pelat pondasi

52
Two-Way Floor Slab System & Footings September, 2004

Upload: beta-saya

Post on 16-Jul-2015

227 views

Category:

Engineering


4 download

TRANSCRIPT

Page 1: Pelat pondasi

Two-Way Floor Slab System & Footings

September, 2004

Page 2: Pelat pondasi

Lecture GoalsLecture Goals

• Direct Method• Reinforcement in Two-way Slabs• Footing Classification• Footing Design

Page 3: Pelat pondasi

Minimum extensions for reinforcementMinimum extensions for reinforcement

The reinforcement is for slabs without beams.

Page 4: Pelat pondasi

Design ExamplesDesign Examples

Look at Example 13-7 Design of a flat plate floor without spandrel beams -Direct Design Method

Look at Example 13-9

Design of a Two-way slab with beams in both directions.

Page 5: Pelat pondasi

Shear Strength of TwoShear Strength of Two--way Slabsway Slabs

Shear failure occurs when inclined cracks form due to flexural and shearing stresses.

Two types of shear failure mechanism in 2-way slabs.

(a) One-way shear

(b) Two-way shear (Punching shear).

Page 6: Pelat pondasi

Shear Failure MechanismShear Failure Mechanism

One-way shear Two-way shear

Page 7: Pelat pondasi

Slabs failing in twoSlabs failing in two--way shearway shear

Inclined cracking Slab slides down column

Top (negative reinforcement pulls out of slab leaving no connection to the column

Inclined cracking

Page 8: Pelat pondasi

Design for twoDesign for two--way Shearway ShearCritical perimeter is located d / 2 from column face, where d = effective depth of slab

Page 9: Pelat pondasi

Design for twoDesign for two--way Shearway Shear

Critical perimeter is located d / 2 from column face, where d = effective depth of slab

Slabs with Drop Panels

Page 10: Pelat pondasi

Design EquationsDesign Equations

Two-way Shear with Negligible Moment Transfer

nu VV φ≤ ACI Eqn. 11-1

where, Vu =

Vn =

φ =

Factored shear force (tributary area bounded by lines of zero shear)

Nominal shear resistance of slab

0.85

Page 11: Pelat pondasi

Design EquationsDesign Equations

Two-way Shear with Negligible Moment Transfer

scn VVV +=

where, Vc =

Vs =

Shear resistance of concrete

Shear resistance of steel (in most slabs, Vs = 0)

Page 12: Pelat pondasi

Design EquationsDesign Equations

(a) Two-way Shear with Negligible Moment TransferFor two-way shear in slabs (& footings) Vc is smallest of

long side/short side of column concentrated load or reaction area

length of critical perimeter around the column

where, βc =

b0 =

ACI 11-35dbfV 0c

c

c 42

+=

β

Page 13: Pelat pondasi

Design EquationsDesign Equations

(b) Two-way Shear with Negligible Moment Transfer

dbfb

dV 0c

0

sc 2

+=

αACI 11-36

40 for interior columns

30 for edge columns

20 for corner columns

where, αs =

Page 14: Pelat pondasi

Design EquationsDesign Equations

(c) Two-way Shear with Negligible Moment Transfer

dbfV 0cc 4= ACI 11-37

Take smaller of (a), (b) and (c)

Page 15: Pelat pondasi

Design EquationsDesign Equations

Tributary area for Vu calculations

Figure 13-41

MacGregor

Page 16: Pelat pondasi

Slab Shear ReinforcementSlab Shear Reinforcement

If , Vn can be increased by:uc VV ≤φ

Increase slab thickness

Use drop panel

Increase b0 by increasing column size or adding a fillet or capital

Add shear reinforcement

(1)

(2)

(3)

(4)

Page 17: Pelat pondasi

Slab Shear ReinforcementSlab Shear Reinforcement

Page 18: Pelat pondasi

Footings

General Introduction

Page 19: Pelat pondasi

FootingFootingDefinition

Footings are structural members used to support columns and walls and to transmit and distribute their loads to the soil in such a way that the load bearing capacity of the soil is not exceeded, excessive settlement, differential settlement,or rotation are prevented and adequate safety against overturning or sliding is maintained.

Page 20: Pelat pondasi

Types of FootingTypes of Footing

Wall footings are used to support structural walls that carry loads for other floors or to support nonstructural walls.

Page 21: Pelat pondasi

Types of FootingTypes of Footing

Isolated or single footingsare used to support single columns. This is one of the most economical types of footings and is used when columns are spaced at relatively long distances.

Page 22: Pelat pondasi

Types of FootingTypes of Footing

Combined footings usually support two columns, or three columns not in a row. Combined footings are used when tow columns are so close that single footings cannot be used or when one column is located at or near a property line.

Page 23: Pelat pondasi

Types of FootingTypes of Footing

Cantilever or strap footingsconsist of two single footings connected with a beam or a strap and support two single columns. This type replaces a combined footing and is more economical.

Page 24: Pelat pondasi

Types of FootingTypes of Footing

Continuous footingssupport a row of three or more columns. They have limited width and continue under all columns.

Page 25: Pelat pondasi

Types of FootingTypes of FootingRafted or mat foundationconsists of one footing usually placed under the entire building area. They are used, when soil bearing capacity is low, column loads are heavy single footings cannot be used, piles are not used and differential settlement must be reduced.

Page 26: Pelat pondasi

Types of FootingTypes of Footing

Pile caps are thick slabs used to tie a group of piles together to support and transmit column loads to the piles.

Page 27: Pelat pondasi

Distribution of Soil PressureDistribution of Soil Pressure

When the column load P is applied on the centroid of the footing, a uniform pressure is assumed to develop on the soil surface below the footing area. However the actual distribution of the soil is not uniform, but depends on may factors especially the composition of the soil and degree of flexibility of the footing.

Page 28: Pelat pondasi

Distribution of Soil PressureDistribution of Soil Pressure

Soil pressure distribution in cohesive soil.

Soil pressure distribution in cohesionless soil.

Page 29: Pelat pondasi

Design ConsiderationsDesign Considerations

Footings must be designed to carry the column loads and transmit them to the soil safely while satisfying code limitations.

The area of the footing based on the allowable bearing soil capacity

Two-way shear or punching shear.

One-way bearing

Bending moment and steel reinforcement required

*

*

*

*

Page 30: Pelat pondasi

Design ConsiderationsDesign Considerations

Footings must be designed to carry the column loads and transmit them to the soil safely while satisfying code limitations.

Bearing capacity of columns at their base

Dowel requirements

Development length of bars

Differential settlement

*

*

*

*

Page 31: Pelat pondasi

Size of FootingSize of Footing

The area of footing can be determined from the actual external loads such that the allowable soil pressure is not exceeded.

( )pressure soil allowable

weight-self including load Total footing of Area =

Strength design requirements

footing of areau

uPq =

Page 32: Pelat pondasi

TwoTwo--Way Shear (Punching Shear)Way Shear (Punching Shear)

For two-way shear in slabs (& footings) Vc is smallest of

dbfV 0c

c

c 42

+=

β ACI 11-35

long side/short side of column concentrated load or reaction area<2

length of critical perimeter around the column

where, βc =

b0 =

When β >2 the allowable Vc is reduced.

Page 33: Pelat pondasi

Design of twoDesign of two--way shearway shear

1

2

Assume d.

Determine b0:

b0 = 4(c+d) for square columns where one side = c

b0 = 2(c1+d) +2(c2+d) for rectangular columns of sides c1

and c2.

Page 34: Pelat pondasi

Design of twoDesign of two--way shearway shear

The shear force Vu acts at a section that has a length b0 = 4(c+d) or 2(c1+d) +2(c2+d) and a depth d; the section is subjected to a vertical downward load Pu and vertical upward pressure qu.

3

( )( )( ) columnsr rectangulafor

columns squarefor

21uuu

2uuu

dcdcqPV

dcqPV

++−=

+−=

Page 35: Pelat pondasi

Design of twoDesign of two--way shearway shear

Allowable

Let Vu=φVc

4

dbfV 0cc 4φφ =

0c

u

4 bf

Vdφ

=

If d is not close to the assumed d, revise your assumptions

Page 36: Pelat pondasi

Design of oneDesign of one--way shearway shear

For footings with bending action in one direction the critical section is located a distance d from face of column

dbfV 0cc 2φφ =

Page 37: Pelat pondasi

Design of oneDesign of one--way shearway shear

The ultimate shearing force at section m-m can be calculated

−−= dcLbqV

22 uu

If no shear reinforcement is to be used, then d can be checked

Page 38: Pelat pondasi

Design of oneDesign of one--way shearway shear

bf

Vd 2 c

u

φ=

If no shear reinforcement is to be used, then d can be checked, assuming Vu = φVc

Page 39: Pelat pondasi

Flexural Strength and Footing Flexural Strength and Footing reinforcement reinforcement

2

y

us

=adf

MAφ

The bending moment in each direction of the footing must be checked and the appropriate reinforcement must be provided.

Page 40: Pelat pondasi

Flexural Strength and Footing Flexural Strength and Footing reinforcement reinforcement

Another approach is to calculated Ru = Mu / bd2 and determine the steel percentage required ρ . Determine As then check if assumed a is close to calculated a

bf

Afa

85.0 c

sy=

Page 41: Pelat pondasi

Flexural Strength and Footing Flexural Strength and Footing reinforcement reinforcement

The minimum steel percentage required in flexural members is 200/fy with minimum area and maximum spacing of steel bars in the direction of bending shall be as required for shrinkage temperature reinforcement.

Page 42: Pelat pondasi

Flexural Strength and Footing Flexural Strength and Footing reinforcement reinforcement

The reinforcement in one-way footings and two-way footings must be distributed across the entire width of the footing.

1

2

directionshort in ent reinforcem Total

widthbandin ent Reinforcem

+=

β

footing of sideshort

footing of side long=β

where

Page 43: Pelat pondasi

Bearing Capacity of Column at BaseBearing Capacity of Column at Base

The loads from the column act on the footing at the base of the column, on an area equal to area of the column cross-section. Compressive forces are transferred to the footing directly by bearing on the concrete. Tensile forces must be resisted by reinforcement, neglecting any contribution by concrete.

Page 44: Pelat pondasi

Bearing Capacity of Column at BaseBearing Capacity of Column at Base

Force acting on the concrete at the base of the column must not exceed the bearing strength of the concrete

( )1c1 85.0 AfN φ=

where φ = 0.7 and

A1 =bearing area of column

Page 45: Pelat pondasi

Bearing Capacity of Column at BaseBearing Capacity of Column at Base

The value of the bearing strength may be multiplied by a factor for bearing on footing when the supporting surface is wider on all sides than the loaded area.

0.2/ 12 ≤AA

The modified bearing strength

( )( )1c2

121c2

85.02

/85.0

AfN

AAAfN

φ

φ

Page 46: Pelat pondasi

Dowels in FootingsDowels in Footings

A minimum steel ratio ρ = 0.005 of the column section as compared to ρ = 0.01 as minimum reinforcement for the column itself. The number of dowel bars needed is four these may be placed at the four corners of the column. The dowel bars are usually extended into the footing, bent at the ends, and tied to the main footing reinforcement. The dowel diameter shall not =exceed the diameter of the longitudinal bars in the column by more than 0.15 in.

Page 47: Pelat pondasi

Development length of the Reinforcing BarsDevelopment length of the Reinforcing BarsThe development length for compression bars was given

but not less than

Dowel bars must be checked for proper development length.

cbyd /02.0 fdfl =

in. 8003.0 by ≥df

Page 48: Pelat pondasi

Differential SettlementFooting usually support the following loads

Dead loads from the substructure and superstructure

Live load resulting from material or occupancy

Weight of material used in backfilling

Wind loads

Page 49: Pelat pondasi

General Requirements for Footing DesignGeneral Requirements for Footing Design

1

2

3

A site investigation is required to determine the chemical and physical properties of the soil.

Determine the magnitude and distribution of loads form the superstructure.

Establish the criteria and the tolerance for the total and differential settlements of the structure.

Page 50: Pelat pondasi

General Requirements for Footing DesignGeneral Requirements for Footing Design

4

5

6

Determine the most suitable and economic type of foundation.

Determine the depth of the footings below the ground level and the method of excavation.

Establish the allowable bearing pressure to be used in design.

Page 51: Pelat pondasi

General Requirements for Footing DesignGeneral Requirements for Footing Design

Determine the pressure distribution beneath the footing based on its width

Perform a settlement analysis.

7

8

Page 52: Pelat pondasi

Example

Design a plain concrete footing to support a 16 in thick concrete wall. The load on the wall consist of 16k/ft dead load (including the self-weight of wall) and a 10 k/ft live load the base of the footing is 4 ft below final grade. fc = 3ksi and the allowable soil pressure = 5k/ft2