CONTROLS: NEC/CEC EXPLOSIONPROOF MOTOR STARTERS Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019 1 PlexPower Factory Sealed Contactors and Motor Starters Stainless Steel Enclosures Full Voltage, Combination and Non-Combination, Single and Multiple NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66 Application PlexPower™ combination and non-combination contactors and motor starters are used in areas where hazardous materials are handled or stored such as: — Petroleum plants — Chemical plants — Refineries — Wastewater Treatment Plants — Paper and Pulp Industries — Other process facilities These units provide disconnecting means, circuit protection, and motor running protection. Ideal for placement in wet, corrosive environments or where flammable gases or vapors are likely to be present. Features No external conduit or cable seals required thus making installations faster, easier, and less costly. The PlexPower™ contactors and motor starters feature a ground-breaking design that uses individual breaker, contactor and motor starter housings to minimize the downtime and costs associated with maintenance in hazardous locations. PlexPower™ breakers, contactors and motor starters accommodate non-proprietary off-the-shelf breakers, contactors and motor starters, making replacements readily available from multiple sources. PlexPower contactor only panels are rated for resistive loads. The lighter weight contactor and motor starter enclosure with quarter turn latches, can be quickly opened in the field for easier servicing. Gland plate at the bottom of enclosure can be easily field punched for cable or conduit entries. Additional gland plates available for sides and top can be ordered with the panelboard. See options. Standard configuration includes external actuation and a solid door. • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and Motor Starters. For multiple contactor or motor starter panels, each contactor or motor starter can be individually padlocked in either the “On” or “Off” position. Ground bars provided as standard. External/internal ground lug provided as standard. • Drain/breather provided as standard. One normally open and one normally closed auxiliary contacts are provided as standard for customer use. Additional auxiliary contacts available as options. Standard Materials • Enclosure: stainless steel • Hardware: stainless steel Bus bar: hard drawn, tin plated, copper Options For Class I, Division 2 Groups B, C, D only, add suffix—D2. Gland plate (bottom is standard), — Top side gland plate, add suffix GPT. — Left side gland plate, add suffix GPL. — Right side gland plate, add suffix GPR. — No gland plate, add suffix GPN. Thermostatically controlled heater, add suffix —HTR. Inverted feed, add suffix —INV. Lockable wing knobs, add suffix —P. Phenolic/ lamacoid nameplate (specify legend), add suffix —NP. Stainless steel legend plate (specify legend), add suffix —SP. Terminal blocks for contactor/motor starter wiring, add suffix —TB. Auxiliary Contacts (1NO and 1NC provided as standard) One additional auxiliary contact (NO or NC) —AUX1 Two additional auxiliary contacts (NO or NC) —AUX2 Three additional auxiliary contacts (NO or NC) —AUX3 Four additional auxiliary contacts (NO or NC) —AUX4 Additional auxiliary contacts may be available, please contact your sales representative for more information. NEC/CEC Certifications and Compliances ANSI/UL Standards: UL 508, UL 50, UL 1203 CSA Standards: C22.2 No. 0-10, C22.2 No. 14-10, C22.2 No. 25-1996, C22.2 No. 30-M1986 and C22.2 No. 94-M91 cCSAus Certified: 039199 Internal View External View T4 when the HTR heater option is included. Only for multiple contactors and motor starter panels. Siemens is a registered trademark of Siemens AG. Schneider is a registered trademark of Schneider Electric.

Upload: others

Post on 21-Jan-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PlexPower Factory Sealed Contactors and Motor Starters ... · • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and

CONTROLS: NEC/CEC EXPLOSIONPROOF MOTOR STARTERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019

1

PlexPower™ Factory Sealed Contactors and Motor StartersStainless Steel EnclosuresFull Voltage, Combination and Non-Combination, Single and Multiple

NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66

Application• PlexPower™ combination and non-combination contactors and

motor starters are used in areas where hazardous materials are handled or stored such as:

— Petroleum plants — Chemical plants —Refineries — Wastewater Treatment Plants — Paper and Pulp Industries — Other process facilities• These units provide disconnecting means, circuit protection,

and motor running protection. • Ideal for placement in wet, corrosive environments or where

flammablegasesorvaporsarelikelytobepresent.

Features• Noexternalconduitorcablesealsrequiredthusmaking

installationsfaster,easier,andlesscostly.• The PlexPower™ contactors and motor starters feature a

ground-breakingdesignthatusesindividualbreaker,contactorand motor starter housings to minimize the downtime and costs associated with maintenance in hazardous locations.

• PlexPower™breakers,contactorsandmotorstartersaccommodatenon-proprietaryoff-the-shelfbreakers,contactorsandmotorstarters,makingreplacementsreadilyavailable from multiple sources.

• PlexPowercontactoronlypanelsareratedforresistiveloads.• The lighter weight contactor and motor starter enclosure with

quarterturnlatches,canbequicklyopenedinthefieldforeasier servicing.

• Glandplateatthebottomofenclosurecanbeeasilyfieldpunched for cable or conduit entries. Additional gland plates available for sides and top can be ordered with the panelboard. See options.

• Standardconfigurationincludesexternalactuationandasoliddoor.

• Siemens Sirius series starters and SchneiderTeSys™ N Series contactors are used in the PlexPower Contactors and Motor Starters.

• For multiple contactor or motor starter panels, each contactor ormotorstartercanbeindividuallypadlockedineitherthe“On”or“Off”position.

• Ground bars provided as standard.• External/internal ground lug provided as standard.• Drain/breather provided as standard.• Onenormallyopenandonenormallyclosedauxiliarycontacts

areprovidedasstandardforcustomeruse.Additionalauxiliarycontacts available as options.

Standard Materials• Enclosure: stainless steel • Hardware: stainless steel• Bus bar: hard drawn, tin plated, copper

Options• ForClassI,Division2GroupsB,C,Donly,addsuffix—D2.• Gland plate (bottom is standard),

— Top side gland plate,addsuffix —GPT.— Left side gland plate,addsuffix —GPL.

— Right side gland plate,addsuffix —GPR.— No gland plate,addsuffix —GPN.

• Thermostaticallycontrolledheater,addsuffix—HTR.• Invertedfeed,addsuffix—INV. • Lockablewingknobs,addsuffix—P. • Phenolic/lamacoidnameplate(specifylegend),add

suffix—NP.• Stainlesssteellegendplate(specifylegend),addsuffix—SP.• Terminalblocksforcontactor/motorstarterwiring,

addsuffix—TB.• AuxiliaryContacts(1NOand1NCprovidedasstandard)

— Oneadditionalauxiliarycontact(NOorNC)—AUX1— Twoadditionalauxiliarycontacts(NOorNC)—AUX2— Threeadditionalauxiliarycontacts(NOorNC)—AUX3— Fouradditionalauxiliarycontacts(NOorNC)—AUX4— Additionalauxiliarycontactsmaybeavailable,pleasecontact

yoursalesrepresentativeformoreinformation.

NEC/CEC Certifications and Compliances• ANSI/ULStandards:UL508,UL50,UL1203• CSAStandards:C22.2No.0-10,C22.2No.14-10,

C22.2No.25-1996,C22.2No.30-M1986and C22.2No.94-M91

• cCSAusCertified:039199

Internal View

External View

T4 when the HTR heater option is included. Only for multiple contactors and motor starter panels. Siemens is a registered trademark of Siemens AG. Schneider is a registered trademark of Schneider Electric.

Page 2: PlexPower Factory Sealed Contactors and Motor Starters ... · • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and

CONT

ROLS

: NEC

/CEC

EXP

LOSI

ONPR

OOF

MOTO

R ST

ARTE

RS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019

2

NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66

PlexPower™ Stainless Steel Contactors and Motor StartersStainless Steel EnclosuresFull Voltage, Combination and Non-Combination, Single and Multiple

Catalog Numbering Guide

RM S P1 4 1 M 4 125 1 4 A C S MC 030 A # #

Step1 Step 2 Step3 Step4 Step 5

Operating Voltage:

1-120Vac2-240Vac4-480Vac6-600Vac

NEC/CEC Certified

RM- PlexPower Motor Starter

Total QuantityofContactors/

Starters:1234

QuantityofContactors/

Starters:1234

Contactor/ Starter

Manufacturer:S - Siemens

D - Schneider

Operators:N - None A - HOA SS,

Start PB, Stop PB, Running Pilot Light, Stopped Pilot Light, Reset PB

B - HOA SS, Illuminated Start PB, Illuminated Stop PB, Reset PB

C - HOA SS, Running Pilot Light

D - Start PB, Stop PB, Reset PB

Z - Custom

Panel Material:

S - Stainless Steel

Bus Rating:0 - No Bus (Single

Contactor or StarterOnly)

1-150Amp (MainBreaker)

2-180Amp (Main Lugs)

Breakertrip (Thermal Mag)

000 - Main Lugs015-15Amp020 - 20 Amp025 - 25 Amp 030-30Amp035-35Amp040-40Amp050 - 50 Amp060-60Amp070 - 70 Amp080 - 80 Amp090-90Amp100-100Amp110-110Amp125-125Amp

Contactor/Starter

Function:A - Full

Voltage Non-Reversing Motor Starter

J - Contactor (3pole)

Branch Isolation/Protection

MC - Branch Breaker

LL-NoBreakerPC- MCP Branch

Breaker

AdditionalContactor/ Starters:Repeat Step3

MainType:M-BreakerL - Lugs

Control Voltage:

1-120Vac2-240Vac5-24Vdc9-208Vac

Starter Size:

A - NEMA 00B - NEMA 0C-NEMA1

MCPorBreakerTrip: Suffix for

Other OptionsRefer to Options Section

MCP003-3Amp007 - 7 Amp015-15Amp030-30Amp

BranchBreakerTrip(Thermal Mag)

000-NoBreaker015-15Amp020 - 20 Amp025 - 25 Amp030-30Amp

T4 when the HTR heater option is included. Always use Main Lugs when total quantity is 1. 24 Vdc control voltage is customer supplied

Main Lugs Main Breaker

Size Dimensions Size Dimensions

Non combination contactor M1 370x370x200 — —

Non combination contactor with heater option W1 450x370x200 — —

Non combination starter N1 560x350x200 — —

Combination contactor N1 560x350x200 — —

Combination starter T1 560x450x200 — —

R1 750x350x200 — —

(2) Combination Contactors I1 875x750x250 E1 1130x750x250

(2) Combination Starters Q1 1130x1000x250 Q1 1130x1000x250

(3)CombinationContactors E1 1130x750x250 G1 1500x750x250

(3)CombinationStarters Q1 1130x1000x250 P1 1500x1000x250

(4)CombinationContactors G1 1500x750x250 G1 1500x750x250

(4)CombinationStarters P1 1500x1000x250 P1 1500x1000x250

Page 3: PlexPower Factory Sealed Contactors and Motor Starters ... · • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and

CONTROLS: NEC/CEC EXPLOSIONPROOF MOTOR STARTERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019

3

NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66

PlexPower™ Stainless Steel Contactors and Motor StartersStainless Steel EnclosuresFull Voltage, Combination and Non-Combination, Single and Multiple

RM S P1 4 1 M 4 125 1 4 A C S MC 030 A # #

Step1 Step 2 Step3 Step4 Step 5

Operating Voltage:

1-120Vac2-240Vac4-480Vac6-600Vac

NEC/CEC Certified

RM- PlexPower Motor Starter

Total QuantityofContactors/

Starters:1234

QuantityofContactors/

Starters:1234

Contactor/ Starter

Manufacturer:S - Siemens

D - Schneider

Operators:N - None A - HOA SS,

Start PB, Stop PB, Running Pilot Light, Stopped Pilot Light, Reset PB

B - HOA SS, Illuminated Start PB, Illuminated Stop PB, Reset PB

C - HOA SS, Running Pilot Light

D - Start PB, Stop PB, Reset PB

Z - Custom

Panel Material:

S - Stainless Steel

Bus Rating:0 - No Bus (Single

Contactor or StarterOnly)

1-150Amp (MainBreaker)

2-180Amp (Main Lugs)

Breakertrip (Thermal Mag)

000 - Main Lugs015-15Amp020 - 20 Amp025 - 25 Amp 030-30Amp035-35Amp040-40Amp050 - 50 Amp060-60Amp070 - 70 Amp080 - 80 Amp090-90Amp100-100Amp110-110Amp125-125Amp

Contactor/Starter

Function:A - Full

Voltage Non-Reversing Motor Starter

J - Contactor (3pole)

Branch Isolation/Protection

MC - Branch Breaker

LL-NoBreakerPC- MCP Branch

Breaker

AdditionalContactor/ Starters:Repeat Step3

MainType:M-BreakerL - Lugs

Control Voltage:

1-120Vac2-240Vac5-24Vdc9-208Vac

Starter Size:

A - NEMA 00B - NEMA 0C-NEMA1

MCPorBreakerTrip: Suffix for

Other OptionsRefer to Options Section

MCP003-3Amp007 - 7 Amp015-15Amp030-30Amp

BranchBreakerTrip(Thermal Mag)

000-NoBreaker015-15Amp020 - 20 Amp025 - 25 Amp030-30Amp

T4 when the HTR heater option is included. Only available when total quantity of contactors and starters equals 1. For motor starter, reset push button for overload is provided.

Page 4: PlexPower Factory Sealed Contactors and Motor Starters ... · • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and

CONT

ROLS

: NEC

/CEC

EXP

LOSI

ONPR

OOF

MOTO

R ST

ARTE

RS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019

4

PlexPower™ Stainless Steel Contactors and Motor StartersStainless Steel EnclosuresFull Voltage, Combination and Non-Combination, Single and Multiple

NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66

Panel Size

Dimensions in Millimeters (Inches)

M1 W1 N1 T1 R1 I1 E1 Q1 G1 P1

Length 370(14.50)

450(18.00)

560(22.00)

560(22.00)

750 (30.00)

875 (34.00)

1130(44.50)

1130(44.50)

1500 (59.00)

1500 (59.00)

Width 370(14.50)

370(14.50)

350(14.00)

450(18.00)

350(14.00)

750 (30.00)

750 (30.00)

1000(39.50)

750 (30.00)

1000(39.50)

Depth 200 (8.00)

200 (8.00)

200 (8.00)

200 (8.00)

200 (8.00)

250 (10.00)

250 (10.00)

250 (10.00)

250 (10.00)

250 (10.00)

Steps to Creating Catalog Number:Complete Catalog Number

RM S P1 4 1 M 4 125 1 4 A C S MC 030 A __ __

Step 1 Step 2 Step 3 Step 4 Step 5Step1: Choose enclosure size and operating voltage based on application.Step 2:Definetotalquantityofcontactorsorstarters.Ifamainbreakerisdesired,indicateamperagerating.Step3:Definethequantity,function,sizeandoperatorsforeachsizeofcontactorandmotorstarter.Step4: Repeat this step for each contactor or starter configuration.Step 5: Options: Add option in alphanumeric order as listed on the PlexPower™ introduction page under Options.

T4 when the HTR heater option is included.

Page 5: PlexPower Factory Sealed Contactors and Motor Starters ... · • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and

CONTROLS: NEC/CEC EXPLOSIONPROOF MOTOR STARTERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019

5

PlexPower™ Stainless Steel Contactors and Motor StartersStainless Steel EnclosuresFull Voltage, Combination and Non-Combination, Single and Multiple

NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66

Dimensions in Millimeters (Inches)

Size T1

D

CB

35.0(1.38”)

65.0(2.56”)

A

E

F

Front View Side View Internal View

Size R1

CB

D35.0(1.38”)

65.0(2.56”)

AF

E

Front View Side View Internal View

Single Contactor and Starter Panel Standard Configurations

Dimensions in Millimeters (Inches)

Approximate Weight kg (lb)

Mounting Feet Horizontal

Mounting Feet Vertical

Overall Length

Overall Width

Overall Height

Height With Operators

A B C D E F

M1 405(15.94) 285(11.22) 370(14.57) 370(14.57) 200 (7.88) 223(8.81) 24(53)

W1 405(15.94) 315(12.4) 450(17.72) 370(14.57) 200 (7.88) 223(8.81) 31(68)

N1 385(15.16) 395(15.55) 560(22.05) 350(13.78) 200 (7.88) 282(11.13) 39(86)

T1 485(19.09) 395(15.55) 560(22.05) 450(17.72) 200 (7.88) 282(11.13) 45(99)

R1 385(15.16) 585(23.04) 750(29.53) 350(13.78) 200 (7.88) 282(11.13) 49(108)

T4 when the HTR heater option is included.

Page 6: PlexPower Factory Sealed Contactors and Motor Starters ... · • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and

CONT

ROLS

: NEC

/CEC

EXP

LOSI

ONPR

OOF

MOTO

R ST

ARTE

RS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019

6

PlexPower™ Stainless Steel Contactors and Motor StartersStainless Steel EnclosuresFull Voltage, Combination and Non-Combination, Single and Multiple

NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66

Dimensions in Millimeters (Inches)

Size G1

D

CB

35.0(1.38”)

65.0(2.56”)

A

F

E

273.9(10.78”)

Front View Side View Internal View

Size P1

B

D

C

35.0(1.38”)

65.0(2.56”)

A E

F

Front View Side View Internal View

Multiple Combination Contactor and Starter Panel Standard Configurations

Dimensions in Millimeters (Inches)

Approximate Weight kg (lb)

Mounting Feet Horizontal

Mounting Feet Vertical

Overall Length

Overall Width

Overall Height

Height With Operators

A B C D E F

I1 785(30.91) 710(27.96) 875(34.45) 750(29.53) 250(9.85) 332(13.09) 100(220)

E1 785(30.91) 965(38.0) 1130(44.49) 750(29.53) 250(9.85) 332(13.09) 129(284)

Q1 1035(40.75) 965(38.0) 1130(44.49) 1000(39.37) 250(9.85) 332(13.09) 162(357)

G1 785(30.91) 1335(52.56) 1500(59.06) 750(29.53) 250(9.85) 332(13.09) 172(379)

P1 1035(40.75) 1335(52.56) 1500(59.06) 1000(39.37) 250(9.85) 332(13.09) 206(454)

T4 when the HTR heater option is included.

Page 7: PlexPower Factory Sealed Contactors and Motor Starters ... · • Siemens Sirius series starters and Schneider TeSys™ N Series contactors are used in the PlexPower Contactors and

CONTROLS: NEC/CEC EXPLOSIONPROOF MOTOR STARTERS

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2019

7

Wiring Diagram

PlexPower™ Stainless Steel Contactors and Motor StartersStainless Steel EnclosuresFull Voltage, Combination and Non-Combination, Single and Multiple

NEC/CEC: Ex de IIB+H2 T6 Class I, Zone 1, AEx de IIB+H2 T6 Class I, Division 2, Groups B, C, D T6 Class II, Division 2, Groups F, G Class III Type 4X, IP66

T4 when the HTR heater option is included.