Model 806 distributor passes through 18 in. [450 mm] nominal manway.

    B

    Model 806

    A

    16 1/4" [413]A-16

  • AT1d[r

    FppfsS

    Ara

    Sd[MODEL 1016/1017 TROUGH DISTRIBUTOR/REDISTRIBUTOR

    Diameters greater than 55 in. [1400 mm]

    Liquid rates between 1 and 20gpm/ft2 [2.5 50 m3/hm2]

    Orifices in troughs he Model 1016 distributor and Model017 redistributor are trough-type istributors for towers greater than 55 in.

    1400 mm] ID. The standard turndownange is 1.8:1.

    or liquid-only feeds use a feed pipe andossibly parting box construction. Twohase feeds (liquid and vapor) require a

    lashing feed device to adequately eparate phases. Refer to Feed Devices,ection B, for more information.

    The Models 1016/1017 are available in any weldable sheet metal. Distributors withliquid rates below 4 gpm/ft2 [10 m3/hm2]are gasketed as standard. See Section Gfor ledge and material requirements. Thisdistributor rests on an annular ring.

    Standard design for a Model 1017 redistributor includes a wall wiper weldedto the tower wall and gas riser covers tocollect and redistribute liquid raining downfrom above.

    Corrosion allowance Cross-mixing (Model 1017 only) Orifice strainers Leveling screws

    CONSTRUCTION DETAILS DESIGN OPTIONS

    sk your Saint-Gobain NorPro epresentative about other options t the time of inquiry.

    tandard design of the Model 1016/1017 istributor passes through 18 in.

    450 mm] nominal manway.

    Model 1016

    Height varies with turndown.

    Model 1017

    A

    B

    12"[300]

    18"[450]-17

  • MODEL 844 PIPE-ARM DISTRIBUTOR

    Diameters larger than 17 in. [430 mm]

    Liquid rates between 1.5 and 10 gpm/ft2

    [4 25 m3/hm2]

    The Model 844 liquid distributor requireslittle column elevation to accomplish itsdistribution task, and it provides high open area for high vapor flow. The Model844 should be used only with clean liquidsor with a filter designed to remove any particles that could block the orifices.

    The standard design of the Model 844handles liquid rates up to 10 gpm/ft2

    [25 m3/hm2], but special designs can handle higher rates. The normal turndownratio for the Model 844 is 2.5:1.

    The Model 844 is available in any weldablemetal pipe or thermoplastic material. Thelaterals are removable to permit passagethrough vessel manways. The header section is flanged for standard horizontalfeed from the side of the tower. Inlet flangemates to a 150 pound flange. See SectionG for material requirements.

    This distributor can be used to redistributeliquid from a liquid collector plate above it.See Liquid Collectors, Section E, formore information.

    Flanged laterals Corrosion allowance (metal only) Vertical-feed header, on tower

    centerline

    Bayonet-style construction for smalltowers (type I or II metal, type II plastic see Section G)

    Threaded header

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    The Model 844 passes through 18 in.[450 mm] nominal manway.

    Lateral may require support by customer

    Model 844

    B

    A

    TOWER CENTERLINE

    INTERIOR FLANGEBY CUSTOMER

    SUPPORT SADDLEBY CUSTOMERA-18

  • MODEL 1044 SPRAY-TYPE LIQUID DISTRIBUTOR

    Liquid rates between 0.2 and 50 gpm/ft2

    [0.5 120 m3/hm2]

    The Model 1044 spray-type distributor isan inexpensive distributor used over shallow beds of packing in heat transferservice. It can be designed for very low liquid rates because each spray nozzlecovers a large area of the tower, so eachnozzle passes a reasonable flow, even atlow irrigation rate. The normal turndownratio is 2:1.

    The Model 1044 is available in any weldable metal for which pipe and flangesare readily available. The laterals areremovable for manway passage. Theheader section is flanged for the feed nozzle connection; a 150 pound internalfeed flange is expected.

    Corrosion allowance 300 pound flanges Double or triple coverage patterns

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 1044

    A

    B

    VARIES

    TOWER CENTERLINE

    INTERIOR FLANGEBY CUSTOMER

    WALL CLIP(S)BY CUSTOMERA-19

  • FEED DEVICES

    Obtaining desirable tower performancerequires the proper handling of liquid andvapor entering the column. The types offeeds, or inlets, into a column can generallybe classified into four major categories:

    Liquid only (contains less than 1%volume vapor)

    Liquid and vapor above a packedbed (flashing or suppressed flash)

    Vapor only below a packed bed Reboiler returns

    Selection criteria for each category of feeddevice is unique. The following tablesassist in selecting the proper equipment.

    The selection of liquid-only feed devices,which are required as pre-distributors,depends on the type of distributor and onturndown needs. Among the factors Saint-Gobain NorPro considers in designing a feed device are flow rate,operating range, degree of sub-cooled liquid versus column size and temperature,and whether mixing with overhead liquid is required.

    For liquid and vapor feed devices above adistributor (Table II), the selection dependson the type of distributor, flow rates, typeof flow at feed (flashing or suppressed),turndown necessary, column height needed for flashing vapor distribution andmixing of the inlet liquid with the overheadliquid. In all cases, separating the twophases is a primary concern. Additionalpre-distribution (via parting boxes) may be required.

    Model

    119

    129

    719

    Used WithType Distributor

    Intalox

    Intalox

    Traditional

    729 Traditional

    TurndownRatio

    2:1

    10:1

    2.5:1

    10:1

    Model Flow RegionTower Size

    in. [mm]

    755

    855

    955

    Any

    Any

    Separated

    > 36 [900]

    < 48 [1200]

    > 48 [1200]

    192* Spray orSeparated

    > 96 [2400]

    655* Any > 60 [1500]

    SELECTING A LIQUID ONLY FEED PIPE(Inlet is less than 1% volume vapor)

    SELECTING A LIQUID/VAPOR FEED PIPE(Inlet is more than 1% volume vapor)

    Table I

    Table II

    *See page G-4 for general descriptionB-1

  • Two factors must be considered in choosing the proper device for a vaporonly feed below a packed bed (Table III).

    1. Kinetic energy of inlet vapor

    The kinetic energy of the inlet vapor mustbe considered in relation to the pressuredrop in the packed bed, the feed nozzlearrangement and tower separation requirements.

    2. Vapor composition

    When the vapor is introduced betweenpacked beds, consider the degree of mixing of the inlet vapor with the risingvapor. If a gross mismatch of compositionand/or temperature exists, mixing of thetwo vapors optimizes packing perform-ance above.

    Specific equipment for vapor distributionmay not be required if the pressure drop in the packed bed is sufficient for propervapor distribution.

    To determine the type of feed devicerequired for a reboiler return, the first stepis to consider the kinetic energy asdescribed above. After it is determined that vapor distribution is required, factorsto consider include feed nozzle size andarrangement, pressure drop in the packedbed, flow rates, tower size and type ofreboiler.

    If vapor distribution equipment is neededabove reboiler return inlets, the Model 896is an effective distributor. Occasionalexceptions are listed in Table IV.

    For those towers employing suppressedvaporization reboilers, the pressure releaseand flash should not occur at the towernozzle. The Model 144 suppressed flashdistributor is effective for these towers.

    Model

    194*

    198

    796*

    Typical UseTower Size

    in. [mm]

    Vapor Diffuser

    Vapor Distributor(For Uniform Flow/Mixing)

    Vapor Distributor(for Uniform flow)

    > 48 [1200]

    > 17 [430]

    All896 Vapor Distributor(for Uniform flow)

    > 48 [1200]

    196 Vapor Diffuser(Reduces Flow Inertia)

    > 48 [1200]

    UsualModel

    896

    896

    896

    AlternateModelsType Reboiler

    796*

    196, 796*

    Thermosiphon

    Forced Circulation

    Kettle-type

    896, 796*Suppressed Flash 144*

    796*

    SELECTING VAPOR ONLY FEED DEVICES

    SELECTING REBOILER RETURN FEED DEVICES(IF VAPOR DISTRIBUTION EQUIPMENT IS NEEDED)

    *See page G-4 for general description

    Table III

    Table IVB-2

  • MODEL 119/129 LIQUID ONLY FEED PIPE

    The Models 119 and 129 liquid only feedpipes are used when liquid is fed from outside the column onto a NorPro Intaloxdistributor or redistributor. Each feed pipemeters flow to one or more appropriatefeed areas, matching the hydraulic requirements of the distributor. Excessiveturbulence and horizontal flow velocity inthe distributor are eliminated in a compactdesign.

    The Model 119 feed pipe is a piping system of headers, lateral branches, anddownpipes. It is limited in turndown to a2:1 ratio or perhaps slightly more. TheModel 129 feed system employs a partingbox or calming boxes below simpler piping. It can handle much higher turndown ratios than the Model 119, but itmay require slightly more tower height.

    A submerged feed is recommended whenthe liquid is sub-cooled more than 30 F[17 C] in large towers with low flow rates.Submerging the feed maintains uniform liquid temperature from the distributor andmay also be used in cases where a morecompact design is required.

    The Model 119/129 is available in anyweldable metal, FRP or thermoplasticmaterial.

    With the standard vertical system design,the Model 119/129 attaches to an internalcolumn flange and is further supported bytower wall clips. The submerged style does not require tower wall clips and issupported by the distributor.

    Corrosion allowance (metal only) Bayonet-style construction see

    Section G

    All-flanged construction, (eliminatesinternal threaded connectionsexcept with some bayonets)

    Submerged feed Support from liquid distributor

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 119

    Model 129

    A

    C

    VARIES

    OPTIONAL PARTING BOXB-3

  • MODEL 719/729 LIQUID ONLY FEED PIPE

    The Models 719 and 729 liquid only feedpipes are used when liquid is fed from outside the column onto a traditional distributor or redistributor. The incomingflow must contain less than 1% by volumevapor.

    The Model 719 feed pipe is a piping system of headers and downpipes. It canprovide a turndown ratio up to 2.5:1. TheModel 729 feed system employs a partingbox below simpler piping. It can handlemuch higher turndown ratios than theModel 719, but it usually requires slightlymore tower height.

    The Models 719/729 are available in anyweldable metal, FRP or thermoplasticmaterial in pipe or tubular form. With thestandard design, feed pipes attach to theinternal column flange and are supportedby tower wall clips. As an option, the feed pipe can be supported from the distributor.

    Corrosion allowance (metal only) Bayonet-style construction see

    Section G

    All-flanged construction, (eliminatesinternal threaded connectionsexcept with some bayonets)

    Support from liquid distributor

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 719

    Model 729

    A

    C

    VARIES

    OPTIONAL PARTING BOXB-4

  • MODEL 755 FLASHING FEED GALLERY

    B-5

    The Model 755 flashing feed gallery is atwo-phase feed device fed by a tangentialinlet tower nozzle or a radial nozzle with aflow deflector (shown below). Incomingflow is directed tangentially onto the towerwall. A gallery below the inlet collects liquidinto a pool, allowing the vapor or gas todisengage. The liquid then falls directly to adistributor or into a pre-distributor (partingbox). The Model 755 is recommended intowers 36 in. [900 mm] ID and larger andhandles any liquid to vapor feed ratio.

    The Model 755 is available in any weldablemetal. The inside of the gallery may beround or polygonal. The gallery is clampedto a ledge as standard attachment.

    Inlet deflector attached to inlet nozzle internal flange

    Joint gasketing Corrosion allowance

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Flow deflectors are supplied by others.They can be uni- or bi-directional.

    Model 755

    A

    B

    Hd Hn

  • BTtttvbitlo

    Tttlba

    AraMODEL 855 FLASHING FEED CHAMBER

    he Model 855 flashing feed chamber is awo-phase feed device which is attachedo a radial inlet. The feed is centrifuged inhe chamber, separating the phases apor out the top and liquid out the ottom to a distributor below. This model

    s used with either a NorPro Intalox or raditional distributor or redistributor. Theiquid falls either directly to a distributor r into a pre-distributor.

    he Model 855 is recommended for owers up to 48 in. [1200 mm] ID on mostwo-phase feeds. This device handles alliquid to vapor ratios. Larger towers mayenefit from use of this device if flow ratesre suitable.

    The Model 855 is available in any weldablemetal. For towers between 10.12 and21.14 in. [250 - 530 mm] ID, the Model855 is constructed in one piece; multi-piece construction is used for larger tow-ers.

    With inlet pipe sizes less than 4 in. [10 mm], the Model 855 has a threadedconnection to a bayoneted inlet pipe sup-plied by others as standard. Larger inletpipe sizes are flanged as standard.

    Corrosion allowance Bayonet construction see

    Section G

    CONSTRUCTION DETAILS DESIGN OPTIONS

    sk your Saint-Gobain NorPro epresentative about other options t the time of inquiry.

    Model 855

    A

    C

    Hd-6

  • MODEL 955 FLASHING FEED PIPE

    The Model 955 flashing feed pipe is usedto separate a two-phase feed when theinlet flow is in a separated flow region. With the Model 955, the two-phase flowenters the center pipe. The vapor isreleased from the upper area of the pipeand the liquid flows to the outer chamberwhere it is metered to desired points onthe distributor below.

    This model is most often used for vacuumservices in towers larger than 48 in. [1200 mm] ID. The compact design of thismodel makes good use of tower height.

    The Model 955 is available in any weldablemetal. The Model 955 is connected to aninternal tower flange and is further support-ed by a tower wall clip as standard. Thedevice is constructed in one piece, provid-ed access diameter is sufficient.Otherwise, multi-piece construction withgasketing is supplied.

    Corrosion allowance

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 955

    TOWER I.D.

    C

    VARIESB-7

  • MODEL 196 VAPOR DIFFUSER

    The Model 196 vapor diffuser is usedwhere the incoming flow is vapor only andthe flow energy is excessive, causing vapormaldistribution to the bed above. Thisdevice reduces the flow inertia, whichallows proper distribution. The Model 196is not a vapor distributor; see Model 198.

    The Model 196 meters the vapor uniformlyout the upper area of the tube and theshroud, then directs it down each side ofthe tube. Pressure drop across this deviceis relatively low compared to the Model198. The vapor flow turndown ratio is generally 4:1; however, higher ratios arepossible. The Model 196 is used in towerslarger than 48 in. [1200 mm] ID.

    The Model 196 is available in any weldablemetal. This model is attached to an internaltower flange and is further supported by atower wall clip as standard construction.Optionally, the inlet end can be made tosleeve into the vapor inlet nozzle in lieu of an internal tower flange. One-piece construction is standard provided accessdiameter is sufficient. Otherwise, multi-piece construction is supplied.

    Sleeve inlet (eliminates internalflange, but may require extra weld-on wall clips)

    Corrosion allowance

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 196

    A

    C

    VARIESB-8

  • MODEL 198 VAPOR DISTRIBUTOR

    The Model 198 pipe arm vapor distributoris used when the feed requires uniform dis-tribution over the tower area. Typical appli-cations include introduction of a vapor feedat the bottom of the tower into a very tightspace or introduction of a vapor which dif-fers in composition or temperature andneeds mixing with the column vapor.

    The maximum vapor rate may be limiteddue to the amount of tower area occupiedby the device. Required pressure dropacross the distributor to achieve properdistribution is determined by size of theinlet and flow rate. Turndown ratio is gen-erally 4:1; however, higher ratios are possi-ble provided the pressure drop is notexcessive for the process. This device canbe used in towers larger than 17 in. [430 mm] ID.

    The Model 198 is available in any weldablemetal or thermoplastic pipe material. Thelaterals are threaded in pipes 3 in. [75 mm] or less and flanged in larger sizes.The access diameter must be sufficient toaccommodate the header. The headersection is flanged at the inlet end and isfurther supported by wall clips. Lateralpipes are also supported by wall clips ontowers larger than 96 in. [2400 mm] ID.Plastic construction may require addedsupport in smaller towers.

    Flanged laterals Corrosion allowance (metal only) Bayonet-style construction for small

    towers (type I or II metal, or type IIplastics see Section G)

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 198

    A

    CB-9

  • MODEL 896 VAPOR DISTRIBUTOR PLATE

    The Model 896 vapor distributor plate isused above vapor-containing tower feedsto assure good vapor distribution to thepacked bed above.

    Most packed beds do not need vapor distributors. These beds include bedsreceiving vapor from other packing, liquiddistributors, or liquid collectors below.Beds receiving vapor from low-velocity-head feeds also do not need vapor distributors. The vapor distributors arenecessary below beds receiving a largefraction of their vapor from high-velocity-head external feeds.

    In performing its vapor distribution task,the Model 896 will consume some pressure drop in the vapor. The designpressure drop will be between 0.5 and 4 in. water [125 - 1000 Pa].

    The turndown ratio of the Model 896 is atleast 4:1.

    The Model 896 is available in any weldablesheet metal. It is supported by an annularring and perhaps by midspan beams inlarge towers. The Model 896 is gasketed;see Section G for ledge and materialrequirements.

    Corrosion allowance Liquid downpipes or sumps

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Model 896

    A B

    Ha

    HdB-10

  • WR

    Fbifod

    U

    Tubw

    TApAiTt

    AraddbdtuogcmapaBED LIMITERS

    hen are bed limiters required?

    andom Packing

    or metal and plastic random packings,ed limiters are recommended when there

    s the potential for sufficient vapor load toluidize the top of the bed. Generally, thisccurs during upset conditions, which areifficult to predict.

    se the table below for guidelines.

    here are three basic ways to preventpward movement of random packing:ed limiters, anti-migration bars andeighted plates.

    he bed limiter is the most common type. bed limiter either sits directly on theacking or is attached to the vessel wall.ttachment to the vessel wall increases

    nterference with the distribution pattern.he bed limiter acts as a screen to confinehe packing to the defined bed.

    nother method of retaining a bed of andom packing is through the use of nti-migration bars at the bottom of theistributors gas risers. Anti-migration barso not prevent the packed bed fromecoming fluidized and unleveled, but theyo prevent packing from being blown uphrough the gas risers. The concern in these of anti-migration bars is the possibilityf restricting vapor passage through theas risers. This could lead to liquid back-ycling due to high vapor velocity, whichay flood the distributor. Hence, close

    ttention to process and internal designarameters is recommended before usingnti-migration bars.

    The Model 905 is a weighted plate usedwith ceramic or carbon tower packing toprevent breakage. It is important to levelthe bed to assure packing contact with thehold-down plate over all areas. In additionto handling vapor surges, weighted platesare recommended when liquid rates aregreater than 15 gpm/ft2 [35 m3/hm2].

    Structured Packing

    Bed limiters are recommended for use withstructured packing when there is thepotential for packing displacement duringupset conditions. Retention of the top layeris accomplished with the Model 133,which may be attached to the distributor.For towers with one-piece layers of pack-ing, the Model 133 is typically integral withthe distributor to provide a means of sup-port for and attachment to the distributor.

    Many columns with structured packing donot need bed limiters.

    Bed Limiter Selection

    Bed limiters must maintain a high free areafor vapor/liquid passage and minimizeinterference with liquid distribution. WithIntalox distributors, non-interfering bed lim-iters such as the Models 103 and 133 arerecommended. The Model 822 is speciallydesigned for use on top of random pack-ing with a spray distributor (Model 1044)above.

    When laying out tower elevations, the bedlimiter is not considered part of the packedbed. The top of the packed bed is normallysix to eight in. [150 - 200 mm] from thedistributor to allow for gas disengagementfrom the packed bed. The bed limiteroccupies this disengagement area.

    The table below summarizes the selectioncriteria for any size tower. The supportmethod is given in reference to vessel wallattachments. See the appropriate modeldescription for further details.

    *Pressure drop is difficult to predict in flood.

    Packing Wt.(lbs/ft3)

    5 10 15

    P(in. WC/ft)

    1.92 3.8*

    20

    4.8*

    25

    0.96 2.9*

    *Contact Saint-Gobain NorPro for plate details

    WallAttachment

    PlateConstruction

    MaterialType ofPacking

    PackingConstruction

    Material

    None; restson packing

    Metalor Plastic

    Metalor Plastic

    Metal

    Metal

    Random

    Random

    Structured

    Random

    Random

    Metalor Plastic

    Metalor Plastic

    Metal

    Metalor Plastic

    Ceramicor Carbon

    Metal

    ModelNumber

    103

    823

    133

    822*

    905*

    Attached tosupport ring

    Attached towall clips

    Attached tosupport ring

    None; restson packing

    APPROXIMATE POINT OF FLUIDIZATION

    SELECTING A BED LIMITERC-1

  • MODEL 823 BED LIMITER FOR RANDOM PACKING

    When traditional metal or plastic randompackings are used, the Model 823 is fixedto the tower wall. The standard method offastening the bed limiter to the vessel wall is by clamps to a ledge welded in the column.

    The Model 823 is available in any weldablemetal or thermoplastic material in sheetform.

    For metal construction, the plate can withstand 50 lbs/ft2 [250 kg/m2] uniformupward force. Towers up to 36.22 in. [900 mm] ID are furnished with either ledgeclamping or jack screws. The plate screenon the opening may vary depending onpacking size.

    For thermoplastic construction, the platecan withstand 5 lbs/ft2 [25 kg/m2] uniformupward force. All plates are clamped to thesupport ledge as standard.

    Greater upward force Corrosion allowance (metal only) Jack screws on plates smaller than

    36.22 in. [920 mm]

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Material

    Metal

    Polypropylene

    CPVC

    lbs./ft2 kg/m2

    3.3

    1.2

    1.8

    16.2

    5.9

    8.8

    Note: Other materials are available.

    APPROXIMATE WEIGHT

    A B

    3" - 5"[75 - 125]

    Model 823C-2

  • TttbmeaeThe Model 133 metal bed limiter isdesigned for use with Intalox structuredpacking or Intalox wire gauze packing. Itsdesign minimizes interference with liquiddistribution. This bed limiter is bolted to thevessel wall by means of vertical clips inlarger towers. The Model 133 is integralwith the distributor when restricting one-piece packing layers.

    The Model 133 is available in any weldablesheet metal. This plate will pass throughany standard manway.

    The standard design can withstand 50 lbs/ft2 [250 kg/m2] uniform upward force.

    Jack screws on plates smaller than36 in. [920 mm]

    Corrosion allowance Attachment to the distributor Support for the distributor Greater upward force

    MODEL 133 BED LIMITER FOR STRUCTURED PACKING

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Model 133MODEL 103 NON-INTERFERING BED LIMITER FOR RANDOM PACKING

    he Model 103 bed limiter is designed o minimize interference with liquid distribu-ion below an Intalox liquid distributor. Theed limiter diameter is expandable to per-it contact with the vessel wall, which

    liminates the need for wall attachmentsnd prevents random packing from scaping.

    The Model 103 is available in any weldablemetal or thermoplastic material. The stan-dard minimum access diameter requiredfor the Model 103 is 17 in. [430 mm].

    With metal construction, standard designcan withstand 50 lbs/ft2 [250 kg/m2] uniform upward force.

    The thermoplastic Model 103 can withstand 10 lbs/ft2 [50 kg/m2] upwardforce.

    Corrosion allowance (metal only) Greater upward force

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Material

    Metal

    Polypropylene

    CPVC

    lbs./ft2 kg/m2

    3.0

    1.1

    1.6

    14.7

    5.4

    7.8

    Note: Other materials are available.

    APPROXIMATE WEIGHT

    Model 103C-3

  • SUPPORT PLATES

    Saint-Gobain NorPro manufactures support plates for random and structuredtower packings. Regardless of the packing, each plate incorporates severalcritical design factors. First, the plate mustphysically support the packing under operating conditions. Second, it must havea high percentage of free area to allowunrestricted flow of downcoming liquid andupward flow of gas. Third, it must be easyto install.

    There are several criteria for selecting asupport plate:

    Type of packing supported (random or structured)

    Process characteristics (corrosion,packing material, temperature)

    Maximum design load supported(bed depth, packing type and material, liquid hold-up, materialbuild up in the bed and surge conditions)

    Note: In cases where the column liquidlevel rises above the vapor entry, the support plates can be subjected to exceptional forces.

    Pressure drop calculations for our towerpackings include the pressure dropthrough support plates of our design: Noextra pressure drop need be added for thesupport plate. Support plates can bedesigned to handle any liquid flow rate. In both cases (pressure drop and liquidrates), the packing is the limiting factor in tower design.

    A random-packed bed depthincludes the height of the supportplate. A structured-packed beddepth does not include the height of the support.

    Where tower height is a premium, specialdesigns for support plates are available to permit integral packing support and either vapor distribution or partial liquid collection.

    Gas injection support plates are designedto provide separate passageways for gasand liquid so both phases do not competefor the same opening. Unrestricted flow ofboth phases minimizes pressure dropacross the plate. This is done by providinggas inlets above the liquid head, preventingexcess liquid build-up. The support platesare designed to retain the various packingsizes while not restricting the capacity ofthe packing.

    Support plates for random packingsinclude the Models 809 light-duty support,

    818 support, and 804 multi-beam support.All are made of metals; the Models 818and 804 are also available in thermoplastic.The Models 819 and 1019 are both available in FRP only.

    Supporting a structured packing is somewhat simpler than supporting random packing because the integralnature of the structured packing physicallyallows support by an open grid. The majordesign criteria is minimization of the gridcross-sectional area while providing sufficient strength. The Model 134 support for structured packing is available in metal only.

    All our support plates sit directly on anannular ring. The weight of the packed bed is normally sufficient to keep the platein place. However, if extra restraint isneeded, the plate can be clamped to itssupport ring.

    Contact your local Saint-Gobain NorPro representative for applications outside the standardsshown in this brochure.

    ModelNumber

    Tower IDin. [mm]

    Type PackingSupported

    ConstructionMaterial

    818

    809

    804

    819

    1019

    < 48 [1200]

    > 48 [1200]

    Any Random

    Random (light)

    Any Random

    Random(except ceramic)

    Random(except ceramic)

    Metals andThermoplastics

    Metals

    Metals andThermoplastics

    FRP

    FRP

    > 36 [900]

    < 48 [1200]

    < 35.25 [890]

    Any Structured134 Metal

    SELECTING A SUPPORT PLATED-1

  • MODEL 818 GAS INJECTION SUPPORT PLATE

    Because the Model 818 support platecombines high free area with excellentmechanical strength, it is generally recommended for all towers less than 36 in. [900 mm] ID. This support incorporates the multi-beam design principle into two- or three-pieced unitsfor towers ranging from 12 to 48.62 in.[305 - 1235 mm] ID.

    Metal plates can support loads up to 1000 lbs/ft2 [4800 kg/m2] or more. Thetable below provides allowable load valuesfor different thermoplastic materials at various temperatures.

    The Model 818 is available in any weldablesheet metal or thermoplastic material.These plates are supported by a full ledge.See Section G for ledge and attachmentrequirements.

    Two-piece construction is provided fortowers between 12 in. and 34 in. [305 - 865 mm] ID. Three or four-piececonstruction is provided for towersbetween 34.1 and 48.62 in. [866 - 1235 mm] ID.

    State the size of packing at the time ofinquiry.

    Corrosion allowance (metal only) One-piece construction in all sizes Heavy-duty construction

    (thermoplastic only)

    Ledge clamping

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Material

    Metal

    Polypropylene

    CPVC

    lb/ft2 kg/m2

    5.5

    2.4

    4.1

    26.9

    11.7

    20.0

    Note: Other materials are available.

    APPROXIMATE WEIGHT

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Curve Plastic

    1 PVC/CPVC @ 75 F [24 C] through 125 F [52 C]

    2 Polypropylene @ 75 F [24 C]

    3 Polypropylene @ 100 F [38 C]

    4 Polypropylene @ 125 F [52 C] orPVC/CPVC @ 150 F [66 C]

    5 Polypropylene @ 150 F [66 C]

    400 600

    1000

    500

    750

    1250

    300

    250

    200

    150

    100

    50

    0

    12 18 24 30 42 48

    (inches)

    (lb/f

    t2)

    (kg

    /m2 )

    250

    (millimeters)

    36

    500 700 800 900 1000 1100 1200

    12345

    Allo

    wable

    Load

    Tower ID

    MAXIMUM ALLOWABLE LOAD - PLASTICS

    Note: Standard heavy-dutyconstruction increases loadcapacity 1.25 times. Highertemperatures and/or loadsare possible.

    Model 818

    A B

    4 1/2" [114]D-2

  • DTriTsmpvaSsMODEL 804 GAS INJECTION SUPPORT PLATE

    he Model 804 support plate is ecommended to support random packingn towers greater than 36 in. [900 mm] ID.he Model 804 is recognized as the typicaltyle due to its high open area andechanical strength. The table below rovides the maximum allowable load alues for different thermoplastic materialst various temperatures. Contact aint-Gobain NorPro for maximum pans when using metal.

    The Model 804 is available in any weldablesheet metal or thermoplastic material. See Section G for ledge and materialrequirements.

    Thermoplastic supports retain #40 IMTP

    packing, 2 in. [50 mm] saddles or in. [19 mm] and larger rings. Contact yourSaint-Gobain NorPro representative ifsmaller packing must be supported.

    All beams can be installed through manways 16 in. [406 mm] ID and larger.The plate is supported by a full ledge onwhich it typically rests freely.

    Corrosion allowance (metal only) Heavy-duty construction

    (thermoplastic only)

    Beam to beam clamps Ledge clamping

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Material

    Metal

    Polypropylene

    CPVC

    lb/ft2 kg/m2

    6.0

    2.4

    4.1

    29.3

    11.7

    20.0

    Note: Other materials are available.

    APPROXIMATE WEIGHT

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    Curve Plastic

    1 PVC/CPVC @ 75 F [24 C] through 125 F [52 C]

    2 Polypropylene @ 75 F [24 C]

    3 Polypropylene @ 100 F [38 C]

    4 Polypropylene @ 125 F [52 C] orPVC/CPVC @ 150 F [66 C]

    5 Polypropylene @ 150 F [66 C]

    1000 1500

    1000

    2000

    500

    750

    1250

    300

    250

    200

    150

    100

    50

    0

    36 48 60 72 84 96

    (inches)

    (lb/f

    t2)

    (kg

    /m2 )

    250

    (millimeters)

    12

    345

    Tower ID or Span

    Allo

    wable

    Load

    MAXIMUM ALLOWABLE LOAD - PLASTICS

    Note: Standard heavy-dutyconstruction increases loadcapacity 1.25 times. Highertemperatures and/or loadsare possible.Contact you Saint-GobainNorPro representative formaximum metal spans.

    A B

    VARIES

    Model 804-3

  • MODEL 809 LIGHT DUTY SUPPORT PLATE

    The Model 809 support plate is availablefor towers between 4 and 35.25 in. [100 - 895 mm] ID supporting metal,ceramic or plastic random packings. Thiscorrugated support plate should be usedonly when:

    Bed height is limited Hydraulic loading is not severe

    Small packings ( in. or 13 mm) areused in towers greater than 11.7 in.[300 mm] ID

    In other cases, consider use of the Model818 as an alternative.

    The Model 809 is available in any weldablesheet metal. Two piece construction isstandard .

    The Model 809 retains #15 IMTP packingor in. [6 mm] and larger saddles andrings.

    Ledge clamps for towers greaterthan 12 in. [300 mm] ID

    Corrosion allowance One-piece construction

    CONSTRUCTION DETAILS DESIGN OPTIONS

    TemperatureF [C]

    300 [149]

    400 [204]

    500 [260]

    600 [316]

    Carbon Steel Stainless

    0.983

    0.957

    0.856

    0.729

    0.917

    0.835

    0.732

    0.777

    700 [371]

    800 [427]

    This table provides correction factors based on maximumoperating temperatures. Multiply allowable load from thecurves by the correction factor to obtain maximumallowable load during operation.

    0.627

    NR

    0.719

    0.686

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    ALLOWABLE LOADCORRECTION MULTIPLIER

    250 750

    3000

    2000

    2500

    3500

    800

    700

    600

    500

    400

    300

    200

    (inches)

    (lb/f

    t2)

    (kg

    /m2 )

    1500

    (millimeters)

    500

    1000

    500100

    06 1812 24 30

    Tower ID

    Allo

    wable

    Load

    MAXIMUM ALLOWABLE LOAD

    Note: Corrosion allowanceis not factored into eithercurve. materials are carbonsteel, 304L and 316Lstainless steel. Contactyour Saint-Gobain NorProrepresentative for allowableloads for other materials.

    A B

    1" - 1 1/2[25 - 38]

    Model 809D-4

  • MODEL 819/1019 FRP GAS INJECTION SUPPORT PLATE

    Both Models 819/1019 use beam-typeconstruction similar to that of the Model804. The Model 819 is designed for towersbetween 18 and 48 in. [450 - 1200 mm] IDwhile the Model 1019 support plate isdesigned for towers greater than 48 in.[1200 mm] ID.

    Use the allowable load graph below to calculate the maximum length of the beam to support the packed bed plus liquid hold-up. If your actual loads are higher than those included in the graph,contact your Saint-Gobain NorPro representative about a special design.

    The Models 819/1019 are available in FRPonly. See Section G for material and ledgerequirements.

    Each model retains 2 in. [50 mm] saddlesor 1 in. [25 mm] and larger rings. Contactyour Saint-Gobain NorPro representative ifsmaller packing must be supported. FRP construction is not recommended for use with ceramic packings.

    The approximate weight for the Model 819is 4.75 lbs/ft2 [23 kg/m2]; for the Model1019, 6 lbs/ft2 [29 kg/m2]. Beams can beinstalled through a 7.5 in. [190 mm] IDhandhole for the Model 819, and through a 17 in. [430 mm] ID manway for theModel 1019.

    This plate is supported on a full ledge.Large plates may require midspans.

    CONSTRUCTION DETAILS

    TemperatureF [C]

    100 [38]

    125 [52]

    150 [66]

    175 [80]

    0.948

    0.908

    0.867

    0.827

    Multiplier

    200 [93]

    225 [107]

    0.787

    0.746

    0.706250 [121]

    This table provides correction factors onmaximum operating temperatures.Multiply the allowable load from thecurves by the correction factor to obtainthe maximum allowable load duringoperation.

    Ask your Saint-Gobain NorPro representative about other options at the time of inquiry.

    1000 2000

    1000

    500

    1500

    400

    350

    300

    250

    200

    150

    100

    (inches)

    (lb/f

    t2)

    (kg

    /m2 )

    (millimeters)

    1500

    50

    0

    18 4230 54 66 78 90 96847260483624

    Tower ID or SpanFor Standard Design Ratings

    Allo

    wab

    le L

    oad

    819 1019

    68

    F [2

    0 C

    ]

    ALLOWABLE LOADCORRECTION MULTIPLIER

    A

    B

    VARIES

    Model 1019D-5

  • MODEL 134 SUPPORT GRID

    The Model 134 is used to support eitherIntalox structured packing or Intalox wiregauze packing. Design of the support gridallows free and uniform passage of gasand liquid so that capacity of the packingis not limited.

    The Model 134 is available in any weldablesheet metal. The approximate weight ofthe grid is 14 lbs/ft2 [68 kg/m2]. Grids canbe installed through a 17 in. [430 mm] IDmanway.

    This plate is supported on a full ledge.Larger plates may require midspan beams.Lightly loaded plates can span up to 14 ft[4270 mm] without beams, but heavilyloaded plates at high temperature mayneed beams at 10 ft [3050 mm] diameter.

    Ledge clamps Corrosion allowance Lower height requirement Hd

    CONSTRUCTION DETAILS DESIGN OPTIONS

    Tower Diameterin. [mm]

    Maximum HeightHd, in. [mm]

    39.37 [1000 ]

    39.37 to 72.25 [1835 ]

    > 96.46 [2450 ]

    3 [75 ]

    4 [100 ]

    5 [125 ]72.26 to 96.45 [2450 ]

    6 [150 ]

    Ask your Saint-Gobain NorPro representative about other options a