physical hydraulic model investigation of critical submergence for
TRANSCRIPT
Thesis presented in partial fulfilment of the requirements for the
degree of Master of Engineering (Civil) at Stellenbosch University
PHYSICAL HYDRAULIC
MODEL INVESTIGATION OF
CRITICAL SUBMERGENCE
FOR RAISED PUMP INTAKES
by
SH KLEYNHANS
FEBRUARY 2012
DEPARTMENT OF CIVIL ENGINEERING
STUDY LEADER:
Prof. GR BASSON
ii
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
SINOPSIS
Oor die afgelope vier dekades is verskeie ontwerpriglyne vir die berekening van minimum
watervlakke, om werwelvorming by pompinlate te voorkom, gepubliseer. Hierdie ontwerpriglyne
vereis dat die klokmond van die pompinlaat nie hoër as 0.5 keer die deursnee van die klokmond
(D) bokant die kanaalvloer geleë moet wees nie.
Sandvang kanale vorm ‘n integrale deel van groot riveronttrekkingswerke, met pompinlate wat
aan die einde van hierdie kanale geleë is. Die kanale word aan die stroomaf kant van die
pompinlaat voorsien met sluise sodat die kanale gespoel kan word. Hierdie sluise is tipies
1.5 m hoog. Dit is derhalwe nodig om die hoogte onder die klokmond dieselfde te maak as die
hoogte van die sluis sodat die klokmond die spoelwerking nie beïnvloed nie. Die vraag is egter
– wat is die impak op die minimum vereiste watervlakke indien die klokmond op ‘n hoër vlak
installeer word?
‘n Fisiese hidrouliese model met ‘n 1:10 skaal is gebruik om die minimum watervlakke te bepaal
waar tipes 2, 5 en 6 werwels aangetref word vir prototipe inlaatsnelhede van 0.9 m/s tot 2.4 m/s
en klokmond hoogtes van 0.5D, 1.0D en 1.5D bokant die kanaalvloer. Vier klokmond
konfigurasies is getoets. Die minimum vereiste watervlakke was die laagste vir die tradisionele
plat klokmond met ‘n lang radius buigstuk en was dus die voorkeur klokmond.
Die eksperimenttoetsresultate vir die voorkeur klokmond is met die gepubliseerde
ontwerpriglyne vergelyk om te bepaal watter van die ontwerpsriglyne van toepassing sal wees
vir verhoogde klokmond installasies.
Uit die eksperimenttoetsresultate is dit duidelik dat die vereiste watervlakke skielik verhoog
sodra die klokmond installasie ‘n seker hoogte bokant die kanaal vloer oorskry. Daar is bevind
dat hierdie verskynsel by al vier klokmond konfigurasies voorkom sodra die verhouding tussen
die prototipe klokmond inlaatsnelheid teenoor die snelheid in die kanaal hoër as 6.0 is.
Daar word aanbeveel dat die minimum vereiste watervlak vir pompinlate met dieselfde
geometrie as die fisiese model, met Knauss (1987) se vergelyking bereken word, naamlik
S = D(0.5 + 2.0Fr), waar die snelheidsverhouding tussen die klokmond en kanaal 6.0 nie
oorskry nie, en dat die vergelyking gepubliseer deur die Hydraulic Institute (1998),
S = D(1 + 2.3Fr), gebruik word waar die snelheidsverhouding 6.0, so bereken met Knauss
(1987) ser vergelyking, wel oorskry. Die prototipe klokmond inlaatsnelheid moet ook beperk
word tot 1.5 m/s.
Stellenbosch University http://scholar.sun.ac.za
iii
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
SYNOPSIS
Various design guidelines have been published over the past four decades to calculate the
minimum submergence required at pump intakes to prevent vortex formation. These design
guidelines also require the suction bell to be located not higher than 0.5 times the suction bell
diameter (D) above the floor.
Sand trap canals are an integral part of large river abstraction works, with the pump intakes
located at the end of the sand trap canals. The canals need to be flushed by opening a gate,
typically 1.5 m high, that is located downstream of the pump intake. This requires the suction
bell be raised to not interfere with the flushing operation, which leads to the question – what
impact does the raising of the suction bell have on the minimum required submergence?
A physical hydraulic model constructed at 1:10 scale was used to determine the submergence
required to prevent types 2, 5 and 6 vortices for prototype suction bell inlet velocities ranging
from 0.9 m/s to 2.4 m/s, and for suction bells located at 0.5D, 1.0D and 1.5D above the floor.
The tests were undertaken for four suction bell configurations with a conventional flat bottom
suction bell, fitted with a long radius bend, being the preferred suction bell configuration in terms
of the lowest required submergence levels.
The experimental test results of the preferred suction bell configuration were compared against
the published design guidelines to determine which published formula best represents the
experimental test results for raised pump intakes.
It became evident from the experimental test results that the required submergence increased
markedly when the suction bell was raised higher than a certain level above the floor. It was
concluded that this “discontinuity” in the required submergence occurred for all the suction bell
configuration types when the ratio between the prototype bell inlet velocity and the approach
canal velocity was approximately 6.0 or higher.
It is recommended that, for pump intakes with a similar geometry to that tested with the physical
hydraulic model, critical submergence is calculated using the equation published by Knauss
(1987), i.e. S = D(0.5 + 2.0Fr), if the prototype bell inlet velocity/approach canal velocity ratio is
less than 6.0, and that the equation published by the Hydraulic Institute (1998), i.e.
S = D(1 + 2.3Fr), can be used where the ratio, as determined with Knauss’ (1987) equation,
exceeds 6.0. It is also recommended that prototype bell inlet velocities be limited to 1.5 m/s.
Stellenbosch University http://scholar.sun.ac.za
iv
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
ACKNOWLEDGEMENTS
The author would like to acknowledge the contributions of the following individuals and funding
institution:
Prof GR Basson, for the support and guidance he provided as study leader;
The laboratory personnel of Stellenbosch University, especially Christiaan Visser, for
arranging the construction of the physical model and assisting with modifications during the
test phase;
TCTA, for funding the construction of the physical hydraulic model;
Charlie Espost, for providing the pumpset and variable speed drive;
My colleague, Schalk van der Merwe, for encouraging me to enrol for a Master’s degree and
for his continuous support at work while I completed my studies on a part-time basis; and
My wife, Maré – this thesis would not have been possible without your support and
encouragement over the past two years.
Stellenbosch University http://scholar.sun.ac.za
v
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
CONTENTS
DECLARATION ........................................................................................................................... i
SINOPSIS ................................................................................................................................... ii
SYNOPSIS ................................................................................................................................ iii
ACKNOWLEDGEMENTS .......................................................................................................... iv
CONTENTS ................................................................................................................................ v
LIST OF FIGURES .................................................................................................................. viii
LIST OF TABLES ..................................................................................................................... xiii
LIST OF ABBREVIATIONS ....................................................................................................... xv
1. INTRODUCTION ................................................................................................................ 1
1.1 Background to the research project ........................................................................................ 1
1.2 Motivation for the study ............................................................................................................. 3
1.3 Objective of study ....................................................................................................................... 7
1.4 Layout of the thesis .................................................................................................................... 7
2. METHODOLOGY ................................................................................................................ 9
2.1 Physical model study ................................................................................................................. 9
2.2 Modelling scenarios ................................................................................................................... 9
2.3 Criteria to decide on minimum submergence in proto-type ............................................... 12
3. LITERATURE REVIEW ......................................................................................................13
3.1 Fundamentals and theory of vortex formation ..................................................................... 13
3.1.1 Introduction ........................................................................................................................ 13
3.1.2 Vortex classification and strengths ................................................................................ 15
3.1.3 Acceptance criteria for pump intakes ............................................................................ 16
3.1.4 Dimensionless parameters ............................................................................................. 17
3.2 Impacts of scale effects in physical models ......................................................................... 20
3.2.1 Physical similarity ............................................................................................................. 20
3.2.2 Similarity laws ................................................................................................................... 22
3.2.3 Modelling criteria .............................................................................................................. 26
3.2.4 Scale of proposed physical model ................................................................................. 28
Stellenbosch University http://scholar.sun.ac.za
vi
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
3.3 Design guidelines to calculated critical submergence ........................................................ 30
3.3.1 The hydraulic design of pump sumps and intakes (Prosser, 1977) ......................... 30
3.3.2 Centrifugal pump handbook (Sulzer Brothers Limited, 1987) ................................... 30
3.3.3 Pump intake design (Hydraulic Institute, 1998) ........................................................... 30
3.3.4 Pump station design (Jones et al., 2008) ..................................................................... 30
3.3.5 Pump handbook (Karassik et al., 2001) ........................................................................ 31
3.3.6 Swirling flow problems at intakes (Knauss, 1987) ....................................................... 31
3.3.7 Gorman-Rupp design guidelines (Strydom, 2010b) ................................................... 31
3.3.8 KSB design guidelines (Gouws, 2010) ......................................................................... 32
3.3.9 Collection and pumping of wastewater (Metcalf and Eddy, 1981, provided by
Strydom, 2010a) ............................................................................................................................... 32
3.3.10 Design recommendations for pumping stations with dry installed submersible
pumps (Flygt, 2002) ......................................................................................................................... 33
3.3.11 Werth and Frizzell (2009) ................................................................................................ 33
4. EXPERIMENTAL SET-UP AND TEST PROCEDURES .....................................................36
4.1 Experimental set-up ................................................................................................................. 36
4.2 Instrumentation ......................................................................................................................... 41
4.3 Test procedure .......................................................................................................................... 42
4.3.1 Submergence for different types of vortices ................................................................. 42
4.3.2 Dye injection tests ............................................................................................................ 45
4.3.3 ADV measurements ......................................................................................................... 48
5. EXPERIMENTAL TEST RESULTS ....................................................................................52
5.1 Experimental test results ......................................................................................................... 52
5.2 Repeatability of tests ............................................................................................................... 64
5.3 Visual observations .................................................................................................................. 71
5.4 Analysis of experimental test results ..................................................................................... 75
5.4.1 Comparison of submergence for different suction bell heights ..................................... 75
5.4.2 Explaining the increase in submergence when raising the pump intake ..................... 83
5.5 Comparison of test results of four bell intake configurations ............................................. 94
5.6 Acoustic Doppler velocimeter measurements ................................................................... 100
Stellenbosch University http://scholar.sun.ac.za
vii
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
5.6.1 ADV measurements at edge of suction bell ................................................................... 100
5.6.2 ADV measurements along approach canal .................................................................... 107
6. COMPARISON OF TEST RESULTS AGAINST DESIGN GUIDELINES .......................... 116
7. CONCLUSIONS AND RECOMMENDATIONS................................................................. 127
7.1 Conclusions ............................................................................................................................. 127
7.2 Recommendations ................................................................................................................. 128
Stellenbosch University http://scholar.sun.ac.za
viii
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
LIST OF FIGURES
Figure 1.1: Dimension variables for pump intake (Hydraulic Institute, 1998) ............................. 2
Figure 1.2: Proposed layout of Lower Thukela abstraction works .............................................. 3
Figure 1.3: Physical model of the proposed Lower Thukela abstraction works .......................... 4
Figure 1.4: Proposed raised suction bell installation in sand trap canal ..................................... 5
Figure 2.1: Flat bell installation for flows ≤ 1 m3/s (Sulzer Brothers Limited, 1987) ...................10
Figure 2.2: Slanted bell installation for flows > 1 m3/s (Sulzer Brothers Limited, 1987) .............10
Figure 3.1: Rankine combined vortex (Prosser, 1977) .............................................................14
Figure 3.2: Free surface and sub-surface vortex strength classification (Hydraulic Institute,
1998) ........................................................................................................................................16
Figure 3.3: Critical submergence versus bell inlet velocity .......................................................34
Figure 3.4: Approach velocities versus bell inlet velocity ..........................................................34
Figure 4.1: Plan view of physical model ...................................................................................36
Figure 4.2: Sectional view of physical model ............................................................................36
Figure 4.3: View of pump model ...............................................................................................38
Figure 4.4: View of stilling basin and flow straightener pipes ....................................................38
Figure 4.5: Dimensions of suction bell configurations ...............................................................39
Figure 4.6: Rear view of suction bell configurations (from left to right: Type 1B, Type 1A, Type
2B, Type 2A) .............................................................................................................................40
Figure 4.7: Side view of suction bell configurations (from left to right: Type 2A, Type 2B, Type
1A, Type 1B) .............................................................................................................................40
Figure 4.8: ADV support frame .................................................................................................42
Figure 4.9: Vectrino instrument ................................................................................................42
Figure 4.10: Flow diagram of daily test procedure ....................................................................44
Figure 4.11: Path of dye injected upstream of suction bell .......................................................47
Figure 4.12: Evidence of a coherent dye core behind the suction bell ......................................48
Figure 4.13: Positions of ADV measurements at inlet bell ........................................................49
Figure 4.14: XYZ coordinates of ADV instrument (Nortek, 2004) .............................................50
Figure 4.15: Position of ADV measurements in sand trap canal ...............................................51
Figure 5.1: Type 1A bellmouth, 0.5D above floor – prototype type submergence .....................53
Stellenbosch University http://scholar.sun.ac.za
ix
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.2: Type 1A bellmouth, 1.0D above floor – prototype type submergence .....................54
Figure 5.3: Type 1A bellmouth, 1.5D above floor – prototype type submergence .....................55
Figure 5.4: Type 1B bellmouth, 0.5D above floor – prototype type submergence .....................56
Figure 5.5: Type 1B bellmouth, 1.0D above floor – prototype type submergence .....................57
Figure 5.6: Type 1B bellmouth, 1.5D above floor – prototype type submergence .....................58
Figure 5.7: Type 2A bellmouth, 0.5D above floor – prototype type submergence .....................59
Figure 5.8: Type 2A bellmouth, 1.0D above floor – prototype type submergence .....................60
Figure 5.9: Type 2A bellmouth, 1.5D above floor – prototype type submergence .....................61
Figure 5.10: Type 2B bellmouth, 0.5D above floor – prototype type submergence ...................62
Figure 5.11: Type 2B bellmouth, 1.0D above floor – prototype type submergence ...................63
Figure 5.12: Type 2B bellmouth, 1.5D above floor – prototype type submergence ...................64
Figure 5.13: Type 1B bellmouth, 0.5D above floor – prototype type submergence for Type 2
vortices .....................................................................................................................................65
Figure 5.14: Type 1B bellmouth, 0.5D above floor – prototype type submergence for Type 5
vortices .....................................................................................................................................66
Figure 5.15: Type 1B bellmouth, 0.5D above floor – prototype type submergence for Type 6
vortices .....................................................................................................................................67
Figure 5.16: Type 2B bellmouth, 0.5D above floor – prototype type submergence for Type 2
vortices .....................................................................................................................................68
Figure 5.17: Type 2B bellmouth, 0.5D above floor – prototype type submergence for Type 5
vortices .....................................................................................................................................69
Figure 5.18: Type 2B bellmouth, 0.5D above floor – prototype type submergence for Type 6
vortices .....................................................................................................................................70
Figure 5.19: Type 2 vortex (surface dimple) .............................................................................72
Figure 5.20: Type 5 vortex (pulling air bubbles to intake) .........................................................72
Figure 5.21: Type 6 vortex (full air core to intake) ....................................................................73
Figure 5.22: Break-away caused when water level is at joint on segmented bend ...................74
Figure 5.23: Type 1A suction bell – submergence required for Type 2 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................75
Figure 5.24: Type 1A suction bell – submergence required for Type 5 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................76
Figure 5.25: Type 1A suction bell – submergence required for Type 6 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................76
Stellenbosch University http://scholar.sun.ac.za
x
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.26: Type 1B suction bell – submergence required for Type 2 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................77
Figure 5.27: Type 1B suction bell – submergence required for Type 5 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................78
Figure 5.28: Type 1B suction bell – submergence required for Type 6 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................78
Figure 5.29: Type 2A suction bell – submergence required for Type 2 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................79
Figure 5.30: Type 2A suction bell – submergence required for Type 5 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................80
Figure 5.31: Type 2A suction bell – submergence required for Type 6 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................80
Figure 5.32: Type 2B suction bell – submergence required for Type 2 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................81
Figure 5.33: Type 2B suction bell – submergence required for Type 5 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................82
Figure 5.34: Type 2B suction bell – submergence required for Type 6 vortices at bell heights of
0.5D, 1.0D and 1.5D .................................................................................................................82
Figure 5.35: Type 1A suction bell – submergence against bell/approach velocity ratios for Type
2 vortices ..................................................................................................................................86
Figure 5.36: Type 1A suction bell – submergence against bell/approach velocity ratios for Type
5 vortices ..................................................................................................................................86
Figure 5.37: Type 1A suction bell – submergence against bell/approach velocity ratios for Type
6 vortices ..................................................................................................................................87
Figure 5.38: Type 1B suction bell – submergence against bell/approach velocity ratios for Type
2 vortices ..................................................................................................................................88
Figure 5.39: Type 1B suction bell – submergence against bell/approach velocity ratios for Type
5 vortices ..................................................................................................................................88
Figure 5.40: Type 1B suction bell – submergence against bell/approach velocity ratios for Type
6 vortices ..................................................................................................................................89
Figure 5.41: Type 2A suction bell – submergence against bell/approach velocity ratios for Type
2 vortices ..................................................................................................................................90
Figure 5.42: Type 2A suction bell – submergence against bell/approach velocity ratios for Type
5 vortices ..................................................................................................................................90
Figure 5.43: Type 2A suction bell – submergence against bell/approach velocity ratios for Type
6 vortices ..................................................................................................................................91
Stellenbosch University http://scholar.sun.ac.za
xi
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.44: Type 2B suction bell – submergence against bell/approach velocity ratios for Type
2 vortices ..................................................................................................................................92
Figure 5.45: Type 2B suction bell – submergence against bell/approach velocity ratios for Type
5 vortices ..................................................................................................................................92
Figure 5.46: Type 2B suction bell – submergence against bell/approach velocity ratios for Type
6 vortices ..................................................................................................................................93
Figure 5.47: Comparison of submergence between Type 1A and 1B suction bell configurations
for Type 2 vortices ....................................................................................................................94
Figure 5.48: Comparison of submergence between Type 1A and 1B suction bell configurations
for Type 5 vortices ....................................................................................................................95
Figure 5.49: Comparison of submergence between Type 1A and 1B suction bell configurations
for Type 6 vortices ....................................................................................................................95
Figure 5.50: Comparison of submergence between Type 2A and 2B suction bell configurations
for Type 2 vortices ....................................................................................................................96
Figure 5.51: Comparison of submergence between Type 2A and 2B suction bell configurations
for Type 5 vortices ....................................................................................................................97
Figure 5.52: Comparison of submergence between Type 2A and 2B suction bell configurations
for Type 6 vortices ....................................................................................................................97
Figure 5.53: Comparison of submergence between Type 1B and 2B suction bell configurations
for Type 2 vortices ....................................................................................................................98
Figure 5.54: Comparison of submergence between Type 1B and 2B suction bell configurations
for Type 5 vortices ....................................................................................................................99
Figure 5.55: Comparison of submergence between Type 1B and 2B suction bell configurations
for Type 6 vortices ....................................................................................................................99
Figure 5.56: X, Y and Z velocities for 0.9 m/s bell inlet velocity at Position 2 .......................... 102
Figure 5.57: Plan view of resultant velocities at suction bell for prototype bell inlet velocities of
0.9 m/s to 2.4 m/s ................................................................................................................... 106
Figure 5.58: Position 1C: X, Y and Z velocities for 0.5D and 1.2 m/s inlet bell velocity ........... 111
Figure 5.59: Position 1C: X, Y and Z velocities for 0.5D and 1.2 m/s inlet bell velocity for sample
numbers 195 to 295 ................................................................................................................ 112
Figure 5.60: Average resultant velocities along centrelines 1-4-7, 2-5-8, and 3-6-9 ............... 113
Figure 5.61: Average resultant velocities along Planes A, B and C ........................................ 114
Figure 5.62: Path of particle approaching the inlet bell ........................................................... 115
Figure 6.1: Comparison of submergence between design guidelines and measured Type 2, 5
and 6 vortices for a bell height of 0.5D .................................................................................... 116
Stellenbosch University http://scholar.sun.ac.za
xii
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 6.2: Comparison of submergence between design guidelines and measured Type 2, 5
and 6 vortices for a bell height of 1.0D .................................................................................... 117
Figure 6.3: Comparison of submergence between design guidelines and measured Type 2, 5
and 6 vortices for a bell height of 1.5D .................................................................................... 118
Figure 6.4: Comparison of submergence between design guidelines and measured Type 2
vortices for bell heights of 0.5D, 1.0D and 1.5D ...................................................................... 119
Stellenbosch University http://scholar.sun.ac.za
xiii
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
LIST OF TABLES
Table 1.1: Recommended dimensions for pump intakes ........................................................... 2
Table 1.2: Recommended dimensions versus proposed dimensions for Vlieëpoort and Lower
Thukela sand trap canals ........................................................................................................... 6
Table 2.1: Modelling scenarios .................................................................................................11
Table 2.2: Repeat tests performed to verify reliability of results ................................................12
Table 2.3: ADV recording scenarios .........................................................................................12
Table 3.1: Prototype information and scale effects ...................................................................29
Table 3.2: Critical submergence recommended by Gorman-Rupp ...........................................32
Table 3.3: Critical submergence recommended by KSB ..........................................................32
Table 3.4: Critical submergence recommended by Metcalf and Eddy (1981) ...........................33
Table 4.1: Configuration set-up of ADV instrument ..................................................................41
Table 5.1: Test results – inlet bell Type 1A, 0.5D above floor ...................................................52
Table 5.2: Test results – inlet bell Type 1A, 1.0D above floor ...................................................53
Table 5.3: Test results – inlet bell Type 1A, 1.5D above floor ...................................................54
Table 5.4: Test results – inlet bell Type 1B, 0.5D above floor ...................................................55
Table 5.5: Test results – inlet bell Type 1B, 1.0D above floor ...................................................56
Table 5.6: Test results – inlet bell Type 1B, 1.5D above floor ...................................................57
Table 5.7: Test results – inlet bell Type 2A, 0.5D above floor ...................................................58
Table 5.8: Test results – inlet bell Type 2A, 1.0D above floor ...................................................59
Table 5.9: Test results – inlet bell Type 2A, 1.5D above floor ...................................................60
Table 5.10: Test results – inlet bell Type 2B, 0.5D above floor .................................................61
Table 5.11: Test results – inlet bell Type 2B, 1.0D above floor .................................................62
Table 5.12: Test results – inlet bell Type 2B, 1.5D above floor .................................................63
Table 5.13: Repeatability test results – inlet bell Type 1B, 0.5D above floor, Type 2 vortices ...65
Table 5.14: Repeatability test results – inlet bell Type 1B, 0.5D above floor, Type 5 vortices ...66
Stellenbosch University http://scholar.sun.ac.za
xiv
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.15: Repeatability test results – inlet bell Type 1B, 0.5D above floor, Type 6 vortices ...67
Table 5.16: Repeatability test results – inlet bell Type 2B, 0.5D above floor, Type 2 vortices ...68
Table 5.17: Repeatability test results – inlet bell Type 2B, 0.5D above floor, Type 5 vortices ...69
Table 5.18: Repeatability test results – inlet bell Type 2B, 0.5D above floor, Type 6 vortices ...70
Table 5.19: Reynolds Numbers for approach velocities ............................................................84
Table 5.20: Water levels for ADV tests at suction bell ............................................................ 100
Table 5.21: Summary of ADV measurements (model) at suction bell for prototype 0.9 m/s bell
inlet velocity ............................................................................................................................ 102
Table 5.22: Summary of ADV measurements (model) at suction bell for prototype 1.2 m/s bell
inlet velocity ............................................................................................................................ 103
Table 5.23: Summary of ADV measurements (model) at suction bell for prototype 1.5 m/s bell
inlet velocity ............................................................................................................................ 104
Table 5.24: Summary of ADV measurements (model) at suction bell for prototype 1.8 m/s bell
inlet velocity ............................................................................................................................ 104
Table 5.25: Summary of ADV measurements (model) at suction bell for prototype 2.1 m/s bell
inlet velocity ............................................................................................................................ 105
Table 5.26: Summary of ADV measurements (model) at suction bell for prototype 2.4 m/s bell
inlet velocity ............................................................................................................................ 105
Table 5.27: Water levels for ADV tests along approach canal ................................................ 107
Table 5.28: Summary of ADV measurements (model) along approach canal ......................... 108
Table 6.1: Bell inlet velocity/approach canal velocity ratios for Type 1B suction bell located 0.6
m (prototype) above canal floor ............................................................................................... 121
Table 6.2: Bell inlet velocity/approach canal velocity ratios for Type 1B suction bell located 1.2
m (prototype) above canal floor ............................................................................................... 122
Table 6.3: Bell inlet velocity/approach canal velocity ratios for Type 1B suction bell located 1.8
m (prototype) above canal floor ............................................................................................... 124
Stellenbosch University http://scholar.sun.ac.za
xv
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
LIST OF ABBREVIATIONS
a Acceleration
A Cross-sectional area of inlet bell
ADV Acoustic Doppler velocimeter
AWWA American Water Works Association
B Distance from back wall to pump inlet centreline
C Distance from floor to underside of the inlet bell
Cd Discharge coefficient
CFD Computational fluid dynamics
d Suction pipe diameter
D Inlet bell diameter
E Euler Number
F Force
Fg Force due to gravity
Fp Force due to pressure
Fr Froude Number at suction bell
Fst Force due to surface tension
Fv Force due to viscosity
g Gravitational acceleration
HDPE High density polyethylene
Hz Hertz
kW Kilowatt
Stellenbosch University http://scholar.sun.ac.za
xvi
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
L Length (linear dimension)
Lr Geometric scale
ℓ/s Litres per second
m Metre
MCC Mokolo Crocodile Consultants
MHz Megahertz
mm Millimetre
m/s Metres per second
m3/s Cubic metres per second
p Prototype
P Pressure
PVC-U Un-plasticised polyvinyl chloride
Q Flow rate
R Radius
Re Reynolds Number
rpm Revolutions per minute
S Submergence
Sc Critical submergence
T Time
TCTA Trans Caledon Tunnel Authority
V Velocity
VSD Variable speed drive
Stellenbosch University http://scholar.sun.ac.za
xvii
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Vt Tangential velocity
Vx Velocity in x-direction
Vy Velocity in y-direction
Vz Velocity in z-direction
W Width of the inlet channel
We Weber Number
Scale factor
% Percentage
°C Degrees Celsius
σ Surface tension of liquid
ρ Mass density of liquid
ⱱ Dynamic viscosity of liquid
Γ Circulation
ω Angular velocity
Stellenbosch University http://scholar.sun.ac.za
Page | 1
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
1. INTRODUCTION
1.1 Background to the research project
The design of pump intakes is often based on published design guidelines and empirical
formulae that were derived from physical model or scaled prototype studies. In a few instances,
designs are also based on existing pump intakes that are operating satisfactorily, provided that
similar site conditions exist.
These design guidelines and empirical formulas have specifically been developed to deal with
hydraulic phenomena that could cause problems at pump intakes, for example (Hydraulic
Institute, 1998):
Submerged vortices;
Free-surface vortices;
Uneven velocity distribution in approach channels;
Excessive pre-swirl of flow entering the pump;
Non-uniform spatial distribution of velocity at the impeller eye; and
Entrained air of gas bubbles.
The presence, duration and magnitude of the above phenomena at pump intakes could impact
negatively the operation of the pumping system and result in a reduction in pump performance
(i.e. both flow rate and pressure), excessive vibrations, increased noise and higher power
consumption.
Figure 1.1 shows a typical single pump intake with the dimension variables to design the pump
intake. Table 1.1 provides a description of each of the dimension variables and the
recommended dimensions based on the guidelines published in the American National
Standard for Pump Intake Design (Hydraulic Institute, 1998).
Stellenbosch University http://scholar.sun.ac.za
Page | 2
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 1.1: Dimension variables for pump intake (Hydraulic Institute, 1998)
Table 1.1: Recommended dimensions for pump intakes
Dimension variable Description of dimension Recommended
dimension
B Distance from the back wall to the pump
inlet centreline
B = 0.75D (1)
C Distance between the inlet bell and the floor C = 0.3D to 0.5D
D Inlet bell diameter See Note 2
Fr Froude number at suction bell -
H Minimum liquid depth H = S + C
S Minimum submergence at pump inlet bell S = 1D + 2.3Fr
W Entrance width of pump inlet bay W = 2D
X Length of pump inlet bay X = 5D minimum
(1) This recommended dimension is not achievable for suction bells fitted with bends inside the wet well.
(2) The inlet bell diameter can be determined from the following recommended velocity ranges:
a. Inlet bell velocities could range from 0.6 m/s to 2.7 m/s for flows less than 315 ℓ/s per pump;
b. Inlet bell velocities could range from 0.9 m/s to 2.4 m/s for flows exceeding 315 ℓ/s but less than
1 260 ℓ/s per pump; and
c. Inlet bell velocities could range from 1.2 m/s to 2.1 m/s for flows exceeding 1 260 ℓ/s per pump.
Stellenbosch University http://scholar.sun.ac.za
Page | 3
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The “minimum submergence at the pump inlet bell” is also referred to in the literature as “critical
submergence”, which is defined as “submergence at which, after the flow reached steady
conditions of depth and discharge, air from free-surface is ingested either continuously or
intermittently through the agency of the vortex” (Denney, 1956; cited in Rajendran & Patel,
2000).
It should be noted that, in Table 1.1, all pump intake dimensions are expressed as a function of
the inlet bell diameter, D. This ensures geometric similarity of the hydraulic boundaries and
dynamic similarity of the flow patterns.
The question that arises is – what will the impact be on the minimum submergence when any of
the recommended pump intake dimensions listed in Table 1.1 are changed?
1.2 Motivation for the study
Figure 1.2 shows the main components associated with the abstraction works proposed for the
Lower Thukela Bulk Water Supply Scheme, i.e. a weir, a boulder trap, a gravel trap, sand trap
canals and a fishway (Basson, 2011). A trash rack is provided at the inlet to the sand traps,
with the raw water pumps located at the end of the sand trap. Figure 1.3 shows the physical
model constructed for the abstraction works of the Lower Thukela Bulk Water Supply Scheme.
Figure 1.2: Proposed layout of Lower Thukela abstraction works
Gravel trap
Submerged slot
Boulder trap
Crump weir:
low notch
Fishway
Sand trap
Stellenbosch University http://scholar.sun.ac.za
Page | 4
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 1.3: Physical model of the proposed Lower Thukela abstraction works
A similar abstraction works arrangement, with six sand traps, is proposed for the river
abstraction works located at Vlieëpoort on the Crocodile River (Basson, 2010).
The sand trap canals are designed with velocities of less than 0.2 m/s at the minimum operating
level to trap sediment larger than 0.3 mm in diameter. The sand trap canals also have bed
slopes of 1:80 to allow flushing of sand and gravel under gravity by opening the downstream
gate (see Figure 1.3). Furthermore, in order to effectively flush the sand trap, the raised
downstream gate opening should be at least 1.5 m (Basson, 2010; Basson, 2011).
Dry well pump installations are proposed for both the Lower Thukela and Vlieëpoort abstraction
works. This would require the installation of a suction bell inside the sand trap canal (see
Figure 1.3). The suction bell, however, needs to be raised to not interfere with the flushing
operation and to ensure an effective gate opening of 1.5 m, as shown in Figure 1.4.
Upstream gate
Downstream gate
Suction bell
Sand trap canal
Stellenbosch University http://scholar.sun.ac.za
Page | 5
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 1.4: Proposed raised suction bell installation in sand trap canal
Table 1.2 summarises the dimensions proposed for the Lower Thukela and Vlieëpoort sand trap
canals in comparison with the dimensions recommended in the American National Standard for
Pump Intake Design (Hydraulic Institute, 1998).
It is evident from Table 1.2 that, for the Vlieëpoort and Lower Thukela sand trap canals,
dimension variables “B” and “C” are not in accordance with the dimensions recommended in the
American National Standard for Pump Intake Design (Hydraulic Institute, 1998). This leads to
the question – what impact does the raising of the suction bell have on the minimum
submergence required to prevent air entrainment? This question is the motivation for this study.
Raising the suction bell to ensure the effective flushing of the sand traps would, however, be
a deviation from the published pump design guidelines.
Stellenbosch University http://scholar.sun.ac.za
Page | 6
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 1.2: Recommended dimensions versus proposed dimensions for Vlieëpoort and Lower Thukela sand trap canals
Dimension
variable
Dimension
description
Vlieëpoort sand trap canal
(2 m3/s per pump)
Lower Thukela sand trap
canal (0.467 m3/s per
pump)
Recommended
dimension (1)
(mm)
Proposed
dimension
(2) (mm)
Recommended
dimension (1)
(mm)
Proposed
dimension
(mm)
D Inlet bell
diameter
1 500 1 200 700 700
W Entrance width
of pump inlet
bay
3 000 2 400 1400 2 000
B Distance from
the back wall to
the pump inlet
centreline
1 125 2 600 525 1 500
C Distance
between the
inlet bell and the
floor
750 1 500 350 1 500 (3)
S Minimum pump
inlet bell
submergence
2 200 2 180 1 450 1 200
(1) Recommended dimensions refer to the dimensions recommended by the Hydraulic Institute (1998).
(2) The sand trap canals were initially designed for a flow of 2.5 m3/s per pump, an inlet bell diameter of 1.4 m and a
pump inlet bay entrance width of 3.0 m. The dimensions were reduced as the design flow reduced to 2 m3/s per
pump.
(3) The initial consideration was to install the suction bell at a height of 350 mm (as reported by Basson, 2011) and
to use a guiderail system to raise the suction bell during times of flushing. This system has the risk that air could
be entrained on the suction pipework should the guiderail system malfunction. It was later decided to rather
install the suction bell at a fixed height of 1 500 mm above the floor.
Stellenbosch University http://scholar.sun.ac.za
Page | 7
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
1.3 Objective of study
The objective of the study was to determine, by means of a physical hydraulic model, the
minimum submergence levels required to prevent air entrainment for suction bell inlets located
at different heights above the canal floor. The measured submergence levels were compared
against the design guidelines that are available to calculate minimum submergence, after which
recommendations were formulated for the design criteria to be applied for raised pump intake
installations, which are similar in geometry to the physical model.
The following variables were investigated in the physical model study:
Different bell inlet heights above the floor level;
Different bell inlet velocities; and
Different bell configurations.
The physical model study did not consider aspects such as the widening or narrowing of the
sand trap canal, or velocity distributions at the impeller eye. The testing and modelling of
changes in geometry, and the determination of velocity distributions at different locations along
the pump intake, can be performed more effectively (both from a time and cost perspective) with
three-dimensional computational fluid dynamics (CFD). Such a CFD model would first have to
be calibrated against the results obtained in the physical model study. Therefore, a further
objective of the physical model study was to obtain sufficient information on velocity distributions
along the sand trap canal to assist with defining the boundary conditions, and the calibration, of
the CFD model. The calibration and application of the CFD model forms part of another study
(Hundley, 2012) and is not covered in this thesis.
1.4 Layout of the thesis
The report is structured as follows:
The methodology to achieve the study objective is described in Section 2;
Section 3 covers the literature review, which focuses on the theory and causes of vortex
formation, the possible scaling effects associated with physical hydraulic models, and the
available design standards to calculate the required submergence;
The experimental set-up, instrumentation and test procedures are described in Section 4;
The experimental test results are presented and discussed in Section 5;
Stellenbosch University http://scholar.sun.ac.za
Page | 8
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Section 6 compares the available design standards with the results obtained from the
physical model testing; and
Section 7 contains the conclusions of the study and recommendations for further work.
Stellenbosch University http://scholar.sun.ac.za
Page | 9
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
2. METHODOLOGY
2.1 Physical model study
The Hydraulic Institute (1998) recommends that physical hydraulic model studies be performed
when the sump and piping geometry deviate from published norms, as is the case with the
suction bell configurations at the Vlieëpoort and Lower Thukela abstraction works. This
recommendation is supported by Prosser (1977), who stated that the main factor influencing the
need for model testing is whether the proposed scheme varies radically from existing
satisfactory designs.
In light of the deviations from published pump intake design norms, the Trans Caledon Tunnel
Authority (TCTA) instructed Mokolo Crocodile Consultants (MCC) to undertake a physical
hydraulic model study, as well as a CFD model study, of the proposed Vlieëpoort sand trap
canals with the raised suction bells, to determine the minimum submergence required to prevent
air entrainment. MCC appointed Stellenbosch University to construct the physical model, but
the TCTA decided to postpone the laboratory testing, and subsequent design of the Vlieëpoort
abstraction scheme, due to uncertainties related to the water demands of end users, which
could vary from 1 m3/s to 2.5 m3/s per pump. The TCTA did, however, agree that the physical
model could be used by Stellenbosch University for other research projects, such as this one,
which focussed primarily on the Vlieëpoort scheme.
2.2 Modelling scenarios
The minimum submergence levels required in the sand trap canals will be the maximum water
level required to:
Prevent air entrainment due to vortex formation; or
Prevent priming problems, i.e. the minimum water level should be above the pump volute.
It should, however, be noted that, in practice, the height of the weir must not only be designed to
ensure that the minimum submergence level in the sand trap canals is achieved, but also needs
to be designed to ensure a sufficient hydraulic head across the abstraction works to flush the
boulder trap, gravel trap and sand trap canals. The latter requirement was not dealt with in this
study.
Stellenbosch University http://scholar.sun.ac.za
Page | 10
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The following variables were considered in the design of the overall study methodology and
determined the scenarios to be tested:
The height of the suction bell above the floor level to be altered to test various heights;
The flow rate to be varied from 1.0 m3/s to 2.5 m3/s per pump, or alternatively the bell inlet
velocities to be varied from 0.9 m/s to 2.4 m/s;
The preferred suction bell configuration to be determined, as Sulzer Brothers Limited (1987)
recommend the use of a slanted bell for flows exceeding 1.0 m3/s (see Figures 2.1 and 2.2
for details of different bell configurations); and
The radius of the suction pipe bend to be determined, as it determines the height of the
pump volute. Sulzer Brothers Limited (1987) recommends that the suction pipe radius
needs to be equal to or greater than 1.5 times the diameter of the suction bell.
Figure 2.1: Flat bell installation for flows ≤ 1 m3/s (Sulzer Brothers Limited, 1987)
Figure 2.2: Slanted bell installation for flows > 1 m3/s (Sulzer Brothers Limited, 1987)
Stellenbosch University http://scholar.sun.ac.za
Page | 11
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 2.1 summarises the modelling scenarios analysed, based on the variables listed above.
Table 2.1: Modelling scenarios
Suction
bell type
Radius of suction
bend (1)
Bell inlet velocities
(m/s)
Height above
canal floor
Bell type
reference (2)
Flat bell 1 x diameter of
suction pipe
0.9; 1.2; 1.5; 1.8; 2.1;
2.4
0.5D; 1.0D;
1.5D
1A
Flat bell 2 x diameter of
suction pipe
0.9; 1.2; 1.5; 1.8; 2.1;
2.4
0.5D; 1.0D;
1.5D
1B
Slanted
bell
1 x diameter of
suction pipe
0.9; 1.2; 1.5; 1.8; 2.1;
2.4
0.5D; 1.0D;
1.5D
2A
Slanted
bell
2 x diameter of
suction pipe
0.9; 1.2; 1.5; 1.8; 2.1;
2.4
0.5D; 1.0D;
1.5D
2B
(1) The radii of the bends were based on the suction pipe diameter and not the bell diameter as proposed by Sulzer
Brothers Limited (1987), as the bends are manufactured in accordance with AWWA C208 where the radius is
given as a function of the suction pipe diameter, e.g. 1d, 1.5d, 2.0d, etc., where “d” is the diameter of the suction
pipe.
(2) The bell type reference shown in the last column is used in the report to refer to the different bell configurations.
The water level at which air was entrained was established in the physical model for each of the
72 scenarios listed in Table 2.1.
The formation of vortices is unsteady and unstable, i.e. vortices form intermittently at different
locations near the pump intake and vary in strength over time. Therefore, the water levels at
which the different types of vortices form, required subjective interpretation through observation
of the predominant type of vortex present at a given water level. As these subjective
interpretations might impact on the reliability of the test results, and in order to verify the
reliability and repeatability of the tests, the tests for the two long radius (i.e. two times the
diameter of the suction pipe) inlet bells, situated 0.5D above the floor, were repeated three (3)
times for all six (6) bell inlet velocities. The decision to repeat the tests only for suction bells
located 0.5D above the floor was based on the fact that almost all conventional pump intakes
are located at this level. Table 2.2 summarises the additional tests that were performed to
validate the reliability of the test results.
Stellenbosch University http://scholar.sun.ac.za
Page | 12
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 2.2: Repeat tests performed to verify reliability of results
Suction
bell type
Radius of suction bend Bell inlet velocities (m/s) Height above
canal floor
Flat bell 2 x diameter of suction pipe 0.9; 1.2; 1.5; 1.8; 2.1; 2.4 0.5D
Slanted bell 2 x diameter of suction pipe 0.9; 1.2; 1.5; 1.8; 2.1; 2.4 0.5D
As the objective of the study was to also take sufficient velocity readings that could be used for
calibrating the CFD model, an acoustic Doppler velocimeter (ADV) was used to take three-
dimensional velocity readings at different positions and heights along the sand trap canal. The
ADV readings were only taken for the preferred inlet bell configuration at the velocities and
heights indicated in Table 2.3. The decision on the bell inlet velocities, for which ADV readings
were taken was based on the fact that the majority of pump intakes are designed for bell inlet
velocities ranging from 1.0 m/s up to 1.5 m/s. ADV readings were also taken for a bell inlet
velocity of 1.8 m/s for calibrating the CFD model for higher bell inlet velocities.
Table 2.3: ADV recording scenarios
Suction bell type Radius of suction
bend
Bell inlet velocities
(m/s)
Height above canal
floor
Preferred option Preferred option 1.2 0.5D, 1.0D, 1.5D
Preferred option Preferred option 1.8 0.5D
2.3 Criteria to decide on minimum submergence in proto-type
The minimum submergence levels required to prevent air entrainment due to vortex formation,
were determined in the physical model study for each of the four suction bell configurations
(refer to Table 2.1). A comparison was made between the results of the four suction bell
configurations to select the configuration with the lowest required submergence levels for all
velocities and heights above the canal floor.
The results of the preferred suction bell configuration were then compared against published
design guidelines that are generally used to calculate minimum submergence levels. The
published formula that best represents the experimental test results for raised pump intakes was
identified, after which recommendations were formulated on the design criteria to be applied for
the prototype design of the Vlieëpoort and Lower Thukela sand trap canals and pump intake
configurations.
Stellenbosch University http://scholar.sun.ac.za
Page | 13
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
3. LITERATURE REVIEW
The purpose of the literature review is to (a) review the causes of vortices, (b) investigate the
likely scale impacts on the formation of vortices in a physical hydraulic model, and (c) obtain
design guidelines for the calculation of critical submergence to avoid the entrainment of air.
This section of the report will therefore address:
The fundamentals and theory of vortex formation (Section 3.1);
The impact of scale effects in physical models (Section 3.2); and
The design guidelines available to calculate critical submergence (Section 3.3).
3.1 Fundamentals and theory of vortex formation
3.1.1 Introduction
Vortex formation at pump intake structures has been studied for more than 50 years. The
guidelines for the “Hydraulic Design of Pump Sumps and Intakes” were developed by the British
Hydromechanics Research Association (Prosser, 1977) and referenced research work
performed in the 1950s, e.g.:
“Studies of submergence requirements of high specific-speed pumps” (Iversen, 1953);
“Hydraulic problems encountered in intake structures of vertical wet-pit pumps and methods
leading to their solution” (Fraser and Harrison, 1953); and
“The prevention of vortices and intakes” (Denny and Young, 1957).
The three fundamental causes of vortices were defined by Durgin and Hecker (1978; cited in
Knauss, 1987) as (a) non-uniform approach flow to the pump intake due to geometric
orientation, (b) the existence of high velocity gradients, and (c) obstructions near the pump
intake.
It was further recommended by Prosser (1977) that flow approaching a pump intake that
changes from free surface to a closed conduit should be:
Uniform flow – the velocity, in magnitude and direction, of fluid particles should be the same
at all points across the section considered;
Steady flow – the velocity, in magnitude and direction, should not change with time; and
Single phase – there should be no entrained air.
Stellenbosch University http://scholar.sun.ac.za
Page | 14
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The equations used to describe the motion of vortex flow are complex, as velocities could vary
spatially (i.e. in terms of the depth and width of the approach canal) and local geometric
features could influence flow fields, which all impact on the calculation of the resulting
circulation. A simplified analytical approach was proposed by Prosser (1977) to calculate
circulation. Figure 3.1 shows a schematic representation of vortex flow that consists of a
relatively small central portion of fluid that is rotating as a highly viscous solid body (also
referred to as a “forced” vortex), combined with a non-viscous “free” vortex region extending
radially outward from this central portion.
Figure 3.1: Rankine combined vortex (Knauss, 1987)
In the central area of the vortex, the fluid is assumed to rotate so that the tangential velocity, vt,
varies linearly with the radius, r, so that
vt = ω r (3.1)
Stellenbosch University http://scholar.sun.ac.za
Page | 15
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
where
vt = tangential velocity (m/s)
ω = angular velocity in radians per unit time
r = radius (m).
In the free vortex area, the tangential velocity varies inversely with the radius and directly with
the circulation. For a circular curve of radius r, the circulation, Γ (m2/s), is expressed as,
Γ = 2 π r vt (3.2)
Figure 3.1 also shows the variation in tangential velocities between the forced and free vortex
areas, i.e. r1 is the radius at which the transition from forced to free vortex occurs.
The velocity head associated with the circulation will reduce the local hydrostatic pressure,
which will result in a localised lowering of the water surface. This drop in water surface will vary
from a surface dimple to a full air core vortex based on the strength of the circulation. The
classification of vortices is the subject of the next paragraph.
3.1.2 Vortex classification and strengths
Vortices are generally classified as (a) free surface vortices, starting from the free water surface,
or (b) sub-surface vortices, starting from the floor, side or back wall of the intake structure.
The free surface vortices, which might result in air being drawn in from the surface, could result
in unbalanced forces on the pump impeller, and vibrations that have a negative impact on the
pump performance.
The sub-surface vortices could introduce excessive swirls at the pump inlet, which could also
result in unbalanced forces on the pump impeller eye.
The Alden Research Laboratory (Hydraulic Institute, 1998) developed a visual classification
system to classify the strength of vortices. Figure 3.2 shows the strength classifications for free
surface and sub-surface vortices.
The focus of this study will be on free surface vortices, as the objective is to determine the
minimum water level required to prevent air entrainment.
Stellenbosch University http://scholar.sun.ac.za
Page | 16
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 3.2: Free surface and sub-surface vortex strength classification (Hydraulic Institute, 1998)
3.1.3 Acceptance criteria for pump intakes
The acceptance criteria for physical hydraulic model studies of pump intakes, as per the
Hydraulic Institute (1998), are:
Free surface vortices entering the pump must be less severe than Type 3, on condition that
they occur less than 10% of the time or only for infrequent pump operating conditions;
Sub-surface vortices entering the pump must be less severe than Type 2;
The average swirl angle must be less than five (5) degrees. Swirl angles of up to seven (7)
degrees will be accepted, but only if they occur less than 10% of the time; and
The time-averaged velocities at points in the throat of the bell inlet must be within 10% of the
average axial velocity in the throat of the bell inlet.
Stellenbosch University http://scholar.sun.ac.za
Page | 17
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The above acceptance criteria do not explicitly address the air-by-water volumes that could be
tolerated by pumps, if any. The following information pertaining to air-by-water volumes was
obtained from various authors:
3% free air showed a drop in hydraulic efficiency of 15% for centrifugal pumps (Prosser,
1977);
3% air-by-water volume in a suction line can considerably reduce the head-discharge curves
of centrifugal pumps (Padmanabhan & Hecker, 1984);
3 to 4% free air may give rise to a small, but continuous, decrease in pump efficiency
(Knauss, 1987);
7 to 20% free air is required before pump operations are interrupted (Knauss, 1987);
The formation of air entraining vortices upstream of the pump intake must be prevented
(Sulzer Brothers Limited, 1987); and
3 to 5% air in the suction pipe can lower the pump efficiency (Karassik, Messina, Cooper, &
Heald, 2001).
Based on the above statements by Prosser and Sulzer Brothers Limited, as well as the
Hydraulic Institute’s acceptance criteria to not permit free surface vortices exceeding Type 3 in
strength, it is recommended that the critical submergence levels be determined in the physical
model as the level at which no air entrainment will take place.
3.1.4 Dimensionless parameters
In order to apply the results of the physical model to the prototype, dimensionless parameters
are used to define the complex interaction between the geometry of the intake structure, the
flow velocity and the liquid properties which all influence the critical submergence. The
following dimensionless parameters were proposed by different authors to describe the motion
of vortex flow:
Jain, Raju, & Garde (1978) proposed the following functional relationship for critical
submergence, which is defined as the water level required above the inlet of the bell to maintain
the circulation within acceptable limits:
Scr = f(W, D, Q, Γ, g, ρ, σ, ν) (3.3)
with Scr = critical submergence (m)
Stellenbosch University http://scholar.sun.ac.za
Page | 18
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
W = width of the inlet channel or diameter of the vortex tank (m)
D = diameter of the inlet bell (m)
Q = flow rate (m3/s)
Γ = circulation of flow (2πrVt) (m2/s)
g = gravitational acceleration (m/s2)
ρ = mass density of liquid (kg/m3)
σ = surface tension of liquid (N/m)
ⱱ = dynamic viscosity of liquid (m2/s).
A typical single pump intake configuration is shown in Figure 1.1 and includes the critical
parameters.
Equation 3.3 was re-written, by means of dimensional analysis and the re-grouping of
parameters, as:
√
(3.4)
With Q = πd2/4, it is possible to re-write Equation 3.4 as follows:
√
(3.5)
The first, third and fourth terms of Equation 3.5 represent the Reynolds, Froude and Weber
Numbers.
Anwar, Weller & Amphlett (1978) proposed the following relationship between the six
independent non-dimensional parameters that could be used to describe the formation of
vortices at horizontal pump intakes:
(
√
) (3.6)
Stellenbosch University http://scholar.sun.ac.za
Page | 19
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
with C = distance from the floor to the underside of the inlet bell (m)
A = cross-sectional area of the inlet bell (m2)
S = submergence depth above intake (m).
Equation 3.6 was re-written in the following form:
(
) (3.7)
with Cd = discharge coefficient
Re =
We = √
Knauss (1987) stated that critical submergence could be expressed by:
Scr = f(V, d, D, R, C, Γ, g, ρ, σ, ν) (3.8)
with V = average velocity at the inlet to the suction bell (m/s)
d = suction pipe diameter (m)
R = radius of rounding of the bellmouth entry (m).
Equation 3.8 was re-written, by means of dimensional analysis, as:
√ √
(3.9)
The three last terms of Equation 3.9 represent the Froude, Weber and Reynolds Numbers.
The Hydraulic Institute (1998) stated that, based on previous research, it can be concluded that
the flow conditions at a pump intake are represented by the following dimensionless
parameters:
Stellenbosch University http://scholar.sun.ac.za
Page | 20
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
√
(3.10)
It is evident that Froude, Reynolds and Weber Numbers need to be considered in physical
model studies of pump intakes. The approach flow pattern in the vicinity of the sump governs
the circulation, Γ. It can be accepted that circulation would be similar between the prototype
and scaled model provided that the approach flow patterns are similar. The relevance and
influence of these dimensionless parameters in physical model studies are considered in
Section 3.2.
3.2 Impacts of scale effects in physical models
3.2.1 Physical similarity
It is usually not financially viable to construct physical models of a pump intake at the full-scale
of the system. Physical models, constructed at a smaller scale than the full-scale system, are
therefore used to examine critical aspects that could influence the performance of the system.
The laws of similitude make it possible to relate the results obtained with the model to the
performance of the prototype. It is not possible, however, to satisfy all the laws of similitude
simultaneously, which results in discrepancies between the performance of the model and that
of the prototype. This is known as the “scale effect” (Webber, 1979).
“Physical similarity” is a generic term used to describe different types of similarity, e.g.
geometric, kinematic and dynamic similarity. These three types of similarity are discussed in
more detail below.
Geometric similarity
Geometric similarity is similarity of shape, which means that the model and prototype are
identical in shape but differ in size. The ratio of any two dimensions in the model therefore
corresponds to the ratio in the prototype, as shown in Equation 3.11.
(3.11)
with L = a linear dimension
m = model
Stellenbosch University http://scholar.sun.ac.za
Page | 21
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
p = prototype.
The “scale factor” is generally defined as the ratio between a linear dimension in the prototype
and the corresponding dimension in the model. If the linear scale of the model is 1:x, the scalar
relationship for area is 1:x2 and for volume it is 1:x3 (Webber, 1979).
It is not always possible to achieve complete geometric similarity, especially in respect of
surface roughness. The hydraulic behaviour arising from the boundary conditions is, however,
the more important factor and dissimilar geometry is therefore often acceptable (Massey, 1989).
Kinematic similarity
Kinematic similarity is similarity of motion, which implies similarity in geometry, time intervals,
velocity and acceleration (Massey, 1989), meaning that the following ratios will apply between
the model and the prototype (Webber, 1979):
and
(3.12)
with v = velocity
a = acceleration.
Fluid motions that are kinematically similar form streamlines that are geometrically similar at
corresponding times.
Dynamic similarity
Dynamic similarity is similarity of forces. If two systems are dynamically similar, the magnitude
of forces at similarly located points in the model and prototype systems must be in the same
ratio and act in the same direction. The following ratios apply between dynamically similar
models and prototypes:
(3.13)
with F = force
Stellenbosch University http://scholar.sun.ac.za
Page | 22
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The forces in a system involving fluids could be due to pressure, gravity, viscosity or surface
tension. The conditions for dynamic similarity can be expressed as (Webber, 1979):
(3.14)
with Fp = force due to pressure
Fg = force due to gravity
Fν = force due to viscosity
Fst = force due to surface tension.
Perfect dynamic similarity implies that all the ratios between all the forces remain fixed. This is,
however, not the case, as the presence and significance of the various forces differ for different
hydraulic structures. It therefore is important to ensure dynamic similarity of the dominant
forces present in the model and prototype under consideration.
3.2.2 Similarity laws
The similarity laws that could be applicable to hydraulic model studies are discussed below.
Euler Law
The Euler number describes the relationship between pressure and velocity and can be
expressed as:
√
(3.15)
with E = Euler Number
V = velocity
∆p = change in pressure
ρ = density of liquid.
Stellenbosch University http://scholar.sun.ac.za
Page | 23
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The Euler Law is relevant to enclosed fluid systems where the forces of gravity and surface
tension are absent.
Froude Law
The Froude Law is applicable to systems where gravity is the significant force that influences
the fluid motion. Systems with free surfaces, e.g. weirs, open channels, spillways and rivers,
are typical examples where gravity is the dominant force.
The Froude number is expressed as:
√ (3.16)
with Fr = Froude Number
V = velocity
g = gravitational acceleration
L = characteristic length, e.g. pipe diameter in the case of flow in a pipe.
For compliance with the Froude Law, the corresponding velocities must satisfy Equation 3.17.
(3.17)
with = scale factor.
Reynolds Law
The Reynolds Law is applicable to systems where only the forces of viscosity and inertia are
present. An example is a submarine submerged deep enough not to create any waves on the
surface.
The Reynolds Number is expressed as:
(3.18)
Stellenbosch University http://scholar.sun.ac.za
Page | 24
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
with Re = Reynolds Number
V = velocity
L = length
= viscosity of liquid.
For compliance with the Reynolds Law, the corresponding velocities must satisfy Equation 3.19:
(3.19)
with = scale factor.
Weber Law
The Weber Law describes the relationship between surface tension and velocity. Surface
tension is very seldom a significant force, but could become a factor where there is an air-water
interface in a structure with small dimensions.
The Weber number is expressed as:
√
(3.20)
with We = Weber Number
V = velocity
σ = surface tension of liquid
ρ = density of liquid
L = length.
Compliance with the Weber Law is achieved when velocities correspond to Equation 3.21:
Stellenbosch University http://scholar.sun.ac.za
Page | 25
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
(3.21)
with = scale factor.
Based on Equation 3.21 it can be derived that for the same fluid in the model and prototype, the
model velocity should be x0.5 times that in the prototype.
Mach Law
The Mach Law describes the relationship between elastic forces and velocity, and is applicable
to systems where the compressibility of the fluid is of importance (Massey, 1989).
The Mach number can be expressed as:
(3.22)
with = Mach Number
V = velocity
C = acoustic velocity in liquid medium
The velocity, flow and time scales for a model based on Froude scaling, can be calculated as
follows (Hydraulic Institute, 1998):
(3.23)
(3.24)
The model for the study of the Vlieëpoort pump intake is an open channel with a free surface.
Gravitational forces are the dominant forces and the Froude Law will be the criterion to be
satisfied. It will, however, be important to ensure sufficiently high Reynolds and Weber
Numbers to mitigate the potential scale effects due to viscosity and surface tension. The
Euler and Mach Laws are not relevant when performing physical model studies on pump
intake channels.
Stellenbosch University http://scholar.sun.ac.za
Page | 26
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
(3.25)
with Lr = geometric scale
m = model
p = prototype
V = velocity
Q = flow
T = time.
3.2.3 Modelling criteria
Minimum Reynolds and Weber Numbers
The following is a summary of minimum Reynolds and Weber Numbers, recommended by
various authors, to minimise the viscous and surface tension effects for physical models based
on Froude similarity:
Jain et al. (1978) indicated that Reynolds and Weber Numbers of 5 x 104 and 120 would be
required as minimum values;
Daggett and Keulegan (1974; cited in Padmanabhan & Hecker, 1984) found that the viscous
effects on vortex formation would be negligible if the Reynolds Number was greater than
3 x 104;
Zielinksi and Villemonte (1968; cited in Padmanabhan & Hecker, 1984) concluded on the
basis of experiments that viscous effects would be negligible for Reynolds Numbers greater
than 1 x 104;
Padmanabhan and Hecker (1984) concluded from their model testing that full-scale inlet
losses were predicted accurately by the reduced scale models for Reynolds Numbers of
1 x 105 or greater;
The Hydraulic Institute (1998) recommended that model studies be performed with Reynolds
and Weber Numbers of 6 x 104 and 240, respectively, which include a 2.0 factor of safety on
the Reynolds Number recommended by Daggett and Keulegan (1974; cited in
Padmanabhan & Hecker, 1984) and the Weber Number recommended by Jain (1978);
Stellenbosch University http://scholar.sun.ac.za
Page | 27
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Jones, Sanks, Tchobanoglous and Bosserman (2008) recommend minimum Reynolds and
Weber Numbers of 3 x 104 and 120 respectively; and
Ahmad, Jain and Mittal (2011) selected the model geometric scale to ensure that minimum
Reynolds and Weber Numbers of 6 x 104 and 240 are achieved at the bell entrance.
The above Reynolds and Weber Numbers refer to those at the bell entrance.
Based on the above information, it is recommended that the minimum Reynolds and Weber
Numbers should be 3 x 104 and 120, respectively, but that where feasible, these Numbers
should be increased to 6 x 104 and 240.
Scales of other physical model studies
The following is a summary of scales used in other physical model studies or recommended for
model studies:
Anwar, Weller and Amphlett (1978; cited in Knauss, 1987) suggested a model scale of not
less than 1:20 to reproduce vortex formation;
Prosser (1977) recommended scales varying from 1:4 to 1:25 for sump models;
A study by Dhillon (1979; cited in Hecker, 1981) indicated good model-prototype agreement
of vortex strength for a 1:20 scale model that was operated on Froude similarity;
A comparison between model-prototype vortex formation was undertaken by Hecker (1981)
on 22 projects with model scales varying from 1:12 to 1:120. It was found that, in 16
projects, the model and prototype vortices were essentially equal, whereas five (5) projects
indicated that the prototype vortices were stronger than that in the model, and only one (1)
study indicated prototype vortices that were weaker than in the model;
A model study by Arboleda and El-Fadel (1996) to evaluate the impact of approach flow
conditions on pump sump design was undertaken at a scale of 1:18;
Ansar and Nakato (2001) undertook a model study at a scale of 1:10 to investigate the
impacts of cross flow on pump intakes; and
Ahmad et al. (2011) used a 1:10 scale to model a pump sump with five cooling water pumps
and three auxiliary cooling water pumps.
It is evident that the above authors recommend scales not exceeding 1:20 for physical model
studies of pump intakes that are based on Froude similarity.
Stellenbosch University http://scholar.sun.ac.za
Page | 28
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
3.2.4 Scale of proposed physical model
The prototype dimensions of the Vlieëpoort pump intake are shown in Table 1.2. It was stated
by the TCTA that the design flow per sand trap canal might be as little 1.0 m3/s and as high as
2.5 m3/s, which will result in prototype bell inlet velocities of 0.88 m/s and 2.21 m/s respectively
for an inlet bell with a diameter of 1 200 mm.
It follows that the scale that has to be selected to model prototype bell inlet velocities ranging
from 0.9 m/s up to 2.2 m/s still has to meet the minimum Reynolds and Weber Numbers for
Froude based models. Table 3.1 summarises the prototype information and scale effects
based on a model with a scale of 1:10. The velocities and flows were scaled in accordance with
Equations 3.23 and 3.24.
It is evident from Table 3.1 that the minimum scaled Reynolds and Weber Numbers will be
3.4 x 104 and 133 respectively for a prototype bell inlet velocity of 0.9 m/s. The Reynolds and
Weber Numbers will increase to 9.1 x 104 and 947, respectively, for a prototype bell inlet
velocity of 2.4 m/s.
A scale of 1:10 therefore will satisfy the minimum recommended Reynolds and Weber
Numbers of 3 x 104 and 120 applicable to physical model studies based on Froude
similarity.
Stellenbosch University http://scholar.sun.ac.za
Page | 29
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 3.1: Prototype information and scale effects
Description Prototype bell
inlet velocity =
0.9 m/s
Prototype bell
inlet velocity =
1.2 m/s
Prototype bell
inlet velocity =
1.5 m/s
Prototype bell
inlet velocity =
1.8 m/s
Prototype bell
inlet velocity =
2.1 m/s
Prototype bell
inlet velocity =
2.4 m/s
P M P M P M P M P M P M
Flow
(P = m3/s)
(M = ℓ/s)
1.02 3.22 1.36 4.29 1.70 5.36 2.04 6.44 2.37 7.51 2.71 8.58
Bell inlet
velocity (m/s) 0.90 0.28 1.20 0.38 1.50 0.47 1.80 0.57 2.10 0.66 2.40 0.76
Froude
number 0.262 0.262 0.350 0.350 0.437 0.437 0.524 0.524 0.612 0.612 0.699 0.699
Reynolds
number
1.1.E+06 3.4.E+04 1.4.E+06 4.6.E+04 1.8.E+06 5.7.E+04 2.2.E+06 6.8.E+04 2.5.E+06 8.0.E+04 2.9.E+06 9.1.E+04
Weber
number 13 318 133 23 665 237 36 966 370 53 221 532 72 429 724 94 661 947
P = prototype
M = model
Stellenbosch University http://scholar.sun.ac.za
Page | 30
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
3.3 Design guidelines to calculated critical submergence
Various design guidelines have been published for the calculation of critical submergence. This
paragraph summarises the critical submergence requirements as proposed by different authors.
Aspects such as approach flow velocities and suction pipework velocities are also addressed for
completeness. The various guidelines discussed in the sub-sections below are compared in
Figure 3.3.
3.3.1 The hydraulic design of pump sumps and intakes (Prosser, 1977)
Approach flow to inlet bell ≤ 0.3 m/s;
Critical submergence, S ≥ 1.5D (D = inlet bell diameter). The recommended mean velocity
at the inlet bell is 1.3 m/s; and
Velocity in suction pipework ≤ 4 m/s.
3.3.2 Centrifugal pump handbook (Sulzer Brothers Limited, 1987)
Approach flow to inlet bell ≤ 0.3 m/s;
Critical submergence, S ≥ 1.5D (D = inlet bell diameter). The recommended maximum
velocity at the inlet bell is 1.3 m/s; and
Velocity in suction pipework ≤ 4 m/s.
3.3.3 Pump intake design (Hydraulic Institute, 1998)
Approach flow to inlet bell ≤ 0.5 m/s;
Critical submergence, S = D(1 + 2.3 Fr). The acceptable inlet bell velocities for a pump flow
exceeding 1 260 ℓ/s ranges from 1.2 m/s to 2.1 m/s, with a recommended inlet bell velocity
of 1.7 m/s; and
Velocity in suction pipework ≤ 2.4 m/s.
3.3.4 Pump station design (Jones et al., 2008)
Approach flow to inlet bell ≤ 0.3 m/s;
Critical submergence, S = D(1 + 2.3 Fr). The maximum allowable velocity at the inlet bell is
1.5 m/s, with 1.1 to 1.2 m/s recommended as the optimum bell intake velocity; and
Velocity in suction pipework ≤ 2.4 m/s.
Stellenbosch University http://scholar.sun.ac.za
Page | 31
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
3.3.5 Pump handbook (Karassik et al., 2001)
Approach flow to inlet bell ≤ 0.4 m/s;
Critical submergence, S = D(1 + 2.3 Fr). It is recommended that inlet bell velocities be
related to the pumping head as follow:
o Vbell ≤ 0.76 m/s for pumping heads up to 5 m (i.e. 15 feet);
o Vbell ≤ 1.20 m/s for pumping heads up to 15 m (i.e. 50 feet);
o Vbell ≤ 1.70 m/s for pumping heads greater than 15 m; and
Velocity in suction pipework ≤ 2.4 m/s.
The reason for linking the pumping head to the maximum allowable bell inlet velocities is to
prevent the velocity head loss at the bell inlet to be a large percentage of the total pumping
head.
3.3.6 Swirling flow problems at intakes (Knauss, 1987)
Approach flow to inlet bell ≤ 0.3 m/s;
Critical submergence:
o S = D(1.5 + 2.5 Fr) was proposed by Paterson and Noble (1982);
o S = D(1 + 2.3 Fr) was proposed by Hecker (Knauss, 1987);
o S = D(0.5 + 2.0 Fr) was proposed by Knauss (1987);
o S ≤ 1.5D was proposed by Prosser (1977); and
Velocity in suction pipework ≤ 4 m/s.
No recommendation was made by Knauss on the formula to be used for calculating critical
submergence, nor were any guidelines provided for allowable bell inlet velocities. Knauss did,
however, refer to the guidelines recommended by Prosser (1977) for approach and suction
pipework velocities.
3.3.7 Gorman-Rupp design guidelines (Strydom, 2010b)
It is proposed by Gorman-Rupp that critical submergence be determined as per the data
presented in Table 3.2.
Stellenbosch University http://scholar.sun.ac.za
Page | 32
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 3.2: Critical submergence recommended by Gorman-Rupp
Bell inlet velocity (m/s) Critical submergence (m)
0.5 0.35
1.0 0.55
1.5 0.80
2.0 1.15
2.5 1.50
3.0 2.00
3.3.8 KSB design guidelines (Gouws, 2010)
KSB proposes that the critical submergence be determined as per the data presented in
Table 3.3. It should be noted that the critical submergence is for pump intakes with an open
feed in the vicinity of the pump intake.
Table 3.3: Critical submergence recommended by KSB
Bell inlet velocity (m/s) Critical submergence (m)
0.5 0.3
1.0 0.5
2.0 1.2
3.0 2.1
3.3.9 Collection and pumping of wastewater (Metcalf and Eddy, 1981, provided by
Strydom, 2010a)
It is proposed by Metcalf and Eddy that critical submergence is determined as per the data
presented in Table 3.4.
Stellenbosch University http://scholar.sun.ac.za
Page | 33
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 3.4: Critical submergence recommended by Metcalf and Eddy (1981)
Bell inlet velocity (m/s) Critical submergence (m)
0.6 0.3
1.0 0.6
1.5 1.0
1.8 1.4
2.1 1.7
2.4 2.15
2.7 2.6
3.3.10 Design recommendations for pumping stations with dry installed submersible
pumps (Flygt, 2002)
Critical submergence, S = 1.7Fr on condition of this being larger than 1.75D. The
acceptable inlet bell velocities for a pump flow exceeding 1 200 ℓ/s range from 1.2 m/s to
2.1 m/s, with a recommended inlet bell velocity of 1.7 m/s.
3.3.11 Werth and Frizzell (2009)
Critical submergence, S = D(2.1 + 1.33Fr0.67)
This equation was developed for pump intakes situated at the end of large reservoirs, which
implies very low approach velocities, and for water levels where no Type 3 vortices (i.e.
coherent dye core) are present.
Figure 3.3 provides a graphical presentation on the equations proposed by the different authors
to calculate critical submergence for a 1.2 m diameter inlet bell and a range of inlet bell
velocities.
The critical submergence presented in Figure 3.3 was used to calculate approach velocities,
assuming a sand trap canal width of 2.4 m (i.e. 2D). The approach velocities are plotted against
the bell intake velocities and are presented in Figure 3.4.
Stellenbosch University http://scholar.sun.ac.za
Page | 34
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 3.3: Critical submergence versus bell inlet velocity
Figure 3.4: Approach velocities versus bell inlet velocity
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00
Cri
tica
l su
bm
erge
nce
(m
)
Bell inlet velocity (m/s)
Critical submergence versus bell inlet velocity
1. Prosser & Sulzer 2. Hydraulic institute & Jones 3. Peterson and Noble
4. Knauss 5. Gorman Rupp 6. KSB
7. Metcalf & Eddy 8. Flygt 9. D Werth
1
23
4 56
7
8
9
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00
Ap
pro
ach
vel
oci
ty (
m/s
)
Bell inlet velocity (m/s)
Approach velocity versus bell inlet velocity
1. Prosser & Sulzer 2. Hydraulic institute & Jones 3. Peterson and Noble
4. Knauss 5. Gorman Rupp 6. KSB
7. Metcalf & Eddy 8. Flygt 9. D Werth
1
23
4
56
7
8
9
Stellenbosch University http://scholar.sun.ac.za
Page | 35
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from Figures 3.3 and 3.4 that:
Large variations exist between the critical submergence recommended by the different
authors. The critical submergence proposed by KSB, Flygt, and Metcalf and Eddy is much
lower compared to that proposed by the other authors (e.g. the critical submergence
required for a bell inlet velocity of 1.5 m/s is 1.0 m according to Metcalf and Eddy, compared
to 2.4 m recommended by the Hydraulic Institute);
The approach velocities, for the critical submergence requirements proposed by KSB, Flygt,
and Metcalf and Eddy exceed 0.5 m/s for all bell inlet velocities, yet they are proposing the
lowest critical submergence levels of all the authors. The high approach velocities are
possibly related to wastewater applications, which require higher approach velocities to keep
solids in suspension. Irrespective of the reason for the higher approach velocities, this
seems like a contradiction, as it would be expected that critical submergence would increase
as the approach flow velocity increases; and
All the authors, apart from KSB, Flygt, and Metcalf and Eddy, propose limiting approach
velocities:
o Prosser recommended an optimum bell inlet velocity of 1.3 m/s, which corresponds
to an approach velocity of 0.3 m/s;
o Sulzer Brothers Limited recommended a maximum bell inlet velocity of 1.3 m/s,
which corresponds to an approach velocity of 0.3 m/s;
o The Hydraulic Institute stated that the maximum inlet velocity for flows exceeding
1 260 ℓ/s should be limited to 2.1 m/s, which corresponds to an approach velocity of
less than 0.5 m/s; and
o The equation proposed by Knauss will result in an approach velocity of less than
0.5 m/s for bell inlet velocities lower than 2.4 m/s.
The experimental test results of the preferred suction bell configuration were compared with the
above published design guidelines for the calculation of minimum submergence levels, in order
to determine which equation or guideline should be used for raised pump intake configurations.
Stellenbosch University http://scholar.sun.ac.za
Page | 36
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
4. EXPERIMENTAL SET-UP AND TEST PROCEDURES
4.1 Experimental set-up
A 1:10 geometric scale was chosen for the physical model study as it satisfies the minimum
Reynolds (i.e. 3 x 104) and Weber (i.e. 120) Numbers to ensure that the effects of viscosity and
surface tension could be neglected for the range of inlet bell velocities to be tested.
Figures 4.1 and 4.2 show a plan and sectional view, respectively, of the scale model based on
the prototype dimensions of the Vlieëpoort sand trap canal (see Table 1.2).
Figure 4.1: Plan view of physical model
Figure 4.2: Sectional view of physical model
The model consisted of a stilling basin, an approach canal, a suction bell and pipework, a pump
and the delivery pipework.
Stellenbosch University http://scholar.sun.ac.za
Page | 37
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The stilling basin, 750 mm wide x 750 mm long x 1 540 mm high, was connected to the 240 mm
wide approach canal with a 340 x 240 mm reducer, 200 mm long. Small pipes, 32 mm in
diameter and 300 mm long, were placed 3 000 mm away from the end of the canal as flow
straighteners.
The canal was 240 mm wide, 1 000 mm high and 4 000 mm long. The sides and bottom of the
canal were constructed from glass panels to allow visualisation of the vortex formation and flow
patterns. The front end of the canal was constructed as an adjustable steel sluice to raise and
lower the suction bell.
The inlet bell diameter was 120 mm. The diameter of the suction pipework was 100 mm, which
was reduced to 65 mm at the pump’s suction flange by means of a 200 mm long eccentric
reducer. The inlet bell and suction pipework were constructed from perspex to allow
visualisation of the vortex formation inside the suction bell and pipework.
A Lowara FHS 450-160 centrifugal end-suction pump, operating at 1 450 rpm, and fitted with an
impeller with a diameter of 174 mm, was installed. A WEG variable speed drive was connected
to the 1.1 kW electric pump motor to alter the pump speed. It has been stated by Karassik et al.
(2001) that vortices are not generated by pumps or pump impellers and that vortices, whether
falling into clockwise or anticlockwise rotation, are not influenced by the pump rotation.
The discharge pipework was constructed from 50 mm diameter HDPE and PVC-U pipes. A
20 mm diameter off-take was located on the discharge pipework, which was used to drain the
water from the canal. A 50 mm diameter Endress & Hauser magnetic flow meter was installed
on the discharge pipeline. The 50 mm diameter discharge pipeline terminated in the stilling
basin situated at the head of the approach canal.
Photographs of the model are shown in Figures 4.3 and 4.4.
As stated in Section 2.2, four suction bell configurations were tested. The dimensions of the
four suction bell configurations are shown in Figure 4.5. The dimensions are in accordance
with the American Water Works Association (1983) guidelines entitled “Dimensions for
fabricated steel water pipe fittings”.
Stellenbosch University http://scholar.sun.ac.za
Page | 38
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 4.3: View of pump model
Figure 4.4: View of stilling basin and flow straightener pipes
Stellenbosch University http://scholar.sun.ac.za
Page | 39
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 4.5: Dimensions of suction bell configurations
Stellenbosch University http://scholar.sun.ac.za
Page | 40
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Photographs of the manufactured suction bells are shown in Figures 4.6 and 4.7.
Figure 4.6: Rear view of suction bell configurations (from left to right: Type 1B, Type 1A, Type 2B, Type 2A)
Figure 4.7: Side view of suction bell configurations (from left to right: Type 2A, Type 2B, Type 1A, Type 1B)
Stellenbosch University http://scholar.sun.ac.za
Page | 41
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
4.2 Instrumentation
The following equipment was used to record flow, pump speed and velocities:
An Endress & Hauser magnetic flow meter was used to measure the flow rate in ℓ/s;
The frequency (in Hertz) was displayed on the WEG variable speed drive; and
Velocities in the approach canal were measured with a Vectrino 25 MHz acoustic Doppler
velocimeter (ADV). A downward-facing probe was used to measure the three-dimensional
velocities. The instrument was mounted on a free-standing frame to avoid any interference
that might be caused by the pump. Table 4.1 summarises the configuration set-up used for
this project.
Table 4.1: Configuration set-up of ADV instrument
Description Unit Setting
Sampling rate Hz 25
Nominal velocity range (1) m/s ± 0.3
Sampling volume mm 1.8
Transmit pulse length mm 7
(1) The nominal velocity range is set to cover the range of the velocities anticipated during the data collection. The
available nominal velocity range settings were 0.01 m/s, 0.1 m/s, 0.3 m/s, 1.0 m/s, 2.0 m/s and 4 m/s.
Photographs of the ADV support frame and the Vectrino instrument are shown in Figures 4.8
and 4.9, respectively.
Stellenbosch University http://scholar.sun.ac.za
Page | 42
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 4.8: ADV support frame
Figure 4.9: Vectrino instrument
4.3 Test procedure
4.3.1 Submergence for different types of vortices
This section provides a step-by-step description of the test procedures followed during the
laboratory testing.
Stellenbosch University http://scholar.sun.ac.za
Page | 43
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The objective was to determine the minimum water level at which no air entrainment occurs,
which corresponds to a Type 5 vortex (refer to Figure 3.2 for the strength classification of
vortices). The acceptance criteria for physical hydraulic model studies of pump intakes
(Hydraulic Institute, 1998), however, requires that free surface vortices entering the pump must
be less severe than Type 3 and should occur less than 10% of the time.
Type 3 vortices are classified as “coherent dye core” vortices, which require the injection of dye
to identify their presence. Vortices, however, vary in strength and duration over time for a given
water level and flow, making it difficult to inject the dye at the correct position and time. It
therefore was decided to rather compare the submergence levels for the four different pump
intake configurations on the types of vortices that can be determined more easily by visual
assessment, and that dye injection should only be done for the preferred pump intake
configuration to determine the water level at which Type 3 vortices occur.
The types of vortices that are the easiest to observe visually are:
Type 2 (surface dimple);
Type 5 (vortex pulling air bubbles to intake); and
Type 6 (full air core to intake).
The water level at which Type 1 vortices (i.e. a surface swirl) occur was not recorded, as
surface swirls were often caused by break-away actions from the suction pipework, especially at
higher approach velocities. The Type 4 vortices (i.e. pulling floating debris to intake) were also
not measured, as no clear guidelines were available in the literature on what constitutes
“floating debris” in terms of size, weight and density. Furthermore, the addition of floating debris
might affect the surface tension. It therefore was decided to record the water levels of Type 2, 5
and 6 vortices as these would be the least subjective.
Figure 4.10 presents a flow diagram that graphically represents the test procedure used to
determine the water levels of the Type 2, 5 and 6 vortices.
Stellenbosch University http://scholar.sun.ac.za
Page | 44
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 4.10: Flow diagram of test procedure
Stellenbosch University http://scholar.sun.ac.za
Page | 45
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is shown in Figure 4.10 that the frequency of the different types of vortices was monitored for
10 minutes at a fixed water level. The 10 minutes represent approximately 32 minutes in a
prototype model, based on Equation 3.25. The minimum time over which observations should
be made in scaled models was recommended as five minutes and 10 minutes by Prosser
(1977) and the Hydraulic Institute (1998), respectively.
It was also decided to follow a methodology whereby the Type 2, 5 and 6 water levels were
determined for one velocity, after which the tests were repeated for the next velocity, compared
to starting at the highest velocity and determining all the Type 2 water levels for the different
velocities by reducing the pump speed and water level, followed by determining all the Type 5
water levels for the different velocities, etc. The main reasons for the approach shown in
Figure 4.10 were to:
Ensure that water levels were tested independently to record any possible anomalies, i.e.
the Type 2 water level at a flow of 4.29 ℓ/s might be higher than that for a flow of 6.44 ℓ/s,
which would be missed with the latter approach; and
Maintain a constant water temperature, i.e. testing started at the lowest velocity and needed
to be raised from the Type 6 level to 100 mm above the recorded Type 2 level, after which
testing for the next velocity commenced.
Once all bell inlet velocities had been tested for a specific suction bell configuration, the bell was
raised to the next level, after which all the tests were repeated.
4.3.2 Dye injection tests
The experimental results obtained for the four suction bell configurations were compared
against one another to determine which of the four bell configurations had the lowest critical
submergence requirements. Dye injection tests were then performed for the preferred suction
bell configuration to determine the water level at which Type 3 vortices occur.
The procedures followed with the dye injection tests are detailed below:
Step 1: Change the VSD to achieve a flow of 3.22 ℓ/s at the water level recorded for a
Type 2 vortex.
Step 2: Sprinkle cinnamon on the water surface while lowering the water level. Stop the
draining of water at the first sign of cinnamon being pulled below the water surface.
Stellenbosch University http://scholar.sun.ac.za
Page | 46
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Step 3: Monitor the frequency of vortices that pull the cinnamon below the water surface. If
this occurs more than three (3) times in five (5) minutes, inject dye at the location where the
vortex forms. Repeat the dye injection each time a vortex forms for a duration of five (5)
minutes. If no coherent dye core vortex is visible during this time, lower the water level by
10 mm and repeat this step until a coherent dye core vortex becomes visible. Record the
water level at which the Type 3 vortex occurs.
Step 4: Fill the canal to the water level recorded for a Type 2 vortex at a flow of 4.29 ℓ/s.
Amend the pump speed on the VSD to achieve this higher flow and repeat Steps 1 to 3.
Repeat this procedure for all the other flows.
It was found that the above test procedure was not practical, as the cinnamon was only pulled
below the water surface at water levels slightly higher than those measured for Type 5 vortices.
It therefore is likely that the water levels at which the cinnamon was pulled below the water
surface represent Type 4 vortices. The test procedure was then amended as follows:
Step 1: Change the VSD to achieve a flow of 3.22 ℓ/s at the water level recorded for a
Type 2 vortex.
Step 2: Inject dye at the surface dimple when it forms. If no coherent dye core is visible,
lower the water level by 5 mm and repeat this until a coherent dye core vortex becomes
visible. Record the water level at which the Type 3 vortex occurs.
Step 3: Fill the canal to the water level recorded for a Type 2 vortex at a flow of 4.29 ℓ/s.
Amend the pump speed on the VSD to achieve this higher flow and repeat Steps 1 and 2.
Repeat this procedure for all the other flows.
This test procedure was also found to be impractical. At the Type 2 water levels, the dye would
disperse with no sign of any coherent dye core vortices. This phenomenon continued to occur
as the water level was lowered to a point where the dye was suddenly pulled from the water
surface into the suction bell, i.e. this occurred when injecting the dye just upstream of the
suction bell with no signs of surface dimples or depressions being present. This is
demonstrated by the series of photos shown in Figure 4.11, where dye was injected upstream
of the suction bell at the location where a Type 2 vortex was busy forming.
Stellenbosch University http://scholar.sun.ac.za
Page | 47
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
(a)
(b)
(c)
(d)
Figure 4.11: Path of dye injected upstream of suction bell
Stellenbosch University http://scholar.sun.ac.za
Page | 48
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It was further noted that, when injecting dye at the location where the surface dimple started, a
vortex with a dye core was starting to form, but that the vortex moved to the back of the canal
(see Figure 4.12) (mainly caused by the approach velocity in the canal), with the dye core never
reaching the inlet to the suction bell, as the vortex strength reduced as it moved away from the
suction bell.
Figure 4.12: Evidence of a coherent dye core behind the suction bell
The results obtained from the dye injection were therefore inconclusive and it was decided that
these results would not be used for further analyses. It is expected that the use of dye injection
would be practical only if the tests are conducted with very low approach velocities (i.e.
prototype approach velocities of less than 0.2 to 0.3 m/s and where the pump intake is situated
in a large reservoir where the velocities at the inlet bell are distributed more evenly compared to
the distribution expected for a pump intake situated in a canal.
4.3.3 ADV measurements
It is also an acceptance criterion (Hydraulic Institute, 1998) that the time-averaged velocities at
points in the throat of the bell inlet must be within 10% of the average axial velocity. In order to
verify whether this criterion would be met for the Type 2 water levels, acoustic Doppler
velocimeter (ADV) readings were taken at the five positions indicated in Figure 4.13. The ADV
measurements were taken only for the preferred inlet bell configuration, located at 0.5D above
the canal floor, but for all six velocities.
Stellenbosch University http://scholar.sun.ac.za
Page | 49
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 4.13: Positions of ADV measurements at inlet bell
The ADV instrument was set to record samples at a frequency of 25 Hz, i.e. every 0.04
seconds. The accuracy of the ADV measurements was influenced by the amount of particles in
the water, which required the addition of fine sand particles to the potable water used in the
model. This influenced the sampling period, as the sand particles settled out at low approach
canal velocities, causing larger fluctuations in the measurements towards the end of the
sampling period. It was found that the sampling time varied from 30 seconds (i.e. 750 samples)
up to 60 seconds (i.e. 1 500 samples) before the measurements became unstable.
Stellenbosch University http://scholar.sun.ac.za
Page | 50
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The ADV instrument recorded velocities in the X, Y and Z direction. Figure 4.14 shows the XYZ
coordinate system, with the X-axis being parallel to the approach canal. A positive Y-axis is to
the right when facing downstream, while a positive Z-axis is towards the electronics of the
instrument (i.e. upwards).
Figure 4.14: XYZ coordinates of ADV instrument (Nortek, 2004)
A further objective of the physical model study was to obtain sufficient information on velocity
distributions along the sand trap canal to assist with the calibration of the CFD model.
Figure 4.15 shows the positions and depths at which ADV measurements were taken for
calibration purposes. The ADV measurements were taken for the scenarios detailed in
Table 2.3.
Stellenbosch University http://scholar.sun.ac.za
Page | 51
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 4.15: Position of ADV measurements in sand trap canal
Stellenbosch University http://scholar.sun.ac.za
Page | 52
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
5. EXPERIMENTAL TEST RESULTS
5.1 Experimental test results
Tables 5.1 to 5.12 summarise the experimental test results for the various inlet bell
configurations. The prototype Type 2, 5 and 6 submergence levels are plotted against the
prototype bell inlet velocities in Figures 5.1 to 5.12 for the corresponding table numbers.
Table 5.1: Test results – inlet bell Type 1A, 0.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.22 4.29 5.36 6.44 7.5 8.57
Pump speed (Hz) 23.0 27.4 32.2 37.4 42.8 48.8
Water temperature
(°C) 20.0 20.0 20.0 20.5 20.5 20.5
Type 2 vortex level
(mm) (1)
80 83 89 96 104 107
Type 5 vortex level
(mm) (1)
42 62 64 69 80 87
Type 6 vortex level
(mm) (1)
36 57 58 64 74 78
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
Stellenbosch University http://scholar.sun.ac.za
Page | 53
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.1: Type 1A bellmouth, 0.5D above floor – prototype type submergence
Table 5.2: Test results – inlet bell Type 1A, 1.0D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.21 4.3 5.37 6.42 7.53 8.58
Pump speed (Hz) 22.7 27.3 32.1 37.4 43.1 48.9
Water temperature
(°C) 20.5 20.0 20.0 20.0 20.5 20.5
Type 2 vortex level
(mm) (1)
73 87 92 95 104 106
Type 5 vortex level
(mm) (1)
45 62 67 72 77 77
Type 6 vortex level
(mm) (1)
34 51 60 67 70 72
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1A bellmouth, 0.5D (60 mm) above floor
Type 2Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 54
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.2: Type 1A bellmouth, 1.0D above floor – prototype type submergence
Table 5.3: Test results – inlet bell Type 1A, 1.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.22 4.28 5.36 6.45 7.52 8.57
Pump speed (Hz) 22.1 26.6 31.6 37.0 43 49
Water temperature
(°C) 20.0 20.0 20.0 20.0 20.0 20.0
Type 2 vortex level
(mm) (1)
154 169 187 218 226 244
Type 5 vortex level
(mm) (1)
47 74 122 146 181 209
Type 6 vortex level
(mm) (1)
29 60 75 111 163 187
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1A bellmouth, 1.0D (120 mm) above floor
Type2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 55
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.3: Type 1A bellmouth, 1.5D above floor – prototype type submergence
Table 5.4: Test results – inlet bell Type 1B, 0.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.22 4.29 5.34 6.44 7.5 8.55
Pump speed (Hz) 22.0 24.7 30.4 37.0 42.7 48.75
Water temperature
(°C) 18.5 18.5 19.0 19.5 19.5 19.5
Type 2 vortex level
(mm) (1)
109 123 144 151 156 166
Type 5 vortex level
(mm) (1)
37 60 66 74 78 85
Type 6 vortex level
(mm) (1)
19 51 54 56 62 73
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1A bellmouth, 1.5D (180 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 56
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.4: Type 1B bellmouth, 0.5D above floor – prototype type submergence
Table 5.5: Test results – inlet bell Type 1B, 1.0D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.21 4.29 5.36 6.44 7.51 8.58
Pump speed (Hz) 23.1 27.6 32.5 37.9 43.4 49.3
Water temperature
(°C) 20.0 20.0 20.0 20.0 20.0 19.5
Type 2 vortex level
(mm) (1)
69 91 100 131 143 188
Type 5 vortex level
(mm) (1)
21 46 55 70 81 86
Type 6 vortex level
(mm) (1)
12 29 48 63 72 78
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 0.5D (60 mm) above floor (Test No 1)
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 57
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.5: Type 1B bellmouth, 1.0D above floor – prototype type submergence
Table 5.6: Test results – inlet bell Type 1B, 1.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.21 4.28 5.32 6.44 7.52 8.57
Pump speed (Hz) 22.0 26.6 31.5 37.0 42.9 49.2
Water temperature
(°C) 19.0 19.0 19.0 19.0 18.5 17.5
Type 2 vortex level
(mm) (1)
164 181 183 206 225 242
Type 5 vortex level
(mm) (1)
36 72 96 149 156 162
Type 6 vortex level
(mm) (1)
18 45 74 119 137 144
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 1.0D (120 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 58
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.6: Type 1B bellmouth, 1.5D above floor – prototype type submergence
Table 5.7: Test results – inlet bell Type 2A, 0.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.19 4.28 5.35 6.44 7.54 8.58
Pump speed (Hz) 22.8 27.3 32.1 37.3 42.8 49.1
Water temperature
(°C) 20.0 20.0 20.0 20.0 19.0 18.5
Type 2 vortex level
(mm) (1)
35 54 66 75 101 118
Type 5 vortex level
(mm) (1)
11 19 31 39 38 37
Type 6 vortex level
(mm) (1)
7 12 26 33 27 31
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 1.5D (180 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 59
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.7: Type 2A bellmouth, 0.5D above floor – prototype type submergence
Table 5.8: Test results – inlet bell Type 2A, 1.0D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.2 4.29 5.36 6.43 7.54 8.58
Pump speed (Hz) 22.0 26.7 31.6 36.7 42.7 48.7
Water temperature
(°C) 21.0 21.0 21.0 21.0 21.0 21.0
Type 2 vortex level
(mm) (1)
122 140 146 150 167 182
Type 5 vortex level
(mm) (1)
38 89 104 116 136 134
Type 6 vortex level
(mm) (1)
10 66 91 102 121 126
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2A bellmouth, 0.5D (60 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 60
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.8: Type 2A bellmouth, 1.0D above floor – prototype type submergence
Table 5.9: Test results – inlet bell Type 2A, 1.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.2 4.31 5.36 6.44 7.54 8.6
Pump speed (Hz) 21.8 26.4 31.3 36.5 42.7 48.9
Water temperature
(°C) 21.0 21.0 21.0 21.0 21.0 21.0
Type 2 vortex level
(mm) (1)
98 134 162 180 189 203
Type 5 vortex level
(mm) (1)
51 83 94 112 119 152
Type 6 vortex level
(mm) (1)
17 65 81 97 109 141
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2A bellmouth, 1.0D (120 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 61
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.9: Type 2A bellmouth, 1.5D above floor – prototype type submergence
Table 5.10: Test results – inlet bell Type 2B, 0.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.21 4.28 5.35 6.42 7.51 8.59
Pump speed (Hz) 22.9 27.4 32.2 37.3 42.7 48.8
Water temperature
(°C) 20.0 20.0 20.0 20.0 20.0 20.0
Type 2 vortex level
(mm) (1)
52 53 62 94 116 159
Type 5 vortex level
(mm) (1)
29 37 40 71 56 44
Type 6 vortex level
(mm) (1)
23 32 37 66 51 41
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.5
1.0
1.5
2.0
2.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2A bellmouth, 1.5D (180 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 62
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.10: Type 2B bellmouth, 0.5D above floor – prototype type submergence
Table 5.11: Test results – inlet bell Type 2B, 1.0D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.22 4.28 5.36 6.44 7.52 8.56
Pump speed (Hz) 22.1 26.7 31.6 36.9 42.8 48.9
Water temperature
(°C) 18.5 18.5 18.5 15.0 16.0 16.0
Type 2 vortex level
(mm) (1)
136 146 167 209 218 221
Type 5 vortex level
(mm) (1)
57 82 121 126 130 139
Type 6 vortex level
(mm) (1)
12 42 101 106 115 132
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 0.5D (60 mm) above floor (Test No 1)
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 63
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.11: Type 2B bellmouth, 1.0D above floor – prototype type submergence
Table 5.12: Test results – inlet bell Type 2B, 1.5D above floor
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Actual measured
flow (ℓ/s) 3.23 4.32 5.36 6.44 7.51 8.59
Pump speed (Hz) 21.7 26.5 31.2 36.5 42.7 48.9
Water temperature
(°C) 17.0 18.0 18.0 18.0 19.0 19.0
Type 2 vortex level
(mm) (1)
153 197 220 224 249 248
Type 5 vortex level
(mm) (1)
36 104 118 127 147 160
Type 6 vortex level
(mm) (1)
19 79 94 112 123 132
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
0.0
0.5
1.0
1.5
2.0
2.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 1.0D (120 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 64
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.12: Type 2B bellmouth, 1.5D above floor – prototype type submergence
The above experimental test results are analysed in more detail in Section 5.4.
5.2 Repeatability of tests
The water levels at which Types 2, 5 and 6 vortices occur are based on subjective visual
observations. In order to verify the accuracy and reliability of the water level measurements, the
tests for the two long radius inlet bells (i.e. Types 1B and 2B), situated 0.5D above the floor,
were repeated.
The results of the additional tests are summarised in Tables 5.13 to 5.19. The prototype
Type 2, 5 and 6 submergence levels for the three tests are plotted against the prototype bell
inlet velocities in Figures 5.13 to 5.19 for the corresponding table numbers.
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 1.5D (180 mm) above floor
Type 2
Type 5
Type 6
Stellenbosch University http://scholar.sun.ac.za
Page | 65
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.13: Repeatability test results – inlet bell Type 1B, 0.5D above floor, Type 2 vortices
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Type 2 vortex level –
Test No 1 (mm) (1)
109 123 144 151 156 166
Type 2 vortex level –
Test No 2 (mm) (1)
108 120 147 155 157 170
Type 2 vortex level –
Test No 3 (mm) (1)
118 126 153 148 158 172
Average Type 2
vortex level (mm) 112 123 148 151 157 169
Maximum deviation
from average Type 2
vortex level
6% 2% 3% 2% 1% 2%
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
Figure 5.13: Type 1B bellmouth, 0.5D above floor – prototype type submergence for Type 2 vortices
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 0.5D (60 mm) above floor, Type 2 vortex
Test 3
Test 1
Test 2
Stellenbosch University http://scholar.sun.ac.za
Page | 66
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.14: Repeatability test results – inlet bell Type 1B, 0.5D above floor, Type 5 vortices
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Type 5 vortex level –
Test No 1 (mm) (1)
37 60 66 74 78 85
Type 5 vortex level –
Test No 2 (mm) (1)
52 53 75 85 88 87
Type 5 vortex level –
Test No 3 (mm) (1)
49 60 78 80 85 92
Average Type 5
vortex level (mm) 46 58 73 80 84 88
Maximum deviation
from average Type 5
vortex level
13% 4% 7% 7% 5% 5%
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
Figure 5.14: Type 1B bellmouth, 0.5D above floor – prototype type submergence for Type 5 vortices
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 0.5D (60 mm) above floor, Type 5 vortex
Test 3
Test 1
Test 2
Stellenbosch University http://scholar.sun.ac.za
Page | 67
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.15: Repeatability test results – inlet bell Type 1B, 0.5D above floor, Type 6 vortices
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Type 6 vortex level –
Test No 1 (mm) (1)
19 51 54 56 62 73
Type 6 vortex level –
Test No 2 (mm) (1)
44 46 59 75 76 74
Type 6 vortex level –
Test No 3 (mm) (1)
44 51 48 62 73 74
Average Type 6
vortex level (mm) 36 49 54 64 70 74
Maximum deviation
from average Type 6
vortex level
23% 3% 10% 17% 8% 0%
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
Figure 5.15: Type 1B bellmouth, 0.5D above floor – prototype type submergence for Type 6 vortices
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 0.5D (60 mm) above floor, Type 6 vortex
Test 3 Test 1
Test 2
Stellenbosch University http://scholar.sun.ac.za
Page | 68
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.16: Repeatability test results – inlet bell Type 2B, 0.5D above floor, Type 2 vortices
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Type 2 vortex level –
Test No 1 (mm) (1)
52 53 62 94 116 159
Type 2 vortex level –
Test No 2 (mm) (1)
51 56 60 101 110 152
Type 2 vortex level –
Test No 3 (mm) (1)
45 56 60 106 109 135
Average Type 2
vortex level (mm) 49 55 61 100 112 149
Maximum deviation
from average Type 2
vortex level
5% 2% 2% 6% 4% 7%
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
Figure 5.16: Type 2B bellmouth, 0.5D above floor – prototype type submergence for Type 2 vortices
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 0.5D (60 mm) above floor, Type 2 vortex
Test 3
Test 1
Test 2
Stellenbosch University http://scholar.sun.ac.za
Page | 69
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.17: Repeatability test results – inlet bell Type 2B, 0.5D above floor, Type 5 vortices
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Type 5 vortex level –
Test No 1 (mm) (1)
29 37 40 71 56 44
Type 5 vortex level –
Test No 2 (mm) (1)
36 40 45 67 45 40
Type 5 vortex level –
Test No 3 (mm) (1)
28 35 36 80 50 42
Average Type 5
vortex level (mm) 31 37 40 73 50 42
Maximum deviation
from average Type 5
vortex level
16% 7% 12% 10% 11% 5%
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
Figure 5.17: Type 2B bellmouth, 0.5D above floor – prototype type submergence for Type 5 vortices
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 0.5D (60 mm) above floor, Type 5 vortex
Test 3
Test 1Test 2
Stellenbosch University http://scholar.sun.ac.za
Page | 70
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.18: Repeatability test results – inlet bell Type 2B, 0.5D above floor, Type 6 vortices
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Theoretical scaled
model target flow
(ℓ/s)
3.22 4.29 5.36 6.44 7.51 8.58
Type 6 vortex level –
Test No 1 (mm) (1)
23 32 37 66 51 41
Type 6 vortex level –
Test No 2 (mm) (1)
19 26 35 62 42 40
Type 6 vortex level –
Test No 3 (mm) (1)
15 30 31 72 44 37
Average Type 6
vortex level (mm) 19 29 34 67 46 39
Maximum deviation
from average Type 6
vortex level
21% 9% 8% 8% 12% 4%
(1) The water levels represent the “S” dimension shown in Figures 2.1 and 2.2, and are also model scale levels.
Figure 5.18: Type 2B bellmouth, 0.5D above floor – prototype type submergence for Type 6 vortices
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 0.5D (60 mm) above floor, Type 6 vortex
Test 3
Test 1
Test 2
Stellenbosch University http://scholar.sun.ac.za
Page | 71
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It can be concluded from Table 5.13 to 5.18 that:
The maximum deviations from the average water levels for Type 2, 5 and 6 vortices were
7%, 16% and 23% respectively;
The average deviation, for all six velocities, from the average water levels for Type 2, 5 and
6 vortices were only 4%, 9% and 10% respectively; and
The water level measurements for the Type 2, 5 and 6 vortices can be repeated with a
reasonably high level of confidence.
The percentage deviations from the average water levels increased for the Type 5 and 6
vortices, but this was expected due to the higher turbulence caused by the much higher
approach velocities in the sand trap canal, which would result in more unstable conditions for
vortices to form.
It is also evident from Tables 5.13 and 5.16 that, for Type 2 vortices, the maximum difference
between the minimum and maximum water levels for all the flows is 18% (i.e. for a bell inlet
velocity of 2.4 m/s). This implies that, should the critical submergence for the prototype design
be accepted as the water level recorded for Type 2 vortices, a safety factor of 18% should be
allowed if only one water level measurement was taken, to cater for the possible inaccuracies
and subjective measurements associated with physical model studies.
5.3 Visual observations
Figure 3.2 shows the strength classification of the different types of vortices. Figures 5.19,
5.20 and 5.21 show photos of Type 2, 5 and 6 vortices as they were identified in the physical
model study.
Stellenbosch University http://scholar.sun.ac.za
Page | 72
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.19: Type 2 vortex (surface dimple)
Figure 5.20: Type 5 vortex (pulling air bubbles to intake)
Stellenbosch University http://scholar.sun.ac.za
Page | 73
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.21: Type 6 vortex (full air core to intake)
A summary of the visual observations made during the physical model testing is provided below:
General remarks applicable to all bell configurations
The formation of surface dimples (i.e. Type 2 vortices) could be influenced by break-away
actions when the water level is at a joint on the segmented suction bend, especially at
higher bell intake velocities, which also lead to higher approach canal velocities. This is
demonstrated graphically in Figure 5.22;
High approach canal velocities resulted in Type 5 vortices breaking up before full air core
entrainment took place, i.e. vortices broke up shortly after they formed; and
The differences in water levels at which Type 5 and 6 vortices formed were often very small,
i.e. 7 mm (which represents 70 mm in the prototype model) or less.
Type 1A bell configuration
Surface oscillations were visible at the water levels for the Type 5 and 6 vortices for a
prototype bell inlet velocity of 0.9 m/s and a bell height of 0.5D; and
The water surface was very turbulent at higher bell inlet velocities (i.e. 2.1 m/s and higher)
for a bell height of 0.5D, which made the identification of Type 2 vortices more difficult.
Stellenbosch University http://scholar.sun.ac.za
Page | 74
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Type 1B bell configuration
Surface oscillations were visible at the water levels for the Type 5 and 6 vortices for
prototype bell inlet velocities of 0.9 m/s and 1.2 m/s, and a bell height of 1.0D. This resulted
in the vortices breaking up before full air core vortices could form; and
The required submergence for Type 2 vortices increased noticeably when the bell height
was changed from 1.0D to 1.5D.
Type 2A bell configuration
Minor surface oscillations were visible at the water levels for the Type 5 and 6 vortices for
prototype bell inlet velocities of 0.9 m/s and 1.2 m/s, and a bell height of 0.5D; and
The water surface was very turbulent at higher bell inlet velocities (i.e. 2.1 m/s and higher)
for a bell height of 0.5D, which made the identification of Type 2 vortices more difficult.
Type 2B bell configuration
Minor surface oscillations were visible at the water levels for the Type 5 and 6 vortices for a
prototype bell inlet velocity of 0.9 m/s and a bell height of 0.5D; and
The water surface was very turbulent at higher bell inlet velocities (i.e. 1.8 m/s and higher)
for a bell height of 0.5D, which made the identification of Type 2 vortices more difficult.
Figure 5.22: Break-away caused when water level is at joint on segmented bend
Stellenbosch University http://scholar.sun.ac.za
Page | 75
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The break-away actions caused by the segmented suction bend, which could influence the
formation of Type 2 vortices, are perhaps one of the reasons why the majority of pump intake
model studies were performed using a long straight pipe as part of the suction configuration. It
has been demonstrated in Section 5.2, however, that the tests could be repeated with a
reasonably high level of confidence which implies that the joints on the segmented bends did
not have a significant impact on the test results.
5.4 Analysis of experimental test results
The motivation for the study is the question – what impact does the raising of the suction bell
have on the minimum submergence required to prevent air entrainment? In answer to this
question, the submergence value required for each of the measured vortex strengths was
plotted against bell inlet velocity for the different suction bell heights.
5.4.1 Comparison of submergence for different suction bell heights
Figures 5.23, 5.24 and 5.25 show the prototype submergence required for Type 2, 5 and 6
vortices for the Type 1A suction bell configuration situated at heights of 0.5D, 1.0D and 1.5D
above the canal floor level.
Figure 5.23: Type 1A suction bell – submergence required for Type 2 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1A bellmouth, 0.5D - 1.5D above floor, Type 2 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 76
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.24: Type 1A suction bell – submergence required for Type 5 vortices at bell heights of 0.5D, 1.0D and 1.5D
Figure 5.25: Type 1A suction bell – submergence required for Type 6 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.5
1.0
1.5
2.0
2.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1A bellmouth, 0.5D - 1.5D above floor, Type 5 vortex
1.5D
0.5D
1.0D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1A bellmouth, 0.5D - 1.5D above floor, Type 6 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 77
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The following is evident from Figures 5.23 to 5.25:
The submergence required for suction bells located at 0.5D and 1.0D is almost identical for
the Type 2, 5 and 6 vortices;
The submergence required for Type 2 vortices, where the suction bell is located at 1.5 D, is
much higher than that required for suction bells located at 0.5D and 1.0D above the floor;
and
At bell inlet velocities of 1.2 m/s or lower, the submergence required for Type 5 and 6
vortices is very similar, irrespective of the height of the suction bell. At bell inlet velocities of
1.5 m/s and higher, the submergence required for Type 5 and 6 vortices for a suction bell
situated at 1.5D becomes substantially higher than that required for the 0.5D and 1.0D
suction bells.
The prototype submergence required for Type 2, 5 and 6 vortices for the Type 1B suction bell
configuration situated at heights of 0.5D, 1.0D and 1.5D above the canal floor level is shown in
Figures 5.26, 5.27 and 5.28 respectively.
Figure 5.26: Type 1B suction bell – submergence required for Type 2 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 0.5D - 1.5D above floor, Type 2 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 78
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.27: Type 1B suction bell – submergence required for Type 5 vortices at bell heights of 0.5D, 1.0D and 1.5D
Figure 5.28: Type 1B suction bell – submergence required for Type 6 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 0.5D - 1.5D above floor, Type 5 vortex
1.5D
0.5D
1.0D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 1B bellmouth, 0.5D - 1.5D above floor, Type 6 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 79
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from the results shown in Figures 5.26 to 5.28 that:
The submergence required for suction bells located at 0.5D and 1.0D is fairly similar for the
Type 2, 5 and 6 vortices;
The submergence required for Type 2 vortices, where the suction bell is located at 1.5 D, is
much higher than that required for suction bells located at 0.5D and 1.0D above the floor;
and
The submergence required for Type 5 and 6 vortices is very similar, irrespective of the
height of the suction bell, provided that the bell inlet velocities are 1.2 m/s or lower. At bell
inlet velocities of 1.5 m/s and higher, the submergence required for Type 5 and 6 vortices for
a suction bell situated at 1.5D becomes substantially higher than that required for the 0.5D
and 1.0D suction bells.
Figures 5.29, 5.30 and 5.31 show the prototype submergence required for Type 2, 5 and 6
vortices for the Type 2A suction bell configuration situated at heights of 0.5D, 1.0D and 1.5D
above the canal floor level.
Figure 5.29: Type 2A suction bell – submergence required for Type 2 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.5
1.0
1.5
2.0
2.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2A bellmouth, 0.5D - 1.5D above floor, Type 2 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 80
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.30: Type 2A suction bell – submergence required for Type 5 vortices at bell heights of 0.5D, 1.0D and 1.5D
Figure 5.31: Type 2A suction bell – submergence required for Type 6 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2A bellmouth, 0.5D - 1.5D above floor, Type 5 vortex
1.5D
0.5D
1.0D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2A bellmouth, 0.5D - 1.5D above floor, Type 6 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 81
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from Figures 5.29 to 5.31 that:
The submergence required for suction bells located at 1.0D and 1.5D is very similar for the
Type 2, 5 and 6 vortices; and
The submergence required for Type 2, 5 and 6 vortices, where the suction bell is located at
1.0D and 1.5 D, is much higher than that required for a suction bell located at 0.5D above
the floor.
The prototype submergence required for Type 2, 5 and 6 vortices for the Type 2B suction bell
configuration situated at heights of 0.5D, 1.0D and 1.5D above the canal floor level is shown in
Figures 5.32, 5.33 and 5.34 respectively.
Figure 5.32: Type 2B suction bell – submergence required for Type 2 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 0.5D - 1.5D above floor, Type 2 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 82
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.33: Type 2B suction bell – submergence required for Type 5 vortices at bell heights of 0.5D, 1.0D and 1.5D
Figure 5.34: Type 2B suction bell – submergence required for Type 6 vortices at bell heights of 0.5D, 1.0D and 1.5D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 0.5D - 1.5D above floor, Type 5 vortex
1.5D
0.5D1.0D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Submergence: Type 2B bellmouth, 0.5D - 1.5D above floor, Type 6 vortex
1.5D
0.5D
1.0D
Stellenbosch University http://scholar.sun.ac.za
Page | 83
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from the results shown in Figures 5.32 to 5.34 that:
The submergence required for suction bells located at 1.0D and 1.5D is fairly similar for the
Type 2, 5 and 6 vortices;
The submergence required for Type 2, 5 and 6 vortices, where the suction bell is located at
1.0D and 1.5 D, is much higher than that required for a suction bell located at 0.5D above
the floor; and
A peak in the submergence required for Type 5 and 6 vortices, for a suction bell located at
0.5 D above the canal floor, is evident for a bell inlet velocity of 1.8 m/s.
5.4.2 Explaining the increase in submergence when raising the pump intake
This section of the thesis focuses on explanations for the sudden increase in submergence
when raising the pump intake to above a certain level from the canal floor.
The following aspects were evaluated in more detail for each of the inlet bell configurations:
The Reynolds Number of the approach flow; and
The approach velocity expressed as a ratio of the bell inlet velocity.
Reynolds Number of approach flow
A Reynolds Number less than 2 000 represents laminar flow, whereas a Reynolds Number
greater than 4 000 represents turbulent flow. The area where Reynolds Numbers vary from
2 000 to 4 000 is referred to as the “transitional zone” (Featherstone & Nalluri, 1988). The
question is whether the sudden increase in submergence could be related to the flow changing
from turbulent to laminar as the approach velocity will reduce in respect to an increase in the
height of the suction bell.
The aspects that stood out from the analysis of the physical model test results are that
(a) the required submergence for flat suction bell configurations (i.e. Types 1A and 1B)
substantially increases when the suction bell is raised above 1.0D, and (b) the same
occurrence is evident for slanted suction bell configurations (i.e. Types 2A and 2B), but
for heights higher than 0.5D above the floor. This leads to the question – what is
causing this “break-away” or increased submergence when raising the pump intakes to
above a certain level?
Stellenbosch University http://scholar.sun.ac.za
Page | 84
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The Reynolds Number for the approach flow was calculated using the following equation:
(5.1)
with Re = Reynolds Number at model scale
V = approach canal velocity (m/s)
L = hydraulic radius (m)
= viscosity of liquid (1 x 10-6 m2/s)
Table 5.19 summarises the model scale Reynolds Numbers calculated for all the suction bell
configurations, the different heights above the canal floor, the different vortex types and the
entire range of bell inlet velocities. The cells in Table 5.19 were highlighted green where the
Reynolds Number was less than 4 000.
Table 5.19: Reynolds Numbers for approach velocities
Bell
configuration
Height
above
floor
Vortex
type
Scale model Reynolds numbers for prototype bell
inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
1A
0.5D
2 6 192 8 156 9 963 11 667 13 204 14 930
5 7 252 8 864 10 984 12 932 14 423 16 049
6 7 454 9 051 11 261 13 197 14 764 16 609
1.0D
2 5 128 6 575 8 087 9 582 10 945 12 399
5 5 632 7 119 8 746 10 288 11 877 13 533
6 5 858 7 388 8 950 10 456 12 145 13 750
1.5D
2 3 546 4 563 5 503 6 226 7 148 7 877
5 4 640 5 722 6 351 7 231 7 817 8 418
6 4 894 5 944 7 147 7 847 8 121 8 799
1B
0.5D
2 5 571 7 079 8 241 9 728 11 161 12 355
5 7 419 8 938 10 854 12 677 14 535 16 132
6 8 090 9 286 11 410 13 644 15 496 16 897
1.0D
2 5 194 6 480 7 882 8 679 9 804 10 023
5 6 149 7 500 9 085 10 387 11 698 13 160
6 6 369 7 974 9 306 10 627 12 035 13 491
1.5D
2 3 459 4 449 5 507 6 364 7 162 7 906
5 4 777 5 753 6 717 7 171 8 246 9 275
6 5 047 6 203 7 112 7 685 8 604 9 651
Stellenbosch University http://scholar.sun.ac.za
Page | 85
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Bell
configuration
Height
above
floor
Vortex
type
Scale model Reynolds numbers for prototype bell
inlet velocities (m/s)
2A
0.5D
2 5 800 7 279 8 742 10 222 11 056 11 983
5 6 355 8 263 9 871 11 541 13 561 15 487
6 6 457 8 492 10 056 11 795 14 120 15 830
1.0D
2 3 791 4 875 6 009 7 144 8 073 8 900
5 4 734 5 514 6 634 7 728 8 647 9 885
6 5 161 5 861 6 854 7 998 8 955 10 070
1.5D
2 3 493 4 362 5 134 5 963 6 867 7 638
5 3 893 4 865 5 903 6 822 7 871 8 398
6 4 244 5 071 6 077 7 046 8 038 8 583
2B
0.5D
2 5 497 7 304 8 858 9 611 10 548 10 764
5 5 967 7 726 9 554 10 322 12 686 15 123
6 6 103 7 868 9 657 10 490 12 904 15 285
1.0D
2 3 693 4 798 5 739 6 326 7 259 8 215
5 4 510 5 602 6 366 7 559 8 744 9 749
6 5 160 6 257 6 683 7 931 9 060 9 907
1.5D
2 3 148 3 878 4 621 5 514 6 166 7 064
5 4 078 4 655 5 607 6 612 7 406 8 260
6 4 261 4 920 5 903 6 822 7 774 8 730
It is evident from Table 5.19 that the Reynolds Numbers for almost all the scenarios fall within
the turbulent zone. The sudden increase in submergence required for suction bell inlets raised
above a certain height from the floor was therefore not due to a change in flow conditions from
turbulent to laminar.
The approach velocity
It is evident from the review of acceptable approach velocities (refer to Section 3.3) that the
maximum prototype approach velocity should be 0.3 m/s or less, and that various authors also
recommend maximum bell inlet velocities ranging from 1.3 m/s (Prosser, 1977) to 2.1 m/s
(Hydraulic Institute, 1998). The approach velocity is linked to the bell inlet velocity and it was
therefore decided to plot prototype submergence against the dimensionless ratio of inlet bell
velocity/approach canal velocity to determine whether the sudden increase in submergence
could be related to this dimensionless ratio.
Figures 5.35, 5.36 and 5.37 show the submergence required for Type 2, 5 and 6 vortices
plotted against the equivalent bell inlet velocity/approach canal velocity ratio for a Type 1A
suction bell configuration.
Stellenbosch University http://scholar.sun.ac.za
Page | 86
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.35: Type 1A suction bell – submergence against bell/approach velocity ratios for Type 2 vortices
Figure 5.36: Type 1A suction bell – submergence against bell/approach velocity ratios for Type 5 vortices
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 1A bellmouth: Bell/approach velocity ratios for Type 2 vortices
0.5D 1.0D 1.5D
0.0
0.5
1.0
1.5
2.0
2.5
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 1A bellmouth: Bell/approach velocity ratios for Type 5 vortices
0.5D 1.0D 1.5D
Stellenbosch University http://scholar.sun.ac.za
Page | 87
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.37: Type 1A suction bell – submergence against bell/approach velocity ratios for Type 6 vortices
The ovals on Figures 5.35 to 5.37 represent the points where the submergence suddenly
increased, i.e. the minimum and maximum submergence required for the 0.5D (the blue
markers) and 1.0D (the red markers) are similar, but the submergence for some points of the
1.5D installation are much higher than for the 0.5D and 1.0D installations. These points are the
same points shown in Figures 5.23 to 5.25 where the submergence suddenly increased as the
bell height was increased.
It is interesting to note from Figures 5.35 to 5.37 that this sudden “jump” in all the graphs is
located near or above an inlet bell/approach velocity ratio of 6.0.
The submergence required for Type 2, 5 and 6 vortices, which is plotted against the equivalent
bell inlet velocity/approach canal velocity ratio for a Type 1B suction bell configuration, is shown
in Figures 5.38 to 5.40 respectively.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 1A bellmouth: Bell/approach velocity ratios for Type 6 vortices
0.5D 1.0D 1.5D
Stellenbosch University http://scholar.sun.ac.za
Page | 88
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.38: Type 1B suction bell – submergence against bell/approach velocity ratios for Type 2 vortices
Figure 5.39: Type 1B suction bell – submergence against bell/approach velocity ratios for Type 5 vortices
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 1B bellmouth: Bell/Approach velocity ratio against submergence for Type 2 vortices
0.5D 1.0D 1.5D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 1B bellmouth: Bell/Approach velocity ratio against submergence for Type 5 vortices
0.5D 1.0D 1.5D
Stellenbosch University http://scholar.sun.ac.za
Page | 89
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.40: Type 1B suction bell – submergence against bell/approach velocity ratios for Type 6 vortices
It is evident from Figures 5.38 to 5.40 that the points inside the ovals, which represent the
points where the submergence suddenly increased, are all plotted near or above an inlet
bell/approach canal velocity ratio of 6.0, which is similar to what was seen in Figures 5.35 to
5.37 for the Type 1A bell configuration.
Figures 5.41 to 5.43 show the submergence required for Type 2, 5 and 6 vortices plotted
against the equivalent bell inlet velocity/approach canal velocity ratio for a Type 2A suction bell
configuration.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 1B bellmouth: Bell/Approach velocity ratio against submergence for Type 6 vortices
0.5D 1.0D 1.5D
Stellenbosch University http://scholar.sun.ac.za
Page | 90
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.41: Type 2A suction bell – submergence against bell/approach velocity ratios for Type 2 vortices
Figure 5.42: Type 2A suction bell – submergence against bell/approach velocity ratios for Type 5 vortices
0.0
0.5
1.0
1.5
2.0
2.5
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 2A bellmouth: Bell/approach velocity ratios for Type 2 vortices
0.5D 1.0D 1.5D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 2A bellmouth: Bell/approach velocity ratios for Type 5 vortices
0.5D 1.0D 1.5D
Stellenbosch University http://scholar.sun.ac.za
Page | 91
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.43: Type 2A suction bell – submergence against bell/approach velocity ratios for Type 6 vortices
The following is evident from Figures 5.41 to 5.43:
Both the 1.0D and 1.5D bell heights plot inside the oval and represent points where a
sudden increase in the required submergence was observed. This is evident for the Type 2,
5 and 6 vortices. It should be noted that a 1.0D slanted bell is similar to a 1.5D flat bell, as
the submergence for the slanted bell is measured from the water level to the top of the bell,
i.e. in this specific application, the vertical distance from the bottom to the top of the slanted
bell is 60 mm, i.e. 0.5D, meaning that the top of the slanted bell is at a height of 1.5D above
the floor level; and
The points inside the oval are all located near or above a bell inlet velocity/approach canal
velocity ratio of 6.0, which was also the case for the Type 1A and 1B bell configurations.
The submergence required for Type 2, 5 and 6 vortices, plotted against the equivalent bell inlet
velocity/approach canal velocity ratio for a Type 2B suction bell configuration, is shown in
Figures 5.44 to 5.46 respectively.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 2A bellmouth: Bell/approach velocity ratios for Type 6 vortices
0.5D 1.0D 1.5D
Stellenbosch University http://scholar.sun.ac.za
Page | 92
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.44: Type 2B suction bell – submergence against bell/approach velocity ratios for Type 2 vortices
Figure 5.45: Type 2B suction bell – submergence against bell/approach velocity ratios for Type 5 vortices
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.00 2.00 4.00 6.00 8.00 10.00 12.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 2B bellmouth: Bell/approach velocity ratios for Type 2 vortices
0.5D 1.0D 1.5D
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 2B bellmouth: Bell/approach velocity ratios for Type 5 vortices
0.5D 1.0D 1.5D
Stellenbosch University http://scholar.sun.ac.za
Page | 93
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.46: Type 2B suction bell – submergence against bell/approach velocity ratios for Type 6 vortices
It is clear from the results presented in Figures 5.44 to 5.46 that the points inside the ovals are
all plotting near or above a bell inlet velocity/approach canal velocity ratio of 6.0, as was seen
for the Type 1A, 1B, and 2A bell configurations.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
Sub
mer
gen
ce (
m)
Bell/approach velocity ratio
Type 2B bellmouth: Bell/approach velocity ratios for Type 6 vortices
0.5D 1.0D 1.5D
It can be concluded that a “discontinuity” in the required submergence occurs for all the bell
configuration types when the bell inlet velocity/approach canal velocity ratio is approximately
6.0 or higher. It is further evident that the submergence required for pump intake
installations with bell inlet velocity/approach canal velocity ratios greater than 6.0 needs to
be much more than for those installations where this ratio is less than 6.0. This finding
applies to pump installations with the same geometry as that of the physical model. The
implications of this finding are further addressed in Section 6 of the thesis.
Stellenbosch University http://scholar.sun.ac.za
Page | 94
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
5.5 Comparison of test results of four bell intake configurations
It is recommended by Sulzer Brothers Limited (1987) that a slanted suction bell configuration be
used for pump intakes where the flow per pump exceeds 1 m3/s (refer to Figures 2.1 and 2.2).
Based on the physical hydraulic model testing, a decision is required on the preferred bell intake
configuration to be used when designing pump intake schemes such as Vlieëpoort and Lower
Thukela. This section describes a comparison between the results of the four bell intake
configurations that were tested and presents a recommendation on the preferred bell intake
configuration.
Figures 5.47, 5.48 and 5.49 show a comparison between the prototype submergence required
for Type 2, 5 and 6 vortices for Type 1A and 1B bell configurations (i.e. both are “flat” bell
types).
Figure 5.47: Comparison of submergence between Type 1A and 1B suction bell configurations for Type 2 vortices
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 1A and 1B bellmouths for Type 2 vortices
0.5D Type 1B 1.0D Type 1B 1.5D Type 1B 0.5D Type 1A 1.0D Type 1A 1.5D Type 1A
Stellenbosch University http://scholar.sun.ac.za
Page | 95
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.48: Comparison of submergence between Type 1A and 1B suction bell configurations for Type 5 vortices
Figure 5.49: Comparison of submergence between Type 1A and 1B suction bell configurations for Type 6 vortices
0.0
0.5
1.0
1.5
2.0
2.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 1A and 1B bellmouths for Type 5 vortices
0.5D Type 1B 1.0D Type 1B 1.5D Type 1B 0.5D Type 1A 1.0D Type 1A 1.5D Type 1A
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 1A and 1B bellmouths for Type 6 vortices
0.5D Type 1B 1.0D Type 1B 1.5D Type 1B 0.5D Type 1A 1.0D Type 1A 1.5D Type 1A
Stellenbosch University http://scholar.sun.ac.za
Page | 96
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from the results presented in Figures 5.47 to 5.49 that:
The required submergence for Type 1A suction bells is slightly lower than that required for
Type 1B suction bells for Type 2 vortices. This difference might, however, be due to
measuring inaccuracies associated with the break-away action from the segmented suction
pipework;
The required submergence for Type 1A and 1B suction bells is similar for Type 5 and 6
vortices; and
The required submergence is not influenced by the length of the suction bend.
A comparison between the prototype submergence required for Type 2, 5 and 6 vortices for
Type 2A and 2B bell configurations (i.e. both are “slanted” bell types) is shown in Figures 5.50,
5.51 and 5.52 respectively.
Figure 5.50: Comparison of submergence between Type 2A and 2B suction bell configurations for Type 2 vortices
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 2A and 2B bellmouths for Type 2 vortices
0.5D Type 2B 1.0D Type 2B 1.5D Type 2B 0.5D Type 2A 1.0D Type 2A 1.5D Type 2A
Stellenbosch University http://scholar.sun.ac.za
Page | 97
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.51: Comparison of submergence between Type 2A and 2B suction bell configurations for Type 5 vortices
Figure 5.52: Comparison of submergence between Type 2A and 2B suction bell configurations for Type 6 vortices
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 2A and 2B bellmouths for Type 5 vortices
0.5D Type 2B 1.0D Type 2B 1.5D Type 2B 0.5D Type 2A 1.0D Type 2A 1.5D Type 2A
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 2A and 2B bellmouths for Type 6 vortices
0.5D Type 2B 1.0D Type 2B 1.5D Type 2B 0.5D Type 2A 1.0D Type 2A 1.5D Type 2A
Stellenbosch University http://scholar.sun.ac.za
Page | 98
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from Figures 5.50 to 5.52 that:
The required submergence for Type 2 vortices is slightly lower for the Type 2A bell
configuration when compared to the Type 2B bell;
The required submergence for the Type 5 and 6 vortices is very similar for both bell
configurations; and
The radius of the suction bend does not influence the required submergence.
The submergence for the Type 1A and 1B bell configurations is very similar, as is the case
when comparing the Type 2A and 2B bell configurations. The submergence required for the
suction bells with the long radius bends seems to be slightly higher for Type 2 vortices and is
therefore regarded as the more conservative approach when determining critical submergence.
Figures 5.53, 5.54 and 5.55 show a comparison between the prototype submergence required
for Type 2, 5 and 6 vortices for Type 1B and 2B bell configurations (i.e. both are “long radius”
type suction bends). The submergence shown in Figures 5.50 to 5.52 for the slanted suction
bell was increased by 0.6 m to be comparable with the flat suction bell, i.e. the submergence is
measured from the same distance above the floor for both types of suction bells.
Figure 5.53: Comparison of submergence between Type 1B and 2B suction bell configurations for Type 2 vortices
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 1B and 2B bellmouths for Type 2 vortices
0.5D Type 1B 1.0D Type 1B 1.5D Type 1B 0.5D Type 2B 1.0D Type 2B 1.5D Type 2B
Stellenbosch University http://scholar.sun.ac.za
Page | 99
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.54: Comparison of submergence between Type 1B and 2B suction bell configurations for Type 5 vortices
Figure 5.55: Comparison of submergence between Type 1B and 2B suction bell configurations for Type 6 vortices
0.0
0.5
1.0
1.5
2.0
2.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 1B and 2B bellmouths for Type 5 vortices
0.5D Type 1B 1.0D Type 1B 1.5D Type 1B 0.5D Type 2B 1.0D Type 2B 1.5D Type 2B
0.0
0.5
1.0
1.5
2.0
2.5
0.9 1.2 1.5 1.8 2.1 2.4
Sub
mer
gen
ce (
m)
Bell inlet velocity (m/s)
Comparison of submergence between Type 1B and 2B bellmouths for Type 6 vortices
0.5D Type 1B 1.0D Type 1B 1.5D Type 1B 0.5D Type 2B 1.0D Type 2B 1.5D Type 2B
Stellenbosch University http://scholar.sun.ac.za
Page | 100
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident, when comparing the results presented in Figures 5.53 to 5.55, that the
submergence required for the Type 1 B bell configuration is lower than that of the Type 2B bell
configurations for all types of vortices. The only exception to this is the submergence for a
Type 2 vortex for a 0.5D bell height, which is similar for the two suction bell configurations.
5.6 Acoustic Doppler velocimeter measurements
The acoustic Doppler velocimeter (ADV) measurements were taken for the recommended
suction bell configuration, i.e. a Type 1B suction bell.
The ADV measurements were taken to:
Determine the time-average velocity distribution near the edge of the suction bell; and
Obtain sufficient velocity data along the approach canal for the calibration of the CFD model.
5.6.1 ADV measurements at edge of suction bell
ADV measurements were taken at the five positions indicated in Figure 4.13. The focus points
of the ADV instrument were set up at a depth of 60 mm above the canal floor level, i.e. the
same level as the bottom of the suction bell. Table 5.20 summarises the water levels used for
each of the tests.
Table 5.20: Water levels for ADV tests at suction bell
Description Prototype bell inlet velocities (m/s)
0.9 1.2 1.5 1.8 2.1 2.4
Water level above
canal floor (mm) (1)
172 183 208 211 217 229
(1) The water levels were the average submergence levels determined for Type 2 vortices
It is recommended that the design of the Vlieëpoort and Lower Thukela pump intakes be
based on the conventional “flat” suction bell configuration as the submergence required is
less than that required for the “slanted” configuration. It is also recommended that the
required submergence be based on a long radius suction bend as the submergence
required for Type 2 vortices was slightly higher than that of a short radius bend, which is a
more conservative approach.
Stellenbosch University http://scholar.sun.ac.za
Page | 101
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Tables 5.21 to 5.26 summarise the average X, Y and Z velocities measured at each of the
positions, as well as the calculated resultant vector, for prototype bell inlet velocities of 0.9 m/s,
1.2 m/s, 1.5 m/s, 1.8 m/s, 2.1 m/s and 2.4 m/s respectively. The resultant vector was calculated
as follows:
Vvector = [Vx2 + Vy
2 + Vz2]0.5 (5.1)
with Vvector = resultant velocity (m/s)
Vx = velocity in x-direction (m/s)
Vy = velocity in y-direction (m/s)
Vz = velocity in z-direction (m/s)
The velocities are presented in mm/s in Tables 5.21 to 5.26 due to the lower velocities
associated with the scaled physical model. The X, Y and Z coordinate system is based on the
following convention, facing downstream towards the pump intake (also refer to Figure 4.14):
Positive X-axis velocities represent flow towards the pump intake;
Positive Y-axis velocities represent flow from left to right, perpendicular to the X-axis; and
Positive Z-axis velocities represent flow towards the ADV instrument, i.e. upwards.
It was noted in Section 4.3.3 that fine sand particles had to be added to improve the accuracy
of the ADV measurements. Each recorded dataset was analysed to determine whether any
part(s) of it should be excluded when calculating the average velocities. Figure 5.56 shows the
recorded dataset at Position 2 for a prototype suction bell inlet velocity of 0.9 m/s. The outliers
represent inaccurate readings caused by insufficient suspended sand particles in the water.
Stellenbosch University http://scholar.sun.ac.za
Page | 102
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.56: X, Y and Z velocities for 0.9 m/s bell inlet velocity at Position 2
It is evident from Figure 5.56 that the average velocities should only be calculated for the
dataset from sample numbers 720 to 1 020.
Table 5.21: Summary of ADV measurements (model) at suction bell for prototype 0.9 m/s bell inlet velocity
Description Position 1 Position 2 Position 3 Position 4 Position 5
Average X-axis velocity
(mm/s) -9.9 76.9 94.3 97.2 50.6
Average Y-axis velocity
(mm/s) 29.5 -29.3 2.0 2.9 1.3
Average Z-axis velocity
(mm/s) -30.6 -76.7 -27.5 -32.3 -55.7
Average resultant
velocity (mm/s) 43.7 112.5 98.3 102.4 75.3
-0.8
-0.6
-0.4
-0.2
0.0
0.2
0.4
0.6
0.8
0 200 400 600 800 1000 1200
Vel
oci
ty (
m/s
)
Sample number
X, Y and Z velocities for 0.9 m/s bell inlet velocity at Position 2
X-velocities Y-velocities Z-velocities
Outliers in dataset
Outliers in dataset
Stellenbosch University http://scholar.sun.ac.za
Page | 103
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The scaled average axial velocity at the entrance to the suction bell is 284.7 mm/s. It is evident
from Table 5.21 that the average resultant velocities are all substantially lower than the axial
velocity at the bell entrance. This is to be expected, as the ADV measurements were taken at
positions located 45 mm from the edge of the suction bell, which are still inside the canal and
not at the edge of the suction bell. It is clear from the results presented in Table 5.21, however,
that:
The resultant velocities are much higher at the positions located in front of the suction bell
(i.e. Positions 2, 3 and 4) compared to the positions behind the suction bell;
The average resultant velocities at Positions 2, 3 and 4 compare reasonably well with one
another;
The average x-axis velocity at Position 1 is negative, indicating some form of “reverse flow”
or swirl behind the suction bell; and
The 10% velocity distribution stated by the Hydraulic Institute (1998) as an acceptance
criterion is not met at the five positions measured.
Table 5.22: Summary of ADV measurements (model) at suction bell for prototype 1.2 m/s bell inlet velocity
Description Position 1 Position 2 Position 3 Position 4 Position 5
Average X-axis velocity
(mm/s) -39.0 105.7 117.4 126.4 10.6
Average Y-axis velocity
(mm/s) -16.3 -35.2 2.0 5.9 -23.9
Average Z-axis velocity
(mm/s) -47.3 -85.2 -37.1 -46.8 -35.6
Average resultant
velocity (mm/s) 63.4 140.2 123.2 134.9 44.2
The same conclusions can be drawn for the results presented in Table 5.22 as those
summarised below Table 5.21, which were for the ADV velocities associated with a suction bell
prototype inlet velocity of 0.9 m/s.
Stellenbosch University http://scholar.sun.ac.za
Page | 104
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.23: Summary of ADV measurements (model) at suction bell for prototype 1.5 m/s bell inlet velocity
Description Position 1 Position 2 Position 3 Position 4 Position 5
Average X-axis velocity
(mm/s) -45.1 116.6 136.5 108.6 59.9
Average Y-axis velocity
(mm/s) 59.6 -42.6 2.0 -5.6 -13.2
Average Z-axis velocity
(mm/s) -27.2 -92.1 -45.9 -40.9 -65.2
Average resultant
velocity (mm/s) 79.5 154.6 144.1 116.2 89.5
The same conclusions can be drawn for the results presented in Table 5.23 as those
summarised below Table 5.21, which were for the ADV velocities associated with a suction bell
prototype inlet velocity of 0.9 m/s.
Table 5.24: Summary of ADV measurements (model) at suction bell for prototype 1.8 m/s bell inlet velocity
Description Position 1 Position 2 Position 3 Position 4 Position 5
Average X-axis velocity
(mm/s) 16.1 146.1 139.7 121.8 98.5
Average Y-axis velocity
(mm/s) -76.0 -49.8 -10.0 -11.9 96.6
Average Z-axis velocity
(mm/s) -44.6 -140.0 -56.8 -58.7 -121.1
Average resultant
velocity (mm/s) 89.5 208.4 151.1 135.8 183.6
It is evident from the results presented in Table 5.24 that:
All the velocities in the x-axis direction are now positive. This might be due to inaccuracies
in the ADV measurements caused by a lack of particles behind the suction bell; and
Larger variances are evident between the resultant velocities at the different positions, even
for Positions 2, 3 and 4, which are situated upstream of the suction bell. These larger
variations might also be due to a lack of particles, which influences the accuracy of the
measurements.
Stellenbosch University http://scholar.sun.ac.za
Page | 105
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.25: Summary of ADV measurements (model) at suction bell for prototype 2.1 m/s bell inlet velocity
Description Position 1 Position 2 Position 3 Position 4 Position 5
Average X-axis velocity
(mm/s) -55.6 166.2 189.8 173.8 83.0
Average Y-axis velocity
(mm/s) 86.9 -47.8 3.0 -0.7 -19.1
Average Z-axis velocity
(mm/s) -43.0 -130.9 -62.6 -78.1 -103.5
Average resultant
velocity (mm/s) 111.8 216.9 199.8 190.5 134.1
The same conclusions can be drawn for the results presented in Table 5.25 as those
summarised below Table 5.21, which were for the ADV velocities associated with a suction bell
prototype inlet velocity of 0.9 m/s.
Table 5.26: Summary of ADV measurements (model) at suction bell for prototype 2.4 m/s bell inlet velocity
Description Position 1 Position 2 Position 3 Position 4 Position 5
Average X-axis velocity
(mm/s) -59.9 191.9 223.6 184.8 77.0
Average Y-axis velocity
(mm/s) 72.1 -20.0 -16.2 -3.9 -26.3
Average Z-axis velocity
(mm/s) -72.4 -118.9 -58.3 -99.7 -93.6
Average resultant
velocity (mm/s) 118.4 226.6 231.7 210.0 124.0
The same conclusions can be drawn for the results presented in Table 5.26 as those
summarised below Table 5.21, which were for the ADV velocities associated with a suction bell
prototype inlet velocity of 0.9 m/s.
Figure 5.57 shows the resulting velocities presented in Tables 5.21 to 5.26 in a plan view.
Stellenbosch University http://scholar.sun.ac.za
Page | 106
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.57: Plan view of resultant velocities at suction bell for prototype bell inlet velocities of 0.9 m/s to 2.4 m/s
Stellenbosch University http://scholar.sun.ac.za
Page | 107
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Based on the ADV measurements taken near the edge of the suction bell for a range of suction
bell inlet velocities, it can be concluded that the 10% time-average velocity distribution,
recommended as an acceptance criterion by the Hydraulic Institute (1998), was not achieved for
this particular installation. It is likely that this acceptance criterion would be met for pump
intakes located in a large reservoir where the approach velocities from all sides would be more
evenly distributed, compared to a suction bell located at the end of a canal.
5.6.2 ADV measurements along approach canal
Figure 4.13 showed the positions and depths at which ADV measurements were taken for
calibration purposes. The ADV measurements were taken for the scenarios detailed in
Table 2.3. The water levels at which the ADV measurements were taken are summarised in
Table 5.27.
ADV measurements were taken at 27 positions for each set-up, i.e. a total of 108 points. The
average X, Y and Z velocities and the average resultant velocity for each of the positions are
summarised in Table 5.28.
Table 5.27: Water levels for ADV tests along approach canal
Prototype suction bell inlet
velocity (m/s)
Suction bell height Water level above
canal floor for Type 2
vortices (mm)
1.2 0.5D 183
1.2 1.0D 183 (1)
1.2 1.5D 361
1.8 0.5D 210
(1) The measured water level for the Type 2 vortex and a 1.0D bell height was 789 mm above the canal floor. The
water level was, however, kept the same for when the suction bell was 0.5D above the floor to allow a
comparison between these two set-ups, where the water level and suction bell inlet velocity are kept constant but
the bell height is varied.
The ADV datasets for each position had to be evaluated for “outliers”, as shown in Figure 5.58.
The average velocities were calculated only after these outliers had been eliminated from the
dataset.
Figure 5.59 shows the velocity distribution for the same dataset presented in Figure 5.58, but
only for sample numbers 195 to 295.
Stellenbosch University http://scholar.sun.ac.za
Page | 108
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 5.28: Summary of ADV measurements (model) along approach canal
Position Average X-axis
velocity (mm/s)
Average Y-axis
velocity (mm/s)
Average Z-axis
velocity (mm/s)
Average resultant
velocity (mm/s)
Suction bell at height of 0.5D with bell inlet velocity of 1.2 m/s
1A 118.5 0.6 -0.8 118.5
1B 118.0 -0.5 -6.7 118.2
1C 105.1 -0.5 -3.7 105.2
2A 118.1 0.1 0.1 118.1
2B 121.0 0.5 -0.3 121.0
2C 116.1 -0.2 0.0 116.1
3A 119.3 1.3 0.1 119.3
3B 122.4 -1.6 1.6 122.4
3C 111.6 0.0 1.7 111.6
4A 114.6 -0.1 -0.6 114.6
4B 112.0 0.5 -6.7 113.2
4C 103.2 1.6 1.2 103.2
5A 118.1 1.9 0.9 118.1
5B 123.2 0.7 1.1 123.3
5C 115.9 3.1 2.5 116.0
6A 119.1 0.3 0.9 119.1
6B 120.6 -3.4 -1.2 120.6
6C 117.4 -1.1 1.3 117.4
7A 117.2 0.6 -3.2 117.2
7B 114.2 -0.6 -2.3 114.2
7C 112.2 -3.3 -2.8 112.3
8A 121.6 -0.2 -2.9 121.6
8B 119.0 0.6 -4.6 119.1
8C 113.8 1.3 -3.0 113.9
9A 120.3 2.6 -3.0 120.4
9B 116.4 -5.8 -6.5 116.7
9C 111.7 0.0 -2.1 111.7
Suction bell at height of 1.0D with bell inlet velocity of 1.2 m/s
1A 120.5 0.5 -2.0 120.6
1B 110.8 -2.4 -20.7 112.7
1C 111.3 0.3 -1.9 111.3
2A 121.7 -0.3 -0.1 121.7
Stellenbosch University http://scholar.sun.ac.za
Page | 109
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Position Average X-axis
velocity (mm/s)
Average Y-axis
velocity (mm/s)
Average Z-axis
velocity (mm/s)
Average resultant
velocity (mm/s)
2B 125.8 -0.1 -2.0 125.8
2C 120.5 0.4 0.9 120.5
3A 123.9 0.6 -1.2 123.9
3B 125.5 0.0 -0.6 125.5
3C 116.0 -0.3 -0.1 116.0
4A 119.3 -0.6 2.5 119.4
4B 119.4 2.5 -4.9 119.5
4C 112.8 1.2 1.5 112.8
5A 122.2 0.8 2.6 122.2
5B 126.1 0.5 0.6 126.1
5C 118.6 0.6 0.0 118.6
6A 122.2 0.2 0.6 122.2
6B 123.8 0.3 1.6 123.8
6C 118.9 -0.2 0.8 118.9
7A 121.6 -0.1 -2.8 121.6
7B 114.8 -4.0 -21.8 117.0
7C 111.6 1.3 -1.5 111.7
8A 123.6 -0.1 -1.2 123.6
8B 129.7 -0.1 -0.8 129.7
8C 120.4 0.5 -0.6 120.4
9A 125.5 2.8 -1.3 125.6
9B 123.3 -0.3 -1.9 123.3
9C 119.1 0.8 -1.2 119.1
Suction bell at height of 1.5D with bell inlet velocity of 1.2 m/s
1A 71.2 1.0 2.4 71.2
1B 72.6 -3.5 -20.4 75.5
1C 81.2 -0.5 8.7 81.7
2A 71.5 -0.4 2.9 71.6
2B 64.5 -0.4 -7.6 65.0
2C 98.7 0.2 10.8 99.3
3A 83.7 -2.6 0.9 83.7
3B 99.8 3.5 4.1 99.9
3C 84.5 1.5 4.6 84.7
4A 85.4 -3.4 2.3 85.5
Stellenbosch University http://scholar.sun.ac.za
Page | 110
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Position Average X-axis
velocity (mm/s)
Average Y-axis
velocity (mm/s)
Average Z-axis
velocity (mm/s)
Average resultant
velocity (mm/s)
4B 71.4 -1.8 -11.0 72.2
4C 77.9 0.1 10.3 78.6
5A 84.0 -0.6 2.2 84.0
5B 70.9 -0.4 0.8 70.9
5C 79.0 2.5 -0.1 79.0
6A 68.5 -1.0 0.4 68.6
6B 63.5 -1.9 -11.4 64.5
6C 79.5 -1.9 7.0 79.8
7A 88.8 -1.6 -4.5 88.9
7B 63.6 1.8 -33.1 71.7
7C 93.6 0.5 -3.4 93.7
8A 89.5 -2.0 -4.4 89.6
8B 79.2 -2.5 -3.4 79.3
8C 96.6 8.9 -5.4 97.1
9A 94.4 0.0 -5.6 94.6
9B 100.6 -4.2 -0.4 100.7
9C 82.0 0.6 -6.1 82.2
Suction bell at height of 0.5D with bell inlet velocity of 1.8 m/s
1A 138.4 2.1 -6.4 138.6
1B 130.9 -1.6 -5.6 131.1
1C 126.8 -0.5 -0.6 126.8
2A 150.0 1.5 -1.3 150.1
2B 145.2 1.8 -0.2 145.2
2C 133.2 -0.8 -2.3 133.2
3A 154.8 1.3 -0.4 154.8
3B 150.0 1.1 -0.7 150.0
3C 144.6 1.1 -4.5 144.7
4A 138.9 3.7 -1.7 139.0
4B 126.9 -6.6 -19.2 128.5
4C 126.7 -1.7 -4.7 126.8
5A 148.6 1.0 0.9 148.6
5B 145.0 1.5 -2.8 145.0
5C 135.1 -4.5 2.1 135.2
6A 157.2 2.0 -0.4 157.2
Stellenbosch University http://scholar.sun.ac.za
Page | 111
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Position Average X-axis
velocity (mm/s)
Average Y-axis
velocity (mm/s)
Average Z-axis
velocity (mm/s)
Average resultant
velocity (mm/s)
6B 155.3 3.0 0.2 155.3
6C 150.6 1.0 0.9 150.6
7A 141.1 2.9 -4.6 141.2
7B 132.2 1.6 -4.3 132.3
7C 126.4 -1.1 -4.1 126.4
8A 150.2 -0.3 -3.5 150.3
8B 139.4 -2.9 -13.8 140.2
8C 139.5 1.4 -3.9 139.6
9A 159.6 1.8 -4.9 159.7
9B 148.6 -0.5 -23.7 150.4
9C 140.9 1.1 -3.6 141.0
Figure 5.58: Position 1C: X, Y and Z velocities for 0.5D and 1.2 m/s inlet bell velocity
-0.6
-0.4
-0.2
0.0
0.2
0.4
0.6
0.8
0 200 400 600 800 1000 1200 1400 1600
Vel
oci
ty (
m/s
)
Sample number
Position 1C: X, Y and Z velocities for 0.5D and 1.2 m/s inlet bell velocity
X velocities Y velocities Z velocities
Outliers in dataset
Outliers in dataset
Stellenbosch University http://scholar.sun.ac.za
Page | 112
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.59: Position 1C: X, Y and Z velocities for 0.5D and 1.2 m/s inlet bell velocity for sample numbers 195 to 295
It is evident from Figure 5.59 that the velocities fluctuate over time. The fluctuations are
generally within 20% of the calculated average velocities, e.g. the average X-axis velocity was
calculated as 0.105 m/s, with all of the samples except for 10 being between 0.08 m/s and
0.12 m/s.
Figure 5.60 shows the average resultant velocities along centrelines 1-4-7, 2-5-8 and 3-6-9 for
an inlet bell velocity of 1.2 m/s and a bell height of 0.5D, whereas Figure 5.61 shows a plan
view of the average resultant velocities for the same bell details at the different levels above the
floor level.
Based on the results presented in Figure 5.60, it appears that the average resultant velocities
are lowest at the highest water level, i.e. Level C.
It is evident from Figure 5.61 that the velocities for the points along the centreline of the canal
are higher than those at the sides of the canal.
-0.04
-0.02
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
180 200 220 240 260 280 300
Vel
oci
ty (
m/s
)
Sample number
Position 1C: X, Y and Z velocities for 0.5D and 1.2 m/s inlet bell velocity
X velocities Y velocities Z velocities
Stellenbosch University http://scholar.sun.ac.za
Page | 113
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
A further interesting observation, when comparing the Z-axis velocities between the points near
the inlet bell (refer to Tables 5.21 to 5.26) to those in the canal (refer to Table 5.28), is that the
average Z-velocities become highly negative as the water approaches the inlet bell, i.e. the
water suddenly “dives” down near the inlet bell.
Figure 5.60: Average resultant velocities along centrelines 1-4-7, 2-5-8, and 3-6-9
Stellenbosch University http://scholar.sun.ac.za
Page | 114
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 5.61: Average resultant velocities along Planes A, B and C
Figure 5.62 shows a series of photos taken of a particle approaching the inlet bell that
demonstrates this observation.
Further analyses of the ADV measurements, and the use thereof to calibrate the CFD model,
are covered in the thesis of Hundley (2012).
Stellenbosch University http://scholar.sun.ac.za
Page | 115
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
(a) (b)
(c) (d)
(e) (f)
(g) (h)
Figure 5.62: Path of particle approaching the inlet bell
Stellenbosch University http://scholar.sun.ac.za
Page | 116
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
6. COMPARISON OF TEST RESULTS AGAINST DESIGN GUIDELINES
It was concluded in Section 5.5 that the Type 1B suction bell configuration is the recommended
configuration for the design of pump intakes such as the Vlieëpoort and Lower Thukela
schemes.
The design guidelines that are available to calculate critical submergence were discussed in
Section 3.3. It was also evident from Figure 3.3 that large differences exist between the critical
submergence recommended by the various authors. In this section, a comparison is made
between the submergence measured in the physical model study, for the Type 2, 5 and 6
vortices, and the published design guidelines to determine which of the design guidelines best
represent the measured submergence.
Figures 6.1, 6.2 and 6.3 show the comparison between the critical submergence recommended
in the design guidelines and the measured Type 2, 5 and 6 submergence for bell heights of
0.5D, 1.0D and 1.5D respectively.
Figure 6.1: Comparison of submergence between design guidelines and measured Type 2, 5 and 6 vortices for a bell height of 0.5D
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00
Cri
tica
l su
bm
erge
nce
(m
)
Bell inlet velocity (m/s)
Critical submergence versus bell inlet velocity for 0.5D bell height
1. Prosser & Sulzer 2. Hydraulic institute & Jones 3. Peterson and Noble 4. Knauss
5. Gorman Rupp 6. KSB 7. Metcalf & Eddy 8. Flygt
9. D Werth Type 2 vortex Type 5 vortex Type 6 vortex
1
23
4 56
7
8
9
Stellenbosch University http://scholar.sun.ac.za
Page | 117
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from Figure 6.1 that:
The measured Type 2 submergence levels are slightly lower than the submergence levels
recommended by Knauss (1987); and
The measured Type 5 and 6 submergence levels are slightly lower than the design
guidelines recommended by KSB (Gouws, 2010) and Gorman-Rupp (Strydom, 2010b).
Figure 6.2: Comparison of submergence between design guidelines and measured Type 2, 5 and 6 vortices for a bell height of 1.0D
It can be seen from the results presented in Figure 6.2 that:
The Type 2 measured submergence closely follows the critical submergence recommended
by Metcalf and Eddy (1981, E-mail communication with Strydom, 2010a); and
The Type 5 and 6 measured submergence is less than any of the design recommendations.
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00
Cri
tica
l su
bm
erge
nce
(m
)
Bell inlet velocity (m/s)
Critical submergence versus bell inlet velocity for 1.0D bell height
1. Prosser & Sulzer 2. Hydraulic institute & Jones 3. Peterson and Noble 4. Knauss
5. Gorman Rupp 6. KSB 7. Metcalf & Eddy 8. Flygt
9. D Werth Type 2 vortex Type 5 vortex Type 6 vortex
1
23
4 56
7
8
9
Stellenbosch University http://scholar.sun.ac.za
Page | 118
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Figure 6.3: Comparison of submergence between design guidelines and measured Type 2, 5 and 6 vortices for a bell height of 1.5D
It is evident from Figure 6.3 that:
The measured Type 2 submergence is now higher than the submergence recommended by
Knauss (1987), but lower than that recommended by the Hydraulic Institute (1998);
The submergence recommended by Metcalf and Eddy (1981, E-mail communication with
Strydom, 2010a) is similar to the measured Type 5 submergence; and
The measured Type 6 submergence is similar to that recommended by KSB (Gouws, 2010)
and Gorman Rupp (Strydom, 2010b).
The objective of this study was to determine the submergence at which air entrainment occur,
which is represented by the Type 6 water levels. The Type 5 water levels represent vortices
that pull air bubbles to the bell intake, but is was found with the physical model testing that the
Type 5 and 6 water levels were generally very similar, which poses a high risk of air entrainment
if the design is based on Type 5 water levels as being the critical submergence. The Hydraulic
Institute (1998) recommended that the critical submergence be based on Type 3 vortices (i.e.
coherent dye core), provided that they occur for less than 10% of the time. It was demonstrated
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00
Cri
tica
l su
bm
erge
nce
(m
)
Bell inlet velocity (m/s)
Critical submergence versus bell inlet velocity for 1.5D bell height
1. Prosser & Sulzer 2. Hydraulic institute & Jones 3. Peterson and Noble 4. Knauss
5. Gorman Rupp 6. KSB 7. Metcalf & Eddy 8. Flygt
9. D Werth Type 2 vortex Type 5 vortex Type 6 vortex
1
23
4 56
7
8
9
Stellenbosch University http://scholar.sun.ac.za
Page | 119
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
in the physical model testing that Type 3 vortices cannot be determined accurately and that it
would be very difficult to determine whether they occur for less than 10% of the time. This
effectively means that the critical submergence should rather be based on the water levels at
which Type 2 vortices are detected.
It was concluded in Section 5.2, which evaluated the repeatability of the results obtained with
the physical model testing, that a safety factor of 18% should be allowed if only one water level
measurement is taken to cater for possible inaccuracies and subjective measurements.
Figure 6.4 therefore shows the measured Type 2 submergence levels that were increased by
20% in comparison with the available design guidelines.
Figure 6.4: Comparison of submergence between design guidelines and measured Type 2 vortices for bell heights of 0.5D, 1.0D and 1.5D
The following conclusions can be drawn from Figure 6.4:
The critical submergence proposed by Knauss (1987) should be used for pump intakes that
are located at 0.5D and 1.0D above the canal floor; and
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00
Cri
tica
l su
bm
erge
nce
(m
)
Bell inlet velocity (m/s)
Critical submergence versus bell inlet velocity for Type 2 vortices
1. Prosser & Sulzer 2. Hydraulic institute & Jones 3. Peterson and Noble 4. Knauss
5. Gorman Rupp 6. KSB 7. Metcalf & Eddy 8. Flygt
9. D Werth Type 2 vortex (0.5D) Type 2 vortex (1.0D) Type 2 vortex (1.5D)
1
23
4 56
7
8
9
Stellenbosch University http://scholar.sun.ac.za
Page | 120
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The critical submergence recommended by the Hydraulic Institute (1998) should be used
when raising the pump intake to 1.5D above the canal floor.
It was also shown in Figures 5.38 to 5.40 that the submergence required for the 0.5D and 1.0D
bell heights plotted below a bell inlet velocity/approach canal velocity ratio of 6.0, whereas the
1.5D bell installation plotted above a ratio of 6.0.
An important question to answer for the above recommendation, is whether the bell inlet
velocity/approach canal velocity ratio of 6.0 should be calculated with the equation published by
Knauss (1987) or by the equation published by the Hydraulic Institute (1998). The following
factors should be considered in answering this question:
1) The bell inlet velocity/approach canal velocity ratio of 6.0 was determined based on the
actual results obtained in the physical model study;
2) The water levels determined in the physical model were for Type 2 vortices, whereas the
equations developed by the Hydraulic Institute (1998) and Knauss (1987) were based on
Type 3 vortices that should not occur less than 10% of the time;
3) Figures 6.1 and 6.2, where the bell inlet velocity/approach canal velocity ratios were less
than 6.0, show that the Type 2 submergence levels measured in the physical model study
were lower than the submergence levels calculated with the equation published by
It therefore is recommended that, for pump intakes with a similar geometry to that tested with
the physical hydraulic model, critical submergence be calculated with the equation published
by Knauss (1987), i.e. S = D(0.5 + 2.0Fr), where the bell inlet velocity/approach canal velocity
ratio is less than 6.0, and that the equation published by the Hydraulic Institute (1998), i.e.
S = D(1 + 2.3Fr), be used where the ratio exceeds 6.0.
The Hydraulic Institute recommended inlet bell velocities of up to 2.1 m/s, with the optimum
inlet velocity being 1.7 m/s. It was, however, recommended by Prosser (1977) and Sulzer
Brothers Limited (1987) that inlet bell velocities be limited to 1.3 m/s, whereas Jones (2008)
recommended 1.5 m/s as the maximum inlet bell velocity. The water surface became
turbulent in the physical model study when the bell inlet velocities were increased above
1.8 m/s, which supports the recommendations by Prosser, Sulzer Brothers Limited and
Jones. It is recommended that bell inlet velocities therefore be limited to 1.5 m/s.
Stellenbosch University http://scholar.sun.ac.za
Page | 121
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Knauss (1987). Similarly, Figure 6.3 shows that the Type 2 submergence levels measured
in the physical model study were lower than the submergence levels calculated with the
equation published by the Hydraulic Institute (1998), for bell inlet velocity/approach canal
velocity ratios exceeding 6.0. Therefore, calculating the bell inlet velocity/approach canal
velocity ratio with the equations published by Knauss (1987) and the Hydraulic Institute
(1998) will result in higher bell inlet velocity/approach canal velocity ratios compared to that
measured in the physical model study.
Based on the above factors, it would appear over-conservative to calculate the bell inlet
velocity/approach canal velocity ratio of 6.0 with the equation published by the Hydraulic
Institute (1998).
Tables 6.1 to 6.3 show the bell inlet velocity/approach canal velocity ratios calculated with both
equations, as well as the Type 2 submergence levels measured in the physical model study, as
further demonstration on which equation to use to calculate the bell inlet velocity/approach canal
velocity ratio of 6.0.
Table 6.1: Bell inlet velocity/approach canal velocity ratios for Type 1B suction bell located 0.6 m (prototype) above canal floor
Flow, Q (m3/s) 1.02 1.36 1.7 2.04 2.37
Assumed bell inlet velocity, V (m/s) 0.9 1.2 1.5 1.8 2.1
Calculated suction bell diameter (m) 1.20 1.20 1.20 1.20 1.20
Actual (rounded) suction bell diameter, D (m) 1.20 1.20 1.20 1.20 1.20
Actual bell inlet velocity, Vb (m/s) 0.90 1.20 1.50 1.80 2.10
Canal width, W (=2D) (m) 2.4 2.4 2.4 2.4 2.4
Required bell height above floor, C (m) 0.6 0.6 0.6 0.6 0.6
Froude Number, Fr 0.26 0.35 0.44 0.53 0.61
Knauss submergence, S = D(0.5+2Fr) (m) 1.23 1.44 1.65 1.86 2.07
Hydraulic Institute submergence, S = D(1+2.3Fr) (m) 1.93 2.17 2.41 2.65 2.89
Knauss approach velocity, Va (m/s) 0.23 0.28 0.31 0.35 0.37
Hydraulic Institute approach velocity, Va (m/s) 0.17 0.20 0.24 0.26 0.28
Ratio Vb/Va (Knauss) 3.89 4.33 4.78 5.22 5.66
Ratio Vb/Va (Hydraulic Institute) 5.36 5.87 6.39 6.90 7.40
Measured Type 2 submergence in physical model
for Type 1B suction bell (m) 1.12 1.23 1.48 1.51 1.57
Stellenbosch University http://scholar.sun.ac.za
Page | 122
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from Table 6.1 that:
The inlet bell velocity/approach canal velocity ratios calculated with the equation published
by Knauss (1987) are all less than 6.0;
The inlet bell velocity/approach canal velocity ratios calculated with the equation published
by the Hydraulic Institute (1998) vary from 5.36 to 7.40;
The Type 2 submergence levels measured in the physical model study correspond
reasonably well with the submergence levels calculated with the equation published by
Knauss (1987) for all bell inlet velocities; and
Calculating the submergence levels with the equation published by the Hydraulic Institute
(1998) for inlet bell velocity/approach canal velocity ratios exceeding 6.0, would result in
very conservative submergence levels when compared to those measured in the physical
model study.
Table 6.2: Bell inlet velocity/approach canal velocity ratios for Type 1B suction bell located 1.2 m (prototype) above canal floor
Flow, Q (m3/s) 1.02 1.36 1.7 2.04 2.37
Assumed bell inlet velocity, V (m/s) 0.9 1.2 1.5 1.8 2.1
Calculated suction bell diameter (m) 1.20 1.20 1.20 1.20 1.20
Actual (rounded) suction bell diameter, D (m) 1.20 1.20 1.20 1.20 1.20
Actual bell inlet velocity, Vb (m/s) 0.90 1.20 1.50 1.80 2.10
Canal width, W (=2D) (m) 2.4 2.4 2.4 2.4 2.4
Required bell height above floor, C (m) 1.2 1.2 1.2 1.2 1.2
Froude Number, Fr 0.26 0.35 0.44 0.53 0.61
Knauss submergence, S = D(0.5+2Fr) (m) 1.23 1.44 1.65 1.86 2.07
Hydraulic Institute submergence, S = D(1+2.3Fr) (m) 1.93 2.17 2.41 2.65 2.89
Knauss approach velocity, Va (m/s) 0.17 0.21 0.25 0.28 0.30
Hydraulic Institute approach velocity, Va (m/s) 0.14 0.17 0.20 0.22 0.24
Ratio Vb/Va (Knauss) 5.16 5.60 6.05 6.50 6.93
Ratio Vb/Va (Hydraulic Institute) 6.63 7.15 7.66 8.17 8.67
Measured Type 2 submergence in physical model
for Type 1B suction bell (m) (1)
1.12 1.23 1.48 1.51 1.57
(1) The Type 2 submergence levels measured in the physical model are the maximum submergence values for suction bells
located at 0.6 m and 1.2 m above the floor, as some of the submergence levels for the 1.2 m suction bell installation were
lower than expected.
Stellenbosch University http://scholar.sun.ac.za
Page | 123
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
It is evident from Table 6.2 that:
The inlet bell velocity/approach canal velocity ratios calculated with the equation published
by Knauss (1987) vary from 5.16 to 6.93;
The inlet bell velocity/approach canal velocity ratios calculated with the equation published
by the Hydraulic Institute (1998) all exceed 6.0;
The Type 2 submergence levels measured in the physical model study correspond
reasonably well with the submergence levels calculated with the equation published by
Knauss (1987) for all bell inlet velocities; and
Calculating the submergence levels with the equation published by the Hydraulic Institute
(1998) for inlet bell velocity/approach canal velocity ratios exceeding 6.0, would result in
very conservative submergence levels when compared to those measured in the physical
model study. Similarly, calculating the submergence levels with the equation published by
Knauss (1987) for bell inlet velocities up to 1.5 m/s (i.e. bell inlet velocity/approach canal
velocity ratios of less than 6.0), and using the Hydraulic Institute’s equation for bell inlet
velocities above 1.5 m/s would also have resulted in conservative submergence levels. This
demonstrates the fact that the submergence levels calculated with the equation published by
Knauss (1987) will result in slightly higher bell inlet velocity/approach canal velocity ratios
compared to those determined from the results of the physical model study.
Stellenbosch University http://scholar.sun.ac.za
Page | 124
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Table 6.3: Bell inlet velocity/approach canal velocity ratios for Type 1B suction bell located 1.8 m (prototype) above canal floor
Flow, Q (m3/s) 1.02 1.36 1.7 2.04 2.37
Assumed bell inlet velocity, V (m/s) 0.9 1.2 1.5 1.8 2.1
Calculated suction bell diameter (m) 1.20 1.20 1.20 1.20 1.20
Actual (rounded) suction bell diameter, D (m) 1.20 1.20 1.20 1.20 1.20
Actual bell inlet velocity, Vb (m/s) 0.90 1.20 1.50 1.80 2.10
Canal width, W (=2D) (m) 2.4 2.4 2.4 2.4 2.4
Required bell height above floor, C (m) 1.8 1.8 1.8 1.8 1.8
Froude Number, Fr 0.26 0.35 0.44 0.53 0.61
Knauss submergence, S = D(0.5+2Fr) (m) 1.23 1.44 1.65 1.86 2.07
Hydraulic Institute submergence, S = D(1+2.3Fr) (m) 1.93 2.17 2.41 2.65 2.89
Knauss approach velocity, Va (m/s) 0.14 0.17 0.21 0.23 0.26
Hydraulic Institute approach velocity, Va (m/s) 0.11 0.14 0.17 0.19 0.21
Ratio Vb/Va (Knauss) 6.43 6.88 7.32 7.77 8.20
Ratio Vb/Va (Hydraulic Institute) 7.91 8.42 8.93 9.45 9.94
Measured Type 2 submergence in physical model
for Type 1B suction bell (m) 1.64 1.81 1.83 2.06 2.25
It is evident from Table 6.3 that:
The inlet bell velocity/approach canal velocity ratios calculated with the equation published
by Knauss (1987) all exceed 6.0;
The inlet bell velocity/approach canal velocity ratios calculated with the equation published
by the Hydraulic Institute (1998) all exceed 6.0;
The Type 2 submergence levels measured in the physical model study correspond
reasonably well with the submergence levels calculated with the equation published by
Hydraulic Institute (1998) for all bell inlet velocities; and
Calculating the submergence levels with the equation published by Knauss (1987) for inlet
bell velocity/approach canal velocity ratios exceeding 6.0, would result in inadequate
submergence levels.
It is evident from Tables 6.1 to 6.3 that the initial submergence should be calculated with the
equation published by Knauss (1987) and that, where the bell inlet velocity/approach canal
velocity ratio exceeds 6.0, the critical submergence be calculated with the equation published by
the Hydraulic Institute (1998).
Stellenbosch University http://scholar.sun.ac.za
Page | 125
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
The two examples presented below demonstrate the application of the two different formulas
recommended to calculate critical submergence for pump intakes.
Example 1 (Vlieëpoort abstraction works)
Flow, Q = 2.0 m3/s
Assumed bell inlet velocity, V = 1.2 m/s
Calculated suction bell diameter, D = 1.5 m
Actual bell inlet velocity, Vb = 1.13 m/s
Canal width, W = 3.0 m (i.e. 2D)
Required bell height above floor for flushing purposes, C = 1.5 m
Submergence, S = D(0.5 + 2.0Fr)
= 1.64 m
Approach canal velocity, Va = Q / (W x (C + S))
= 0.21 m/s
Ratio of Vb/Va = 5.3, which is less than 6.0, i.e. use the equation
published by Knauss
Final submergence, S = 1.64 m
Example 2 (Lower Thukela abstraction works)
Flow, Q = 0.467 m3/s
Assumed bell inlet velocity, V = 1.2 m/s
Calculated suction bell diameter, D = 0.7 m
Actual bell inlet velocity, Vb = 0.71 m/s
Canal width, W = 1.4 m (i.e. 2D)
Stellenbosch University http://scholar.sun.ac.za
Page | 126
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Required bell height above floor for flushing purposes, C = 1.5 m
Submergence, S = D(0.5 + 2.0Fr)
= 1.00 m
Approach canal velocity, Va = Q / (W x (C + S))
= 0.13 m/s
Ratio of Vb/Va = 9.1, which is greater than 6.0, i.e. use the equation
published by the Hydraulic Institute (1998)
Final submergence, S = D(1 + 2.3Fr)
= 1.45 m
Stellenbosch University http://scholar.sun.ac.za
Page | 127
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
7. CONCLUSIONS AND RECOMMENDATIONS
7.1 Conclusions
A physical hydraulic model study, at a 1:10 scale, was undertaken to evaluate the impact on
critical submergence when raising the pump intake to above the recommended norm of 0.5
times the diameter of the inlet bell from the floor. Four different configurations of pump intakes
were tested. The following conclusions ensued from the results of the physical hydraulic model
investigation and associated literature review:
Various equations have been published to calculate critical submergence for pump intakes.
The submergence values calculated with these equations vary substantially, which posed
questions as to their validity.
The water level measurements at which Type 2, 5 and 6 vortices occurred in the physical
hydraulic model could be repeated with a reasonably high level of confidence. The
maximum deviations from the average water levels for Type 2, 5 and 6 vortices were 7%,
16% and 23% respectively. The maximum difference between the minimum and maximum
water levels for Type 2 vortices was 18%.
The submergence required to prevent Type 2, 5 and 6 vortex formation increased markedly
when the pump intake was raised above a certain height. The marked increase in
submergence occurred when the ratio, inlet bell velocity to approach canal velocity,
exceeded 6.0.
The submergence required for slanted suction bells was higher than for conventional flat
suction bells. The submergence required was similar for suction bells with short (i.e. 1 x
suction pipe diameter) and long radius (i.e. 2 x suction pipe diameter) bends, with the
recommendation to design based on long radius bends which had marginally higher
submergence requirements.
Critical submergence should be based on the water levels at which Type 2 (i.e. surface
dimples) vortices occur due to the difficulty associated with identifying Type 3 (i.e. coherent
dye core) vortices in the physical hydraulic model and given the Hydraulic Institute (1998)
guideline that Type 3 vortices should occur less than 10% of the time.
The Type 2 water levels, for different prototype bell inlet velocities and a prototype inlet bell
velocity/approach canal velocity ratio of less than 6.0, closely followed the submergence
levels calculated with the equation published by Knauss (1987), i.e. S = D(0.5 + 2.0Fr). The
Stellenbosch University http://scholar.sun.ac.za
Page | 128
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Type 2 water levels, where the prototype bell inlet velocity/approach canal velocity ratio
exceeded 6.0, closely followed the submergence levels calculated with the equation
published by the Hydraulic Institute (1998), i.e. S = D(1 + 2.3Fr).
Prototype bell inlet velocities should be limited to 1.5 m/s, as the water surface became
turbulent in the physical hydraulic model when the bell inlet velocities were increased above
1.8 m/s. This was also reported by various authors referenced in the literature review.
7.2 Recommendations
The following recommendations are made for the design of pump intakes with a similar
geometry to that tested in the physical hydraulic model:
Conventional flat bottom suction bells can be used for flows of up to 2.5 m3/s per pump.
Prototype bell inlet velocities should be limited to 1.5 m/s.
The use of short or long radius suction bends should be evaluated against other criteria
such as net positive suction head requirements of the pumps and the overall height of the
pump installation.
The equation published by Knauss (1987), i.e. S = D(0.5 + 2.0Fr), can be used to calculate
critical submergence where the bell inlet velocity/approach canal velocity ratio, as
determined with Knauss’ equation, is less than 6.0. The equation published by the Hydraulic
Institute (1998), i.e. S = D(1 + 2.3Fr), can be used where the ratio exceeds 6.0.
The need may arise in future designs of sand trap canals to increase the width to more than the
recommended pump bay entrance width of 2D in order to reduce the approach velocity
sufficiently to trap sand particles upstream of the pump inlet. It is recommended that further
physical hydraulic model testing be performed in which the width of the sand trap canal is varied
to determine the bell inlet velocity/approach canal velocity ratio where the marked increase in
submergence occurs.
Stellenbosch University http://scholar.sun.ac.za
Page | 129
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
REFERENCE LIST
Ahmad, Z., Jain, B., & Mittal, M. (2011). Rational design of a pump-sump and its model testing.
Journal of Pipeline Systems Engineering and Practice, Vol 2 (p53-63).
American Water Works Association. (1983). C208: Dimensions for Fabricated Steel Water Pipe
Fittings. Denver, USA.
Ansar, M., & Nakato, T. (2001). Experimental study of 3D pump-intake flows with and without
cross flow. Journal of Hydraulic Engineering, Vol 127 (p825-834).
Arboleda, G., & El-Fadel, M. (1996). Effects of approach flow conditions on pump sump design.
Journal of Hydraulic Engineering, Vol 122 (p489-494).
Basson, G. (2010). Mokolo Crocodile Project: Hydraulic design and modelling of the Crocodile
River abstraction works. Johannesburg: TCTA.
Basson, G. (2011). Lower Thukela Bulk Water Supply Scheme: Hydraulic design and modelling
of the proposed Lower Thukela abstraction works. Pietermaritzburg: Umgeni Water.
Daggett, L., & Keulegan, G. (1974). Similitude in free-surface vortex formations. Journal of the
Hydraulics Division, Vol 100 (p1565-1581).
Denney, D., & Young, G. (July 1957). The prevention of vortices and intakes. 7th International
Association of Hydraulic Research, (p. Paper C1). Lisbon.
Featherstone, R., & Nalluri, C. (1988). Civil engineering hydraulics. Oxford: BSP Professional
Books.
Flygt. (2002). Design recommendations for pumping stations with dry installed submersible
pumps. Stockholm: Flygt.
Fraser, W., & Harrison, N. (1953). Hydraulic problems encountered in intake structures of
vertical wet-pit pumps and methods leading to their solution. American Society of
Mechanical Engineers, Vol 4 (p643-652).
Gouws, J.([email protected]) (2010, December 13). Minimum submergence for
KSB pumps. E-mail correspondence, 13 December 2010.
Stellenbosch University http://scholar.sun.ac.za
Page | 130
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Hecker, G. (1981). Model-prototype comparison of free surface vortices. Journal of Hydraulic
Division, Vol 107 (p1243-1259).
Hundley, K. (2012). Modelling of a pump intake with a single phase CFD model. Stellenbosch:
Stellenbosch University.
Hydraulic Institute. (1998). American national standard for pump intake design. New York:
ANSI.
Iversen, H. (1953). Studies of submergence requirements of high specific speed pumps.
American Society of Mechanical Engineers, Vol 4 (p635-641).
Jain, A., Raju, K., & Garde, R. (1978). Vortex formation at vertical pipe intakes. Journal of
Hydraulics Division, Vol 104 (p1429-1445).
Jones, G., Sanks, R., Tchobanoglous, G., & Bosserman, B. (2008). Pumping station design (3rd
edn). Elsevier.
Karassik, I., Messina, J., Cooper, P., & Heald, C. (2001). Pump handbook (4th edn). McGraw-
Hill.
Knauss, J. (1987). Swirling flow problems at intakes. Rotterdam: AA Balkema Publishers.
Massey, B. (1989). Mechanics of fluids. London: Chapman & Hall.
Nortek. (2004). Vectrino velocimeter: User guide. Norway: Nortek.
Padmanabhan, M., & Hecker, G. (1984). Scale effects in pump sump models. Journal of
Hydraulic Engineering, Vol 110 (p1540-1556).
Paterson, I., & Noble, R. (1982). The right approach. Proceedings of the IAHR-Symposium on
Operating Problems of Pump Sations and Power Plants. Amsterdam.
Prosser, M. (1977). The hydraulic design of pump sumps and intakes. Bedford, UK: British
Hydromechanics Research Association.
Rajendran, V., & Patel, V. (2000). Measurement of vortices in model pump-intake bay by PIV.
Journal of Hydraulic Engineering, Vol 126 (p322-334).
Stellenbosch University http://scholar.sun.ac.za
Page | 131
PHYSICAL HYDRAULIC MODEL INVESTIGATION OF CRITICAL SUMBERGENCE FOR RAISED PUMP INTAKES
Strydom, D. ([email protected]) (2010a, December 14). Collection and pumping of
wastewater (Metcalf & Eddy, 1981). E-mail correspondence, 14 December 2010.
Strydom, D. ([email protected]) (2010b, December 14). Critical submergence used for
Gorman-Rupp pumps. E-mail correspondence, 14 December 2010.
Sulzer Brothers Limited. (1987). Centrifugal pump handbook. Switzerland: Sulzer Brothers
Limited.
Webber, N. (1979). Fluid mechanics for civil engineers. London: Chapman & Hall.
Werth, D., & Frizzell, C. (2009). Minimum pump submergence to prevent surface vortex
formation. Journal of Hydraulic Research, Vol 47 (p142-144).
Stellenbosch University http://scholar.sun.ac.za