pe-adz-7e05010104-mdc-948-r01 powerhouse - model for power system stability - thyne5&thyne6

Upload: augusto-calderon

Post on 06-Jul-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    1/19

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s

    b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e n n a ,

    A u s t r i a .

    R e s e c

    t a r

    l a n o

    t a d e

    r o t e c c

    i ó n

    I S O

    1 6 0 1 6

    R01R00

    Rev.Index

    R e

    f e r e n c i a

    C l i e n

    t e / C u s

    t o m e r

    R e f e r e n c e

    OW

    CO

    CO

    Lista de PieDimensiónGrupo / Gro

    M HAVDib/DrawnRev/CheckRev/Check

    Apr/Appr

    Cha

    ER:

    TRACT:TURCON

    TRACTOR:

    zas / Partslist/ Dimensionup

    del for

    Fech/Date05.05.201507.05.201507.05.201507.05.2015

    ge accordingF

    MM

    KEY ENTRACT F

    ExcitaTHYN

    Power

    Nom/Name ClEGR Pr MIT PMIT CMIT Fil

    dAPE-AGM-Airst issue

    odificaciónodification

    INEERINR THE C

    ion Sys5/THY

    ystem S

    iente/Clientoyecto/Plantdido/Project N°ntrato/Contract Ne/Date

    InternoDibujoPE-A

    Z-C-077-16

    G , PROCERRO D

    emE6tability

    Cerro del ÁguCerro del ÁguH110.002217

    °07.05.2015

    N° / Internal N°N° / Drawing N°DZ-7E0501

    18.007.0

    F

    UREMENL AGUIL

    tudies

    ila S.Aila HPP

    0104-MDC

    STAM

    3.2016 EG5.2015 EG

    chaate

    DibujPrep.

    AND CO HYDRO

    WA N°Class NTipo / TEscala

    Peso /

    Similar/Rempla

    =+

    948

    P RESE

    MITMIT

    óby

    RevisóChecked

    NSTRUCOWER P

    °pe/ Scale

    Weight (kg)

    imilara/Replace

    Rev/IndexR01

    RVED S

    MIT MMIT M

    RevisóChecked

    Ap A

    IONLAN

    Material

    Hoja / Sht 1de / of 19

    ACE

    ITIT

    obópr.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    2/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 2 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    CONTENT

    1 INTRODUCTION .......................... ............................ ............................ ............................. ............ 4 2 S IMULATION MODEL AND P ARAMETERS ......................... ............................ ............................ ..... 5 2.1 Generator, Transformer and Grid Connection .................................................................... ..................................... 5 2.2 THYNE5/THYNE6 Static Excitation System ........................................................................................ ....................... 7 2.2.1 Basic Structure of AVR and Power Part .......................................................................... .......................................... 7 2.2.2 Power System Stabilizer ......................................................................... ................................ ................................11 2.2.3 Instantaneous Field Current Limiter ........................................................... ..................................... ......................13 2.2.4 Under Excitation Limiter ........................................................................................................................................14 2.2.5 Thermal Limiter ................................................................................ ....................................... ...............................15

    3 S TANDARD MODELS ............................ ............................ ............................ ............................. 17 3.1 Standard Model IEEE 421.5 ST8C ................................................................................................ ...........................17

    REFERENCES .......................... ............................ ............................. ............................ .......................... 19

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    3/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 3 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    Disclaimer

    ANDRITZ HYDRO DOES NOT MAKE ANY WARRANTY OR REPRESENTATIONWHATSOEVER, EXPRESS OR IMPLIED, WITH RESPECT TO THE MERCHANTABILITY ORFITNESS FOR ANY PARTICULAR PURPOSE OF ANY INFORMATION CONTAINED IN THISREPORT OR THE RESPECTIVE WORKS OR SERVICES SUPPLIED OR PERFORMED BY

    ANDRITZ HYDRO. ANDRITZ HYDRO DOES NOT ACCEPT ANY LIABILITY FOR ANYDAMAGES, EITHER DIRECTLY, CONSEQUENTIALLY OR OTHERWISE RESULTING FROMTHE USE OF THIS REPORT.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    4/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 4 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    1 INTRODUCTION

    This document provides the mathematical models of the THYNE5/THYNE6 excitation system forpower system stability studies together with the required system parameters of the generator,

    transformer and grid as well as the excitation (power part and controller).

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    5/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 5 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    2 SIMULATIONMODEL ANDPARAMETERS

    2.1 Generator, Transformer and Grid Connection

    The synchronous generator model for power system stability studies is typically a sub transientmodel of a salient pole machine (hydro units) or round rotor machine (thermal units). Thecorresponding model parameters are summarized in Table 1 with typical values for hydro andthermal units, see [2].

    Symbol Parameter name Unit

    S r Rated apparent power 201.35 MVA

    Ur Rated terminal voltage 13.8 kV

    cos(phi) Power factor 0.85

    f r Grid frequency 60 Hz

    wr Rated speed rpm

    Xd d-axis synchronous reactance 1.044 p.u.

    Xd’ d-axis transient reactance 0.352 p.u.

    Xd” d-axis sub transient reactance 0.261 p.u.

    Xq q-axis synchronous reactance 0.724 p.u.

    Xq’ q-axis transient reactance – p.u.

    Xq” q-axis sub transient reactance 0.228 p.u.

    Xl Stator leakage reactance 0.13 p.u.

    R a Stator resistance

    Td0 ’ d-axis transient open circuit time constant 8.64 s

    Td0 ” d-axis sub transient open circuit time constant 0.107 s

    Tq0 ’ q-axis transient open circuit time constant – s

    Tq0 ” q-axis sub transient open circuit time constant s

    H Overall inertia of turbine and generator 4.35 s

    IE,r Excitation current at rated load 1575 A

    VE,r Excitation voltage at rated load 270.2 V

    IE,ag Excitation current at no-load air-gap 756 A

    Table 1: Synchronous generator data.

    For the step-up transformer the required parameters are summarized in Table 2.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    6/19

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    7/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 7 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    2.2 THYNE5/THYNE6 Static Excitation System

    2.2.1 Basic Structure of AVR and Power Part

    Figure 2 shows the mathematical model of the THYNE5/THYNE6 excitation system (AVR + powerpart) in shunt field connection. A list of the corresponding input, output and internal signals is givenin Table 4 and a list of all system parameters is provided in Table 5 and Table 6.

    Symbol Signal name Unit

    VT Terminal voltage magnitude p.u.

    IT Terminal current magnitude p.u.

    IP Terminal current active component p.u.

    IQ Terminal current reactive component p.u.P Active power p.u.

    Speed p.u.

    Load angle deg

    VC Compensation voltage p.u.

    VCF Filtered compensation voltage p.u.

    IE Excitation current p.u.

    VE Excitation voltage p.u.IEF Filtered excitation current p.u.

    VREF Reference voltage (set-point) p.u.

    IE,REF Reference excitation current (set-point) p.u.

    VS PSS output p.u.

    VUEL Under excitation limiter output p.u.

    VTHL Thermal limiter output p.u.

    VOEL Over excitation limiter output p.u.

    Table 4: Excitation model signals.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    8/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 8 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    Figure 2: THYNE5/THYNE6 excitation system model.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    9/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 9 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    Symbol Parameter name Value Unit

    VTH Thyristor voltage 550 V

    KE Amplification of rectifier 1.35 1)

    KT Amplification of excitation transformer K T = V TH / VE,r 2.03

    KN Re-normalization factor K N = IE,r / IE,ag 2.08

    TE Time constant rectifier 0.003 s

    Table 5: Power part model parameters.

    1) For a 3-phase thyristor bridge.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    10/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 10 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    Symbol Parameter name Value Unit

    Active power compensation (droop) factor - p.u.

    Reactive power compensation (droop) factor - p.u.

    TFU Time const. voltage transducer 0.01 s

    VPU Proportional gain, voltage controller 5 p.u.

    TNU Integrator time constant, voltage controller 0.7 s

    KDU Differential gain, voltage controller 0 p.u.

    TDU Differential filter time constant, voltage controller 1 s

    VPUmin Min. input limit, voltage controller -2.0 p.u.

    VPUmax Max. input limit, voltage controller 2.0 p.u.

    VTUmin Min. integrator limit, voltage controller I E - 0.33 p.u.

    VTUmax Max. integrator limit, voltage controller I E +0.33 p.u.

    VOUmin Min. output limit, voltage controller I E - 0.33 p.u.

    VOUmax Max. output limit, voltage controller I E +0.33 p.u.

    TFI Time const. field current transducer 0.005 s

    VPI Proportional gain, current controller 4 p.u.TNI Integrator time constant, current controller 0 s

    VPImin Min. input limit, voltage controller -16.0 p.u.

    VPImax Max. input limit, voltage controller 16.0 p.u.

    VTImin Min. integrator limit, voltage controller -0.8660 p.u.

    VTImax Max. integrator limit, voltage controller 0.9962 p.u.

    VOImin Min. output limit, voltage controller -0.8660 p.u.

    VOImax Max. output limit, voltage controller 0.9962 p.u.

    Table 6: AVR model parameters.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    11/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 11 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    2.2.2 Power System Stabilizer

    The power system stabilizer is a PSS2A/B type according to IEEE 421.5 as shown in Figure 3. Thecorresponding parameters are listed in Table 7.

    Figure 3: Power system stabilizer block diagram.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    12/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 12 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    Symbol Parameter name Value Unit

    TW1 Wash out time constant 1 5 s

    TW2 Wash out time constant 2 5 s

    TW3 Wash out time constant 3 5 s

    TW4 Wash out time constant 4 0 s

    T6 Low pass filter time constant 6 0 s

    T7 Low pass filter time constant 7 5 s

    KS2 Proportional gain 2 0.64

    KS3 Proportional gain 3 1

    T8 Ramp tracking filter time constant of numerator 0.5 s

    T9 Ramp tracking filter time constant of denominator 0.1 s

    M Ramp tracking filter exponent of denominator 5

    N Ramp tracking filter exponent of numerator 1

    T1 Lead lag 1 time constant of numerator 0.13 s

    T2 Lead lag 1 time constant of denominator 0.04 s

    T3 Lead lag 2 time constant of numerator 0.15 s

    T4 Lead lag 2 time constant of denominator 0.04 s

    T10 Lead lag 3 time constant of numerator 0.14 s

    T11 Lead lag 3 time constant of denominator 0.04 s

    S AB Switch: 0 … PSS2A / 1 … PSS2B 1

    KS1 Proportional gain 1 4

    VSmin Min. PSS output limit -0.05 p.u.

    VSmax Max. PSS output limit 0.05 p.u.

    Table 7: Power system stabilizer parameters.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    13/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 13 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    2.2.3 Instantaneous Field Current Limiter

    The instantaneous field current limiter as shown in Figure 4 consists of two parallel PIcontrollers with anti-wind-up integrators. The corresponding parameters can be found inTable 8.

    +

    +

    VFCL

    1

    sT I,FCLmin+

    KP,FCLmin

    IEmin

    0

    VFCLmin

    IE

    +

    +1

    sT I,FCLmax+

    KP,FCLmax

    IEmax

    0

    VFCLmaxIE

    Figure 4: Instantaneous field current limiter block diagram.

    Symbol Parameter name Value Unit

    IEmin Lower field current limit p.u.

    KP,FCLmin Proportional gain of minimum regulator

    TI,FCLmin Integrator time constant of minimum regulator s

    VFCLmin Output limit of minimum regulator p.u.

    IEmax Upper field current limit p.u.

    KP,FCLmax Proportional gain of maximum regulator

    TI,FCLmax Integrator time constant of maximum regulator s

    VFCLmax Output limit of maximum regulator p.u.

    Table 8: Instantaneous field current limiter parameters.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    14/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 14 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    2.2.4 Under Excitation Limiter

    The structure of the under excitation limiter is shown in Figure 5. Is comprises a differentialand a PI controller with separate limits. The corresponding parameters can be found inTable 9.

    Figure 5: Under excitation limiter block diagram.

    Symbol Parameter name Value Unit

    D,LIM Differential rotor angle limit p.u.KDUEL Differential gain

    TDUEL Filter time constant of differentiator s

    VD,UELmax Output limit of differentiator 1.0 p.u.

    LIM Rotor angle limit p.u.

    KPUEL Proportional gain

    TIUEL Integrator time constant s

    VUELmax Output limit 2.0 p.u.

    Table 9: Under excitation limiter parameters.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    15/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 15 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    2.2.5 Thermal Limiter

    The block diagram of the thermal limiter is illustrated in Figure 6. Two separate timeconstants for the delayed signals of the stator current and field current as well as thehysteresis can be chosen. The controller is an integrator with two different time constants,i.e. TI1 for raising or lowering if the limiter becomes active and TI2 for resetting the limiter.The corresponding parameters can be found in Table 10.

    IT

    VTHLmin

    VTHLmax

    &

    ITd

    IQ

    ITd > ITmax

    A

    B

    C

    D

    1

    1-

    1

    s

    A

    S

    f RAISE

    f LOWER

    f RESETP

    f RESETN

    1

    1-

    0

    E

    f 0

    S

    RIf A=1: S=AIf B=1: S=BIf C=1: S=CIf D=1: S=DELSE: S=E

    1

    1+sT 1ITd < ITmax - ITzone

    IQ > IQmax

    IQ < IQmin

    IE

    IEd > IEmax S

    R1

    1+sT 2IEd < IEmax - IEzome

    IE > IEmax

    IE < IEmax - IEzone

    &

    &

    ORB

    V

    VTHL > 0 S

    RVTHL < 0

    &

    &

    C

    D

    If C=1: V THLmax =0If D=1: V THLmax =1ELSE: V THLmax =1

    If C=1: V THLmin =-1If D=1: V THLmin = 0ELSE: V THLmin =-1

    TI1

    TI1

    TI2

    TI2

    IT > ITmax

    IT < ITmax - ITzone

    IEd

    Figure 6: Thermal limiter block diagram .

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    16/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 16 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    Symbol Parameter name Value Unit

    T1 Time constant for delayed stator current s

    ITmax Limit for stator current p.u.

    ITzone Hysteresis for stator current p.u.

    IQmin Lower limit for reactive current p.u.

    IQmax Upper limit for reactive current p.u.

    T2 Time constant for delayed field current s

    IEmax Limit for field current p.u.

    IEzone Hysteresis for field current p.u.

    TI1 Integrator time constant 1 s

    TI2 Integrator time constant 2 s

    Table 10: Thermal limiter parameters.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    17/19

    E s t e

    d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s

    b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e n n a ,

    A u s t r i a .

    R e s e c t a r

    l a n o

    t a d e

    r o t e c c

    i ó n

    I S O 1 6 0 1 6

    Cliente / CliCentral / Pla

    Proy. / Proj.

    3 S TA3.1 S

    For thesee FigTHYNEThe diff

    nt Cerro del Águnt Cerro del Águ

    N° H110.002217

    NDARD M O

    andard M

    next revisiure 7 simil6 excitatioerential co

    ila S.Aila HPP

    ELS

    del IEEE 4

    n of the Ir as pres system. Tponent of

    Dibujado / DrawnCompr. / Check.

    Aprobado / Appr.

    =Interno / InternalDOC Nº

    1.5 ST8C

    EE standanted in [5],he correspthe voltage

    Figure 7: P

    NºPE-ADZ-

    rd 421.5 a which willnding par regulator

    roposed IE

    A In

    0

    +

    E05010104-MDC

    new staticallow a pr meters (inDU cannot

    EE 421.5

    rchivo / Filenamed. Fecha / Date

    07.05.2015

    -948

    excitationcise model. calculati

    be represe

    T8C mode

    PE-ADZ-7E0501010

    Fecha de Arch

    Hoja / Page 1

    odel ST8lling of then) are list

    nted by the

    l.

    -MDC-948-R00 _PSS.d. / Filedate 18.03.

    de /

    -

    is proposTHYNE5d in TableST8C mod

    ocx.2016

    f 19

    ed,nd11.el.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    18/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 18 de / of 19

    = + -Interno / Internal NºDOC Nº PE-ADZ-7E05010104-MDC-948

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    Symbol Parameter name Value Unit

    KP Potential circuit gain coefficient K P = K T, SW1 = A (shunt field) p.u.

    KI1 Potential circuit gain coefficient 0 p.u.

    XL Potential circuit gain coefficient 0 p.u.

    KI2 Potential circuit gain coefficient for compound 0 p.u.

    KC1 Rectifier loading factor proportional to commutating reactance 0 p.u.

    KC2 Rectifier loading factor proportional to commutating reactance 0 p.u.

    RC Active power compensation (droop) factor R C = p.u.

    XC Reactive power compensation (droop) factor X C = p.u.

    TR Time const. voltage transducer T R = T FU 0.01 s

    KPR Proportional gain, voltage controller K PR = V PU p.u.

    KIR Integrator time constant, voltage controller K IR = V PU / T NU 1/s

    VPRmin Min. input limit, voltage controller -2.0 p.u.

    VPRmax Max. input limit, voltage controller 2.0 p.u.

    VIRmin Min. integrator limit, voltage controller I FDF - 0.33 p.u.

    VIRmax Max. integrator limit, voltage controller I FDF +0.33 p.u.

    VORmin Min. output limit, voltage controller I FDF - 0.33 p.u.

    VORmax Max. output limit, voltage controller I FDF +0.33 p.u.

    KF2 Field current re-normalization factor K F2 = 1/K N

    TF2 Time const. field current transducer T F2 = T FI 0.005 s

    KPA Proportional gain, current controller K PA = V PI p.u.

    KIA Integrator gain, current controller K IA = V PI / TNI 1/s

    VPMmin Min. input limit, voltage controller -16.0 p.u.

    VPMmax Max. input limit, voltage controller 16.0 p.u.

    VIMmin Min. integrator limit, voltage controller -0.8660 p.u.

    VIMmax Max. integrator limit, voltage controller 0.9962 p.u.

    VOMmin Min. output limit, voltage controller -0.8660 p.u.

    VOMmax Max. output limit, voltage controller 0.9962 p.u.

  • 8/17/2019 PE-ADZ-7E05010104-MDC-948-R01 Powerhouse - Model for Power System Stability - THYNE5&THYNE6

    19/19

    Cliente / Client Cerro del Águila S.A Dibujado / Drawn Archivo / Filename PE-ADZ-7E05010104-MDC-948-R00 _PSS.docxCentral / Plant Cerro del Águila HPP Compr. / Check. Ind. Fecha / Date Fecha de Arch. / Filedate 18.03.2016

    Proy. / Proj. N° H110.002217 Aprobado / Appr. 01 07.05.2015 Hoja / Page 19 de / of 19

    = + -Interno / Internal Nº

    E s

    t e d o c u m e n

    t o e s p r o p r i e

    d a

    d d e

    A N D R I T Z H

    Y D R O

    G m

    b H

    , E i b e s b r u n n e r g a s s e

    2 0

    , 1 1 2 0 V i e

    n n a ,

    A u s

    t r i a

    .

    R e s p e c

    t a r

    l a n o

    t a d e p r o

    t e c c i

    ó n

    I S O

    1 6 0 1 6

    K A Amplification of excitation K A = K N KE

    T A Time constant rectifier 0.0013 s

    VRmin Min. output limit, converter V Rmin = K A VOMmin p.u.VRmax Max. output limit, converter V Rmin = K A VOMmax p.u.

    Table 11: ST8C model parameters.

    REFERENCES

    [1] Andritz Hydro, “GMR3 – Voltage Regulator and Gate Control Functional Description”, Andritz Hydro GmbH, Austria, 2012.

    [2] P. Kundur, "Power System Stability and Control", McGraw-Hill, New York, 1993.[3] IEC 60034-16-2 1991 Standard “Rotating electrical machines - Part 16: Excitation

    systems for synchronous machines - Chapter 2: Models for power system studies”.

    [4] IEEE Standard 421.5, "IEEE Recommended Practice for Excitation System Models forPower System Stability Studies" April 2006.

    [5] A. Glaninger-Katschnig, F. Nowak, M. Baechle and J. Taborda, “New Digital ExcitationSystem Models in addition to IEEE.421.5 2005”, IEEE PES General Meeting, 2010