performance based design for fire safety

Upload: tharanga-pradeep

Post on 14-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    1/23Advances in Structural Engineering Vol. 7 No. 4 2004 311

    1. PERFORMANCE BASED DESIGNFOR FIRE SAFETYA rational approach to fire safety assessment is to relate

    functional requirements, such as prevention of spreading

    heat and smoke, safe evacuation and rescue etc., to fire

    resistance considering both local and global stability of

    structures. In a performance-based design, the designer

    needs to first understand the level of performance is

    expected, then to design to these levels and finally to

    predict the performance that will be achieved to ensure

    the reliability and robustness of the design.

    At the beginning of the performance-based analysis

    and design, the designer and the stakeholders should

    both agree on the project scope, intent and building use.

    The designer will then define and prioritize the fire safety

    plans and performance criteria and define the fire safety

    goals and objectives pertaining to the design intent. The

    next step to follow is to determine the implementation of

    the selected solutions into the project scope and execution.

    The final stage is to establish the necessary verification

    and quality assurance to ensure compliance with the

    agreed solutions.

    In general, a process for performance-based design

    would involve the following steps:

    1. identify goals and defining stakeholder and design

    objectives

    2. identify the possible fire scenarios which could

    occur during the service life of the structure,

    Performance Based Fire Safety Design of

    Structures A Multi-dimensional Integration

    J. Y. Richard Liew*

    Department of Civil Engineering, National University of Singapore, Blk E1A, #05-13, 1 Engineering Drive 2, Singapore 117576

    (Received 16 July 2003; Received revised form: 17 November 2003; Accepted: 18 November 2003)

    Abstract: Design codes for fire safety in buildings can be either a prescriptive type or

    performance-based type. It is now widely recognized that performance-based codes

    provide greater advantages over the prescriptive codes in that it allows designers to use

    the fire engineering methods to assess the fire safety of the structure. However, as the

    assessment of the whole structure performance is not easy, most codes currently used

    are still prescriptive codes or a combination of prescriptive codes and performance-

    based codes. The key feature for implementing the performance-based fire design

    codes is the assessment of the fire resistance of the structure. This paper provides an

    overall view on performance-based code and the approaches for designing steel structure

    in fire considering a multi-dimensional integration of fire engineering simulation,

    emergency evacuation and structural resistance. Various fire models and heat transfer

    analysis methods are reviewed and discussed. The basis to modelling of large deflection

    and plasticity using appropriate stress-strain relationship at elevated temperature is

    explained. Finally, structural response calculations from simplified hand calculation

    method to advanced numerical procedures are presented. Future trends for research are

    identified.

    Key words: fire safety, emergency evacuation, explosion, fire modelling, fire protection, performance-based design, tall buildings,

    plastic hinge analysis.

    *Corresponding author. Email address: [email protected]; Fax: +65-6779-1635; Tel: +65-6874-2154.

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    2/23

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    312 Advances in Structural Engineering Vol. 7 No. 4 2004

    3. evaluate the likelihood and consequences of such

    scenarios,

    4. establish appropriate performance criteria by

    ensuring effective evacuation, escape and rescue

    and to prevent injury arising from such events,

    5. predict the performance of the system based on

    available engineering data, and6. ensure robustness of the designs, reliability and

    durability of the protection systems, etc.

    Although the governing criteria for impairment of

    the main safety functions are often non-structural (for

    example exposure to heat, temperature, toxic gases etc.),

    it is, however, a functional requirement that the structure

    would remain stable to allow adequate time for safe

    evacuation and rescue. Therefore a quantitative

    assessment on fire resistance of a structure is necessary

    and this opens up the opportunity in using advanced

    simulation tools and computational methods developed

    as reported in the recent fire workshops (Liew 2002;Moss 2002).

    2. EMERGENCY EVACUATIONThe objective of providing emergency evacuation is to

    allow occupants to travel safely to a place of safety in

    the event of fire. In general, the procedure involved in

    estimating evacuation time is given below:

    1. define the space domain to be analyzed

    2. estimate the response time of occupants

    3. calculate the travel time to a specific location

    4. determine whether this location is safe5. if the specific location is safe, record the total

    required safe escape time and make sure that it

    does not exceed the available safe escape time,

    which is determined by untenability condition.

    If the specific escape route is not safe, select

    another one and repeat Step 3.

    A range of possible emergency scenarios may occur in

    high-rise and complex buildings for which it is necessary

    to develop a range of strategies for managing accidental

    fires. The following points are considered when planning

    for an evacuation strategy for such systems:

    Risk perception in high rise/complex buildings

    Types of fire scenarios that may occur and may

    need different evacuation strategies

    Fire scenarios that will affect building protection

    strategies and the emergency plans proposed

    Limitations of each emergency plans

    Integration of fire service into the emergency

    plan

    Types of information to be provided to the

    occupants

    Emergency evacuation training and fire

    protection maintenance plan

    A major limitation on prediction of incident outcomes

    for performance-based design and hazard assessment

    is the lack of quantitative data on pre-movement time

    and evacuation time, and occupant behaviours for

    different fire scenarios and occupancies. There is a need

    to study human behaviour during evacuation from a

    range of occupancies. Advanced computer software isavailable to predict the evacuation time considering the

    effects of exposure to fire effluence on occupant

    evacuation behaviour. However, improvements are

    still needed to include the effects of different warning

    systems, information provided to occupants, occupant

    characteristics, pre-training, building complexity and

    level of fire safety management on pre-movement and

    evacuation time. The September 11 incident had shown

    that fire service intervention occurred while there were

    many occupants still in the buildings, many were in the

    process of evacuating while other remained in refuge

    were trapped by fire. In order to achieve effective designfor buildings in emergency situations, it is essential to

    consider occupants characteristics, their abilities to

    evacuate and the effects of exposure to fire effluence on

    occupant evacuation behaviour.

    3. FIRE MODELLINGFire modelling is a mathematical simulation of the fire

    conditions in a compartment and is capable of giving

    information based on the parameters which have been

    designed. The fire development in a room normally

    involves three phases: pre-flashover, post-flashover andfire decay. In the pre-flashover phase, fuels begin to burn

    and the gas temperature varies from one point to another

    in the compartment. In the post-flashover phase, the

    fire develops fully, and the gas temperature increases

    rapidly to a peak value and becomes practically uniform

    throughout the compartment. The fire has the most

    influence on structural design because of high temperature

    and radiant heat fluxes produced in this phase. In the fire

    decay phase, the available fuel begins to decrease and

    the gas temperature falls. There is considerable benefit

    when the effects of natural fires in buildings, where the

    amounts of the combustible contents are small and the

    buildings are of large volume, is considered than using

    the standard ISO fire.

    For many years, fire engineering research has shown

    that overall structure performs better than isolated

    members in a fire situation. Numerous studies have been

    carried out to determine the temperature reached in real

    (natural) fires, to quantify the factors that govern fire

    severity and to investigate the parameters that cause

    structures to fail in fire. The studies show that the severity

    of natural fires in building compartments is governed by

    the amount of combustible material (the fire load), the

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    3/23

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 313

    area of the doors and windows (the ventilation), and the

    thermal characteristics of the wall, floor and ceiling

    materials. In addition, fire-fighting measures are also

    important for the determination of fire exposure.

    The following subsections discuss the various models

    available for modelling fire of different complexity and

    severity.

    3.1. Design Fire ModelsDesign fires are derived empirically and may yield

    reasonable and consistent predictions provided that the

    fire conditions are similar to those in the underlying

    assumptions. Standard fire curves such as ISO-834 do

    not represent the real fire in a compartment and serve

    only as criteria to evaluate the fire resistance capacity of

    single structural members. Simplified code prescribed

    method often assumes that the fire has a constant

    temperature throughout the burning period.

    Eurocode 1: Part 1-2 (2001) recommends equationsfor parametric fires, allowing a temperature-time curve

    to be produced for any combination of fuel load, opening

    factor, height of opening and thermal characteristic of

    the boundary materials.

    The temperature T (C) and time relation during theheating phase is given as (Eurocode 1: Part 1-2, 2001):

    (1)

    where t* is the fictitious time given by

    t* = t. (2)

    t is the time (hr) and

    (3)

    where b is the square root of thermal inertial of the

    boundary material of the compartment and O is the

    opening factor (m1/2) given by

    (4)

    Av is the total area of vertical openings on all walls;

    heq is the weighted average of window heights on all

    walls andAt is the total area of enclosure (walls, ceiling

    and floor, including openings). In case of= 1, Eqn 1approximates the ISO834 standard temperature-time

    curve.

    Depending on whether the fire is fuel controlled or

    ventilation controlled, the duration of the heating phase

    tmax (hr) is given as:

    (5)

    qt,d is the design value of the fire load per total surface area

    At of the enclosure. The recommended fire growth rate is

    taken as tlim = 25 minutes, 20 minutes and 15 minutes for

    slow, medium and fast growth rate, respectively.

    The introduction of tlim is to avoid unrealistic short

    fire duration when the ratio between the fire load and the

    opening factor decreases. Any object or fire load needsa certain amount of time to burn, even if there is

    unlimited presence of air (Franssen 1997).

    The temperature-time curve during the cooling phase

    is given by:

    T = Tmax 625(t* t*max.x) for t*max 0.5

    T = Tmax 250(3 t*max)(t* t*max.x)for 0.5 < t*max < 2

    T = Tmax 250(t* t*max.x) for t*max 2 (6)

    in which

    t* = t.

    t*max = (0.2 103 qt,d/O).

    x = 1.0 if tmax > tlim

    x = tlim./ t*max if tmax = tlim

    Figure 1 shows the parametric fire curves plotted for a

    range of opening factors (OF), fuel loads and materials

    according to the Eurocode 1: Part 1-2 (2001). Fire curvesare produced for three fire loads, four opening factors

    and two types of construction, showing the significant

    dependence of fire temperature on the bounding materials.

    The fire loads are 400, 800 and 1200 MJ per floor area,

    for a room 5 5 m in plan and 3 m high. Feasey &Buchanan (2002) pointed out that the Eurocode equation

    gives extremely fast decay rates for large openings in

    well insulated compartments (e.g., OF = 0.12 in Figure 1)

    and extremely slow decay rates for small openings in

    poorly insulated compartments. They proposed some

    modifications to the Eurocode formula to give a better

    estimation of the temperature-time curve in the fire

    decay phase.

    3.2. Zone ModelsZone models represent more of the phenomenological

    behaviour of fire. They solve the conservation equations

    for distinct and relatively large regions. In each zone,

    the heat balance equations are solved to generate gas

    temperatures. There are several options for calculating

    the heat release rate, based on ventilation control, fuel

    control or the porosity of wood crib fuels. Other computer

    models including ZONE, CSTBZ1, CFAST, BANZFIRE,t = Maximum 0.2 q O, tmax t,d lim[ ]

    103

    O = A h Av eq t

    =( )

    ( )

    O b/

    . /

    2

    20 04 1160

    T

    e e et t t

    =

    + ( ) 20

    1325 1 0 324 0 204 0 4720 2 1 7 19

    . . .. * . * *

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    4/23

    are summarised in SFPE (2002). Schleich (1996)

    developed a realistic fire evolution model, which not

    only takes into account the physical factors, but also the

    influence of active protection measures in the structure.

    The multi-zone fire model (Liew et al. 2002) places

    heating boxes one outside another and assumes uniform

    heating in each box, as shown in Figure 2. The smallest

    box nearest to the heat source has the highest

    temperature. The boxes further from the heat source have

    lower temperature, and the farthest box has the lowest

    temperature. The structural elements enclosed within

    each heating box are subjected to a uniform heating

    rate, which can be either constant or vary as a function

    of time. The temperature-time relationship in each box

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    314 Advances in Structural Engineering Vol. 7 No. 4 2004

    1400

    1200

    1000

    800

    600

    400

    200

    00 50 100 150 200

    Time (min)

    T

    emperature(C)

    250 300 350

    ISO 834

    Concrete

    GypsumOF = 0.02

    400

    1400

    1200

    1000

    800

    600

    400

    200

    00 50 100 150 200

    Time (min)

    T

    emperature(C)

    250 300 350

    ISO 834

    Concrete

    Gypsum OF = 0.04

    400

    1400

    1200

    1000

    800

    600

    400

    200

    00 20 40 60

    Time (min)

    Temperature(C)

    80 100

    ISO 834

    Concrete

    GypsumOF = 0.08

    120

    1400

    1200

    1000

    800

    600

    400

    200

    00 20 40 60

    Time (min)

    Temperature(C)

    80 100

    ISO 834

    Concrete

    GypsumOF = 0.12

    120

    Figure 1. Parametric temperature-time curves (fuel load = 400, 800, 1200 MJ/m2 floor area)

    Figure 2. Multi-zone fire model

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    5/23

    may be obtained by calibration with fire tests or from

    numerical simulation based on the theory of thermal

    energy balance. The air temperature at each time step

    can be prescribed.

    The multi-zone fire model (Liew et al. 2002)

    provides a means to calibrate actual fires. The heat

    intensity and the flame size of the actual fires dependon many factors such as fire load, ventilation, active fire

    control devices, and so on. If there is such a part in a

    structure that is heated significantly more or less than

    others, the multi-zone model could be a more suitable

    fire model to simulate an open fire. The multi-zone fire

    model can be used to simulate uniform heating. In this

    case, only one-box is prescribed and all structural

    members within this box will be heated simultaneously

    under the same fire load.

    3.3. Radiation Model

    Radiation model may be used to simulate fire as aradiating source with the heat flux intensity defined by

    its distance from the source, as shown in Figure 3. The

    heat rays are emitted in all directions. The heat intensity

    may be constant or vary as a function of time. The heat

    flux intensity, q, received by the individual elements is

    calculated as (SINTEF 1995):

    (7)

    where

    Ei = total energy emitted from the sourceri = distance between the heat source and the midpoint

    of ith element

    i = angle between the ray and the element surface

    normal (see Figure 3).

    The air temperature can be computed by adopting the

    Stefan-Boltzman formula once the heat flux intensity is

    known (Yao et al. 1995):

    (8)

    where

    = the emissivity coefficient;

    qi = the heat flux intensity calculated from Eqn 7;= the Stefan-Boltzman constant of 5.67 108 W/m2K4;TK= the temperature on the spherical surface with a unit

    of Kelvin (K).

    The radiation model is a convenient way to propose a

    simple relationship between the air temperature and its

    distance from the fire source. For large and complex

    structures, the radiation model is preferred as it is

    relatively simpler to use for simulating an open fire.

    On the other hand, the multi-zone fire model requires a

    descritization of space into finite boxes. Each heating

    box needs to be prescribed with an appropriate time-

    temperature relationship.

    3.4. Computational Fluid Dynamic (CFD)ApproachThe CFD model can be used to represent various types

    of walls of different materials and the exact location

    and dimensions of openings. The fire compartment to

    be modelled by CFD is divided into a number of small

    volumes. The fluid dynamics equations are written in

    each of these small volumes, and each volume is linked

    to the adjacent volumes. The heat transient problems are

    expressed in differential equations, and time integrationhas to be performed by solving a large number of

    equations in the time domain. The main drawback of

    CFD model is that a significant number of parameters

    have to be given and many of them are variable with

    very little, if any, link to any physical phenomenon. It

    requires an experienced user before the any meaningful

    Tq

    ki=

    1 4

    qE

    r2i

    i

    i=4

    cos

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 315

    I = intensity cos()

    y

    x

    z

    radius

    (x, y, z)

    Intensity

    Figure 3. Radiation model to simulate open fires

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    6/23

    result can be obtained. Practising engineers often find

    difficulties in understanding the hypothesis underlying

    the CFD models and they have to be careful in interpreting

    the results.

    A large amount of results can be produced by CFD

    computation. For instance, it provides the temperature

    components of the velocity, the pressure, the oxygen

    concentration, etc, in every volume at every time step. A

    graphical representation of the results is mandatory, see

    Figure 4. To some extend, the amount of results can

    even create a difficulty if the interest is for the behaviourof structure. An interface is often needed to be created

    between the CFD model and the structural model, because

    thermal environment in the compartment calculated by

    the CFD model would influence the structural element.

    The main advantage of CFD models is to model

    compartments with complex geometry because only the

    flexibility given by the fine discretisation of the space

    inherent to CFD models allows a correct representation

    of this complexity. Notwithstanding the costs and

    problems associated to these models, they are favoured

    by researchers who use them as the design tools for fire

    analysis. Their application domain is for complex

    projects which are very often combined the geometrical

    complexity and the financial resources which make the

    CFD model an attractive choice.

    4. HEAT TRANSFER ANALYSISThe process of heat transfer between a fire and a

    structure can be described by the balance between the

    net incident thermal radiation and convective heat flux

    and the rate of heat conducted in the material. The rate

    of heating of any structural member is dependent at any

    time on the temperatures of both the fire atmosphere and

    the member. Calculation of member temperature requires

    solution in time domain via a fairly complex differential

    equation. There are two kinds of heat transfer methods

    used in fire engineering design: analytical method and

    finite element method.

    4.1. Analytical MethodDifferent standards or specifications give simplified way

    to calculate the net heat flux and temperature development

    in the steel member. The heat flux due to convection is

    proportional to the temperature gradient between theambient gas temperature and temperature of the steel

    member. The heat flux due to radiation is proportional to

    the temperature gradient of the forth order of the ambient

    gas temperature and the steel temperature. ECCS (1993)

    uses a single expression to represent the total heat flux as

    (9)

    where

    As = surface area of the member per unit length exposed

    to heating

    f= fire temperature at time t

    s = temperature of the steel member

    h = coefficient of total heat transfer

    Based on this heat flow law, the temperature

    development in unprotected steel member can be

    calculated. Eurocode 3: Part 1-2 (2001) provides a rational

    means to estimate steel temperature development by

    considering the section factor and configuration factor

    for internal steelwork and external steelwork. The

    temperature increments in the structural members are

    calculated over small time steps. This method is

    particularly suitable for calculation using simple

    spreadsheet programming.

    ( )Q h As f s=

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    316 Advances in Structural Engineering Vol. 7 No. 4 2004

    8.00

    Plot 3dSpeedm/s

    7.20

    6.40

    5.60

    4.80

    4.00

    3.20

    2.40

    1.60

    0.80

    0.00

    Figure 4. Example of smoke velocity in a fire compartment from CFD model

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    7/23

    For internal steelwork, the increase of temperature

    (s) in an unprotected steel section during in a timeinterval tmay be calculated as (Eurocode 3: Part 1-2

    2001):

    (10)

    in which

    correction factor for the shadow effect of

    flanges, defined as a ratio of the box value of the section

    factor to the section factor

    specific heat of steel [J/kgK]

    density of steel [kg/m3]

    section factor for unprotected steel members

    Heat transfer coefficient per unit area per degree

    Kelvin

    t= The time interval [seconds]On the fire exposed surface the heat transfer

    coefficient may be determined by considering heat

    transfer by radiation and convection as

    (11)

    where the radiative term may be expressed as:

    (12)

    where

    Stefan-Boltzmann constant of

    resultant emissivity using f = 1.0 and

    m = 0.7, where f and m are the emissivity of the fire

    and the surface of the member,

    f and s = Fire and steel temperature, respectively, in

    Celsius.

    The convective heat transfer coefficient is hnet,c =

    25 W/m2K for standard fire, 35 W/m2K for natural fire

    and 50 W/m2K for hydrocarbon fire.

    The section factor uses the fire exposed

    perimeter in calculating an appropriate value of . The

    section factors for selected examples are shown in

    Figure 5.

    For protected steel members under fire, the protection

    material of low thermal conductivity reduces the rate of

    heat transfer from the fire to the steel section. The

    increase in steel temperature in a time increment

    due to the heat transfer from the fire through the fireprotection to the steel section may be calculated as:

    (13)

    in which the relative heat storage in the protection

    material is given as

    (14)

    andsection factor for protected steel member,

    where is the inner perimeter of the protection material.

    specific heats of steel and protection material

    thickness of fire protection material

    temperatures of steel and fire at time t

    increase of fire temperature during the time step tthermal conductivity of the fire protection material

    densities of steel and fire protection material

    The temperature development in protected steel

    members can be evaluated based on the thermal

    properties of the insulation materials.

    4.2. Finite Element MethodFinite element method may be used to estimate the

    thermal effects on the structural elements by subdividing

    the structural element into a number of quadrilateral

    heat transfer elements. Heat conduction, heat convection

    and exchanges of radiation are calculated on the basis of

    the heat transfer element. One simplified approach is to

    store the temperature history in each structural member

    and then calculate the equivalent nodal expansion based

    on the incremental temperature change. Consistent nodal

    forces are produced on an elastic element at elevated

    s p, =kp =f = s f, =tp =c , cs p =

    Ap

    A /Vp =

    =c

    ct

    A

    V

    p p

    s s

    p

    p

    /

    sp f s

    p p s s

    f

    A V )

    t k )ct e=

    +

    / (

    ( / ( )( )

    /

    1 31

    10

    ts

    Am

    A Vm/

    r f m= =5 67 10

    8. =

    hnet r r f s

    f s

    , ( ) ( )

    = + +[ ]

    + +[ ]

    273 273

    546

    2 2

    h h hnet net c net r = +, ,

    hnet

    hnet =A Vm/ =s =cs =

    kshadow =

    s shadow

    m

    s s net f s

    kA V

    ch t= ( )

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 317

    B

    tD

    Am/V = 2(2B+Dt)/A

    A = area of the steel section

    D

    B

    Am/V = (3B+2D2t)/A Am/V = 2(B+D)/A

    Figure 5. Values of parameter for use in the calculation of Section factor A m/V

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    8/23

    temperatures due to the axial expansion and temperature

    gradient increment over the cross-section. These forces

    can be used in the structural analysis to determine the

    responses of the structure in fire (Ma and Liew 2004).

    Although the techniques for solution of the heat

    transfer problem are relatively well established, several

    complicating factors exist. For examples, physicalproperties such as thermal conductivity, specific heat,

    emissivity/absorbtivity and heat transfer coefficients

    vary with temperature. Surfaces may also be exposed

    to re-radiation from other surfaces. The fraction of

    the emitted radiation received is governed by the

    configuration factor, which may be tedious to calculate,

    especially if shadowing of other members are present.

    Numerical method is often used to improve the accuracy

    of the heat transfer analysis.

    5. MATERIAL BEHAVIOUR AT

    ELEVATED TEMPERATUREExperimental evidence shows that the stiffness and

    strength of steel deteriorate at elevated temperatures.

    Typical stress-strain curve of steel at elevated temperatures

    is shown in Figure 6.

    The stress-strain relationship at elevated temperature

    does not exhibit a distinctive yield plateau. Therefore,

    the yield stress, or 0.2% proof stress, which is conventional

    design strength for steel at ambient temperature, loses

    its relevance because of the nonlinearity of the stress

    strain curve. Since fire is considered to be an accidental

    situation, large plastic strains are allowed. Hence, aneffective yield stress is used, which is attainable when

    the strain is considerably larger than the elastic limit at

    normal temperatures. Eurocode 3: Part 1-2 (2001) adopts

    a yield strain of 2% to define the effective yield

    stress. The temperature dependence of the proportional

    limit, the effective yield strength as well as the elastic

    modulus recommended by the code is shown in Figure 7.

    Creep may be of importance in a fire situation where

    a cross section is subjected to high temperature (above

    400C) and high stress for a long period of time. The

    stress-strain curves given in the Eurocode code arebased on measurements at constant temperature within a

    period of time to allow creep to take place in the tests.

    Therefore, creep effect is implicitly included in the

    effective yield strength used for design. In other words,

    when the design is based upon code values, creep does

    not need to be considered explicitly. If the temperature

    and load history is such that a structural component

    remains at high temperature or is highly stressed for

    only a short period, the prediction using the code values

    should yield conservative results.

    6. NONLINEAR ANALYSIS ATELEVATED TEMPERATUREModern design standards such as Eurocodes provide

    sufficient guidance to assess the fire performance of

    individual members in a fire compartment of a building

    framework. In the case of a braced frame in which each

    storey comprises a separate fire compartment with

    sufficient fire resistance, the effective buckling length of

    a column may be used to compute the limit load of the

    frame. However, guidance is not given for sway frames

    in which storey buckling and overall stability may

    dominate the design of individual member. Wang et al.(1995) provide simplified methods to analyse the

    performance of steel frames. They study the effect of

    continuity on the fire resistance of columns in both sway

    and non-sway steel frame and suggested some restraint y,

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    318 Advances in Structural Engineering Vol. 7 No. 4 2004

    Strain x

    fy, h effective yield strength;

    fp, h proportional limit;

    Ea, h slope of the linear elastic range;

    xp, h strain at the proportional limit;

    xy, h yield strain;

    x t, h limiting strain for yield strength;

    x u, h Ultimate strain;

    x u, hx t, hxy, hxp, h

    fy, h

    fp, h

    Ea, h= tan a

    a

    Stress q

    Figure 6. Stress-strain relationship of steel at elevated temperature according to European Committee for Standardisation (2001)

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    9/23

    stiffness values at the end of the column due to the

    continuity of the sub-frame from the parametric study.

    General commercial programs such as ABAQUS,

    ANSYS, NASTRAN, may be used for analysing

    structures exposed to fires. They offer the advantages of

    full validation, powerful ability to model different kinds

    of problems and availability of further developmentso that they can almost suffice all needs. But these

    programs are rather inconvenient to use for being both

    time-consuming and complicated to operate since they

    are general purpose program not specifically written to

    perform analysis of structures under fire condition

    which is highly non-linear and transient.

    One powerful tool for analyzing large-scale steel

    structures exposed to fire is to adopt a second order

    plastic hinge-based analysis (Liew et al. 1998, 2002). In

    this approach, it is assumed that cross section is compact

    and the full plastic capacity can be achieved. At elevated

    temperature the plastic strength surface should follow

    the effective yield strength and its temperature reduction

    curve for yield, as illustrated in Figure 7. The elastic

    modulus also degrades at elevated temperature following

    the temperature degradation curve for the slope of linear

    elastic range as in Figure 7. Other fire effects

    include thermal expansion and thermal bowing. Further

    improvement to this model is to model the gradual

    plastification of members cross section using a two-

    surface plastic hinge method, which captures the gradual

    yielding of cross sections at elevated temperature (Ma

    and Liew 2004; Liew et al. 2000).

    The two-surface plastic hinge model, which is

    formulated based on the bounding surface plasticity

    concept, represents the inelastic cross section behaviour

    by considering the interaction of axial force and bi-axial

    bending. The initial yield surface is assumed to be a

    scaled down version of the bounding surface that is

    fixed in size and translates without rotation in a stress-resultant space. The gradual translation of the initial

    yield surface towards the bounding surface provides a

    smooth transition from initial yield to full plastification

    of cross section. Moreover, the element displacement

    fields are derived from the exact solution of the fourth

    order differential equation for a beam-column subjected

    to end forces (Liew et al. 2000), hence it is accurate

    enough to use only one beam-column element to model

    the stability behaviour of column member.

    At elevated temperature, the yield surface and the

    bounding surface have to contract in size in order to

    satisfy the yield condition. The degradation of the yield

    strength is based on the effective strength concept. At

    high temperature, the stress-strain relationship of steel

    is highly nonlinear and does not exhibit a distinct yield

    plateau. The idea of the effective strength is introduced

    to define a yield plateau at a relatively high strain level.

    For the two-surface plasticity model, the size of the

    bounding surface corresponding to full cross-sectional

    plastification, follows the reduction curve for effective

    yield strength in Eurocode 3: Part1-2 (2001), as illustrated

    in Figure 8. The size of the initial yield surface is

    assumed to degrade proportional to the bounding surface.

    kE,

    ky,

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 319

    Reduction factor, k

    0 200 400 600 800 1000 1200

    0.2

    0

    0.4

    0.6

    0.8

    1.0

    Temperature [C]

    Proportional limitkp,h= fp,h/fy

    Slope of linear elastic rangekE,h= Ea,h/Ea

    Design strength for satisfying

    deformation criteriakx,h= fx,h/fy

    Effective yield strengthky,h= fy,h/fy

    Figure 7. Reduction factor for steel according to Eurocode 3: Part 1-2 (2001)

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    10/23

    However, it can be observed from Figure 8 that the

    initial yield strength decreases at a faster rate than the

    effective yield strength; therefore, the size of the initial

    yield surface may be over predicted at higher temperature.

    In practice, this will not have any significant effect on

    the inelastic behaviour of members in fire.

    The verification of the two-surface plasticity model at

    ambient and elevated temperature is reported in Liew

    et al. (1998) and Ma and Liew (2004). Verification studies

    have been carried out on both components and frames

    over a wide range of parameters including uniformly

    heated members, three-side heated members with

    concrete slab acting as heat sink, members with passive

    fire protection and 2-D frames. Several examples are

    given in the next section to illustrate the application of

    the plasticity model and to study the accuracy of the

    model in modelling the inelastic behaviour of frame

    structures.

    7. COMPARISON OF PLASTICHINGE METHOD WITH SPREAD-OF-PLASTICITY ANALYSISFigures 9 to 11 show a simply supported beam, a single

    storey braced frame and a multi storey braced frame

    subjected to fire. The main purposed of the study is to

    compare the results obtained from fire analyses based on

    the plastic hinge (P-Hinge) method and the Spread of

    plasticity (S-Plastic) methods.

    All the structural models are subject to ISO

    standard fire. For the simply supported beam (model 1),

    the member cross section is exposed to 4-side fire

    (Figure 9). The temperature is assumed to be uniform

    over the cross section and along the length. The second

    and the third models are based on the portal frame

    shown in Figure 10. In model 2, the frame members are

    exposed to fire from all sides without fire protection

    while in model 3, the beam is protected by concrete slab,

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    320 Advances in Structural Engineering Vol. 7 No. 4 2004

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1

    0 200 400 600 800 1000 1200

    Temperature [C]

    Strengthdegradation

    Ratio

    effective yieldstrength

    initial yield strength

    bounding surface(200C)

    initial yield surface(200C)

    bounding surface(700C)

    initial yield surface(700C)

    Figure 8. Size of yield and bounding surface at elevated temperature according to Eurocode 3

    q = 15 KN/m

    Uy

    Ux

    254 146 UB

    4.5 m

    Figure 9. Model 1: simply supported beam (4-side heated)

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    11/23

    and the beam section is 3-side heated. Model 4 is a

    3-bay, 3-storey rigid frame (Figure 11), in which the

    lower left corner compartment is subject to fire. S275

    steel with yield strength of 275 N/mm2 is used for all the

    structural members.

    For model 1, only vertical deflection of the beam is

    compared. For the other models, the comparison is made

    both on the mid-span deflection of the beam and the

    lateral deflection at the top of the heated column. The

    results are shown in Figures 12 to 15. In all figures, solid

    lines represent the vertical deflection of the beam, and the

    dashed line means the lateral deflection of the column.

    The comparison of the results indicates that the

    plastic hinge method gives satisfactory results before

    the formulation the first plastic hinge in the structure. If

    the failure is not due to the formation of plastic hinge

    mechanism, then, the plastic hinge method shows a greater

    stiffness reduction than the spread-of-plasticity method

    (Figures 12 and 13).

    If a collapse mechanism occurs (Figures 14 and 15),

    the plastic hinge method shows collapse with rush out

    of deformation while the spread-of-plasticity analysis

    shows ability to sustain further load with moderate

    deformation. Hence the plastic hinge method may be

    used to predict the collapse of structures. But it may

    underestimate the post-collapse stiffness of the

    structures.

    For steel structures under fire attack, it is possible to

    allow the structure to undergo large deformation as long

    as the structure maintains stable. Therefore, when post-

    collapse behaviour is needed, the spread-of-plasticity

    method should be used.

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 321

    Ux Uy

    P = 500 kN P = 500 kNq = 25.4 kN/m

    Beam section: 305*165UB40

    Column section: 203*203UB52S275 steel

    5.5 m

    3.5 m

    Columns are 4-side heated

    Figure 10. Rigid portal frame: Model 2: beam is 3-side heated; Model 3: beam is 4-side heated

    P = 75.5 kN P = 151 kN P = 75.5 kNP = 151 kN

    5.5 m 5.5 m 5.5 m

    3m

    3m

    3m

    Beam section:305*165UB40

    Column section:203*203UB52

    U.D.L = 25.4 kN/m over all beams

    Ux

    S275 steel

    Uy

    Figure 11. Model4: three-bay, three-storey rigid frame

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    12/23

    8. VERIFICATION OF NUMERICALMETHODSVerification studies are important to ensure the validity of

    any analytical or numerical methods. Ma and Liew (2004)

    established the accuracy of their proposed advanced

    analysis method against experimental results for both

    individual members and complete frames exposed to fire.

    8.1. Uniformly Heated MembersCritical temperatures from the advanced analysis are

    compared with those in BS5950: Part 8 (BSI 1990) for

    beams under uniform distributed loads and columns

    under axial loads in Table 1. Critical temperature for

    beams is taken at a mid-span deflection of L/20 and

    critical temperature for columns is taken at the failure

    of the column symbolized by a sudden increase of

    lateral deflection. The results agree well with each

    other.

    8.2. Three-side Heated BeamsEighteen UK standard fire tests on unprotected simply

    supported steel beams supporting concrete slabs without

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    322 Advances in Structural Engineering Vol. 7 No. 4 2004

    1600

    1400

    1200

    1000

    800

    600

    400

    200

    00 2 4 6 8 10

    Time (minute)

    Formulation of the plastic hinge

    at the mid of the beam

    PHinge

    SPlasticity

    uy(mm)

    12 14 16

    Figure 13. Deformation of structural model 2

    700

    100

    0

    1000

    P-HingeS-Plasticity

    Solid line: Uy

    Dash line: Ux

    Time (minute)

    Deformation(

    mm)

    5 10 15 20 25

    600

    500

    400

    300

    200

    Figure 12. Deformation of structural model 1

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    13/23

    composite action are simulated. The test descriptions

    and data are available in Wainman (1988). Table 2

    summarizes the measured and calculated critical time

    and temperature for each test. In general, the agreement

    is good except for a few cases (such as Test 14). The

    discrepancy is possibly resulted from the assumed steel

    strength degradation at elevated temperatures due to

    lack of material test data. Figure 16 plots the temperature

    and the mid-span deflection predictions against

    experimental results for test 11.

    8.3. Two-dimensional FramesTwo frames (Li et al. 1997; Zhao 1995) have been

    studied. The configuration of the frame and the loading

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 323

    Solid line: Uy

    Dash line: Ux

    yielding of the column

    P-Hinge

    S-Plasticity

    Plastic hinge of the beam

    350

    400

    300

    250

    200

    150

    100

    50

    0 5 10

    Time (minute)

    Deformation(m

    m)

    15 20 25

    0

    50

    Figure 14. Deformation of structural model 3

    Solid line: Uy

    Dash line: Ux

    P-Hinge

    Time (minute)

    Deformation(mm)

    S-Plasticity

    300

    250

    200

    150

    100

    50

    00 2 4 6 8 10 12

    Figure 15. Deformation of structural model 4

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    14/23

    is shown in Figures 17 and 18. In both studies, the

    measured temperature of each member is used in

    the structural analysis. Figures 19 and 20 illustrate

    the excellent correlation between the predicted and the

    measured displacements.

    8.4. Three-dimensional FrameA full scale fire test was carried out on a three-

    dimensional steel tubular frame in SINTEF. The test

    details and the verification procedures can be found in

    Skallerud and Amdahl (2002). The proposed advanced

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    324 Advances in Structural Engineering Vol. 7 No. 4 2004

    Table 2. Critical time and temperature of UK standard fire tests

    Critical Time (min) Critical Temperature (C)

    Test No Load Ratio Test Analysis Error % Test Analysis Error %

    Test 2 0.50 22.5 20.7 8.0 660 693 5.0

    Test 3 0.57 22.0 20.6 6.4 634 682 7.6Test 4 0.36 29.0 28.2 2.8 701 745 6.3

    Test 5 0.61 26.7 22.9 14.2 647 694 7.3

    Test 6 0.37 22.8 25.9 13.6 737 734 0.4

    Test 7 0.36 22.3 24.2 8.5 731 743 1.6

    Test 8 0.36 21.3 24.4 14.6 705 742 5.2

    Test 9 0.37 24.2 26.4 9.1 714 734 2.8

    Test 10 0.49 20.5 21.0 2.4 655 709 8.2

    Test 11 0.50 21.4 20.8 2.8 683 706 3.4

    Test 12 0.53 28.4 29.3 3.2 681 680 0.1

    Test 13 0.40 25.1 24.3 3.2 727 736 1.2

    Test 14 0.25 26.4 33.2 25.8 745 791 6.2

    Test 89 0.50 20.0 22.4 12.0 651 692 6.3

    Test 90 0.65 20.7 19.0 8.2 630 640 1.6

    Test 91 0.34 23.0 29.5 28.3 705 742 5.2

    Test 92 0.05 117.0 109.0 6.8 1061 1046 1.4

    Test 93 0.09 75.0 56.4 24.8 977 932 4.6

    Table 1. Critical temperature of uniformly heated members

    Simply Supported BeamCritical Temperature (C) at load ratio R1

    in Bending 0.2 0.3 0.4 0.5 0.6 0.74-side BS5950 715 660 620 585 555 520

    heated Analysis 725 671 629 591 559 527

    % difference 1.4 1.7 1.5 1.0 0.7 1.3

    Critical Temperature (C) at load ratio R2

    Column in Compression 0.2 0.3 0.4 0.5 0.6 0.74-side BS5950 710 655 615 580 540 510

    heated Analysis 723 678 641 608 564 529

    70 % difference 1.9 3.5 4.2 4.8 4.5 3.8

    4-side BS5950 635 635 590 545 510 460

    heated Analysis 662 649 611 568 529 478

    >70 % difference 4.2 2.2 3.5 4.2 3.8 3.9

    R1 = Mf/Mc R2 = F/Agpy + Mx/Mcx + My/Mcy

    : slenderness ratio Mf: applied mid-span moment at fire

    Mc: moment capacity at ambient temperature F: axial force

    Ag: cross-section areapy: yield strength

    Mx and My: applied major and minor axis moment at fire

    Mcx and Mcy: major and minor axis moment capacity at ambient temperature

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    15/23

    analysis is used for the verification. It has been found

    that the correlation between simulation and test results

    with respect to the mechanical response was extremely

    good. The primary collapse load obtained was almost

    perfectly predicted.

    9. FIRE ANALYSIS OF ANOFFICE BUILDINGThis section presents a performance-based approach for

    analysing a six-storey building frame subject to various

    scenarios of fire attack. Advanced analysis method (Ma

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 325

    Time (min)

    Test (deflection)

    Analysis (deflection)

    Test (temperature)

    Analysis (temperature)

    Mid-Span

    Deflection(m)

    0.20

    0.16

    0.12

    0.08

    0.04

    0.00

    LowerFlan

    geTemperature

    800

    600

    400

    200

    0

    0 10 20 30 40 50

    Figure 16. Test and analysis results for test 11

    30 30 30 30 30 30 30 kN

    540 540540 540 540 540

    4.2

    55

    4.5

    7.2

    column crosssection

    beam crosssection

    A B

    100

    100

    100

    1400mm

    Figure 17. Lis frame

    beam & columncross-section

    82 kN 82 kN

    9.45 kN

    1500 mm

    1500mm

    DC

    6.0

    100

    4.5

    56

    Figure 18. Zhaos frame

    010

    0

    Horizontaldisplacement

    (mm)

    Time (min)

    Node B,Analysis

    Node A,Analysis

    Node B, Test

    Node A, Test

    10

    20

    10 20 30

    Figure 19. Analysis and test results (Lis frame)

    Analysis

    Test20

    10

    0

    0 20 3010

    Horizontaldisplacement at D

    Vertical displacement

    at CDisplacement(mm)

    Time (min)

    Figure 20. Analysis and test results (Zhaos frame)

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    16/23

    and Liew 2004) is used to propose a much reduced fire

    protection plan for beams and columns and prove that

    the design can satisfy the performance criteria of fire

    safety. The building is classified as office building as

    shown in Figure 21.

    9.1. Limit States DesignThe frame is designed for the strength limit state at

    ambient temperature according to Eurocode 3 with the

    following actions:

    Permanent Dead load (Gk,1) 3.6 kN/m2

    actions Gk:

    Permanent imposed 1.9 kN/m2

    load (Gk,2)

    Variable Variable imposed 1.6 kN/m2

    actions Qk: load (Qk,1)

    Wind load (Qk,2) 593 kN (in

    Y-direction)The beam and column sizes are indicated in

    Figure 21. A36 steel (design strength of 250 N/mm2) is

    used in all sections. Plastic hinge analysis method is

    adopted. Each beam is modelled using 4 elements and

    each column using 1 element. Wind load is simulated

    by applying a point load in Y-direction at every beam-

    column joint of the front elevation.

    At the fire limit state, which is treated as accidental

    loads in Eurocode 3 Part 1-2 (2001), the design effect of

    the actions is expressed as:

    Efi,d,t = Gk+ 1Qk,1 + 2Qk,2 (15)

    Where 1, 2 are factors due to the probability of loadsacting individually or in combination. Depending upon

    which variable load is the dominant action, two load

    combinations are possible under fire limit state:

    Load combination 1:

    Efi,d,t = Gk,1 + Gk,2 + 0.5Qk,1 + NL (Notional Load)

    Load combination 2:

    Efi,d,t = Gk,1 + Gk,2 + 0.3Qk,1 + 0.5Qk,2

    In load combination 1, the notional load is taken as

    0.5% of the factored gravity load at each storey, applied

    in Y-direction and is distributed to the beam-column

    joints as point load. In both cases, the structure is subjected

    to gravity load or the combination of gravity load and

    wind load first, followed by fire.

    9.2. Fire ModellingParametric fire recommended in Eurocode 1 Part 1-2

    (2001), is used to simulate the fire in the compartment

    by considering the type of building, floor layout,

    realistic fire load and possible fire fighting measures.

    Fire load density per floor area qf,k = 420 MJ/m2 is

    adopted for common office building. The design fire

    load qf,d is defined as:

    qf,d = qf,k. m. q1. q2 . n (16)

    where m is the combustion factor and is assumed as

    0.8; q1 is the partial factor taking into account thefire activation risk due to the size of the compartment.

    For floor area from 25 m2

    up to 250 m2

    , q1 is equal to

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    326 Advances in Structural Engineering Vol. 7 No. 4 2004

    Z

    7.315 m 7.315 m

    1 2 3

    X

    Y

    7.315m

    W12 26 W12 26

    W12 26 W12 26

    W1253

    W1287

    W1253

    PLAN

    W12x87

    W1287

    W12120

    X

    W

    1060

    H=6x3.658m=2

    1.948m

    1 2 3

    W1060

    FRONT ELEVATION

    Figure 21. Six-storey building frame

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    17/23

    1.5 (in this case the floor area Af is 53.5 m2). q2 is 1.0

    for occupancies such as office, residence and hotel. It is

    assumed that no automatic fire suppression and

    detection system is installed but an off site fire brigade

    is available from which n is calculated as 0.78. Thedesign fire load qf,d is thus computed as 393 MJ/m

    2,

    which is equivalent to 98 MJ/m

    2

    per total area (qt,d). Thesurrounding surfaces of the compartment are assumed to

    be normal concrete with b value of 1900 J/m2s1/2K.

    Assuming an opening factor OF = 0.4, the temperature

    time curve is plotted as shown in Figure 22. It can be

    seen from Figure 22 that the fire curve with opening

    factor OF = 0.04 are below the standard ISO 834 fire

    curve, providing the possibility of reducing passive fire

    protections. Two compartments are considered asshown in Figure 23. The columns in compartment 1 are

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 327

    0

    200

    400

    600

    800

    1000

    1200

    0 20 40 60 80 100 120

    ISO 834

    OF = 0.04

    Time (Min)

    Temperature (C)

    Figure 22. Parametric time-temperature curves for six-storey office building frame

    Firecompartment 1

    Firecompartment 2

    1

    4

    5

    2

    7Z

    X

    Y

    9

    40

    42

    43

    41

    Elementnumber

    Figure 23. Fire compartments in 6-storey space frame

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    18/23

    most heavily loaded and the size of columns reduces

    from the 4th storey onwards.

    9.3. Fire at the First Storey CompartmentIf all the beams and columns in the lower floor fire

    compartment are unprotected, it is found that load

    combination 2 is more severe as the structure fails at a

    critical time of 33.7 minutes while it can survive the fire

    under load combination 1. The deformed shape of the

    structure under fire for each load combination is shown

    in Figure 24.

    Under load combination 1, as the beams expand

    under fire, column heads are forced to open up in both

    X and Y directions. When the frame is subjected to load

    combination 2, the effect of wind load in Y-direction

    becomes pronounced, causing the frame to deform in a

    twisting mode. Despite the expansion of the heated

    beams, all columns (1, 2, 4 and 5) sway to the same

    direction as the wind load. The center of gravity of the

    frame thus shifts to the leeward columns (4 and 5),

    producing large axial force in the columns (Figure 25).

    It is the failure of column 4 which triggers the collapse

    of the frame under fire.

    Load combination 2 is found to be most critical;

    therefore subsequent analyses are carried out using only

    this load combination.

    Since the columns are found to be the critical

    members, it is proposed that all the fire affected

    columns are fully protected. Second-order plastic hinge

    analysis is again carried out on the partly protected

    structure, and the displacement of the column head in Y-

    direction is found to be greatly reduced (see Figure 25),

    in contrast to the runaway deflection of column 4 when

    approaching failure for the unprotected columns.

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    328 Advances in Structural Engineering Vol. 7 No. 4 2004

    Buckling ofColumn 4

    Load Combination 1 (no collapse) Load Combination 2

    Z

    X

    Y

    Figure 24. Deformed shapes of 6-storey frame for load combinations 1 and 2

    Case 1: Column Unprotected

    Case 2: Column Protected

    0.40

    0.35

    0.30

    0.25

    0.20

    0.15

    0.10

    0.05

    0.000 5 10 15 20

    Time (min)

    ColumnHeadDeflection(m)

    25 30 35

    1

    4

    Figure 25. Column 4 head displacement in the Y-direction

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    19/23

    However, the critical time shows only marginal

    improvement, from 33.7 min to 35.5 min. Beam collapse

    mechanism forms at beams 7 and 9 (the smallest beams)

    in X-direction due to large restraint force from the

    supporting columns, causing larger mid-span deflection

    as shown in Figure 26.

    The next logical step is to provide fire protection to

    beams 7 and 9. In this case, the building survives the

    entire fire duration with plastic hinges occur at the

    beams in Y-direction.

    9.4. Fire at the Fourth Storey CompartmentFire is assumed to occur at the 4th storeys compartment

    as shown in Figure 23. When all the members are

    unprotected, extensive plastic hinges form at the four

    columns, triggering the collapse of the frame during the

    fire. Although the loads on the fourth storeys columns

    are smaller than those on the first storeys columns, the

    column size from the fourth storey onward is also smaller.

    At a critical time of 33 min, columns experience runaway

    deflections in both X and Y directions (Figure 27),

    symbolizing the failure of the columns. Figure 28 shows

    the axial force in windward and leeward columns. The

    shift of the center of gravity due to wind load produces

    larger axial force in the leeward column.

    If a realistic fire model is considered, it is possible

    to reduce the cost of fire protection. In this 6-storey

    building frame, columns and beams in X-direction

    require passive fire protection from 1st storey to 3rd

    storey. But from 3rd storey onwards, only columns

    need to be protected while all the beams can be left

    unprotected. However if ISO standard curve is used

    irrespective of layout of the building, fire loads and

    ventilation condition, all the members in the building

    need to be fire protected Further study will be carried

    out on high-rise buildings where the savings in passive

    fire protection may become more significant if a

    realistic fire is considered.

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 329

    00 5 10 15

    Case 1: Column Unprotected

    Case 2: Column Protected

    20

    Beam 7

    Beam 9

    25 30 35

    0.05

    0.1

    0.15

    BeamMid-SpanDeflection(m)

    Time (min)

    0.25

    0.27

    9

    Figure 26. Mid-span deflection of Beams 7 and 9

    Column 42

    Deflection in X-direction

    35302520

    Time (min)

    ColumnHeadDeflection(m)

    1510500.35

    0.30

    0.25

    0.20

    0.15

    0.10

    0.05

    0.00

    0.05

    0.10

    0.15

    Column 42

    Column 40

    Column 40

    Deflection in Y-direction

    40

    42

    Figure 27. Column head displacements in X and Y directions (unprotected)

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    20/23

    10. FIRE PROTECTIONFire protection falls into two main categories, prevention

    and protection. Preventative measures include control

    of flammable inventories, control of ignition sources,

    monitoring of environmental conditions leading to

    initiation of alarms and automatic process control,

    and fire detection systems designed to extinguish fires

    immediately on detection. Protection measures fall into

    two categories, passive and active. Passive measures

    include fire barriers, fire resistant enclosures, fire doors,

    fire retardant coatings and fire protective coatings. Active

    measures include water and chemical sprays or deluges,foam dispersion and inert gas dispersal.

    After the WTC incident, people expect the public

    buildings and their work place to be designed to allow

    safe evacuation in the event of fire or explosion. Certain

    industrial buildings have stringent fire protection

    requirements. For examples, oil and gas production

    and processing, nuclear related product storage and

    processing, chemical process and storage and key

    infrastructures and transportation routes are facilities

    that attracted greater risks.

    From safety and licensing authorities point of view, the

    structure must be capable of safe evacuation in the event

    of fire. From the owners view point, the fire protection

    is often an expensive statutory feature, which requires

    initial capital investment. From the operator point of

    view, fire protection must be maintained to preserve the

    safety margins declared in the safety documentation. The

    volume and cost of passive fire protection materials are

    often a critical factor for consideration; therefore, there is

    a need to balance these conflicting requirements when

    specifying fire protection.

    Fire protection can be provided as an all

    encompassing scheme, or it can be functionally designed

    to optimize on cost, weight and maintenance. Researchhas shown that fire can be successfully suppressed using

    a properly design and maintained active protection system

    without the need of passive fire protection. Evidently

    the structural member affected by the fire may not be

    reusable, but there is no guarantee that a fire protected

    structure could be re-used anyway.

    Computer models have been developed to predict

    the response of structures considering fire protection

    materials. This model will include the basic thermal

    transmission phenomena, radiation, conduction and

    convection, the temperature dependent properties ofmaterials and the location and nature of fire protection

    measures. The resulting thermal histories are then

    applied to the structure to predict time to collapse, or

    to demonstrate the degree of collapse. From this, the

    structure can be economically protected to meet the

    safety requirements.

    11. INTEGRATED EXPLOSIONAND FIRE ASSESSMENTOF STRUCTURESThe assessment of the response of structures to explosion

    is an increasingly important factor in design, particularly

    where the storage and processing of explosive materials

    is concerned. Many structures are required to be blast

    resistant to protect personnel and adjacent facilities, and

    to reduce the possibility of escalation of events. These

    structures are therefore designed to contain the effects of

    explosion or to act as a significant barrier.

    There is a great difference in the structural behaviour

    of buildings subject to explosion and fire loads. The short

    duration of explosion loading implies that the material is

    strain-rates dependent, i.e., high strain rate will increase

    the yield strength of steel (Izzuddin & Fang 1997). On

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    330 Advances in Structural Engineering Vol. 7 No. 4 2004

    Column 40

    00

    50

    100

    150

    200

    250

    300

    5 10 15

    Time (min)

    ColumnAxialFor

    ce(kN)

    20 25 30 35

    Column 42

    40

    42

    Figure 28. Axial force in columns 40 and 42 (unprotected members)

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    21/23

    the other hand, fire loading is associated with elevated

    temperatures which cause thermal strains and lead to

    significant deterioration in the material properties of steel.

    Izzuddin et al. (2000) proposed an integrated analysis

    method for explosion and fire analysis of steel structures

    incorporating material models which account both for

    rate-dependency and thermal property of steel.Liew and Chen (2004) presented a numerical

    approach for inelastic transient analysis of steel frame

    structures subjected to explosion loads followed by

    fire. The proposed transient inelastic analysis can be

    used effectively to solve explosion and thermal response

    problems, taking account of geometric and material non-

    linearities. To achieve both computational accuracy and

    efficiency, an analysis procedure has been proposed in

    which fire can be treated as a separate event after the

    occurrence of an explosion. The fire resistance of the

    structure can be evaluated by analyzing the deformed

    geometry of the structure caused by the explosion. Theapproximate fire analysis method does not require time

    domain solutions but it predicts higher fire resistance

    than the strict inelastic transient analysis. Nevertheless,

    it offers an alternate means to evaluate the performance

    of structures subjected to combined scenarios of explosion

    and fire at a much reduced computational cost.

    Hand calculation procedure and computational

    techniques have been developed with the aim of predicting

    how a structure will respond under the interaction of blast

    and fire. The followings summarized some of the works

    that are being investigated using the explosion responsetechnologies developed.

    Pseudo-dynamic or pseudo-static methods these

    are the simplest to apply since they take the

    explosion overpressure as a blanket loading, and

    are usually combined with dynamic amplification

    factors. The methods can assess both elastic and

    inelastic responses and can be applied to complex

    structures.

    Single Degree of Freedom Method this is a

    dynamic analysis technique, which predicts the

    response of a structure by reducing the structure

    to a simplified spring/mass system. The method

    is effective for simple structures that behave in a

    similar manner as to a spring/mass system. The

    method can assess both linear and non-linear

    responses and can be applied to simulate the

    response behaviour of more complex structures.

    Finite Element Analysis they can be used

    effectively to solve explosion response problems,

    taking account of geometric and material non-

    linearities. In term of computation time usage,

    balance has to be sought since there is a fine line

    between a model which is detailed enough to

    predict the response, and coarse enough not to

    run for impracticable lengths of time. Evidently,

    with the continued increase in the speed and

    capacity of computers, this problem will be less

    critical. The model detail is a matter to be

    addressed by the analysts carrying out the work

    as is the choice of solution method. The twomost common time domain solutions, implicit

    integration and explicit integration can both be

    used, each having their own pros and cons.

    Significant experience has been gained in the

    assessment of structures subjected to explosion loading

    using both hand and FEA based methods. Combining

    the structural response analysis with the explosion

    prediction analysis, it is possible to predict and hence

    optimize structural resistance.

    12. CONCLUSIONSThe difference in perspective between architect andengineer is noticeable in the design and construction

    process. In the conventional approach, the architect

    would specify the fire designs based on prescriptive

    code requirements and the engineer would design the

    structures with fire protection to achieve a certain fire

    rating. It becomes apparent in the recent years that

    the structural engineers should directly involve in fire

    engineering rather than the traditional approach of the

    architect specifying the fire designs. In a performance

    based design approach, the first step is to understand

    what level of performance is expected, then to design tothese levels and followed by predicting the performance

    that will be achieved, and finally to be able to assure the

    reliability and robustness of the design in the occurrence

    of an extreme event.

    To carry out a quantitative assessment on the

    performance of a building in fire requires the knowledge

    of fire science, material properties at elevated temperature,

    occupant behaviour and evacuation procedure during an

    emergency situation, heat transient and structural response

    phenomena, and fire protection etc. All these would

    require a multi-dimensional integration approach, as

    described in this paper, for performance-based design of

    structures.

    Fire may be treated as a building load, consistent with

    the treatment of other loads in building design such that

    it can be integrated with structural design in various load

    combinations. Design fire scenarios can be prescribed

    for standard building forms and further examined for

    more complex systems. Structural design should also

    consider the integration between evacuees and fire-

    fighter interactions. Proper fire model with interaction

    with the active and passive protection measures should

    be developed, and relationship between emergency

    J. Y. Richard Liew

    Advances in Structural Engineering Vol. 7 No. 4 2004 331

  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    22/23

    response and fire resistance should be established so

    that appropriate performance-based method can be

    developed to predict the building response to extreme

    events. The examples given in this paper illustrated that

    saving in passive fire protection could be substantial for

    high-rise and large building framework if realistic

    natural fires, instead of the conventional standard fire,were considered in design.

    Improved understanding of the real behaviour of

    natural fire in tall buildings opens new ways of integrating

    fire safety and structural design. Prescriptive codes

    without considering the systems limit states behaviour,

    are often quite approximate in nature. With the advance in

    computing technologies, there is an increasing demand for

    robust and efficient nonlinear analysis methods for

    performance-based design of structures subject to fire and

    explosion. Some of the works mentioned in this paper are

    a step towards this development.

    ACKOWLEDGEMENTSThe author would like to acknowledge the contributions

    made by Dr H Chen, Dr L K Tang, Ms K Y Ma, and

    Ms H X Yu for their research work on steel structures

    in fire in the Department of Civil Engineering at the

    National University of Singapore. The work is funded

    by research grants (R264000138112) made available by

    the National University of Singapore.

    REFERENCES

    ECCS (1993). Fire Safety in Open Car Parks, Modern FireEngineering, Technical Committee 3, European Convention for

    Constructional Steelwork, Brussels, Belgium.

    Eurocode 1: Part 1-2 (2001). Actions on Structures Part 1-2:

    General Actions Actins on Structures Exposed to Fire, EN

    1991-1-2, European Committee for Standardization, Brussels.

    Eurocode 3: Part 1-2 (2001). Design of Steel Structures Part 1-2:

    General Rules Structural Fire Design, prEN 1993-1-2,

    European Committee for Standardization, Brussels.

    Feasey, R. and Buchanan, A. (2002). Post-flashover fires for

    structural design, Fire Safety Journal, Vol. 37, pp. 83-105.

    Franssen, J. M. (1997). Improvement of the parametric fire of

    eurocode 1 based on experimental test results, Fire Safety

    Science Proceedings of the Sixth International Symposium,

    pp. 927-938.

    Izzuddin, B. A. and Fang, Q. (1997). Rate-sensitive analysis of

    framed structures - Part I: model formulation and verification,

    Structural Engineering and Mechanics, Vol. 5, No. 3, pp. 221-237.

    Izzuddin, B. A., Song, L., Elnashai, A. S. and Dowling, P. J. (2000). An

    integrated adaptive environment for fire and explosion analysis of

    steel frames - Part II: verification and application, Journal of

    Constructional Steel Research, Vol. 53, No. 1, pp. 87-111.

    Li, G. Q., Jiang, S. C., Lin, G. X. and Yu, L. H. (1997). An

    experimental research on behaviour of steel frames subjected to

    fires, Proceedings of the 3rd Sino-Japan Conference on

    Structural Technology, 4-8 November, Shenzhen, P. R. China,

    pp. 68-78.

    Liew, J. Y. R., Tang, L. K., Holmaas, T. and Choo, Y. S. (1998).

    Advanced analysis for the assessment of steel frames in fire,Journal of Constructional Steel Research, Elsevier Science, UK,

    Vol. 47, No. 1-2, pp. 19-45.

    Liew, J. Y. R., Chen, H., Shanmugam, N. E. and Chen, W. F. (2000).

    Improved nonlinear plastic hinge analysis of space frames,

    Engineering Structures, Vol. 22, pp. 1324-1338.

    Liew, J. Y. R. and Tang, L. K. (2000). Advanced plastic-hinge

    analysis for the design of tubular space frames, Engineering

    Structures, Elsevier Science, UK, Vol. 22, No. 7, pp. 769-783.

    Liew, J. Y. R. ed (2002.). Structures in Fire, Proceedings of Int.

    Sym. on Structures in Fire, Oct. 25, 2002, Singapore, Singapore

    Structural Steel Society.

    Liew, J. Y. R., Tang, L. K., and Choo, Y. S. (2002). Advanced

    analysis for performance-based design of steel structures exposed

    to fires, Journal of Structural Engineering, ASCE, USA,

    Vol. 128, No. 12, pp. 1584-1593.

    Liew, J. Y. R. and Chen, H. (2004). Explosion and fire analysis of

    steel frame structures using fiber element approach, Journal

    Structural Engineering, ASCE, July Issue, In Press.

    Ma K. Y. and Liew J. Y. R. (2004). Nonlinear Plastic Hinge Analysis

    of Three-dimensional Steel Frames in Fire, Journal Structural

    Engineering, ASCE, July Issue, In Press.

    Moss, P. J. ed (2002). Structures in Fire, Proceedings of Second

    International Workshop on Structure in Fire, March 18-19,Christchurch, New Zealand.

    Schleich, J. B. (1996). A natural fire safety concept for buildings -

    1, Fire, Static and Dynamic Tests of Building Structures, E &

    FN SPON.

    SINTEF (1995). Fire and Heat Transfer Simulations (FAHTS) of

    Frame Structures, Theory and Users Manual, SINTEF

    Structures and Concrete, Trondheim, Norway.

    SFPE (2002).Handbook of Fire Protection Engineering, 3rdEdition,

    P.J. DiNenno, (Ed.), NFPA: Quincy, MA.

    Skallerud, B. and Amdahl, J. (2002).Nonlinear Analysis of Offshore

    Structures, Research Studies Press, England, 323p.

    Wang, Y. C., Lennon, T. and Moore, D. B. (1995). The behaviour

    of steel frames subject to fire, Journal of Constructional Steel

    Research, Elsevier Science, UK, Vol. 35, pp. 291-322.

    Wainman, D. E. and Kirby, B. R. (1988). Compendium of UK

    Standard Fire Test Data: Unprotected Structural Steel 1& 2,

    British Steel Corporation, Ref. No. RS/RSC/S10328/1/87/B.

    Yao, Z. P., Wang, R. J. and Zhang, X. J. (1995).Heat Transmission,

    Beijing Science and Technology University, Beijing, P. R. China.

    Zhao, J. C. (1995). Fire Resistance of Steel Framed Structures,

    Ph. D. thesis, Tong Ji University, Shanghai, P. R. China.

    Performance Based Fire Safety Design of Structures A Multi-dimensional Integration

    332 Advances in Structural Engineering Vol. 7 No. 4 2004

    http://www.ingentaconnect.com/content/external-references?article=0379-7112()37L.83[aid=6106548]http://www.ingentaconnect.com/content/external-references?article=0379-7112()37L.83[aid=6106548]http://www.ingentaconnect.com/content/external-references?article=1225-4568()5:3L.221[aid=6106550]http://www.ingentaconnect.com/content/external-references?article=1225-4568()5:3L.221[aid=6106550]http://www.ingentaconnect.com/content/external-references?article=0143-974X()53:1L.87[aid=6106549]http://www.ingentaconnect.com/content/external-references?article=0143-974X()53:1L.87[aid=6106549]http://www.ingentaconnect.com/content/external-references?article=0143-974X()53:1L.87[aid=6106549]http://www.ingentaconnect.com/content/external-references?article=0143-974X()47:1L.19[aid=6106553]http://www.ingentaconnect.com/content/external-references?article=0143-974X()47:1L.19[aid=6106553]http://www.ingentaconnect.com/content/external-references?article=0143-974X()47:1L.19[aid=6106553]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22L.1324[aid=6106547]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22L.1324[aid=6106547]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22:7L.769[aid=6106552]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22:7L.769[aid=6106552]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22:7L.769[aid=6106552]http://www.ingentaconnect.com/content/external-references?article=0143-974X()35L.291[aid=6106551]http://www.ingentaconnect.com/content/external-references?article=0143-974X()35L.291[aid=6106551]http://www.ingentaconnect.com/content/external-references?article=0143-974X()35L.291[aid=6106551]http://www.ingentaconnect.com/content/external-references?article=0143-974X()47:1L.19[aid=6106553]http://www.ingentaconnect.com/content/external-references?article=0143-974X()47:1L.19[aid=6106553]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22:7L.769[aid=6106552]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22:7L.769[aid=6106552]http://www.ingentaconnect.com/content/external-references?article=0143-974X()35L.291[aid=6106551]http://www.ingentaconnect.com/content/external-references?article=0143-974X()35L.291[aid=6106551]http://www.ingentaconnect.com/content/external-references?article=1225-4568()5:3L.221[aid=6106550]http://www.ingentaconnect.com/content/external-references?article=0143-974X()53:1L.87[aid=6106549]http://www.ingentaconnect.com/content/external-references?article=0143-974X()53:1L.87[aid=6106549]http://www.ingentaconnect.com/content/external-references?article=0379-7112()37L.83[aid=6106548]http://www.ingentaconnect.com/content/external-references?article=0141-0296()22L.1324[aid=6106547]
  • 7/30/2019 PERFORMANCE BASED DESIGN FOR FIRE SAFETY

    23/23

    J. Y. Richard Liew

    Jat-Yuen Richard Liew is an associate professor and the director of the centre forconstruction materials and technology in the National University of Singapore (NUS). Hereceived his B.Eng and M.Eng degrees (Civil Engineering) from NUS and his Ph.D degreefrom Purdue University in 1992. His research interests include deployable structures, steel-concrete composite systems and fire safety design of buildings. Arising from theseworks, he has generated some 150 technical publications. These include technical articles

    in journals, presentations, reports, books, and patents. He interacts closely with the steelindustry in the Asian region as a technical advisor in the areas of steel and compositestructures. He has also seen his R&D brought from the laboratory to full-scale applications.The latter include projects in airport structures, high-rise buildings, large-span andprestressed structures. He is a registered professional engineer in Singapore and achartered engineer in U.K.