performance standards hvac equipment performance consultancy
TRANSCRIPT
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
1/25
PERFORMANCE STANDARDSOF HVAC EQUIPMENT
(HVAC EQUIPMENT PERFORMANCECONSULTANCY)
For
Australian Building Codes Board
Prepared by:
DASCEM Holdings Pty LimitedPO Box 285
World Trade Centre
MELBOURNE VIC 3005GC 576
In conjunction with
ORART & COGrd. Fl., Bellevue
Street Surrey Hills,NSW 2010
February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
2/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
TABLE OF CONTENTS
EXECUTIVE SUMMARY 1 1 INTRODUCTION 2 1.1 Background 2 1.2 Object ives 2 1.3 Scope 3 1.3.1 Stage 1: 3 1.3.2 Stage 2: 3 2 STAGE 1 4 2.1 Survey and Identification of Equipment Performance 4 2.1.1 General Comments 4 2.1.2 Water Chilling Packages 4 2.1.3 Heat Rejection Equipment 7 2.1.4 Boilers 7 2.1.5 Warm Air Furnaces & Combinations 8 2.1.6 Pumped Water Systems 8 2.1.7 Fan Systems 8 2.2 Recommendations on Steps in Capacity 9 2.2.1 Water Chilling Packages 9 2.2.2 Heat Rejection Equipment 9 2.2.3 Boilers 9 2.2.4 Warm Air Furnaces & Combinations 9 2.2.5 Pumped Water Systems 9 2.2.6 Fan Systems 9 2.3 Codes and Standards for Equipment Performance Rating 9 2.3.1 Water Chilling Packages 9 2.3.2 Heat Rejection Equipment 10 2.3.3 Boilers 10 2.3.4 Warm Air Furnaces & Combinations 10 2.3.5 Pumped Water Systems 10 2.3.6 Fan Systems 10
HVAC Performance Criteria(Dec2002) February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
3/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
2.4 Referenced Manufacturers & Suppliers 11 2.4.1 Water Chilling Packages 11 2.4.2 Heat Rejection Equipment 11 2.4.3 Boilers 12 2.4.4 Warm Air Furnaces & Combinations 12 2.4.5 Pumped Water Systems 12 2.4.6 Fan Systems 12 GLOSSARY 13
BIBLIOGRAPHY 14
APPENDICES 15
APPENDIX A EQUIPMENT PERFORMANCE SCHEDULES 16
HVAC Performance Criteria(Dec2002) February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
4/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
EXECUTIVE SUMMARY
This report presents a summary of the results of the HVAC equipment performance survey and
assessment of energy consumption rates.
A survey of equipment suppliers for each of the equipment type categories has been completed.
A tabulation of equipment performance data based on data gathered is included at Appendix A.
Comments on the process of data gathering have been included where applicable.
As shown in appendix A, steps in capacity for Water Chilling Packages are practical and reflect
chillers available currently on the Australian market.
The performance requirement for Heat Rejection Equipment covered the full range of
capacities. There was no significant variation in the performance indicator from large to small
cooling towers hence a single indicator seems appropriate. The same is applicable to air
cooled condensers.
Three performance indicators for small, medium and large boilers are more than sufficient since
the manufacturers supplied efficiency varies little.
There was little variation between the 75 kW capacities for gas fired unducted
type warm air furnaces and therefore one figure for all sizes would seem more appropriate.
The capacity steps for the pump systems are appropriate and a reasonable level of size
discernment is necessary since the performance indicator varies significantly with the size of
system.
Again, a reasonable level of size discernment is necessary for the fan systems since the
performance indicator varies significantly with the size of system.
HVAC Performance Criteria(Dec2002) Page 1 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
5/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
1 INTRODUCTION
1.1 Background
The ABCB, in cooperation with the AGO, is developing energy efficiency measures suitable for
inclusion in the Building Code of Australia (BCA). Measures for the largely commercial
buildings covered by Volume One of the Code are being prepared separately from those for
housing referred to in Volume Two. The Commercial strand of the energy efficiency project will
employ extensive computational modelling; first to set benchmarks for the annual energy usage
of commonplace (or baseline) buildings and then to assess the reductions available from
specific energy saving features that could be applied to them. Comparison of energy cost
savings with the lifecycle cost of proposed features will identify the features suitable for the
deemed-to-satisfy provisions of the BCA.
To keep computational modelling effort within practical bounds, a limited number of
Representative Buildings will exemplify Australias diverse building stock. Each Representative
Building is defined by its:
Form (shape and size) Function (usage profile - based on BCA Class) Fabric (envelope construction) Facilities (or building services - including HVAC, power and light)Fabric and building services profiles may change with location to suit different climatic
conditions. Five basic forms, systematically selected, have been fitted with varying
combinations of fabric, function and services to generate a much larger set of Representative
Buildings that are articular to their location and use.
1.2 Objectives
The equipment performance will be:
1. used to develop the future energy efficiency Deemed-to-Satisfy provisions forVolume One of the BCA; and
2. included in a Verification Method, for assessing Alternative Solutions for specific buildings inspecific locations, or in an advisory document; and
3. used in developing a Regulatory Impact Statement (RIS).
HVAC Performance Criteria(Dec2002) Page 2 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
6/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
1.3 Scope
The proposal was undertake the survey in two stages. The content and the stages proposed
are as follows:
1.3.1 Stage 1:
1. Survey and identify the current performance criteria for the equipment shown in Appendix A.Current performance criteria must be representative of equipment performance used by
Australian industry and, specifically, must be able to be supplied by equipment of three
different manufacturers.
2. Examine the steps in capacity shown in Appendix A and provide recommendations on theirsuitability for inclusion in the energy provisions.
3.Tabulate current performance levels in table format shown in Appendix A.
4. Identify codes and standards that are used to rate the performance of the air conditioning,heating and ventilation equipment shown in Appendix A. Consider only those codes in
Australia and from overseas that are acceptable to Australian industry.
5. Provide a summary report, in tabulated form and in Microsoft Excel or Word format, on theresults of the survey and the codes.
1.3.2 Stage 2:
6. Carry out a limited survey of manufacturers and suppliers in Australia and identify anyimprovements in the performance of equipment up to the end of 2004 that the ABCB and
AGO should be cognisant of when formulating the energy provisions in the BCA.
7. Provide recommendations for equipment performance that could be incorporated into theenergy code. Tabulate the recommendations in the table format shown in Appendix A.
8. Provide a final report, in tabulated form and in Microsoft Excel and Word format, on theresults of the survey, the codes and recommendations.
HVAC Performance Criteria(Dec2002) Page 3 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
7/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
2 STAGE 1
2.1 Survey and Identification of Equipment Performance
2.1.1 General CommentsA survey of equipment and plant has been completed for chillers, heat rejection equipment,
boilers, warm air furnaces, pumps and fans. Data has been collected and values entered for a
range of sizes. The results of the equipment performance survey are tabulated in Appendix A.
Generally data has been rather difficult to assemble due to a number of factors. Some makers
will not to give out specific data, preferring rather to quote sizes and performances for a specific
job, for fear of being under cut by competition.
Much time was wasted pursuing well known manufacturers only to find that in the current
business climate they had either gone out of business or been taken over.
Manufacturers were not very interested in giving out information if they felt that they would not
get any returns so it was not politic to mention energy surveys or the like.
The best course of action was to request catalogues that you needed to pursue design
requirements and this was the course adopted.
Entering fan and pump data was very time consuming and because the values selected were
random and not for a specific job, the equipment selected could appear very inefficient. Insome cases the pump chosen could not be fitted into the performance curves so it was not
possible to make a selection.
The amount of data requested was considerable; for pumps and fans particularly all flows
against all pressures, meant a great deal of time was spent sorting through selection data.
2.1.2 Water Chill ing Packages
COP and testing procedures relating to water chilling packages of various cooling capacities
and compressor types currently available on the Australian market as indicated bymanufacturers/ suppliers are presented.
Equipment Types
a) For the Australian market, the DTS provisions covering over 99% of applications allowamalgamation of the absorption chiller types into
Engine driven Gas/hot water/ steam driven
HVAC Performance Criteria(Dec2002) Page 4 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
8/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
b) Air cooled with and without condenser could be grouped together as whether or not thechiller/air cooled condenser is purchased as a package or with remote condenser, the
performance criteria are essentially the same (assuming the air cooled condenser is sized
correctly for rated heat rejection and ignoring pipe losses). The COP/IPLV must include air
cooled condenser energy use for remote as well as package unit.
Performance Levels
The scheduled COP/IPLV attached Appendix A, are lower/middle range available at ARI
550/590 standard conditions.
Note that performance (COP levels) are substantially altered by refrigerant types, generally
increasing by about 10% using R134 and reducing by about 10% using 407C, compared with
R22.
The compressor choice, screw, scroll and rotary, compared to reciprocating, also have a
significant effect on COP.
Some manufacturers have calculated (not tested) IPLV part load COP figures (as per ARI
550/590).
RIS Considerations
There is also a cost effect and a subsequent regulatory impact statement (RIS) would need to
take this into account particularly at the under 500 kW water and air cooled reciprocating,
compared to higher COP, but higher cost screw and other compressor options.
The IPLV efficiency is substantially altered by the method of capacity control, multiple
reciprocating or single reciprocating with unloading, versus other compressor types and
controls, all of which have significant cost versus efficiency effects.
This is another situation that an RIS may have to consider as; COP/IPLV is played off against
initial cost of cheaper components having reduced efficiency versus higher initial expense.
Design Considerations & Criteria for Other Parts of the HVAC System
It is most important that the DTS performance, minimum efficiency selections do not allow
seemingly efficient chillers to be installed at the expense of inefficient or impractical other
components. Noise, pipe longevity, insulation, and maintainability, and need to be kept to
industry standards, as do air and water velocities and pressures and temperature differences.
We must not allow a wag the dog situations where regulations, DTS, favour an efficient chiller
coupled to an inefficient air handler, tower, pump, pipe and duct system.
HVAC Performance Criteria(Dec2002) Page 5 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
9/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
Reference to and mandatory use of equivalents to AIRAH handbook guidelines (or
ASHRAE/CIBSE guidelines) for velocities and temperature differences, air and water, can
prevent this from occurring.
Fluid moving energy (air and water, fans and pumps) is a major component of energy
consumption in most larger HVAC systems.
The DTS solution needs to address fluid moving energy by
Optimal selection of temperature and pressure differences in air and water Length of the distribution system ducts and pipes. Operating pressures and velocities
have significant impact on system energy consumption and must be optimised in
conjunction with chillers and other energy consuming equipment.
One of the manufacturers, Trane, with their earthwise concept has given a revised emphasis.
Their data shows that the complete system energy efficiency can be improved by widening the
temperature splits for chilled water/condenser water. This may in fact have the chillers
operating outside of their maximum efficiency range, but the significant savings in other system
equipment produce overall, a system, which reduces energy consumption. This concept is
applicable to new installations and refurbishments.
Part load operation is a difficult area. How do we protect users of chillers from what appear to
be high efficiency chillers but which due to the particular load profiles for an application,
operate for a substantial time at very poor actual operating efficiencies.
The ARI 550/590 attempts to address this problem with the 1998 issue, but the very detailed
assumptions relating to the IPLV, may not apply to a significant number of projects.
Part Load and Capacity Control
The various manufacturers have many strategies for providing part load, at varying efficiencies,
unloading variable speed drives, multiple compressors these are manufacturer and model
specific and would not easily fit into a regulatory framework.
Standard Test Conditions
The ARI 550/590 1998, standard rating conditions Table 1, correspond quite well to Sydney
design conditions
ambient 35.0 C. wet bulb 23.9 C. condenser water entering temp. 29.4 C
HVAC Performance Criteria(Dec2002) Page 6 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
10/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
Leaving chiller water 6.7 C.Several of the other seven climatic regions may need to correct ratings for their ambient
conditions.
Does the DTS need to adjust minimum COP to take account of the differing Australian ambient
conditions - that is different from any international standard rating method?
2.1.3 Heat Rejection Equipment
The following cooling tower manufacturers have been surveyed:
Manufacturer No 1 B.A.C. Pacific - Forced draft type towers with centrifugal and axial flow
fans for sizes between 30 l/sec and 87 l/sec condenser water flow rate corresponding to a heat
rejection range of 750 kW to over 2,000 kW.
Manufacturer No 2 SULZER Superchill Forced draft towers with centrifugal fans for sizes
between 37.5 l/sec and 78 l/sec condenser water flow, and induced draft towers with propeller
type fans for sizes between 36 l/sec and 105 l/sec, rate corresponding to a heat rejection range
of 900 kW to over 2,600 kW.
Manufacturer No 3 Tower Thermal Induced type tower with propeller fans for sizes between
31.3 l/sec and 81.9 l/sec rate corresponding to a heat rejection range of 780 kW to over 2,000
kW. This manufacturer in common with many who make fibreglass towers doesnt produce
towers with centrifugal fans.
Cooling towers presented difficulties in finding 3 manufacturers covering the range and types of
towers requested. Some makers will not give out catalogues or general data for fear of
compromising their competitive edge, preferring instead to quote and provide information for
specific jobs.
It was only possible to find two manufacturers that produced towers with centrifugal and axial
flow fans. Most manufacturers of fibreglass towers only make a model using propeller or axial
flow fans.
Three manufacturers of air cooled condensers were surveyed; Buffalo Trident, Muller and Kirby.
Their equipment surveyed covered a range from 10 kW to over 700 kW of heat rejection.
2.1.4 Boilers
The following boiler manufacturers have been surveyed:
Manufacturer No 1 AIRA F.T.B. for gas fired boilers between sizes 300 kW and 2000 kW.
Manufacturer No 2 BIASI for gas fired boilers between sizes150 kW and 2907 kW.
Manufacturer No 3 ROCA for gas fired boilers between sizes 81.4 and 1744.2 kW.
HVAC Performance Criteria(Dec2002) Page 7 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
11/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
Manufacturer No 4 CHAPPEE for gas fired boilers between sizes 88kW and 835 kW.
No difference was indicated in the efficiencies between gas and oil fired boilers, though gas
fired would be cleaner and less trouble to maintain.
2.1.5 Warm Air Furnaces & Combinations
Only two manufacturers of industrial type warm-air furnaces were located though there are
many companies producing small domestic type furnaces. The following warm-air furnace
manufacturers have been surveyed:
Manufacturer No 1 CELMEC for unducted heaters from 12kW to 94kW and ducted type
heaters from 17kW to 92kW.
Manufacturer No 2 DRAVO for unducted heaters from 11kW to 93.76kW; ducted type heaters
from 23.4kW to 187.5kW and direct type heaters from 117kW to 586kW.
Again no difference was indicated between the efficiencies of gas and oil heaters in the
manufacturers data.
With the direct fired ducted type of heaters there are no flue losses and the tables for Dravo
heaters show output and input values the same which indicates 100% efficiency. In actual fact
tests in the factory and at installation show a water vapour loss of 8%.
One warm air heater manufacturer mentioned that the efficiency of the units could be improved
but is limited to 80-81% by the Gas Council of Australia who has to be present when units are
tested or commissioned.
When contacted the Gas Council refuted this but mentioned that all tests and requirements are
in accordance with AG 501 and AS 3814 (Industrial and Gas Fired Appliances). The emission
requirements of this standard in Clause 3.6.1. could have an influence on the efficiency of warm
air units.
2.1.6 Pumped Water Systems
The following pump manufacturers have been surveyed:
Manufacturer No 1 Ajax International
Manufacturer No 2 Regent Dinflow
Manufacturer No 3 Thomson Kelly Lewis
For flow rates between 50 m3/hour to 300 m3/hour at various pressures.
2.1.7 Fan Systems
The following fan manufacturers have been surveyed:
HVAC Performance Criteria(Dec2002) Page 8 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
12/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
Manufacturer No 1 Flakt Richardson for air flows from 500 l/sec to 2000 l/sec.
Manufacturer No 1 SWG Forde for air flows from 500 l/sec to 2000 l/sec
Manufacturer No 1 Fantech for air flows from 500 l/sec to 2000 l/sec
2.2 Recommendations on Steps in Capacity
2.2.1 Water Chill ing Packages
As shown in appendix A, steps in capacity are practical and reflect chillers available currently on
the Australian market.
2.2.2 Heat Reject ion Equipment
The performance requirement covered the full range of capacities from small to medium-large
installations. There was no significant variation in the performance indicator from large to smallcooling towers hence a single indicator seems appropriate. The same is applicable to air
cooled condensers.
2.2.3 Boilers
Three performance indicators for small, medium and large boilers are more than sufficient since
the manufacturers supplied efficiency varies little.
2.2.4 Warm Air Furnaces & Combinations
There was little variation between the 75 kW capacities for gas fired unducted
type warm air furnaces and therefore one figure for all sizes would seem more appropriate.
2.2.5 Pumped Water Systems
The capacity steps for the pump systems are appropriate and a reasonable level of size
discernment is necessary since the performance indicator varies significantly with the size of
system.
2.2.6 Fan Systems
Again, a reasonable level of size discernment is necessary for the fan systems since the
performance indicator varies significantly with the size of system.
2.3 Codes and Standards for Equipment Performance Rating
2.3.1 Water Chill ing Packages
Australian AS3823 series related only to non ducted and ducted air conditioning units not
applicable to chillers. These standards are adapted from ISO 5151-B25.
There is a Eurovent chiller standard (Europe) but European manufacturers seem to recognise
the ARI standard.
HVAC Performance Criteria(Dec2002) Page 9 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
13/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
There is a J IS standard (J apan) for chiller testing (details not available at this time)
At this stage, ARI 550/590 1998, seems readily applicable to Australian conditions does
address comprehensively, for U.S. conditions, the part load efficiency situation and relates to
U.S. and European designed chillers.
The Japanese chillers surveyed are rated at typically 7 C leaving water, 35 C ambient air and
28 C. condenser water, with a range of performance relating to an envelope of conditions
either side of these figures.
If we refer to ARI 550/590 - 1998 in the DTS references, and use this code as a verification
method for performance based solutions, we have and authoritative and consistent document to
refer to, which does relate in the main to conditions which are recognisable in Australia, by
practitioners and chiller manufacturers/suppliers.
2.3.2 Heat Rejection Equipment
Tower Thermal to AS 3666.1.1995
SULZER Superchill to AS3666.1.
BAC> C.T.I (Cooling Tower institute) thermal performance standard STD-201.
And CTI acceptance test code ATC-105.
2.3.3 BoilersNo codes or standards were able to be identified in relation to the performance ratings of the
equipment surveyed. Further research is needed in this area to identify appropriate standards
for performance testing. It s expected that European standards have been used in most cases;
however no specific reference has been made in the data.
2.3.4 Warm Air Furnaces & Combinations
As above no codes or standards were able to be identified in relation to the performance ratings
of the equipment surveyed.
2.3.5 Pumped Water Systems
Thomson, Kelly, Lewis to I.S.O.2858 (DIN24255 not satisfying demands of heavy duty
performance pumps).
Regent. To DIN24255.
Ajax to AS2417 and DIN24255.
2.3.6 Fan Systems
SWG Forde. Factory tested for each fan but no data on how values are obtained.
HVAC Performance Criteria(Dec2002) Page 10 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
14/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
Fantech tested to BS 848:part1 1980 for airflow and part 2, 1985 for noise.
ABB Flakt Richardson. N.A.T.A. CERTIFIED Fan Test Laboratory. Testing in accordance with
BS 848 Part 1. 1980 test method type B-D and BS848 Part 2 1966 test method type 3. Also
compliance with A.M.C.A.210 method fig 7. Working with CSIRO on project to reduce
centrifugal fan noise through mechanical design refinement.
2.4 Referenced Manufacturers & Suppliers
2.4.1 Water Chill ing Packages
Chiller Efficiency Survey Respondents
The product survey included detailed discussions with the following
importers/manufacturers/suppliers of chillers to the Australian market, currently and in the near
future.
Carrier Ross J acka (02) 9818 9700
York J im Mawer (02) 9418 3002
Hirotech Robert Garnet (02) 9750 4666
Hitachi J ohn McDermott (02) 9888 4124
Daikin Gary Knox (02) 9755 3322
Trane G.S. Rao (02) 9888 6122
Multistack Changis Tolouee (03) 9265 8000
University of NSW Air Conditioning Testing Laboratory, Mechanical Engineering Prof. Eddie
Leonardi re testing and standards.
AREMA Ian Binger (03) 9867 0111
Referenced to the major chiller suppliers for technical information. AREMA as an organisation
do not keep technical data
We worked in conjunction with Simon Hill ph: (02) 9449 7183
2.4.2 Heat Rejection Equipment
The following cooling tower manufacturers/suppliers were surveyed:
B.A.C. Pacific. ph: (03) 9872 0111.
SULZER Superchill. ph: (03) 9793 6166.
Tower Thermal. ph: (03) 9877 5066.
HVAC Performance Criteria(Dec2002) Page 11 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
15/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
Buffalo Trident. ph: (03) 9311 4480.
Muller Industries. ph: (03) 9355 3333.
Kirby Refrigeration. ph: (03) 9561 0199.
2.4.3 Boilers
The following boiler manufacturers/suppliers were surveyed:ROCA - AIRA. ph: (03) 9728 5566. AIRA F.T.B. ph: (03) 9728 5566. BIASI Hunt Heating. ph: (03) 9558 7077 CHAPPEE Automatic Heating appliances. ph: (03) 9330 3300. 2.4.4 Warm Air Furnaces & Combinations
The following warm air furnace manufacturers/suppliers were surveyed:CELMEC. ph: (03) 9555 3667. DRAVO - AIRA. ph: (03) 9728 5566. 2.4.5 Pumped Water Systems
The following pump manufacturers/suppliers were surveyed:Ajax International. ph: (03) 9314 0611. Regent Dinflow. ph: (03) 9551 5111.
Thomson Kelly Lewis. ph: (03) 9562 0744. 2.4.6 Fan Systems
The following fan manufacturers/suppliers were surveyed: Flakt Richardson. ph: (03) 9248 8500. SWG Forde. ph: (03) 9808 6511. Fantech. ph: (03) 9560 2599.
HVAC Performance Criteria(Dec2002) Page 12 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
16/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
GLOSSARYCOP Coefficient of Performance. Performance indicator applied to chillers. Refer to
ARI 550/590.
IPLV Integrated Part Load Value. Performance indicator applied to chillers. Refer to
ARI 550/590.
l/s.kW Air flow rate divided by heat rejection capacity. Performance indicator applied
to heat rejection equipment.
W.s/l Pump nameplate power divided by water flow rate. Performance indicator
applied to pumps. OR
Fan nameplate power divided by air flow rate. Performance indicator applied
to fans.
HVAC Performance Criteria(Dec2002) Page 13 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
17/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
BIBLIOGRAPHY
1. ARI Standard 550/590 - 1998: Water Chilling Packages using the Vapour CompressionCycle. Air Conditioning & Refrigeration Institute.
2. ARI Standard 560 - 2000: Absorption Water Chilling and Water Heating Packages. AirConditioning & Refrigeration Institute.
3. Application Manual No. DA17: Cooling Towers. Australian Institute of Refrigeration AirConditioning and Heating.
4. Application Manual No. DA1: Centrifugal Pumps Selection and Application. AustralianInstitute of Refrigeration Air Conditioning and Heating.
5. Application Manual No. DA13: Fans Selection and Application. Australian Institute ofRefrigeration Air Conditioning and Heating.
HVAC Performance Criteria(Dec2002) Page 14 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
18/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
APPENDICES
HVAC Performance Criteria(Dec2002) Page 15 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
19/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
Appendix A
Equipment Performance Schedules
HVAC Performance Criteria(Dec2002) Page 16 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
20/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
WATER CHILLING PACKAGES MINIMUM REQUIREMENTS
Equipment type Size. K Minimum Effic iency (*) Test Procedure
W COP IPLV
refrigeration
Air cooled with condenser,electrically operated
< 500
> 500
2.5
to
2.9
Approx.
10% above
COP
ARI
550/590
Air cooled without condenserelectrically operated
< 500
> 500
3.5
to
4.0
Approx.
10% above
COP
ARI
550/590
Water cooled, electricallyoperated, reciprocating
All capacities 3.3
to
3.5
Approx.
10% above
COP
ARI
550/590
Water cooled, electrically
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
21/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
HEAT REJECTION EQUIPMENT - PERFORMANCE REQUIREMENTS
Equipment Type
Cooling tower,
propeller or axial fan
Cooling tower,
centrifugal fan
Air cooled condensers
Total system heat
rejection capacity at
rated condition
all
all
all
Rated condition
35C entering water
29C leaving water
24C wb outdoor air
35C entering water
29C leaving water
24C wb outdoor air
R-22 test fluid
52C condensing temperature
88C entering gastemperature
8K subcooling
35C db entering air
Performance
Requirement
(L/s.kW)
< 18
< 17
< 77
Test Procedure
C.T.I (Cooling Tower
institute) thermal
performance standard
STD-201
HVAC Performance Criteria(Dec2002) Page 18 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
22/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
BOILERS - MINIMUM REQUIREMENTS
Equipment Type
Boilers, gas fired
OR oil fired.
Size, kW (heating)
< 90
< 750
> 750
Rated condition
maximum capacity
maximum capacity
maximum capacity
Minimum
Efficiency
> 91%
> 90%
> 88%
Test Procedure
HVAC Performance Criteria(Dec2002) Page 19 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
23/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
WARM AIR FURNACES & COMBINATIONS - MINIMUM REQUIREMENTS
Equipment Type
Warm air furnaces, gas
fired unducted type.
Warm air furnaces, gas
fired unducted type.
Warm air furnaces,
gas fired ducted type
Size, kW (heating)
< 75
> 75
all capacities
all capacities
Rated condition
maximum capacity
maximum capacity
maximum capacity
maximum capacity
Minimum
Efficiency
> 80%
> 80%
> 79%
> 92%
Test Procedure
HVAC Performance Criteria(Dec2002) Page 20 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
24/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
PUMPED WATER SYSTEMS - PERFORMANCE REQUIREMENTS
Equipment Type System static head, kPaPerformance
Requirement, kW.s/L (*)Test Procedure
Condenser Water
&
Chilled water
&
Heating hot water
< 150
< 200
< 250
< 300
< 350
> 350 < 450
< 0.14
< 0.20
< 0.26
< 0.33
< 0.44
< 0.57
AS2417, DIN24255,
I.S.O.2858
* - sum of all pumps in series in a circuit (eg. primary + secondary +)
- derived from the pump water flow rate divided by the pump nameplate power
HVAC Performance Criteria(Dec2002) Page 21 February 2003
-
7/29/2019 Performance Standards Hvac Equipment Performance Consultancy
25/25
Australian Building Codes Board PERFORMANCE STANDARDS OF HVAC EQUIPMENT
FAN SYSTEMS - PERFORMANCE REQUIREMENTS
Equipment TypeVolumetric flow
rate, L/s
Operating
static
pressure, Pa
Performance
Requirement, W.s/L (*)Test Procedure
< 2,000 < 500 < 0.39
< 750
< 1,000
> 1,000
< 0.83
< 1.35
< 2.19
Fan systems with clean filters
pressure static pressure loss of
less than 250Pa
< 5,000
< 10,000
> 10,000
< 2,000
< 500
< 750
< 1,000
> 1,000
< 500
< 750
< 1,000
> 1,000
< 500
< 750
< 1,000
> 1,000
< 500
< 750
< 1,000
> 1,000
< 0.38
< 0.77
< 1.27
< 2.06
< 0.34
< 0.73
< 1.19
< 1.99
< 0.35
< 0.73
< 1.18
< 1.78
< 0.83
< 1.35
< 2.19
< 3.56
BS 848:part1 1980 for
airflow and part 2, 1985
for noise
Fan systems with clean filter
pressure static pressure loss
greater than 250Pa
< 5,000
< 10,000
> 10,000
< 500
< 750
< 1,000
> 1,000
< 500
< 750
< 1,000
> 1,000
< 500
< 0.77
< 1.27
< 2.06
< 3.38
< 0.73
< 1.19
< 1.99
< 3.27
< 0.73
BS 848:part1 1980 for
airflow and part 2, 1985
for noise
< 750< 1,000
> 1,000
< 1.18< 1.78
< 2.81
* - sum of all fans in series in a circuit (eg.supply + return +)
- derived from the fan volumetric flow rate flow rate divided by the fan nameplate power